Kidde Engineered

Fire Suppression System


Designed for use with 3M™ Novec™ 1230 Fire Protection Fluid
Effective: June 2015
3M™ Novec™ 1230 Fire Protection Fluid K-45-1900

FEATURES
• People Safe at Concentration Levels Required to • Electrically Non-Conductive
Extinguish Fire • Space Saving; Quantity of Agent Needed to Extin-
• Zero Ozone Depletion Potential guish Fires Typically Required Minimal Cylinders,
• Atmospheric Lifetime of Five Days thus Minimal Space Required
• Colorless, with Low Odor and No Particulate or Oily • UL Listed, ULC Listed, and FM Approved for use with
Residue Allowing for Minimal Business Disruption Novec 1230 Systems
After a Discharge

EXTINGUISHING AGENT fluid as acceptable for use as a total flooding agent in


3M™ Novec™ 1230 Fire Protection Fluid (Novec 1230) occupied spaces with specific limitations. Refer to the
is a fluorinated ketone (FK-5-1-12) Dodecafluoro-2-meth- SNAP program rules or NFPA 2001 for more information.
ylpentan-3-one) compound of carbon, fluorine and oxy- Novec 1230 fluid has been judged acceptable by the U.S.
gen (CF3CF2C(O)CF(CF3)2). It is colorless, electrically EPA for use in occupied spaces when used in accor-
dance with the guidance of NFPA 2001. In accordance
non-conductive and has a low odor. It suppresses fire pri-
with NFPA 2001, Novec 1230 fluid designed for use with
marily by physical mechanisms due to its relatively high
agent vapor concentrations up to ten volume percent in
heat capacitywith minimal effect on the available oxygen.
air are permitted. See NFPA 2001, Sect. 1-6, Safety.
This allows people to see and breathe, permitting them to
leave the fire area safely. Although Novec 1230 fluid has negligible toxicity in con-
centrations needed to suppress most fires, certain safety
Novec 1230 fluid is acceptable for use in occupied
considerations must be observed when applying and
spaces when used in accordance with the United States
handling the agent. For example, Novec 1230 fluid is a
Environmental Protection Agency (EPA) Significant New
liquid at room temperature and has been superpressur-
Alternatives Policy (SNAP) program rules.
ized with dry nitrogen. Upon release to atmospheric pres-
Although Novec 1230 fluid is considered non-toxic to sure (e.g., from nozzles) the liquid flash evaporates at a
humans in concentrations necessary to extinguish most low temperature. Thus, nozzles must be located to avoid
fires, certain safety considerations should be observed direct impingement on personnel.
when applying and handling the agent. The discharge of
DECOMPOSITION
Novec 1230 fluid may create a hazard to people from the
decomposition products which result when the agent is When Novec 1230 fluid is exposed to high temperatures,
exposed to fire or other hot surfaces. Exposure to the such as what may be expected in a flame front, hazard-
agent is generally of less concern than is exposure to the ous products of thermal decomposition (halogen acids)
decomposition products. Unnecessary exposure to the are produced. If the Novec 1230 fluid is discharged in 10
agent or the decomposition products should be avoided. seconds or less, flames will be extinguished rapidly and
the amount of by-products produced will be minimal.
TOXICITY
CLEANLINESS
Unnecessary exposure to clean agents is to be avoided
in accordance with the requirements of NFPA-2001. As Novec 1230 fluid is clean and leaves no residue, thereby
such, upon operation of a system pre-discharge alarm, eliminating costly after-fire clean-up and keeping expen-
all personnel should immediately exit the protected sive downtime to a minimum. Most materials such as
space. In no case shall personnel remain in a room in steel, stainless steel, aluminum, brass and other metals
which there is a fire. In the very unlikely instance where a as well as plastics, rubber and electronic components are
clean agent system should discharge unexpectedly into unaffected by exposure to Novec 1230 fluid.
an occupied room, all personnel should proceed in a APPROVALS
calm and orderly manner to an exit and leave the room.
Novec 1230 fluid complies with the NFPA Standard 2001,
Novec 1230 fluid has been evaluated for cardiac sensiti- Standard for Clean Agent Fire Extinguishing Systems,
zation in accordance with test protocols approved by the EPA SNAP Program, (Significant New Alternate Policy),
United States Environmental Protection Agency (U.S. Underwriters Laboratories, Inc. (UL) FM Approvals (FM).
EPA). The EPA’s SNAP Program classifies Novec 1230

1
USE
Kidde Engineered Fire Suppression Systems Designed
Table 3: Novec 1230 Fluid Design
for use with 3M™ Novec™ 1230 Fire Protection Fluid are
Concentrations
designed to extinguish fires in specific hazards or equip-
ment located where an electrically non-conductive agent Fuel Design Concentration, % v/v
is required, where agent cleanup creates a problem,
where extinguishing capability with low weight is a factor 1-Butane 6.37
and where the hazard is normally occupied by personnel.
1-Propanol 7.02
Novec 1230 fluid is an acceptable alternative to Halon
and is approved by the EPA and NFPA for use in fire sup- 2,2,4-trimethylpentane 6.11
pression systems.
2-butoxyethanol 6.76

Acetone 5.59
Table 1: Novec 1230 Fluid Physical Properties
Acetonitrile 4.20
Chemical Formula CF3CF2C(O)CF(CF3)2 Commercial Heptane 5.72
Molecular Weight 316.04 Commercial Hexanes 5.59
Freezing Point -162.4°F (-108°C) Cyclohexane 5.85
Boiling Point at 1 Atm. 120.6°F (49.2°C) Cyclopentanone 5.98
Critical Temperature 335.6°F (168.7°C) Denatured Alcohol 6.89
(92.2% EtOH, 4.6% IPA,
Critical Density 39.91 lb./ft.3 (639.1 kg/m3) and 3.1% MeOH)
Critical Pressure 270.44 PSIA (1865 kPA) Diesel Fuel 4.42
Critical Volume 0.0251 ft.3/lbm (494.5 cc/mole) Diethl Ether 6.37

Ozone Depletion Potential 0 Ethanol 7.15

Global Warming Potential 1 Ethyl Acetate 6.11

Gasoline-87 oct. 5.85


unleaded

Table 2: Novec 1230 Fluid Toxicity Properties Hexene 5.98

Novec 1230 Fluid Toxicity Properties Isooctane 6.11

NOAEL 10.0% Isopropanol Alcohol 6.37


(No Observable Adverse Effect Level)
Methane 7.28
LOAEL 10.0% >
Methanol 8.45
(Lowest Observable Adverse Effect Level)
Methyl Ethyl Ketone 5.85

Methyl Isobutyl Ketone 5.72

Methyl Tert Butyl Ether 5.95

n-Heptane 5.85

n-Pentane 6.11

Octane 5.72

Propane 7.54

Pyrrolidine 6.11

2 K-45-1900

Effective: June 2015


Table 3: Novec 1230 Fluid Design
Concentrations (Continued)

Fuel Design Concentration, % v/v

Technical Heptane 5.59

Tetrahydrofuran 6.50

Toluene 4.55

Transformer Oil 5.85

• Minimum Design Concentration for Class A and de-


energized Class C Fires = 4.2%
• Design concentrations for Class B Fire are shown in
the above table and include a 30% safety factor from
the minimum extinguishing concentration.

K-45-1900 3
Effective: June 2015
Kidde Engineered
Fire Suppression System
Designed for use with 3M™ Novec™ 1230 Fire Protection Fluid
Effective: June 2015
Cylinder and Valve Assemblies, 350 lb. Capacity K-45-2050 Rev AC

FEATURES
• UL Listed, ULC Listed, and FM Approved for use with
Novec 1230 Systems

P/N: 45-10035X-001 ORDERING INFORMATION

VALVE OUTLET
Part Number Description
30°
45-100350-001 STD

45-100351-001 with LLI

MATERIALS
PLAN VIEW
• Valve Body: Brass
SAFETY CAP CYLINDER VALVE • Cylinder: Steel, Painted Red
LIQUID LEVEL
INDICATOR
LIFTING LUGS

CYLINDER
58.36 in.
(1482 mm)

CYLINDER
53.14 in. NAMEPLATE
(1350 mm)

16.00 in. DIA.


(406 mm)

Note:

1. The safety cap must be installed on the valve outlet


at all times, except when the cylinders are connected
to the system piping, or being filled. The safety cap
must not be removed from its chain.
2. See K-45-2070 for additional information.

Kidde is a registered trademark of Kidde-Fenwal, Inc.


3M and Novec are trademarks of 3M.
All other trademarks are property of their respective owners.

This literature is provided for informational purposes only. KIDDE-


FENWAL, INC. assumes no responsibility for the product’s suitability for
a particular application. The product must be properly applied to work
correctly.If you need more information on this product, or if you have a Kidde Fire Systems
particular problem or question, contact KIDDE-FENWAL, Inc. 400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
Fax: 508.881.8920
©2015 Kidde-Fenwal, Inc.
www.kiddefiresystems.com
Kidde Engineered
Fire Suppression System
Designed for use with 3M™ Novec™ 1230 Fire Protection Fluid
Effective: June 2015
Cylinder and Valve Assemblies,
600 lb. (271.1 kg) Capacity K-45-2060 Rev AC

FEATURES
• UL Listed, ULC Listed, and FM Approved for use with
Novec 1230 Systems

P/N: 45-10060X-001 ORDERING INFORMATION

Part Number Description


VALVE OUTLET

30° 45-100600-001 STD

45-100601-001 with LLI

MATERIALS

• Valve Body: Brass


PLAN VIEW
• Cylinder: Steel, Painted Red
SAFETY CAP CYLINDER VALVE

LIQUID LEVEL INDICATOR

LIFTING LUGS

CYLINDER
56.72 in.
(1441 mm)

50.51 in.
(1283 mm) CYLINDER
NAMEPLATE

22.00 in. DIA


(559 mm)

Note:

1. The safety cap must be installed on the valve outlet


at all times, except when the cylinders are connected
to the system piping, or being filled. The safety cap
must not be removed from its chain.
2. See K-45-2070 for additional information.

Kidde is a registered trademark of Kidde-Fenwal, Inc.


3M and Novec are trademarks of 3M.
All other trademarks are property of their respective owners.

