Beruflich Dokumente
Kultur Dokumente
210-6610 H102
Operation Manual Rev.
Excitation System 2007-07-23
A
Thyricon 500
Static excitation system
Operation manual
Table of contents:
1 Safety instructions
2 Technical description
Thyricon 500
Static excitation system
1 Safety instructions
Safety information
WARNING
Hazardous voltages and rotating parts (fans) are present in this electrical equipment during
operation. Non-observance of the safety instructions can result in death, severe personal injury
or substantial property damage.
Only qualified personnel should work on or around the equipment after first becoming
thoroughly familiar with all warning and safety notices and maintenance procedures contained
herein. The successful and safe operation of this equipment is dependent on proper handling,
installation, operation and maintenance.
Definitions:
• QUALIFIED PERSONNEL
For the purpose of this Instruction Manual and product labels, a "Qualified person" is
someone who is familiar with the installation, construction and operation of the equipment
and the hazards involved. He or she must have the following qualifications:
1. Trained and authorized to energize, de-energize, clear, ground and tag circuits and
equipment in accordance with established safety procedures.
2. Trained in the proper care and use of protective equipment in accordance with
established safety procedures.
3. Trained in rendering first aid.
• DANGER
indicates an imminently hazardous situation which, if not avoided, will
result in death or serious injury.
• WARNING
indicates a potentially hazardous situation which, if not avoided, could
result in death or serious injury.
• CAUTION
used with the safety alert symbol indicates a potentially hazardous
situation which, if not avoided, may result in minor or moderate injury.
• CAUTION
used without the safety alert symbol indicates a potentially hazardous
situation which, if not avoided, may result in property damage.
Executed by: Checked by: Approved by: Date:
VSO Name Sign. Name Sign. Name Sign.
24.11.04
Maal GSm GSm
Page 2 of 6
GE01-OI-MI-OperationInstructionsManual-RevA.doc
Marun II
210-6610 H102
Operation Manual Rev.
Excitation System 2007-07-23
A
• NOTICE
NOTICE used without the safety alert symbol indicates a potentially
situation which, if not avoided, may result in an undesireable result or
state.
NOTE
These operating instructions do not purport to cover all details or variations in equipment, nor to
provide for every possible contingency to be met in connection with installation, operation or
maintenance.
Should further information be desired or should particular problems arise which are not covered
sufficiently for the purchaser's purposes, the matter should be referred to the local Voith
Siemens Sales Office.
The contents of these operating instructions shall not become part or modify any prior or existing
agreement, commitment or relationship. The Sales Contract contains the entire obligations of
Voith Siemens. The warranty contained in the contract between the parties is the sole warranty
of Voith Siemens. Any statements contained herein do not create new warranties or modify the
existing warranty.
DANGER
Converters contain hazardous electrical voltages, Death, severe bodily injury or significant
material damage can occur if the safety measures are not followed.
1. Only qualified personnel, who are knowledgeable about the converters and the
provided information, can install, start up, operate, troubleshoot or repair the converters.
2. The converters must be installed in accordance with all relevant safety regulations (e.g.
DIN VDE) as well as all other national or local regulations. Operational safety and reliability
must be ensured by correct grounding, cable dimensioning and appropriate short-circuit
protection.
3. All panels and doors must be kept closed during normal operation.
4. Before carrying out visual checks and maintenance work, ensure that the AC power
supply is disconnected and locked out. Before the AC supply is disconnected, converters
have hazardous voltage levels. Even when the converter contactor is open, hazardous
voltages are still present.
5. When making measurements with the power supply switched on, electrical connections
must not be touched under any circumstances. Remove all jewelry from wrists and fingers.
Ensure that the test equipment is in good conditions and operationally safe.
6. Carefully follow the relevant instructions and observe all danger, warning and
cautionary instructions.
7. This does not represent a full listing of all the measures necessary for safe operation of
the equipment. If you require other information or if certain problems occur which are not
handled in enough detail in the information provided in the Instruction Manual, please
contact your local Voith Siemens office.
CAUTION
Electrostatically sensitive devices
The converter contains electrostatically sensitive devices. These can easily be destroyed if they are not
handled correctly. If, however, it is absolutely essential for you to work on electronic modules, please pay
careful attention to the following instructions:
• Electronic modules (PCBs) should not be touched unless work has to be carried out on them.
