Power and Industrial Plant Engineering Part 2

Name: PADILLA, MARK DARYL C.


Student No. 20130152453

Problem No. 1:

Determine the power per kW of refrigeration if COP is 4.2786.


a. 0.3372 b. 0.2337 c. 0.7332 d. 0.3732

1
Power per KW of refrigeration=
COP
1
Power per KW of refrigeration=
4.2786

Power per KW of refrigeration=0.2337

Problem No. 2:

A refrigerator is maintained at 5 deg C. Heat is removed from the stored food at a rate
of 5.5 kJ/s. What is the COP if the necessary power input to the refrigerator is 180
kJ/min?
a. 0.67 b. 1.57 c. 1.83 d. none of these

QR
COP H =
W net

5.5 KW ( 60 sec )
COP H =
KJ
180 ( 1 hr )
hr

COP H =1.8333

Problem No. 3:

A double pass condenser with a mass flow rate of 1,000,000 kg/hr has a leaving flow
velocity of 1.5 m/s. The cross- sectional area of the condenser tube is 0.0003 sq. m.
Calculate the number of tubes.
a. 1235 b. 2153 c. 1532 d. 2315


no . of tubes=
ρAV

kg 1 hr
¿
1 000000 (
hr 3600 s )
kg
1000 3
( 0.0003 m2 ) 1.5 m
( )
m s

no . of tubes=617.2840

Double pass=2(no . of tubes)

no . of tubes=1234.5679