This literature is provided for informational purposes only. KIDDE-


FENWAL, INC. assumes no responsibility for the product’s suitability for
a particular application. The product must be properly applied to work
correctly.If you need more information on this product, or if you have a Kidde Fire Systems
particular problem or question, contact KIDDE-FENWAL, Inc. 400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
Fax: 508.881.8920
©2015 Kidde-Fenwal, Inc.
www.kiddefiresystems.com
Kidde Engineered
Fire Suppression System
Designed for use with 3M™ Novec™ 1230 Fire Protection Fluid Effective: June 2015

Cylinder Valve Data Sheet K-45-2080 Rev AC

FEATURES
• UL Listed, ULC Listed, and FM Approved for use with
Novec 1230 Systems

P/N: 45-1X0000-000
TECHNICAL DATA
CAP

• Working Pressure: 360 to 609 PSIG

BODY
• Proof Pressure: 1000 PSIG
SLAVE CYLINDER
ACTUATION PORT • Burst Pressure: 2000 PSIG
1/8" NPT
• Temperature Range: 0°F to 130°F (-18°C to 54°C)
A
SAFETY
DISC
PRESSURE
GAUGE MATERIALS

B • Valve Body: Brass


SAFETY CHAIN ACTUATION PORT
• Piston: Brass
CONTROL HEAD
VENT HOLE CONNECTION
• Finish: Natural

DISCHARGE
• Seat: Rubber
OUTLET PORT PISTON

SUPERVISORY
PRESSURE
SWITCH
SAFETY CAP CONNECTION

SEAT

P/N Valve Size A B C D E F

45-140000-000 1-1/2 in. 7.63 in. 4.83 in. 5.22 in. 754-900 PSI 242461 9.9 lb.
(194 mm) (123 mm) (133 mm) (52-62 bar) (4.5 kg)

45-150000-000 2 in. 8.80 in. 5.32 in. 6.28 in. 798-972 PSI 264925 15 lb.
(224 mm) (135 mm) (159 mm) (55-67 bar) (6.8 kg)

Kidde is a registered trademark of Kidde-Fenwal, Inc.


3M and Novec are trademarks of 3M.
All other trademarks are property of their respective owners.

This literature is provided for informational purposes only. KIDDE-


FENWAL, INC. assumes no responsibility for the product’s suitability for
a particular application. The product must be properly applied to work
correctly.If you need more information on this product, or if you have a Kidde Fire Systems
particular problem or question, contact KIDDE-FENWAL, Inc. 400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
Fax: 508.881.8920
©2015 Kidde-Fenwal, Inc.
www.kiddefiresystems.com
Kidde Engineered
Fire Suppression System
Designed for use with 3M™ Novec™ 1230 Fire Protection Fluid

Effective: April 2017


Cylinder Data Sheet K-45-2070 Rev AD

FEATURES
• UL Listed, ULC Listed, and FM Approved for use with
Novec 1230 Systems

Empty
Fill Range Gross Weight Height Diameter Volume
Weight With
Part Number
LLI
lb. kg lb. kg Min. Fill Max. Fill in. cm in. cm ft.3 m3

45-100010-001 6 to 11 2.7 to 25 11 31 14.1 36 16.3 No 17.3 44 7.07 18 0.167 0.0047


5.0

45-100020-001 12 to 23 5.4 to 31 14 43 19.5 54 24.5 No 24.97 64 7.07 18 0.289 0.0081


10.4

45-100040-001 20 to 40 9.1 to 38 17 58 26.3 78 35.4 No 26.76 68 9.00 23 0.572 0.0162


18.1

45-100070-001 35 to 70 15.9 to 52 24 87 39.5 132 59.9 No 38.83 99 9.00 23 1.000 0.0283


31.8

45-100121-001 63 to 28.6 to 98 45 161 73.0 223 101.2 Yes 35.93 92 12.75 33 1.788 0.0506
125 56.7

45-100125-001 63 to 28.6 to 98 45 161 73.0 223 101.2 No 35.93 92 12.75 33 1.788 0.0506
125 56.7

45-100200-001 100 to 45.4 to 133 60 233 105.7 333 151.0 No 52.75 134 12.75 33 2.859 0.0810
200 90.7

45-100201-001 100 to 45.4 to 133 60 233 105.7 333 151.0 Yes 52.75 134 12.75 33 2.859 0.081
200 90.7

45-100350-001 175 to 79.4 to 201 91 376 170.6 551 249.9 No 58.36 149 16.00 41 5.000 0.1416
350 158.8

45-100351-001 175 to 79.4 to 203 92 378 171.5 551 249.9 Yes 58.36 149 16.00 41 5.000 0.1416
350 158.8

45-100600-001 300 to 136.1 to 362 165 662 300.3 962 436.4 No 58 147 22.00 56 8.680 0.2460
600 272.1

45-100601-001 300 to 136.1 to 362 165 667 302.5 962 436.4 Yes 58 147 22.00 56 8.680 0.2460
600 272.1

45-100900-001 455 to 206.3 to 505 230 960 435.5 1415 641.8 No 70 178 24.00 61 13.00 0.3680
910 412.7

45-100901-001 455 to 206.3 to 505 230 960 435.5 1415 641.5 Yes 70 178 24.00 61 13.00 0.3680
910 412.7

Note: Engineered Systems have a fill density range of 35 lb./ft.3 to 70 lb./ft.3

EXPORT INFORMATION (USA)


Jurisdiction: EAR
All trademarks are the property of their respective owners.
Classification: EAR99
This document does not contain any
This literature is provided for informational purposes only. KIDDE-FENWAL, INC. believes this data to be export controlled technical data.
accurate, but it is published and presented without any guarantee or warranty whatsoever. KIDDE-FENWAL,
INC. assumes no responsibility for the product's suitability for a particular application. The product must be
properly applied to work correctly. If you need more information on this product, or if you have a particular Kidde Fire Systems
problem or question, contact KIDDE-FENWAL, INC., Ashland, MA 01721 USA. Telephone: (508) 881-2000. 400 Main Street
Ashland, MA 01721 USA
©2017 Kidde-Fenwal, Inc. Ph: 508.881.2000
Fax: 508.881.8920
www.kiddefiresystems.com
Kidde ECS Fire Suppression System
Component Description
Effective: June 2014
Cylinder Mounting Straps K-90-8130 Rev BA

FEATURES
• For Use with UL Listed, ULC Listed and FM Approved Systems • RoHS Compliant

CYL. O.D. A B C D E F
CYL.
PART NO.
SIZE
in. mm in. mm in. mm in. mm in. mm in. mm in. mm

WK-283945-000 10, 20 7.07 1.80 6.48 165 9.62 244 8.62 219 1.00 25 2.78 71 .437 11.1

WK-283934-000 40, 70 9.00 229 8.16 207 11.69 297 10.69 272 1.00 25 3.50 89 .437 11.1

292971 200 13.60 345 13.09 332 17.06 433 15.44 392 1.75 44 6.06 154 .625 15.9
pre-3/98

06-235317-001 125, 200 12.75 324 12.93 329 16.18 411 14.56 370 1.75 44 5.59 142 .625 15.9

WK-281866-000 350 16.00 406 15.5 394 19.5 495 17.88 454 1.75 44 6.06 154 .625 15.9

WK-294651-000 600 22.00 559 21.56 548 25.75 654 24.12 613 1.75 44 10.25 260 .625 15.9

06-236125-001 900 24.00 610 23.75 603 27.75 705 26.00 660 1.75 44 12.13 308 .625 15.9

MATERIALS
• Steel, Painted Black SAE 1020

COMPATIBILITY

For Use
Series
With

Kidde ECS HFC-227ea X

Kidde ECS Advanced Delivery FM-200® X

FM-200 is a registered trademark of E.I. du Pont de Nemours and Company.


This literature is provided for informational purposes only. KIDDE- Kidde is a registered trademark of Kidde-Fenwal Inc. All other trademarks are
FENWAL, INC. assumes no responsibility for the product’s suitability for the property of their respective owners.
a particular application. The product must be properly applied to work
correctly.If you need more information on this product, or if you have a Kidde Fire Systems
particular problem or question, contact KIDDE-FENWAL, Inc. 400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
Fax: 508.881.8920
©2014 Kidde-Fenwal, Inc.
www.kiddefiresystems.com
Kidde ECS Fire Suppression System
Component Description
Effective: June 2014
Valve Outlet Adapters K-90-2100 Rev BA

FEATURES
• For Use with UL Listed, ULC Listed and FM Approved Systems • RoHS Compliant

P/N: WK-28390X-000

B (VALVE OUTLET CONNECTION)

D C

A (SYSTEM PIPE CONNECTION)

Note: For direct connection of cylinder valve to distribution piping.

MATERIAL
• Brass

ORDERING INFORMATION

Dimensions
Part Number Size (in inches)

A B C D
1-1/2 1.874
WK-283904-000 1 1/2 2.69 2.50 HEX
11-1/2 NPT 12 UNJ

2 2.500
WK-283905-000 2 3.12 3.00 HEX
11-1/2 NPT 12 UNJ

2-1/2 3.00
WK-283906-000 2 1/2 3.00 3.75 HEX
8 NPT 12 UNJ

COMPATIBILITY

For Use
Series
With

Kidde ECS HFC-227ea X

Kidde ECS Advanced Delivery FM-200® X

FM-200 is a registered trademark of E.I. du Pont de Nemours and Company.


This literature is provided for informational purposes only. KIDDE- Kidde is a registered trademark of Kidde-Fenwal Inc. All other trademarks are
FENWAL, INC. assumes no responsibility for the product’s suitability for the property of their respective owners.
a particular application. The product must be properly applied to work
correctly.If you need more information on this product, or if you have a Kidde Fire Systems
particular problem or question, contact KIDDE-FENWAL, Inc. 400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
Fax: 508.881.8920
©2014 Kidde-Fenwal, Inc.
www.kiddefiresystems.com
Kidde ECS Fire Suppression System
Component Description
Effective: June 2014
Electric Control Head K-90-8010 Rev BA

FEATURES
• For Use with UL Listed, ULC Listed and FM Approved Systems

P/N: WK-890181-000

Ordering Information

Part Number Control Head

Voltage Current

WK-890181-000 24 VDC 2.0A

COMPATIBILITY

For Use
Series
With

Kidde ECS HFC-227ea X

Kidde ECS Advanced Delivery FM-200® X

FM-200 is a registered trademark of E.I. du Pont de Nemours and Company.