• Before touching a PCB, the person carrying out the work must himself be electrostatically discharged.
The simplest way of doing this is to touch an electrically conductive earthed object, e.g. socket outlet
earth contact.
• PCBs must not be allowed to come into contact with electrically insulating materials − plastic foil,
insulating table tops or clothing made of synthetic fibers −
• PCBs may only be set down or stored on electrically conducting surfaces.
• When carrying out soldering jobs on PCBs, make sure that the soldering tip has been earthed.
• PCBs and electronic components should generally be packed in electrically conducting containers
(such as metallized-plastic boxes or metal cans) before being stored or shipped.
• If the use of non-conducting packing containers cannot be avoided, PCBs must be wrapped in a
conducting material before being put in them. Examples of such materials include electrically
conducting foam rubber or household aluminium foil.
For easy reference, the protective measures necessary when dealing with sensitive electronic components
are illustrated in the sketches below.
a = Conductive flooring d = Anti-static overall
b = Anti-static table e = Anti-static chain
c = Anti-static footwear f = Earthing connections of cabinets
d d d
b b
e e
f f f f f
c a c
a a
WARNING
Hazardous voltages and rotating parts (fans) are present in this electrical equipment during
operation.
Non-observance of the safety instructions can result in death, severe personal injury or
substantial property damage.
Only qualified personnel should work on or around the equipment after first becoming
thoroughly familiar with all warning and safety notices and maintenance procedures contained
herein.
The successful and safe operation of this equipment is dependent on proper handling,
installation, operation and maintenance.
Thyricon 500
Static excitation system
2 Technical description
Table of content:
2.4. Interface 27
Voltage Regulator
Excitation Transformer
Potential Transformer
Generator output
Control
Current Transformer
Figure 1
Interconnections are bus or cables and all wires that link the excitation system parts
together.
Executed by: Checked by: Approved by: Date:
VSO Name Sign. Name Sign. Name Sign.
24.11.04
GSm GSm
Page 4 of 29
GE01-OI-MI-OperationInstructionsManual-RevA.doc
Marun II
210-6610 H102
Operation Manual Rev.
Excitation System 2007-07-23
A
Potential and Current Transformers are used to transform the generators voltage and
current into values that can be read by the Voltage Regulator. In Thyricon there are
transducers that convert the signals to electronic levels. Both the Potential and Current
transformers and the transducers share the task of adapting signals from the machine to
electronic signal levels.
The Excitation Transformer is a step down transformer used to feed the rectifier bridge and
consequently the field. The Standard Excitation Transformer is a dry three-phase, Y / ∆ or ∆ /
Y, which is dimensioned to guarantee 110% of maximum excitation system power.
Thyricon Voltage Regulators are compact standard products which are used in small,
medium or large Hydro Power Plants. The selection of Thyricon model and type depends on
the current and field voltage.
The concept of redundancy in Thyricon 500 is 1+1 which can be executed in a cold or hot
standby.
Thyricon 500 uses a standard converter from Siemens AG (Simoreg 6RA70) with specific
boards working as an integrated control system. Integrated control means the control is
executed in boards (T400, CUD1, CUD2) placed in the converter unit.
PLC Siemens
OP Siemens S7-300
Transducers Control
Integrated Control
boards
Siemens Converter
Field Discharge and
pre-excitation Simoreg
Over voltage Protection
Figure 2
Voltage Regulators are normally divided in two parts: the control and the power part as
shown in Figure 1.
The power part is composed by circuits and components more robust than the control part.
Rectifier bridges, overvoltage detection circuit, field flashing circuit, discharge circuit and bus
are located in the power part (see figure 3).
For Thyricon 500, it is used two cubicles as standard, one for power parts and one for
electronic parts. (Two power cubicles for redundant system) The communication boards and
control boards are standard Siemens boards mounted inside the Simoreg frame. The
overvoltage detection, field flashing and discharge circuits are located in the upper part of the
control cubicle.
