EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
A. General Requirements
Verify and ensure the battery rooms are well and properly ventilated,
either by a natural (vented to outside air) or induced ventilation system to
SAES-T-151,
A1 prevent accumulation of hydrogen and to maintain the design
para. 4.1.1
temperature. Ensure that there shall be no return air duct of air
conditioning systems from the battery room.
Verify that the door of the battery has permanent indelible sign in both
English and Arabic: 'Keep Door Open for Five Minutes before Entering' SAES-T-151,
A2 and that the room doors shall be open outward away from the room. No para. 4.2.1 and
hasp, padlock or other device shall be installed which will hinder para. 4.2.3
operation of the emergency door.
SAES-T-151,
A3 Room lighting shall be in accordance with SAES-P-123
para. 4.2.4
The battery system shall be designed for a service life of 20 years for
lead acid batteries and nickel-cadmium batteries. For lead-antimony SAES-T-151,
A5
(including tubular), lead calcium, and sealed cell batteries the design para. 4.5.3
service life shall be 10 years.
Battery sizing shall conform with the required battery reserve to be large
enough to sustain operation of the communications load under busy hour
SAES-T-151,
A6 conditions (hereinafter called "full DC load") for a period of 8 hours where
para. 4.6.1
standby AC power is available and 12 hours for unattended remote
offices. (Reference: IEEE 485)
Page 1 of 2
Battery chargers shall be provided with individual alarms with isolated
contact closure for the following conditions:
a) AC failure
b) Charger failure
SAES-T-151,
A8 c) DC Output failure
para. 4.7.3
d) High DC voltage
e) Low DC voltage
f) Breaker Trip (could be integrated with "b" above)
g) Equalizer/float mode status
Page 1 of 2
MBER
RACTOR
PLANT NO.
/ MCC NO.
TRAVEL TIME
O USE ONLY
WORK PERMIT REQUIRED?
RE-INSP DATE
Page 1 of 2
Page 1 of 2
SAUDI ARAMCO ID/PID - 18-May-05 - REV 0 (Standards Cutoff - March 2013) REV 7 30-Apr-13
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
D.C. Power System - Installation Inspection SAIC-T-5118 31-Aug-11 TELECOM
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Verify Ventilation Test for Sealed Battery Rooms complies with SAES-T-151,
C4
ventilation requirements of paragraph 4.1 para. 6.4
REMARKS:
REFERENCE DOCUMENTS:
1. NFPA 70 (National Electric Code)
2. SAES-P-103 -- UPS and DC System dated 20 October 2008
3. SAES-P-123 -- Lighting, issue 02 March 2011
4. SAES-T-151 -- D.C. Power System dated 22 April 2012
5. SAES-T-795 -- Communication Facility Grounding System dated 21 May 2012
NOTES:
Page 2 of 2
SAUDI ARAMCO ID/PID - 18-May-05 - REV 0 (Standards Cutoff - March 2013) REV 7 30-Apr-13
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
D.C. Power System - Installation Inspection SAIC-T-5118 31-Aug-11 TELECOM
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Name, Signature and Name, Signature and
Date: Date:
Page 2 of 2