This literature is provided for informational purposes only. KIDDE- Kidde is a registered trademark of Kidde-Fenwal Inc. All other trademarks are
FENWAL, INC. assumes no responsibility for the product’s suitability for the property of their respective owners.
a particular application. The product must be properly applied to work
correctly.If you need more information on this product, or if you have a Kidde Fire Systems
particular problem or question, contact KIDDE-FENWAL, Inc. 400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
Fax: 508.881.8920
©2014 Kidde-Fenwal, Inc.
www.kiddefiresystems.com
Kidde ECS Fire Suppression System
Component Description
Effective: June 2014
Electric Control Head K-90-6011 Rev BA

FEATURES
• For Use with UL Listed, ULC Listed and FM Approved Systems

P/N: WK-890181-000 COMPATIBILITY

For Use
.750 NPT TO FLEXIBLE Series
CONDUIT ADAPTER With

Kidde ECS HFC-227ea X

FLEXIBLE Kidde ECS Advanced Delivery FM-200® X


CONDUIT
PLUS OR HOT
CONNECTION OPTIONAL CONNECTION
(TERMINAL #3) FOR MICROSWITCH
(TERMINAL #2)

MINUS, NEUTRAL,
OR GROUND CONNECTION
TERMINAL STRIP (TERMINAL #1)

MICROSWITCH

SWIVEL NUT
MICROSWITCH LEVER

CAM

INDICATOR AND
RESET STEM

Part Number Control Head


Voltage Current
WK-890181-000 24 VDC 2.0A

FM-200 is a registered trademark of E.I. du Pont de Nemours and Company.


This literature is provided for informational purposes only. KIDDE- Kidde is a registered trademark of Kidde-Fenwal Inc. All other trademarks are
FENWAL, INC. assumes no responsibility for the product’s suitability for the property of their respective owners.
a particular application. The product must be properly applied to work
correctly.If you need more information on this product, or if you have a Kidde Fire Systems
particular problem or question, contact KIDDE-FENWAL Inc. 400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
Fax: 508.881.8920
©2014 Kidde-Fenwal, Inc.
www.kiddefiresystems.com
Kidde Engineered
Fire Suppression System
Designed for use with 3M™ Novec™ 1230 Fire Protection Fluid
Effective: June 2015

360 Degree Pendant Nozzle Data Sheet K-45-2140 Rev AE

FEATURES
• UL Listed, ULC Listed, and FM Approved for use with Novec 1230 Systems

P/N: 45-1946XX-XXX (Stainless Steel)


P/N: 45-1947XX-XXX (Brass)

A B

C
-XXX

Note: A selection of orifices are available for each nozzle size and make. Consult the Kidde Engineered Fire Sup-
pression System Design, Installation, Operation, and Maintenance Manual for details.

Dimension
Nozzle Size
A B C

1/4 in. (6 mm)* 1.91 in. (49 mm) 1.03 in. (26 mm) 0.88 in. (22 mm)

3/8 in. (10 mm)* 2.03 in. (52 mm) 1 in. (25 mm) 1.19 in. (30 mm)

1/2 in. (13 mm) 2.25 in. (57 mm) 1.13 in. (29 mm) 1.38 in. (35 mm)

3/4 in. (19 mm) 2.69 in. (68 mm) 1.38 in. (35 mm) 1.63 in. (41 mm)

1 in. (25 mm) 2.88 in. (73 mm) 1.63 in. (41 mm) 1.94 in. (49 mm)

1-1/4 in. (32 mm) 3.29 in. (83 mm) 2 in. (51 mm) 2.38 in. (60 mm)

1-1/2 in. (38 mm) 3.63 in. (92 mm) 2.25 in. (57 mm) 2.69 in. (68 mm)

2 in. (51 mm) 4.50 in. (114 mm) 3 in. (76 mm) 3.50 in. (89 mm)

Note: * Nozzles Sizes marked with an * are not UL Listed or FM Approved.

Kidde is a registered trademark of Kidde-Fenwal, Inc.


3M and Novec are trademarks of 3M.
All other trademarks are property of their respective owners.

This literature is provided for informational purposes only. KIDDE-


FENWAL, INC. assumes no responsibility for the product’s suitability for
a particular application. The product must be properly applied to work
correctly.If you need more information on this product, or if you have a Kidde Fire Systems
particular problem or question, contact KIDDE-FENWAL, Inc. 400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
Fax: 508.881.8920
©2015 Kidde-Fenwal, Inc.
www.kiddefiresystems.com
Kidde ECS Fire Suppression System
Component Description
Effective: June 2014
Supervisory Pressure Switch,
1-1/2”, 2”, and 3” Valve, P/N: 06-118262-001 K-90-9047 Rev BA

FEATURES
• Both Normally Open and Normally Closed Configuration • UL Listed and FM Approved
with One Unit • CRUUS Recognized Component (US and Canada)
• Suitable for 10 lb. Through 900 lb. Kidde ECS Systems

DESCRIPTION
The Kidde ECS System cylinder supervisory pressure
switch is intended to detect a fall in pressure in the agent
cylinder. The cylinder supervisory pressure switch can be
wired for either normally open or normally closed opera-
tion, depending on installation requirements. This cylin-
der supervisory pressure switch can be installed on
Kidde Engineered System cylinders, 10 lb. through 900
lb. size. For 3” valves manufactured prior to May 1, 2013
use Supervisory Pressure Switch P/N: 06-118263-001.
OPERATION
When the pressure in the agent container drops from the
standard charge pressure of 360 psi (25 bar) to below
288 psi (19.86 bar) the switch operates. If wired in the NC
(open-under-pressure) configuration the resulting pres-
sure drop will cause the contacts to close. When con-
nected to a monitored circuit of a suppression control ORDERING INFORMATION
panel the switching will result in an alarm or trouble con- The cylinder supervisory pressure switch offers com-
dition. bined normally opened and normally closed functionally.
The part number for ordering the cylinder supervisory
Note: If the temperature of the cylinder contents drop
pressure switch is 06-118262-001.
close to a temperature of 32°F (0°C) or less the
pressure in the cylinder will be equal to or less SPECIFICATIONS
than 288 psi (19.86 bar) and the switch will oper- Setting: 288 psi (19.86 bar) on
falling pressure
ate. However the minimum operating tempera- Electrical rating: 5 Amps, 250 Vac
ture of the system is 32°F (0°C). Wire color coding: Blue = Normally Open Black =
Normally Closed Violet =
INSTALLATION Common
The supervisory pressure switch can be installed on a Operating temperature range: 32 to 130°F (0 to 54°C)
Pressure connection: 0.25” SAE 45° flare female
fully charged cylinder, without loss of pressure, provided
with valve core deflector
the unit is handled with care and only by trained service Wetted materials: EPR, Brass Copper
personnel. Remove the protective cap from the pressure Lead length: 36 in. +/- 2 in.
connection. Do not apply thread compound to the (914 mm +/- 50 mm)
threads. Install the switch with an 1-1/16” open-ended COMPATIBILITY
wrench while holding the pressure connection with a 7/
16” open-end wrench. Tighten hand-tight, plus one-quar- For Use
Series
ter turn. Leak check using a leak detector or bubbling With
solution. Secure switch body with wrench when connect-
Kidde ECS HFC-227ea X
ing electrical conduit. Isolate the assembly from shock,
vibration and areas subject to wide-ranging or rapid tem- Kidde ECS Advanced Delivery FM-200® X
perature fluctuations. Disconnect all supply circuits
before wiring the supervisory switch.
FM-200 is a registered trademark of E.I. du Pont de Nemours and Company.
This literature is provided for informational purposes only. KIDDE- Kidde is a registered trademark of Kidde-Fenwal Inc. All other trademarks are
FENWAL, INC. assumes no responsibility for the product’s suitability for the property of their respective owners.
a particular application. The product must be properly applied to work
correctly.If you need more information on this product, or if you have a Kidde Fire Systems
particular problem or question, contact KIDDE-FENWAL Inc. 400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
Fax: 508.881.8920
©2014 Kidde-Fenwal, Inc.
www.kiddefiresystems.com
AEGIS™ 2.0
Conventional Fire Alarm-Suppression Control Unit

Effective: April 2016


K-84-200

FEATURES
• Suppression Focused Control Unit • Built-in Class-A and Class-B Circuitry
• Triple R Redundancy Provides Maximum Protection • Listed for use with Kidde, Fenwal and Chemetron agent
Against Inadvertent Release release devices including Control Heads and Initiators
• Agency Approvals • Sophisticated Programmable NACs
• FM Approved to ANSI 864, 9th edition, NFPA 72 (2002) • Independently Programmable Agent Releasing Circuits
and ULC S527-99 • Input and Output
• UL Listed to ANSI 864, 9th edition and ULC S527-99 • 3 Detection Circuits
• Listed for a Wide Range of Suppression Systems: • 2 Supervisory Circuits
• Kidde ECS HFC-227ea and FK-5-1-12 • Option to Use SUP 1 as 4th Detection Circuit
• Kidde ADS HFC-227ea and FK-5-1-12 • 1 Manual Release Circuit
• Kidde HP CO2 • 1 Abort Input Circuit (with 6 Abort Modes)
• Kidde IG Argonite & Nitrogen • 3 Notification Appliance Circuits
• Kidde FE-13 • 2 Release Circuits
• Fenwal Spheres • 3 Programmable and 1 Trouble Form-C Relays
• Fenwal BDCs • 1 Auxiliary Power Output, 1 Amp
• Kidde INDTM Dry Chemical & WHDRTM Wet Chemical • 5.4 Amp Power Supply Unit
Systems • 120/240 V, 50/60 Hz AC Input
• Sprinkler Supervisory Service • Easy-to-Use User Interface and Display
• Deluge, Pre-Action, Foam, Foam-Water Systems • Flexible Configuration Options
• Combination Clean Agent plus Pre-Action System • Password Protected
• Compact Cabinet Design Supports Large Number of • Digital Release Countdown
Input and Output Circuits
• Battery Voltage and Charging Current Display
• Option with Door Mounted Abort and Manual Release
• Charging Capacity of 68 AH
Switches Available
• Extensive Diagnostics
• Backwards Compatible