In the Thyricon 500 power cubicle, two splice bars in the DC-circuit can be crossed to enable
polarity exchange on the field,
ExcitationTransfor
BOD
= VCC
3ф≈ VAC
Votage Regulator
Figure 3
Note: Field circuit breaker (DC) and a three phase field flashing supply are
optional.
The controlled rectifier bridge is used to transform the voltage and current from AC to DC.
The generator output voltage is controlled by changing the bridge(s) firing angle and
consequently the field voltage amplitude. Thus the reactive power is controlled and the
generator can produce or consume reactive power from the grid.
As the thyristor bridge is supplied directly for the generator, it is necessary to use an auxiliary
power supply for starting the machine. The residual voltage is not enough to the excitation
system starts by itself. The auxiliary power supply may come from the dc battery circuit or
from an auxiliary ac circuit, managed for the Field Flashing circuit.
On the machine starting, the Voltage Regulator builds-up the generator output voltage to the
setpoint voltage and waits the automation/synchronoscope orders to equalize the generator
voltage to the grid voltage, making possible the synchronization.
Synchronization
Sincronization
voltage (pu)
1,1
Voltage Regulator
0,9
0,7
0,5
Governor
0,3
0,1
-0,1 0 0 , 0 1 0, 0 2 0, 0 3 0, 0 4 0, 0 5 0 , 0 6
time
-0,3
-0,5
-0,7
grid
-0,9
-1,1 Generator output
Figure 4
The Figure 5 illustrates how the speed governor and voltage regulator work in order to adjust
the synchronous machine operational point.
Machine
MachineOperation Point
Operational Point
105
P [W]
90
75
Governor
60
45
30
15
Voltage Regulator
0
-100 -50 0 50 100
Q [VAR] ind
Q [VAR] cap
Figure 5
The Voltage Regulator Thyricon 500 is a compact standard product which is used in small or
medium Power Plants
As an advantage Thyricon 500 is built with standard products that are easily found worldwide
in case of maintenance, technical support or specific training.
The hardware philosophy was developed for using only one (01) bridge to supply the field
current. This single bridge is able to supply currents at least of 1,4 of nominal field generator
current. In case of redundant configuration (optional) two bridges are used but only one
bridge work per time supplying a hundred percent (100%) of the momentary Field current.
The redundant configuration is implemented using a configuration with two (02) bridges. The
control of these rectifiers can either follow the cold stand-by or the hot stand-by philosophy
(optional). The difference concerning cold and hot stand-by is how the transference between
bridges is done.
With could stand-by philosophy the system is shut down and the transference is done
manually. This means that one thyristor bridge is in operation, while the other is not in
operation. Auxiliary power to the redundant bridge is switched off by a latched relay and
ensures that no surges in auxiliary power damage both bridges.
In case of a trip of the excitation system, the HPP operator can inspect the system before he
switches over to the other bridge with a pushbutton in front of the cubicle.
The advantage of this solution is that a short-circuit on the slip-rings will not blow the fuses of
both thyristor bridges.
In the hot stand-by philosophy the transference is done automatically with the machine
running, without any disturbance at generator output voltage (bumpless transition) .One
bridge is in operation and the other is in standby. Should an internal fault on one of the
bridges occure, the other will take over the load. The advantage of this system is that you
avoid power loss in critical grids, and water loss in river hydro power plants.
Thyricon 500 can be operated locally by HMI or remotely via Profibus and conventional
signals (relays or analog signals). The selection between Local and Remote operation is
made using a key localized in front of panel.
Thyricon 500 has five (05) operating modes: three (03) in Automatic and two (02) in Manual.
Automatic modes:
9 AVR – Automatic Voltage Regulator
9 VAR – Reactive Power Regulator
9 Cosφ – Cosine φ Regulator
Manual modes:
Executed by: Checked by: Approved by: Date:
VSO Name Sign. Name Sign. Name Sign.
24.11.04
GSm GSm
Page 12 of 29
GE01-OI-MI-OperationInstructionsManual-RevA.doc
Marun II
210-6610 H102
Operation Manual Rev.
Excitation System 2007-07-23
A
The switch over from Automatic to Manual modes occurs automatically when specific fails
happen or manually for testing and commissioning.