DESCRIPTION
The Kidde AEGISTM 2.0 is a Conventional Single Hazard
Agent Releasing Unit which provides configuration
flexibility in a compact footprint to protect life and assets in
commercial, high-tech and industrial applications. The
AEGIS 2.0 control unit has a NEMA1 enclosure and an
option for door mounted Manual Release and Abort
switches to avoid the additional expense of wall mounting
these items.
The AEGIS 2.0 is well equipped to handle all special
hazard extinguishing systems due to the high degree of
programming flexibility provided and the following full
complement of input and output circuits:
• Three (3) Class A or Class B Detection Circuits
• Two (2) Class A or Class B Supervisory Circuits
• Option to Use SUP 1 as Fourth Detection Circuit
• One (1) Class A or Class B Manual Release Circuit
• One (1) Class A or Class B Abort Input Circuit
• Three (3) Class A or Class B Notification Appliance Circuits
• Two (2) Class B Agent Release Circuits
• Three (3) Programmable and 1 Trouble Form-C Relays
DETECTION CIRCUITS MANUAL RELEASE AND ABORT CIRCUITS
The Detection Circuits support Conventional 700 Series, Both the Manual Release and Abort Circuits accept
CPD-705x Ionization Smoke, PSD-715x Photoelectric Normally Open contact closure type devices. Activation
Smoke and THD-705x Heat Detectors as well as of the Agent Release Circuits can either be
Normally Open contact closure type devices. Two circuits instantaneous or delayed up to 30 seconds (maximum)
are dedicated to the main suppression function and can upon receipt of Manual Release input. Agent release can
be programmed to activate the release circuits by either be temporarily delayed by activating the Abort Circuit.
single-shot or cross-zone input. The user configuration The Abort input can be programmed for 6 modes of
allows automatic release via detection to be delayed from operation. These include the UL 10-second mode, the
0 to 60 seconds in 10-second intervals and also allows a full-delay mode, the IRI mode, two NYC modes, or the
choice of which of the two Agent Release Circuits to abort can be disabled. Aborts can also be programmed to
activate. be applicable for either one (ARC 1) or both Agent
The third Detection Circuit is programmable for either Release Circuits thereby allowing use with Deluge/Pre-
Waterflow or as an independent Detection circuit. When Action systems.
programmed for Waterflow, Notification Appliance NOTIFICATION APPLIANCE CIRCUITS (NAC)
Circuits can be programmed as Non-Silenceable as
The three Notification Appliance Circuits are rated 1.5
required by certain jurisdictions. Additionally, the
Amps each and accept polarized 24 VDC Notification
Supervisory 1 circuit can be configured to be the fourth
Appliances. Each circuit is driven independently and is
detection circuit.
user configurable for First Alarm, Pre-Release, and
SUPERVISORY CIRCUITS Releasing as well as for 60 BPM, 120 BPM, Temporal, or
The Supervisory Circuits accept Normally Open contact Continuous pattern.
closure type devices such as pressure switches on the The control unit supports appliances that provide the
agent cylinders or on the water or air pipe network. The option to use silenceable horns and non-silenceable
system configuration enables the supervisory input to be strobes on the same NAC. Multiple NAC circuits
a participant in the suppression function. For example, (connected to audible devices only) programmed with the
low air supervisory can be included with detection for same master code pattern are synchronized, regardless
release of pre-action systems as required by certain of any differing starting times that preceded their
jurisdictions. concurrent operation. The NACs configuration includes a
user-selectable intelligent synchronization feature which
allows a silenceable horn to be shut off while the strobe
continues to flash in synchronized fashion.
SUPERVISORY 1/ MANUAL WATERFLOW/
SUPERVISORY 2 DETECTOR 4 ABORT RELEASE DETECTOR 3 DETECTOR 2

TB7 TB6 TB5 TB4 TB3 TB2


TROUBLE TB8
TB1 DETECTOR 1
RELAY 3 TB9

RELAY 2 TB10

RELAY 1 TB11

BATT OUT TB12

AC SUPPLY SELECT SWITCH (S6)


NAC 1
TB19

AC IN TB14 TB15 TB16 TB17 TB18 NAC 2

TB13

RELEASE 1 RELEASE 2 AUX NAC 3


ARC 1 ARC 2 24 VDC

Figure 1. Printed Circuit Board (PCB)

-2-
BUILT-IN CLASS A AND B CIRCUITRY POWER-LIMITED CIRCUITRY
For the input and NAC circuits, the choice of Class A or All circuits are inherently power-limited. ARCs can be
Class B supervision is made at site on the board itself by configured for power-limited or non-power-limited
selecting the terminals used for wiring. Neither operation. One in-line releasing device is required for
conversion boards nor additional hardware nor jumper each solenoid on a power limited ARC. In-line releasing
selection is required for this purpose. devices are not included with the panel; the appropriate
number of in-line releasing devices should be ordered
AGENT RELEASING CIRCUITS (ARC)
using part number 06-220023-001.
The two circuits can be programmed for activation by
different inputs, with independent time delays and abort ROBUST POWER SUPPLY UNIT (PSU)
modes to fire combinations of two of the following The AEGIS 2.0 features a universal 120/240 V, 50/60 Hz
releasing devices: AC Power Supply Unit with a robust 5.4 Amps of 24 VDC
• 1 or 2 Kidde Continuous and Momentary Solenoid power. Input voltage selection is via a slider switch with
Control Heads no jumper cutting required. The on-board battery charger
is able to charge 24 VDC (2 x 12) batteries of capacity up
• 1 Kidde Actuator or Fenwal Initiator to 68 AH thereby allowing from 24 hours of supervision
• 1 Factory Mutual Group A, B, D, E, F, G, I, J, or K plus 5 minutes of alarm to 90 hours of supervision plus 10
Solenoid minutes of alarm required by some jurisdictions.
In other words, operating in tandem, the two circuits can AUXILIARY POWER SUPPLY
release: Up to 1 Amp of auxiliary power at 24 VDC is available to
• 1 or 2 Control Heads on ARC 1 and 1 or 2 Control power external 4-wire devices such as Flame Detectors,
Heads on ARC 2 AlarmLine modules, Duct Detectors, etc. The auxiliary
• 1 or 2 Control Heads on ARC 1 and 1 Actuator/ power output is resettable.
Initiator on ARC 2 or vice-versa
ELEGANT USER INTERFACE
• 1 or 2 Control Heads on ARC 1 and 1 FM Sprinkler
Solenoid on ARC 2 or vice-versa The user interface consists of an array of LED Indicators,
• 1 Actuator/Initiator on ARC 1 and 1 Actuator/Initiator Control Switches, a Digital Display, and Buzzer. Over and
on ARC 2 above the System, Power Supply status, Input circuit Fire
• 1 FM Solenoid on ARC 1 and 1 FM Solenoid on and Trouble and Output circuit Trouble LEDs, the AEGIS
ARC 2 2.0 annunciates its suppression state-of-alarm via three
This configurability is useful for those jurisdictions where additional Pre-Release, Releasing and Post Release
the gaseous suppression agent is required to be LEDs. Four switches are provided, one each for
supplemented with a pre-action system. Acknowledge, Signal Silence, System Reset and Output
Disable. The 3-digit display provides a countdown of
TRIPLE-R PROTECTION FOR ARCS impending agent release. On command from the user
The two ARCs feature a triple failure redundancy interface switches, it also indicates the battery open
safeguard system to protect them from inadvertent circuit voltage and charging current.
activation by the main microprocessor. The Triple-R SIMPLE SITE-SPECIFIC CONFIGURATION
system requires that in order to activate an ARC, the
main microprocessor issues two release commands of Setting the site-specific configuration is easily done using
opposing polarity via separate channels and that these the digital display and user interface buttons. To prevent
commands be combined with a third signal from the panel unauthorized use, the configuration menu is protected by
watchdog timer to confirm the microprocessor operation. a user-changeable password. Factory technical support
The Triple-R system ensures that electrical transients or can provide assistance with lost or forgotten passwords.
disturbances such as power surges that could interfere Apart from the input voltage selection performed on both
with the operation of the main microprocessor will not the PSU and main board via a slider switch, no other on-
inadvertently activate the connected suppression system. board settings or jumper cuttings are required.
The result is a more robust and reliable suppression- EXTENSIVE DIAGNOSTICS
focused panel.
Also initiated via the digital display and user interface
PROGRAMMABLE RELAYS switches, the troubleshooting function displays diagnostic
Of the 4 relays, three are user-programmable for a variety codes that assist in determining causes of trouble. A
of alarm related conditions and the fourth is a dedicated complete list of diagnostic codes and their meaning ships
trouble relay. All relay contacts are rated 3.0 Amps at 30 factory installed on the inside of the enclosure door for
VDC/120 VAC (resistive). easy reference.

-3-
BACKWARDS COMPATIBILITY TECHNICAL SPECIFICATIONS (cont’d)
The AEGIS 2.0 is backwards compatible and listed for • One (1) Abort Circuit
use with a full range of conventional detectors and alarm - Compatible with normally open contact-closure type
devices as well as suppression accessories from Kidde, devices
Fenwal and Chemetron. Going forward, this will allow - Configurable as Class A/Style D or Class B/Style B
legacy panels to be replaced with relative ease. - Supervised for ground faults and open circuits
EASY TO INSTALL CABINET - Six (6) Abort Modes available
The cabinet design allows for easy installation by fitting - Power-limited
between the studs of a standard 16 inch studded wall. It • Two (2) Supervisory Circuits
is large enough to house two 12 VDC, 12 AH Batteries - Compatible with normally open contact-closure type
and provides up to 2 inches (51 mm) of wiring and finger devices
space between the circuit board and the cabinet wall. - Configurable as Class A/Style D or Class B/Style B
An optional door design features a Manual Release and - Option to use SUP 1 as 4th detection circuit
Abort switch for applications with space constraints. Both - Supervised for ground faults and open circuits
switches incorporate guards that prevent their - Power-limited
inadvertent activation. • Three (3) Notification Appliance Circuits (NACs)
TECHNICAL SPECIFICATIONS - Compatible with polarized 24 VDC Audio-Visual
devices
• Hazards Protected
- Rated at 1.5 Amps each
- One - Up to 35 synchronized appliances
• Power Supply - Configurable as Class A/Style Z or Class B/Style Y
- 120/240 V, 50/60 Hz (90 to 264 Vrms, 47 to 63 Hz) - Supervised for ground faults, shorts, and open
AC Main Input circuits
- 5.4 Amps at 27 VDC Output - Power-limited
- Battery capacity up to 68 AH @ 24 VDC - Common NAC/ARC output disconnect switch
- Auxiliary power output rated at 1 Amp at 18.8 - 27.6 • Two (2) Agent Release Circuits
VDC (resettable) - Each compatible with 1 or 2 control heads, or 1
• Three (3) or Four (4) Detection Circuits actuator/initiator, or 1 FM sprinkler solenoid
- Compatible with 700 Series, CPD-705x, PSD-715x, - Circuits electrically capable of simultaneously
and THD-705x detectors as well as Normally Open releasing any combination of two of the above
contact closure type devices. Refer to documents devices
K-70-100 and F-70-63 for details on compatibility - Factory configured as Class B/Style Y
and the maximum number of devices supported. - Supervised for ground faults and open circuits
- Configurable as Class A/Style D or Class B/Style B - Default setting: Power-Limited. Each solenoid on a
- Supervised for ground faults and open circuits power-limited ARC requires the use of an in-line
- Power limited releasing device, P/N 06-220023-001 (order
- DET 1 and DET 2 used for suppression separately, not included with panel).
- DET3/WF configurable for detection or waterflow - Common NAC/ARC output disconnect switch
- Option to use SUP 1 circuit as DET 4 circuit • Four (4) Relays
• One (1) Manual Release Circuit - 3 independently programmable, normally de-
- Compatible with normally open contact-closure type energized Form-C Relays
devices - 1 dedicated normally energized Form-C Trouble
- Configurable as Class A/Style D or Class B/Style B Relay
- Supervised for ground faults and open circuits - Relay contacts rated 3 Amps at 30 VDC/120 VAC
- Power limited (resistive)

-4-
TECHNICAL SPECIFICATIONS (cont’d) ORDERING INFORMATION
• Enclosure
- NEMA 1 rated 18 gauge sheet steel with door Description Part Number
- Red color
- Suitable for wall and surface mounting Kidde AEGIS 2.0 Control Unit 84-732001-901
- Optional Trim Ring
Kidde AEGIS 2.0 Control Unit with 84-732001-902
- Optional door with Manual Release and Abort
Switches
switches
-Optional Dead Front Plate In-Line Releasing Device 06-220023-001
- Dimensions:
Dead Front Plate for NEMA1 Enclosure 06-220175-001
- with Standard Door:
14-1/4 in. W x 5 in. D x 19 in. H EOL Resistors (10 pk) 06-220184-001
(362 mm x 127 mm x 483 mm)
- with Switch Door: EOL Backbox (Canadian applications 06-129963-002
14-1/4 in. W x 6 in. D x 19 in. H only)
(362 mm x 152 mm x 483 mm) Trim Ring 76-600000-007
• Environmental Criteria
Large Capacity Battery Enclosure 76-100010-001
- Indoor/Dry use only
- Operating temperature range: 32°F to 120°F Installation/Configuration Kit 06-220148-902
(0°C to 49°C)
Replacement Hardware Installation Kit 06-220149-001
- Humidity: 93 ± 2% RH at 90 ± 3°F (32 ± 2°C)
• Packaging/Shipping Replacement Enclosure Assembly 06-220172-902
- Enclosure, PCB, and PSU packaged in individual Replacement Enclosure Assembly 06-220174-902
cartons. Field assembly is required. (with Switches)
- Accessories shipped include mounting hardware,
battery leads, IOM manual on CD-ROM, operating Replacement Door Switches Kit 06-220176-001
instruction sheet, and EOL resistor kit. Replacement PCB Assembly 06-220150-901
- Order in-line releasing device (required for power-
limited ARCs) and batteries separately. Replacement Power Supply 06-118394-002

Replacement Bezel Assembly 06-220151-001

Spare Key 06-118013-001

Spare Keylock with Keys 06-129924-001

-5-
EXPORT INFORMATION (USA): Jurisdiction: EAR, US ECCN: EAR99 For detailed installation, operation, and configuration
This document does not contain any export-controlled technical data.
information, refer to the Kidde AEGIS 2.0 Conventional
AEGIS is a trademark of Kidde-Fenwal, Inc. Fire Alarm-Suppression Control Unit Installation,
All other trademarks are the properties of their respective owners. Operation, and Maintenance Manual P/N 06-237463-001.

This literature is provided for informational purposes only. KIDDE-FENWAL, INC.


assumes no responsibility for the product’s suitability for a particular application. The
product must be properly applied to work correctly. If you need more information on this
product, or if you have a particular problem or question, contact KIDDE-FENWAL, INC.,
Ashland, MA 01721 USA. Telephone: (508) 881-2000. 400 Main Street
Ashland, MA 01721 USA
Tel: 508.881.2000
K-84-200 Rev AA © 2016 Kidde-Fenwal Inc. www.kiddefiresystems.com
For detailed installation, operation, and configuration
AEGIS is a trademark of Kidde-Fenwal, Inc. information, refer to the Kidde AEGIS Conventional Fire
FM-200 is a registered trademark of The Chemours Company FC, LLC. Alarm-Suppression Conventional Unit Installation,
Novec 1230 Fire Protection Fluid is a trademark of 3M Company.
Argonite is a registered trademark of Kidde Products Limited. Operation, and Maintenance Manual P/N 06-236716-001.

This literature is provided for informational purposes only. KIDDE-FENWAL, INC.


assumes no responsibility for the product’s suitability for a particular application. The
product must be properly applied to work correctly.
If you need more information on this product, or if you have a particular problem or ques- 400 Main Street
tion, contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000. Ashland, MA 01721
Ph: 508.881.2000
K-84-100 Rev AD © 2015 Kidde-Fenwal Inc. Fax: 508.881.8920
www.kiddefiresystems.com
Two- and Four-Wire
Conventional Smoke Detectors
700 Series
Effective: July 2015
K-70-140

STANDARD FEATURES
• FM Approved • Low-profile design blends into the ceiling
• UL Listed • Advanced alarm verification feature reduces
• CSFM Approved chance of nuisance alarms
• Self-diagnostic capability continually monitors • Extensive two-wire compatibility listings
operation • Compatible with most Kidde, Fenwal and
• Meets NFPA 72 sensitivity test requirements Chemetron Conventional Control Panels
• Head and terminal base design (base sold (See compatibility chart in Datasheet No. K-70-100)
separately)
• Automatic drift compensation
• Field-replaceable optical chamber

DESCRIPTION
The 700 Series conventional photoelectric smoke detector
is an interchangeable head and base detector with a light-
scattering optical sensor that provides outstanding stability
and excellent response to a wide range of fires.
A pulsed infrared LED light source and a high-speed pho-
todiode sensing element are housed in an omnidirectional
sensing chamber protected by an insect screen. For easy
cleaning, the detector features a field-replaceable optical
chamber (P/N 211).
Model 721UT photoelectric detectors include integral fixed
temperature and rate-of-rise heat detectors. The 721UT
provides remote alarm and trouble LED driver outputs.
The 700 Series smoke detectors were the industry’s first
conventional self-diagnostic detectors specifically
designed for the demands of commercial and industrial ENGINEERING SPECIFICATIONS
environments. If the detector drifts out of its UL Listed sen- The 700 Series photoelectric smoke detector is a low-pro-
sitivity range or fails internal diagnostics, the alarm LED file, self-diagnostic, two-wire detector that monitors its own
flashes once a second to indicate a trouble condition. This sensitivity and operational status. The detector meets
meets NFPA 72 field sensitivity testing requirements with- NFPA 72 field sensitivity testing requirements without the
out the need for external meters. need for external meters. Built-in drift compensation auto-
Additional diagnostic information is activated by applying a matically adjust the sensitivity if the detector gets dirty. The
magnet near the detector’s integral reed switch. This initi- 700 Series features an alarm verification feature to further
ates a self-diagnostic routine and provides visual indica- reduce the chance of a nuisance alarm. Normal sensing
tion of sensitivity level, or if service is required. The occurs every 9 seconds. This rate doubles when a signal
magnet test causes the LED to blink. The number of blink exceeding the alarm threshold value is sensed. Two addi-
counts corresponds to a smoke detector sensitivity range. tional successive signals above the threshold level initiate
an alarm. The patented optical sensing chamber is field
And, if they become dirty over time, the 700 Series detec-
replaceable, allowing quick and easy cleaning and mainte-
tors automatically adjust the alarm threshold through built-
nance.
in drift compensation. If the detector ever does need to be
cleaned, the patented field replaceable optical chamber
makes cleaning a snap.
TECHNICAL SPECIFICATIONS

Electrical Physical
Voltage 8.5 - 33VDC, non polarity sensitive Color White head and base

Maximum ripple (peak Detector head


10% (vp - p) 4” D x 1.75” H (10cm x 4.44cm)
to peak) dimensions

Typical standy current 701U, 702U: 6” D x 0.06” H


70µA
(24V) (15.24 cm x 1.3 cm),
Base dimensions
Typical alarm current up to 60 mA max, 702E: 4” D x 0.06” H
(24V) if not limited by control panel (10.16 cm x 1.3 cm)
Photoelectric Total height,
2.85%, +0.37, -0.75% 1.98” (5 cm) H
Sensitivity (head and base)
Operating
32°F to 100°F (0°C to 38°C) Regulations
temperature
Listing UL 268, FM, CSFM
Operating
0 to 95% Non-condensing
humidity range
ORDERING INFORMATION
RFI immunity 20 V/m min; 0-1000 MHz
711U Smoke detector head only, photoelectric,
Remote LED two-wire
5 mA min, 8.5 mA max
output current
721UT Smoke detector head only, photoelectric,
Drift compensation two-wire w/integral heat detector, output for
1.0% ft, max
adjustment remote LED
Environmental 741UT Smoke detector head only, photoelectric,
four-wire, w/integral heat detector, alarm
Heat Sensor Ratings Fixed 135°F/Rate of rise 15°F/min, >
relay (N.O.) output and output for remote
(721UT, 741UT) 105°F (8.3°C/min., >40.6°C)
LED
Maximum
300 ft/min 701U Smoke detector base, 3 terminals, 6 in. dia.
wind velocity
702U Smoke detector base, 6 terminals, 6 in. dia.
Field wiring size 12-18 AWG
204-12/24VG End-of-Line, power supervision relay for
Remote test input
100 ohm max four-wire applications
(721 UT)
211-10PKG Replacement optical chamber for smoke
Reset voltage 2.5V max
detectors, set of 10
Reset time 1 second max
06-117883-001 Test magnet
UL two-wire
S10A (711U, 721UT) SM200-12PKG Canned smoke for functional testing of
compatibility identifier
smoke detectors
Note: Refer to Kidde Fire Systems Datasheet
706U1A Remote LED indicator for 721UT or 741UT
Number K-70-100 for smoke detector
compatibility. 706U2A Remote LED indicator and keyed remote
for 721UT or 741UT

706U3A Remote LED indicator, keyed remote and


reset for 721UT or 741UT
All trademarks are the property of their respective owners.
This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes no responsibility for the product’s suitability for a particular
application. The product must be properly applied to work correctly. If you need more information on this product, or if you have a particular problem
or question, contact Kidde-Fenwal Inc.