The following descriptions focus on a standard product that aims on cost reduction,
representing the minimum requirements for a medium sized power plant. All other customer
specific requirements shall be handled with delta engineering effort.
The electronic modules from SIMOREG DC-MASTER 6RA70 are used in Thyricon 500 to
implement all control, supervision and protection functions. The basic controller card, CUD1,
is always delivered with the Simoreg converters.
Some additional electronic components are used to make the specific operation of the
automatic voltage regulator. T400 and CBP2 are optional boards from SIMOREG series
used to complement the Thyricon functions. The mainly functions of CUD1, T400, CBP2 and
the other electronic modules are described below.
2.2.1.1. T400
The T400 is an independent programmable SIMOREG Series board. It is responsible for the
control loop central processing. Its software is implemented with standard CFC/STEP7
packages.
T400 is also used for alarming, supervision and monitoring functions of the entire excitation
system.
2.2.1.2. CUD1
CUD1 (Control Unit / Direct Current) is a basic electronic board from SIMOREG converter.
CUD1 shares with T400 the control and monitoring supervision of the excitation system. It
has a PID (Proportional Integral) controller usually by-passed when T400 is working, which is
used as an emergency field current controller. It generates the thyristor bridge firing pulses.
CUD2 is an extension card for the CUD1 to achieve more I/O.
2.2.1.3. HMI
Thyricon 500 uses Siemens OP177B HMI (Human Machine Interface). All the necessary
information requested for a safe and friendly Thyricon 500 operation can be obtained on the
HMI; it is possible to choose Thyricon 500 control mode, to adjust the controller setpoint, to
access the chronological alarm list and to survey equipments status.
With the option EFCR, an optional HMI, OP1S, is assembled on the Simoreg rectifier that
enables HMI with defect OPO177B
2.2.1.4. PLC
Thyricon 500 uses a programmable logic controller from S7-300 series when a Profibus DP,
Profibus FMS or Ethernet protocol is required to provide communication with the power plant
network. The S7-300 PLC provides also, by PROFIBUS-DP, communication between the
control boards and the HMI.
2.2.1.5. CBP2
The Communication Board Profibus CBP2 is used to provide a communication channel to
external devices/networks. In other words, to exchange signals by communication channel,
Thyricon 500 uses the CPB2 as the communication port.
It links the T400 board to S7-300 CLP via PROFIBUS-DP.
The Crowbar has the function of detecting field overvoltages and firing the static switch that
is composed of two thyristors in anti-parallel connection. The static switch inserts rapidly the
Field Discharge Resistor in parallel with the field winding. The CUD1 detects the current
flowing through the shunt and start a trip condition, asking for the shutdown of the system.
When the excitation system received the trip signal, the Excitation circuit breaker opens and
the Field Discharge Contactor is forced to close reducing the static switch electrical
stressing.
So, the field discharge contactor action is coordinated with the excitation circuit breaker,
when one is opened, the other is closed.
During the Field Discharge process, the thyristors bridge firing angle is turned to 150o, that
decreases the field discharging time.
2.2.5.1. Transducers
The transducers convert electrical signals coming from the power plant to adequate
voltage/current levels for Thyricon 500 inputs.
2.2.5.2. Relays
The auxiliary relays are used to provide galvanic insulation between the Thyricon 500
electronic boards and the power plant signal cables.
The Automatic Modes are responsible for terminal voltage regulation, reactive power
regulation or power factor regulation.
The Manual Modes control the generator field current. They are used for commissioning and
as Automatic Modes backup.
The Thyricon 500 is equipped with follow-up functions that force the inactive modes to track
the active mode. This feature ensures that the transitions between the control modes,
requested by the operator or caused by a defective device, are always bumpless.
Figure 6
The range of the AVR setpoint is typically from 90% to 110% of the nominal voltage. The
setpoint can be increased or decreased locally, from the HMI in the excitation panel’s door,
or remotely by network or hard-wire connections from the control room.
The VAR Regulator increases or decreases the voltage setpoint of the AVR, now operating
as a subordinated module, in order to achieve the required reactive power supplied or
consumed by the synchronous machine.
The Manual Mode works as a backup of the Automatic Mode, but it has additional purposes
in tests like obtaining both the generator no-load and short-circuit characteristics, and also
calibrating the protection devices during commissioning.