Kidde Fire Systems


400 Main Street
Ashland, MA 01721
K-70-140 Rev AC Ph: 508.881.2000
©2015 Kidde-Fenwal, Inc. Fax: 508.881.8920
www.kiddefiresystems.com
Manual Pull Stations
Series 3300 A UTC Fire & Security Company

Effective: April 2007


K-84-08

FEATURES
• Exclusive KIDDE® Design • FM Approved
• Unique Field Labeling for either Fire Alarm or • cULus Listed for US and Canada
Suppression Applications • Other domestic approvals in process
• Dual Action Operation • Surface and Weatherproof Backboxes
• Single Pole or Double Pole • Backwards compatible mounting with the B-10 and
• Keylock for Reset B-11

DESCRIPTION
The Kidde® Conventional SPST and DPST Series 3300
Manual Pull Stations are high quality, non-coded alarm
initiating devices. The Manual Pull Stations are con-
structed of heavy die-cast aluminum for long life and use
an internal toggle switch for reliable operation.
The SPST Manual Pull Station provides an Single Pole,
Single Throw switch with screw terminal connections for
wiring to the Fire Alarm/Suppression Control Unit.
The DPST Manual Pull Station provides a Dual Pole, Sin-
gle Throw switch with screw terminal connections. One
set of contacts must be wired to the Fire Alarm/Suppre-
sion Control Unit and the other may be used for local or
remote annunciation.
These Manual Pull Stations are designed for quick, effi-
cient response by personnel in an emergency, while the
double action PUSH/PULL levers prevent accidental
operation. This unit should use a break rod as an indica-
tor of operation.
The Manual Pull Stations can be mounted in an indoor or
outdoor weatherproof backbox (Model SBG-32S or
Model SGB-32C) or a North American 2-1/2 in. (64 mm)
deep 1-gang box. The Manual Pull Station terminal block
accepts 14, 16 and 18 AWG wire.
FIRE ALARM OR SUPPRESSION RELEASE
LABELING These permanent, heavy-duty Lexan® self-adhesive
labels are die-cut with raised lettering. During installation,
The Kidde Series 3300 Manual Pull Stations have a the installer simply chooses the appropriate label,
unique labeling method which provides the installer the removes the protective backing, and places the label into
greatest amount of flexibility. Seven labels are shipped the space on the top of the station. This flexibility allows
with each station: installations to be customized for each customer, without
the expense of having to carry extra inventory.
• FIRE ALARM • FM-200 RELEASE
OPERATION
• CO2 RELEASE • FE-13 RELEASE The dual action Series 3300 manual stations are oper-
ated by simply pushing the PUSH bar inwards, allowing
• FIRE SYSTEMS • HALON-1301 RELEASE the PULL handle to be grasped in a one-handed motion.
RELEASE The handle is then pulled down as far as it will go. If the
• NOVEC 1230
optional breakrod is installed, it would break at this point.
RELEASE The handle is now locked in place, and is easily visible
from up to 50 feet away. The handle is reset by opening
the station with the key and placing the handle in the nor-
mal upright position. Place the switch actuator in the
down position, insert breakrod into cavity beneath handle ORDERING INFORMATION
(if applicable), and re-lock the station.
Part Number Description
SPECIFICATIONS 84-330001-001 Double Action Manual Pull Station with
SPST Switch — ships with mounting
Station Type: Double Action, Non-coded hardware, 2 keys, 1 break rod, and label
set.
Switch Type: P/N 84-330001-001: SPST
P/N 84-330001-002: DPST 84-330001-002 Double Action Manual Pull Station with
DPST Switch — ships with mounting
Switch rating: 2 Amp @ 240 Vac or 125 Vdc hardware, 2 keys, 1 break rod, and label
set.
Operating Tempera- -40ºF to 150ºF (-40ºC to 66ºC)
ture Range: 84-100009-001 SGB-32S Indoor Backbox
Operating Humidity 0-95% RH 84-100009-002 SGB-32C Outdoor Waterproof Backbox
Range:
84-100008-002 Pkg. of (12) Breakrods
Construction: Die-cast metal housing
06-118013-001 Spare Key
Compatible Electrical Indoor: Sheet metal Model SGB-
Boxes: 32S 06-231866-930 Label Set
Outdoor: Weatherproof Die-cast
Model SGB-32C

Shipping Weight: 1.12 lbs. (510 g) DIMENSIONS


(shown with Fire System Release Label installed)
SGB-32S INTERIOR SURFACE BACKBOX 1-5/64 in.
(27 mm)

Dimensions: 4.75 in. H x 3.25 in. W x 2.25 in. D 3-1/4 in.


(83 mm) 31/32 in.
(24 mm)

Construction: Steel sheet metal.

Conduit: Two knockouts for 1/2 in. conduit FIRE FIRE


connectors, one on top and bottom. SYSTEM SYSTEM
RELEASE RELEASE

Mounting: Mounts to the box with (4) 8/32


screws, which ship with each box.
PUSH
4-3/4 in.
SGB-32C WEATHERPROOF SURFACE (121 mm)
PULL
BACKBOX
ON
ON

Dimensions: 4.75 in. H x 3.25 in. W x 2.25 in. D

Construction: Cast aluminum.

Conduit: One threaded opening for 1/2 in.


conduit connector.

Mounting: Mounts to the box with (4) 8/32


screws and a foam gasket, which
ship with each box.

Kidde is a registered trademark of Kidde-Fenwal, Inc.


FM-200 is a registered trademark of the Greak Lakes Chemical Corporation.
3M and Novec are trademarks of 3M.
FE-13 is a trademark of DuPont.
Lexan is a registered trademark of the General Electric Company.

This literature is provided for informational purposes only. KIDDE-FENWAL, INC.


assumes no responsibility for the product’s suitability for a particular application. The prod-
uct must be properly applied to work correctly.
If you need more information on this product, or if you have a particular problem or ques- A UTC Fire & Security Company
tion, contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000. 400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
K-84-08 Rev AA © 2007 Kidde-Fenwal Inc. Printed in USA
Fax: 508.881.8920
www.kiddefiresystems.com
Model 878752
Suppression System Abort Station
Effective: November 2014
K-84-10

FEATURES
• UL Listed • Large Yellow Push Button Switch
• Flush or Surface Mount • Abort Station Becomes Addressable SLC Device with
• One Normally Open Contact installation of one (1) Model AI Addressable Monitor
• Sized for Double Gang Box Module, N.O.

DESCRIPTION
The Kidde® Model 878752 Abort Station features a large,
easy-to-operate abort push button. The momentary type
switch is very easy to see due to its highly visible yellow
color. The abort station stainless steel faceplate is clearly
labeled with operation procedures—eliminating indeci-
sion and hesitation.
The Backbox is painted with red enamel and is provided
with four 1/2-inch knockouts. The pre-drilled and tapped
mounting tabs allow for easy attachment of the abort
station.
To make the Abort Station an addressable SLC device for
use with Kidde Intelligent control units, one SmartOne®
Model AI monitor module (purchased separately) must
be installed into the backbox. The Model AI monitor mod-
ule is seated inside a bracket (included) and easily
installs with two mounting screws. 4-1/2 in.
(114 mm)
A cULus-listed Abort Station for Canadian applications
that require compliance to ULC S527-11 (3rd edition) is
also available (blue faceplate with white raised lettering).
Order P/N 84-878752-110.
4-1/2 in.
TECHNICAL SPECIFICATIONS (114 mm)

Electrical Ratings: One normally open momentary SUPPRESSION SYSTEM ABORT


contact, rated 2.5 Amps @ 120 Vdc
1-11/16 in.
Ambient (43 mm)
Temperature: -13°F to 158°F (-25°C to 70°C) 3-3/64 in.
(77 mm)
Terminals: Captive screws and saddle clamps
accept 14 AWG to 24 AWG wire 2 in .
(51 mm)
4-5/8 in .
Mounting: Four 6-32 x 1/2-inch mounting 117 mm
screws included

ORDERING INFORMATION
Shipping 4-5/8 in .
Part Number Description
Weight 117 mm

84-878752-010 Abort Station 2 lb. (0.9 kg)

06-236881-001 Backbox, Red 1 lb. (0.45 kg)

Model AI Addressable 5 oz. (145 g)


70-407008-001 Monitor Module, N.O.
(includes bracket) Figure 1. Dimension Details

This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes Kidde Fire Systems
no responsibility for the product’s suitability for a particular application. The product must be 400 Main Street
properly applied to work correctly. Ashland, MA 01721
If you need more information on this product, or if you have a particular problem or question, Ph: 508.881.2000
contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000. Fax: 508.881.8920
www.kiddefiresystems.com
K-84-10 Rev AC © 2014 Kidde-Fenwal Inc.
Key Maintenance Switch
A UTC Fire & Security Company

Effective: May 2009


K-76-606

FEATURES
• cFMus Approved to ANSI/UL 864, 9th edition, • Safely Disconnects Actuation Circuits
CANADA/ULC-S527 and ANSI/NFPA 72 by Shorting Metron Actuators
• Stainless Steel Plate • Key Operated (Nonremovable When Operated)
• Status LED Indicators • Four-Pole Double-Throw Switch
• Surface or Flush Mount Installations • Meets the Requirements of NFPA72 (2007 edition)