2.3.2. Limiters
A limiter is an element that modifies or replaces an excitation control function when
predetermined circumstances have been reached. Limiters act in a way of avoiding
inappropriate operational conditions of the excitation system, generator or step-up
transformer.
Limiter interventions are properly signalized; however, they do not request trip to the
automation or protection systems.
The curve for the UExc can be defined with up to 6 points. When the reactive power is
outside this curve the UEXc increase the setpoint for the AVR and with that increasing the
reactive power such that the operating point is returned to the positiv side of the limiter.
The figure below shows the capabilities curve for the synchronous generator and an example
of settings for the underexcitation limiter with three points. The Loss of Excitation Protection
will have a setting in between 3 Practical stability and 5 Underexcitation limiter.
Active output
Underexcited 0,5
Overexcited
B
3
1
4
A
1,0 0,5 0,5 1,0 P.U.
Reactive output
If [P.U.]
prospective value of
field current
1.5 Case 1
1.4
Case 2
1.1
1.0
10 t [s]
By activated Volts / Hertz limiter the influence of the Volts / Hertz limiter reduces the upper
limit of generator reference setter.
At nominal frequency the VHz limiter have no influence. Normal setting is that the reference
for the voltage regulator is reduced with 1% with 1% reduction in the frequency
• at rated frequency 50 Hz the reference value range is 90% up to 110%
• at frequency 45 Hz the reference value range is 90% up to 100%
• at frequency 40 Hz the reference value is 90%
Stator overcurrent combined with capacitive stator current demand increasing of the
excitation current; on the other hand, stator overcurrent combined with inductive stator
current demand decreasing of the excitation current.
The Generator Overcurrent limiter works with an adjustable time delay to admit short
overcurrents of the generator for supporting the grid.
The GOC has an adjustablle deadzone near Cosφ=1. This is to avoid oscillation between
over and underexcitated.
If the reactive current is within this deadband and the generator current still is too high, the
active current must be decreased with the turbine governor.
Active current
No operation near
cos phi=1
A B
generator
current
Reactive current
Deadzone +/- 10%
2.4. Interface
The excitation system has signal interfaces with:
• Automation system
• Protection System
• Excitation Transformer
Most signals are exchanged by the serial communication channel but the main signals are
hardwired through potential free contacts to allow the system working without serial
communication. Transducers, relays and optical interface are used to provide galvanic
isolation between the external equipment and the Thyricon 500 panels.
Analog signals for remote indication (actual setpoint, field current and field voltage) are
supplied in current signals from 4 to 20 mA, with galvanic isolation, available in the screw
terminals of the excitation system.
All signals and status generated and processed internally at the Thyricon 500 are supplied by
serial communication PROFIBUS DP. The standard signals are showed in the I/O list.
There is a HMI in front of the cubicle which allows local operation and maintenance.
• Concerning the maximum field voltage (Ceiling Voltage) supplied by Thyricon 500, it
is assumed the following factors:
o Positive Ceiling Voltage: 2,0 pu (higher value on request).
o Negative Ceiling Voltage: -1,6 pu (higher value on request).
Note: 1,0 pu = Nominal field generator voltage.
• For maximum excitation current it is defined to 140% of the nominal field generator
current for 10 seconds as a standard (higher value on request).
Thyricon 500
Static excitation system
Table of content:
3.1 General 3
3.1.1 Application 3
3.2 Design 4
3.2.1 Password 4
3.4 Screens 8
3.4.1 Main page 8
3.4.2 System settings 9
3.4.3 PLC diagnostic buffer 10
3.4.4 Operational page 11
3.4.4.1 Per unit presentation 12
3.4.4.2 Setpoint 13
3.4.5 Trend curves 14
3.4.6 Limiters 15
3.4.7 Alarm list 16
3.4.8 Temperatures 17
3.4.9 Transformer temperature 18
3.1 General
SIMATIC-HMI OP-177B graphic operator panel is based on the Microsoft Windows CE
operating system.