DESCRIPTION
This Key Maintenance Switch is a key-switch that discon-
nects actuation circuits in the system to prevent acciden-
tal discharge of fire suppression systems during
maintenance operations.
The Key Maintenance Switch provides a means to short
the Metron Actuator circuit leads for safe disconnection
of conventional and addressable control units. Refer to
the installation wiring diagram for detailed wiring connec-
tions.
• Two LEDS indicate "SYSTEM ARMED" or "SYSTEM
INACTIVE" when the key is inserted and turned. The
key can only be removed in the armed position.
• Key Maintenance Switch mounts to a 4-inch backbox
and operates on 24 Vdc.
• Designed for mounting on the wall with a back box.
• Key Maintenance Switch can be installed in either
ELECTRICAL
surface mount or flush mount configurations.
• Key Maintenance Switch physically disconnects the Switch: 4PDT Key Switch
release circuit wiring in addition to the trouble open - one set of contacts control
signal, the switch provides a means to generate a indicators on the faceplate.
supervisory condition. - Three remaining contacts are
available for application wiring.
Device Current: 10 A @ 250 Vac
ORDERING INFORMATION 15 A @ 125 Vac
Part Number Description 15 A @ up to 30 Vdc
Electrical Life: 50,000 cycles - maintained
76-600000-200 Key Maintenance Switch 25,000 cycles - -momentary
06-236881-001 Backbox
ENVIRONMENTAL
Operating Temperature 32 to 120°F (0 to 49°C)
Range:
MECHANICAL
Mechanical Life: 100,000 cycles
Switch Plate Stainless Steel
Construction:

This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes Kidde Fire Systems
no responsibility for the product’s suitability for a particular application. The product must be A UTC Fire & Security Company
properly applied to work correctly. 400 Main Street
If you need more information on this product, or if you have a particular problem or question, Ashland, MA 01721
contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.
Ph: 508.881.2000
K-76-606 Rev AB © 2009 Kidde-Fenwal Inc. Printed in USA Fax: 508.881.8920
www.kiddefiresystems.com
Notification Appliances
Effective: March 2013
K-75-020

FEATURES
• Sleek Modern Aesthetics • Universal Mounting Base (Patented)
• Finger Slide Switches • Ceiling and Wall, Mounts to 5 Backbox Types
• Voltage Test Points • Environmentally Friendly
• Multiple Voltages • Low Current Draw
• 3 Audible Settings: 90, 95, 99 dB • FM Approved
• 8 Candela Settings (Patented) • UL Listed
• Wall: 15/15_75/30/75/95/110/135/185 • ULC Listed
• Ceiling: 15/30/60/75/95/115/150/177 • California State Fire Marshal (CSFM) Approved

DESCRIPTION
The Exceder Series notification appliances are compati- Wall models provide an optional locking screw for extra
ble with all Kidde suppression control panels and offer secure installation, while the ceiling models provide a capti-
modern designs with pleasing aesthetics and low cost of vated screw to prevent the screw from falling during instal-
ownership. lation.
The Exceder Series devices incorporate high reliability
COMPATIBILITY AND REQUIREMENTS
and high efficiency optics to minimize current draw allow-
ing for a greater number of appliances on the notification- – Synchronize using the Sync Modules or panels
appliance circuit. All strobe models feature an industry with built-in Patented Sync Protocol
first of 8 candela settings on a single appliance. Audible – Compatible with UL “Regulated Voltage” using
models feature 3 sound settings (90, 95, 99 dB). All filtered VDC or unfiltered VRMS input voltage
switches to change settings can be set without the use of
a tool and are located behind the appliance to prevent – Strobes produce 1 flash per second over the
tampering. Wall models feature voltage test points to take “Regulated Voltage” range
readings with a voltage meter for troubleshooting and
AHJ inspection.
An additional included benefit is the Universal Mounting
Base (UMB). The UMB allows retrofitting for previous
generation of Wheelock notification appliances. The UMB
can be pre-wired to allow full testing of circuit wiring
before the appliance is installed. It comes complete with a
Contact Cover for protection against dirt, dust, paint and
damage to the contacts. The Contact Cover also acts as a
shunting device to allow pre-wire testing for common
wiring issues. The Contact Cover is polarized to prevent it
from being installed incorrectly and prevents the
appliance from being installed while it is on the UMB.
When the Contact Cover is removed, the circuit will show
an open until the appliance is installed.
PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY
BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. CONTACT KIDDE FIRE SYSTEMS FOR
THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE
INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION,
WARNING INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH
COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.

GENERAL NOTES:
• Strobes are designed to flash at 1 flash per second minimum over their “Regulated Voltage Range”.
• All candela ratings represent minimum effective strobe intensity based on UL Standard 1971.
• Series Exceder Strobe products are Listed under UL Standards 1971 and 464 for indoor use with a temperature range
of 32°F to 120°F (0°C to 49°C) and maximum humidity of 93% (± 2%) UL 464 (85% UL 1971).
• Series Exceder horns are under UL Standard 464 for audible signal appliances (Indoor use only).
Strobe Rating per UL Standard 1971
UL Max Current*
24 VDC / 24 FWR 12 VDC
Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75
Range VDC
ST 8.0-33.0 0.057 0.070 0.085 0.135 0.163 0.182 0.205 0.253 0.110 0.140
STC 8.0-33.0 0.061 0.085 0.103 0.135 0.163 0.182 0.205 0.253 0.110

Horn Strobe Rating per UL 1971 & UL 464 at 24 VDC


UL Max Current* at 99 dBA
24 VDC 12 VDC
Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75
Range VDC
HS 8.0-33.0 0.082 0.095 0.102 0.148 0.176 0.197 0.242 0.282 0.125 0.159
HSC 8.0-33.0 0.082 0.102 0.141 0.148 0.176 0.197 0.242 0.282 0.125
UL Max Current* at 95 dBA
24 VDC 12 VDC
Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75
Range VDC
HS 8.0-33.0 0.073 0.083 0.087 0.139 0.163 0.186 0.230 0.272 0.122 0.153
HSC 8.0-33.0 0.073 0.087 0.128 0.139 0.163 0.186 0.230 0.272 0.122
UL Max Current* at 90 dBA
24 VDC 12 VDC
Model Regulated Voltage 15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75
Range VDC
HS 8.0-33.0 0.065 0.075 0.084 0.136 0.157 0.184 0.226 0.267 0.120 0.148
HSC 8.0-33.0 0.065 0.084 0.120 0.136 0.157 0.184 0.226 0.267 0.120

Horn Ratings per UL 464


* UL max current rating is the maximum RMS current within
Regulated Voltage the listed voltage range (16-33 VDC for 24 VDC units). For
Model 99 dB 95 dB 90 dB
Range YDC strobes, the UL max current is usually at the minimum listed
HN 16-33.0 0.064 0.044 0.022 voltage (16 VDC for 24 VDC units). For audibles, the max
HNC 16-33.0 0.084 0.044 0.022 current is usually at the maximum listed voltage (33 VDC for
HN 8.0-17.5 0.047 0.026 0.017 24 VDC units). For unfiltered ratings, see installation
HNC 8.0-17.5 0.047 0.026 0.017 instructions.

-2-
SPECIFICATIONS & ORDERING INFORMATION
All Exceder Series of notification appliances meet the following requirements:
• Can be powered by 12 or 24 VDC
• Can synchronize with SM, DSM, or SD-6 and PS-8 power supplies
• Uses the Universal Mounting Base
• In the case of any model including a strobe, can be set to the following candela: 15, 15-75, 30, 75, 95, 110, 135, 185

The model numbers and descriptions are as follows:

Model Description Model Description


HSR Horn, Strobe, Red STR-A Strobe, Red, Agent Label
HSW Horn, Strobe, White STW-A Strobe, White, Agent Label
HSRC Horn, Strobe, Red, Ceiling Mount ESBCR Universal Back Box, Ceiling Mount, (Use
with P/Ns starting with HS, ST, or HN) Red
HSWC Horn, Strobe, White, Ceiling Mount ESBCW Universal Back Box, Ceiling Mount, (Use
with P/Ns starting with HS, ST, or HN)
White
STR Strobe, Red ESBR Universal Back Box, Wall Mount, (Use
with P/Ns starting with HS, ST, or HN) Red
STW Strobe, White ESBW Universal Back Box, CWall Mount, (Use
with P/Ns starting with HS, ST, or HN)
White
STRC Strobe, Red, Ceiling Mount
MODEL LEGEND
Example:
STWC Strobe, White, Ceiling Mount HN = Horn STWC= Strobe, White, Ceiling Mount
HNR Horn, Red ST = Strobe HSR= Horn Strobe, Red, Wall Mount
HNW Horn, White HS = Horn Strobe
HNRC Horn, Red, Ceiling Mount R = Red
HNWC Horn, White, Ceiling Mount W = White
HSR-A Horn, Strobe, Red, Agent Label C = Ceiling Mount
HSW-A Horn, Strobe, White, Agent Label A = Agent Label

-3-
ARCHITECTS & ENGINEERS SPECIFICATIONS

The notification appliances shall be Exceder Series HS


The Series HS and ST wall models shall have a low profile
Audible Strobe appliances, Series ST Visual Strobe appli-
measuring 5.24” H x 4.58” W x 2.19” D. Series HN wall
ances and Series HN Audible appliances or approved
shall measure 5.24” H x 4.58” W x 1.6” D. The Series HSC
equals. The Series HS and ST Strobes shall be listed for
and STC shall been round and have a low profile with a
UL Standard 1971 (Emergency Devices for the Hearing-
diameter of 6.68” x 2.63” D. Series HNC ceiling shall have a
Impaired) for Indoor Fire Protection Service. The Series HS
diameter of 6.68” x 1.50” D.
and HN Audibles shall be UL Listed under Standard 464
(Fire Protective Signaling). All Series shall meet the Synchronization is achieved through Kidde control panel
requirements of FCC Part 15 Class B. All inputs shall be synchronization protocol. The strobes shall not drift out of
compatible with standard reverse polarity supervision of cir- synchronization at any time during operation. If the sync
cuit wiring by a Fire Alarm Control Panel (FACP) with the protocol fails to operate, the strobe shall revert to a non-
ability to operate from 8 to 33 VDC. Indoor wall models synchronized flash-rate and still maintain (1) flash per sec-
shall incorporate voltage test points for easy voltage ond over its Regulated Voltage Range. The appliance shall
inspection. also be designed so that the audible signal may be silenced
while maintaining strobe activation when used with syn-
The Series HS Audible Strobe and ST Strobe appliances
chronization protocol.
shall produce a flash rate of one (1) flash per second over
the Regulated Voltage Range and shall incorporate a Wall Appliances – UL Standard 1971, UL Standard 464,
Xenon flashtube enclosed in a rugged Lexan® lens. The California State Fire Marshal (CSFM), ULC
Series shall be of low current design. Where Multi-Candela Ceiling Appliances – UL Standard 1971, UL Standard
appliances are specified, the strobe intensity shall have 8 464, California State Fire Marshal (CSFM), ULC
field selectable settings at 15, 15/75, 30, 75, 95, 110, 135,
185 candela for wall mount and 15, 30, 60, 75, 95, 115,
150, 177 candela for ceiling mount. The selector switch for
selecting the candela shall be tamper resistant. The 15/75
candela strobe shall be specified when 15 candela UL
Standard 1971 Listing with 75 candela on-axis is required
(e.g. ADA compliance). Appliances with candela settings
shall show the candela selection in a visible location at all
times when installed.
The audible shall have a minimum of three (3) field select-
able settings for dBA levels and shall have a choice of con-
tinuous or temporal (Code 3) audible outputs.
The Series HS Audible Strobe, ST Strobe and Series HN
Audible shall incorporate a patented Universal Mounting
Base that shall allow mounting to a single-gang, double-
gang, 4-inch square, 3.5-inch octal, 4-inch octal or 100mm
European type back boxes. Two wire appliance wiring shall
be capable of directly connecting to the mounting base.
Continuity checking of the entire NAC circuit prior to attach-
ing any notification appliances shall be allowed. Product
shall come with Contact Cover to protect contact springs.
Removal of an appliance shall result in a supervision fault
condition by the Fire Alarm Control Panel (FACP). The
mounting base shall be the same base among all horn,
strobe, horn strobe, wall and ceiling models. All notification
appliances shall be backwards compatible.
Wheelock and Exceder are registered trademarks of Cooper Technologies Company.
Lexan is a registered trademark of General Electric Company.
All other trademarks are the property of their respective owners.