3.1.1 Application
The panel is mounted in front of the Thyricon panel left door and directly linked to a
SIMATIC-S7 300 series CPU through the standard SIMATIC-S7 MPI bus. The MPI bus is a
local network inside the Thyricon cubicle, independent from surrounding networks. The
SIMATIC-S7 CPU communicates both internally and externally on the Profibus DP network.
The figure above shows a section from the network design application in the STEP7
programming tool for SIMATIC-S7. The section describes the two internal networks in
Thyricon. The MPI is for visualisation and programming, 187.5 Kbps. The Profibus DP bus is
for process data, 1.5 Mbps.
3.2 Design
The figure below shows the operator panel in operation.
3.2.1 Password
Enter password to navigate certain areas in OP177B. Entered password expires after 5
minutes. The password is can be adjusted according to customers specifications.
The most important functions are placed directly at function keys, which are common
regardless of the window chosen. Some of the keys are short-cuts to certain
pictures/windows, and some keys set direct commands to the process.
F5 LIMIT LIST Status screen with indication for limiter functions inside
the regulator SW-
F7 TREND Open trend screen with curves trace at time around the
PAGE latest trip condition.
K13 TEMP PAGE Temperatures inside cubicle, on heatsinks and calculated
rotor temperature.
K12 MAIN PAGE Start page/ main page.
3.4 Screens
s
3.4.1 Main page
After an OP177B reboot the main page screen appears. The main page screen is also linked
to the key K12. The screen does not contain any direct functions, but provides access to
system settings, PLC diagnostic buffer and an overview of the external signals received from
the automation system
In addition the main page contains actual date and time. This is the system time fetched from
the SIMATIC-S7 CPU. The time can be synchronized once a night, through the Profibus DP,
from the automation system. Default time is 03:00.
9 F9
10 F9
11 F9
12 13 14
FT1 FT1
FT2 FT3
FT1 FT4
FT1 FT5 FT6
The system setting screen is not in use during normal operation of Thyricon. The screen
enables the operator to change certain settings for the operator panel.
This screen contains actual time, including functionality for time and date setting of the plc
and the operator paneø. These values are changed by inserting correct numbers in the
fields. The numbers are entered with the keyboard that appears when pressing on the
desired field. By pressing the ‘Set Time’ the plc and operator panel clock is set according to
the new values. All time information is handled by the plc, the operator panel is thus updated
whenever the plc clock is set.
9 F9
10 F9
11 F9
12 13 14
FT1 FT1
FT2 FT3
FT1 FT4
FT1 FT5 FT6
This screen is not in used in normal operation, but provides access to the SIMATIC-S7 PLC
diagnostic buffer. This is for remote diagnosis of the S7 CPU, and provides the operator
information about fault causes.
9 F9
10 F9
11 F9
12 13 14
FT1 FT1
FT2 FT3
FT1 FT4
FT1 FT5 FT6
This screen is opened by the F1 key and contains the most important measurements,
operational mode, and also the status of the State Machine within the regulator. Through the
functional keys it is also possible to view measurements presented in per unit as either
numeric values or bar graphs. The setpoint for all different states are also accessible from
this screen.
9 F9
10 F9
11 F9
12 13 14
FT1 FT1
FT2 FT3
FT1 FT4
FT1 FT5 FT6
These screens are only reached from the operational page, by pressing functional key
‘FT1’ for textual presentation or ‘FT2’ for bar graph presentation. The measured values are in
the per unit value system. The base for the per unit is related to the generators nominal
ratings, except for the cosine phi which is the actual cosine phi of the generator.
9 F9
10 F9
11 F9
12 13 14 9 F9
10 F9
11 F9
12 13 14
FT1 FT1
FT2 FT1
FT3 FT1
FT4 FT5 FT6 FT1 FT1
FT2 FT1
FT3 FT1
FT4 FT5 FT6
3.4.4.2 Setpoint
This screen is only reached from the operational page, by pressing functional key ‘FT3’. Here
the operator can initiate and activate a specified setpoint. This is possible in all regulation
modes (except FCR/EFCR), when the LOCAL state is active. The screen also contains
information, such as regulator mode, actual setpoint and the actual process value for each
regulator mode.
The value is entered through the keyboard that appears after pressing in the field related to
the setpoint. The setpoint change is executed by pressing functional key ‘FT5’.