This literature is provided for informational purposes only. KIDDE-FENWAL, INC.


assumes no responsibility for the product’s suitability for a particular application. The
product must be properly applied to work correctly. If you need more information on
this product, or if you have a particular question, contact KIDDE-FENWAL, INC., 400 Main Street
Ashland, MA 01721. Ashland, MA 01721
Tel.: 508-881-2000
K-75-020 Rev AB © 2013 Kidde-Fenwal Inc. Fax: 508-881-8920
www.kiddefiresystems.com
Series MBA Motorized Bells
by Kidde A UTC Fire & Security Company

Effective: January 2012


K-75-015

FEATURES ing options are provided in the Mounting


Options table below.
• Agency approvals include: UL, ULC, FM, CSFM,
NYMEA
• 6-inch and 10-inch shell sizes, 24 Vdc models
• Mounting options for surface, semi-flush,
outdoor, and concealed conduit installation
• Red smooth finish to improve appearance
and durability

DESCRIPTION
Potter® manufactured Motor Bells provide a superior
engineered notification product for fire and life safety
alarm systems. The motorized bells are designed for
public mode signaling in accordance with NFPA 72. The
bells produce a long and continuous higher dBA ringing
sound at low current draw; low frequency shells for better
audibility, low RFI noise and high torque. A permanent
magnet motor is incorporated for durable, reliable perfor- Series MBA Motorized Bells
F. SEMI-FLUSH C. SURFACE
mance.

MOUNTING
The unit mounts on a standard 4-in. (101 mm) square Standard BB
4” square
electrical backbox for indoor applications. Other mount- backbox
SFP

Mounting
Model Number Part Number
Options
G. CONCEALED CONDUIT E. OUTDOOR
SFP-R 75-000000-005 F
WBB
BB-R 75-000000-006 C
AP-R 75-000000-007 G
WBB-R 75-000000-008 E AP

ORDERING INFORMATION
Max. RMS Operating Current (mArms) Min. Sound Output Min. Sound Output
Part Number Input Voltage Shell Size (dBA at 10 ft. per (dBA at 10 ft. per
Regulated 12 Vdc Regulated 12 Regulated 12 Vdc Regulated 12 VFWR UL464) ULC-S525)
(per UL464) VFWR (per UL464) (per ULC-S525) (per ULC-S525)

MBA-6-24 24 Vdc 6 in. 13.5 24.5 17.0 30.0 75.6 at 8Vdc 95.0 at 8Vdc
(150 mm)
MBA-10-24 24 Vdc 10 in. 34.0 46.0 34.0 46.0 79.1 at 8Vdc 92.0 at 8Vdc
(250 mm)
Notes:
1. Minimum dB ratings are calculated from integrated sound pressure measurements made at Underwriters Laboratories as specified in UL Standard 464 and ULC-S525. Due to changes in UL
Standard 464 and ULC-S525, all minimum dBA ratings are calculated at minimum operating voltage. Typical operating dBA will be higher. UL temperature range is -40 to 150°F (-40 to 66°C).
2. Typical dB ratings are calculated from measurements made with a conventional sound level meter and are indicative of output levels in an actual installation.

Kidde is a registered trademark of Kidde-Fenwal Inc.


Potter is a registered trademark of Potter Electric Signal Company, LLC

Kidde Fire Systems


This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes
no responsibility for the product’s suitability for a particular application. The product must be
UTC Climate | Controls | Security
properly applied to work correctly. 400 Main Street
If you need more information on this product, or if you have a particular problem or question, Ashland, MA 01721
contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000. Ph: 508.881.2000
K-75-015 Rev AA © 2012 Kidde-Fenwal Inc. Fax: 508.881.8920
www.kiddefiresystems.com
Kidde ECS Fire Suppression System
Component Description
Effective: June 2014
Pressure Operated Switch K-90-5180

FEATURES
• For Use with UL Listed, ULC Listed and • See Kidde® Manual 06-236225-001 for
FM Approved Systems USCG Approval

P/N: 81-486536-000
STEM SHOWN IN SET POSITION-
PULL UP ON STEM TO MANUALLY
OPERATED OPERATED OPERATE SWITCH
SET SET

0.375"
PRESSURE OPERATED SWITCH
WIRING 3P.D.T. 8 COVER SCREWS
4.00" SCREW TO RESET
PUSH STEM TO SET POSITION
TERMINALS U
15 AMP.— 125 V.AC L 10 AMP.—250 V.AC
3/4HP—250 VAC
PT. NO. 486536
FM

TO RESET
KIDDE-FENWAL, INC.
400 MAIN STREET
ASHLAND, MA 01721

PUSH STEM TO SET POSITION

15 AMP 125 VAC


4.00" 10 AMP 250 VAC
3/4 HP 1-2-3 PH 125-480 VAC
FRONT VIEW
COVER REMOVED
1/2” SUPPLY PIPE WITH UNION
FRONT VIEW

OPERATED
SET
NC NC NC
BOX 3 EACH SIDE
1/2” CONDUIT
SWITCH 3PDT KNOCKOUTS C C C

COVER
NO NO NO

GASKET ½” NPT FEMALE,


CONNECT TO SYSTEM PRESSURE INLET
PIPING
SIDE SECTION WIRING DIAGRAM

NOTES:
• The switch may be mounted in any position; how- • Contact Ratings (3 PDT):
ever, the preferred installation is upright, as shown. – 15 Amp @125 Vac
• Any load connection to the switch must not exceed – 10 Amp @ 250 Vac
the switch rating, and shall utilize a suitable protec- – 3/4 HP @ 250 Vac
tion device (i.e., circuit breaker, fuse). – 1, 2 or 3 Phase

1
COMPATIBILITY

For Use
Series
With

Kidde ECS HFC-227ea X

Kidde ECS Advanced Delivery FM-200® X

FM-200 is a registered trademark of E.I. du Pont de Nemours and Company. Kidde is a registered trademark of Kidde-Fenwal Inc. All other trademarks are the property
of their respective owners.

This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes no responsibility for the product’s suitability for a particular application. The
product must be properly applied to work correctly.If you need more information on this product, or if you have a particular problem or question, contact Kidde-Fenwal Inc.

2 Kidde Fire Systems


400 Main Street
Ashland, MA 01721
Ph: 508.881.2000
Fax: 508.881.8920
K-90-5180 Rev BA ©2014 Kidde-Fenwal, Inc. www.kiddefiresystems.com
Key Maintenance Switch
A UTC Fire & Security Company

Effective: May 2009


K-76-606

FEATURES
• cFMus Approved to ANSI/UL 864, 9th edition, • Safely Disconnects Actuation Circuits
CANADA/ULC-S527 and ANSI/NFPA 72 by Shorting Metron Actuators
• Stainless Steel Plate • Key Operated (Nonremovable When Operated)
• Status LED Indicators • Four-Pole Double-Throw Switch
• Surface or Flush Mount Installations • Meets the Requirements of NFPA72 (2007 edition)

DESCRIPTION
This Key Maintenance Switch is a key-switch that discon-
nects actuation circuits in the system to prevent acciden-
tal discharge of fire suppression systems during
maintenance operations.
The Key Maintenance Switch provides a means to short
the Metron Actuator circuit leads for safe disconnection
of conventional and addressable control units. Refer to
the installation wiring diagram for detailed wiring connec-
tions.
• Two LEDS indicate "SYSTEM ARMED" or "SYSTEM
INACTIVE" when the key is inserted and turned. The
key can only be removed in the armed position.
• Key Maintenance Switch mounts to a 4-inch backbox
and operates on 24 Vdc.
• Designed for mounting on the wall with a back box.
• Key Maintenance Switch can be installed in either
ELECTRICAL
surface mount or flush mount configurations.
• Key Maintenance Switch physically disconnects the Switch: 4PDT Key Switch
release circuit wiring in addition to the trouble open - one set of contacts control
signal, the switch provides a means to generate a indicators on the faceplate.
supervisory condition. - Three remaining contacts are
available for application wiring.
Device Current: 10 A @ 250 Vac
ORDERING INFORMATION 15 A @ 125 Vac
Part Number Description 15 A @ up to 30 Vdc
Electrical Life: 50,000 cycles - maintained
76-600000-200 Key Maintenance Switch 25,000 cycles - -momentary
06-236881-001 Backbox
ENVIRONMENTAL
Operating Temperature 32 to 120°F (0 to 49°C)
Range:
MECHANICAL
Mechanical Life: 100,000 cycles
Switch Plate Stainless Steel
Construction:

This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes Kidde Fire Systems
no responsibility for the product’s suitability for a particular application. The product must be A UTC Fire & Security Company
properly applied to work correctly. 400 Main Street
If you need more information on this product, or if you have a particular problem or question, Ashland, MA 01721
contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.
Ph: 508.881.2000
K-76-606 Rev AB © 2009 Kidde-Fenwal Inc. Printed in USA Fax: 508.881.8920
www.kiddefiresystems.com