9 F9
10 F9
11 F9
12 13 14
FT1 FT1
FT2 FT3
FT1 FT4
FT1 FT5 FT6
This screen is reached by pressing the ‘F7’ key at the bottom left of the operator panel
display area. The values are presented in per unit and the total time for the trend display is
20 seconds. This is not a real time trend, but is read from the plc after certain conditions are
met. This gives a historical view of the conditions related to the last trip command sent to the
excitation system.
The plc starts buffering the measurement to its internally memory when the excitation
breaker closes. If the breaker opens without the system receiving an excitation off command
a trip is defined. The buffered data is transferred to the trend view, along with the
measurements following the trip until the trend view is filled. The number of samples in the
buffered area, the time between each sample and system date and time for the last curve is
also displayed.
9 F9
10 F9
11 F9
12 13 14
FT1 FT1
FT2 FT3
FT1 FT4
FT1 FT5 FT6
The trend view is scaled automatically according to the maximum value within the trend, to
give the best possible presentation the curves are defined as follows:
Symbol Description y-axis Line type Color
If Field current Left Solid Black
Uf Field voltage Right Solid White
Ug Generator voltage Left Dash Black
Q Reactive power Right Dash White
The screen also contains touch keys for scrolling forwards and backwards within the trend as
well as zooming in and out.
The plc stores the values for the trend if power is shut off, thus the last instance can be
retrieved by opening the trend screen later. Please note that the trend view will define an
excitation off command from the OP1S as a trip and trend the measurements accordingly.
3.4.6 Limiters
This screen is opened by the ‘F5’ key. It contains operation status for the five most important
limiters in the Thyricon excitation system. While a limiter is active the LED on the ‘F3’ key
flashes. Details about which limiter is active is indicated within this screen.
9 F9
10 F9
11 F9
12 13 14
FT1 FT1
FT2 FT3
FT1 FT4
FT1 FT5 FT6
This screen is opened by the <’F3’ key. Fault information is collected from the DC master
through the CBP2 interface card 400 card in several levels.
9 F9
10 F9
11 F9
12 13 14
FT1 FT1
FT2 FT3
FT1 FT4
FT1 FT5 FT6
When a new alarm is triggered it enters the alarm view with the active state (K). If the alarm
is reset in the DC master by the ‘K2’ key, and the trigger is no longer active, the alarm will
change to the active / deactivated state (KG). By acknowledging the alarm with the ‘FT1’ key
the alarm changes to the active / deactivated acknowledged state (KGQ) and is removed
from the alarm view.
If an alarm is in the active (K) state when ‘FT1’ is pressed the alarm changes to the
active / acknowledged state (KQ). The alarm will then be removed from the alarm view when
it is deactivated in the DC master (Reset) and changes to the KGQ state.
3.4.8 Temperatures
This screen is activated by the ‘K13’ key, and presents cubicle, heatsink and also calculated
rotor temperature. The values on the left hand side, in the column “Measured”, are actual
values. The two other columns are trip and warning levels for the three different
measurements. All values in this screen are read from the T400 card via the Profibus DP
interface. All values are presented in degrees Celsius.
9 F9
10 F9
11 F9
12 13 14
FT1 FT1
FT2 FT3
FT1 FT4
FT1 FT5 FT6
9 F9
10 F9
11 F9
12 13 14
FT1 FT1
FT2 FT3
FT1 FT4
FT1 FT5 FT6
Thyricon 500
Static excitation system
Table of content:
The OP1S is installed as a backup for the OP170B and for the EFCR-mode.
Key Function
In all mode you can adjust the set point for voltage or field current using the arrow-keys up
and down. Note: that set point limits (both upper and lower) are programmed, and this means
that one will not get a response if pressing ”Voltage up” while the regulator has reached the
upper or lower limit.
Faults in the T400-card (c701-c747) will not appear in the OP1S. To read out these fault it’s
necessery to go int the parameter menu.
The fault messages will be reset once the <RESET>-button on OP1S or OP170B is pressed.
It is therefore crucial for further diagnosis that these are read at trip; fault on Thyricon. When
notet, you can press the <RESET>-button in order to succesfully excite again if the Thyricon
fault was temporary.