Alarms and Action list


Turbine Lube Oil System

PREPARED CHECKED APPROVED


REV. DATE MODIFICATIONS
BY BY BY
0 26/2/19 MH SA AK Draft

ALL RIGHT PERTAINING TO THE REPRODUCTION, TRANSFORMATION AND USE OF THIS DOCUMENT. IN ANY FORM OR MANNER
REMAIN THE EXCLUSIVE PROPERTY OF HPSL
Doc. Ref. No.
BOILER AIR & GAS PASS 10HLA/
Revision: 01

ALARMS AND ACTION LIST OF GENERATOR SEAL OIL SYSTEM


Date Issued:
Issued by:
Checks Performed by:

S. No. Alarm Description Actions Remarks


Confirm the Combine Tank oil level from local gauge
indicator MAV02CL501, if level found normal inform I&C,
else:
Check the lube and control oil piping for any leakage
Check the lube and control drain valves 10MAV02AA201,
10MAV02AA202, MAV02AA401 and MAV02AA402 are
Combine Oil Tank Level < L closed
1. MAV02CL001, MAV02CL002 Check the transfer valve of Clean Oil Tank 10MAV02AA202
and MAV02CL003 is closed
Check the Lube oil to Purifier Line drain valve MAV34AA401
is closed
Check Lube oil purification system pump, and ensure that it
is in service
In case if all checks are found OK, perform make up of
Combine lube oil tank
Confirm the Combine Tank oil level from local gauge
indicator MAV02CL501, if level found normal inform I&C,
else:
Check the Air Breather for any choking
Check the dampers setting of Vapor Extractor Fan
Combine Oil Tank Level < L (10MAV02AN001, 10MAV02AN002) of Combine Oil Tank
2. MAV02CL001, MAV02CL002 Check Gland Seal Steam pressure for any steam ingress in
and MAV02CL003 lube oil system
Check lube oil physical condition and perform lube oil
analysis to check Moisture content in it
Check the abnormal operation of Lube oil Transfer Pump
(10MAV31AP001) and BFPT Lube oil transfer pump
(10MAV20AP001)
3. Lube Oil Temperature > High Check the Lube oil cooler outlet temperature indicator
(MAV02CT002) 10MAV22CT501, If the value is OK, inform I&C for
corrective actions, else:
Check the controller set point and control valve
(10PGB51AA101), if found NOT OK, set it accordingly, else:
Check the close cooling water system temperature
Check Lube oil cooler oil inlet and outlet temperature
(****) to check for any degradation in cooler performance
Check the

Page 1|7
Doc. Ref. No.
BOILER AIR & GAS PASS 10HLA/
Revision: 01

S. No. Alarm Description Actions Remarks

4.
5.
6.
Ambient temperature below generator start-up condition
e.g. after long standstill
Startup seal oil heaters 10MKW20AH001/002 to increase oil
Seal oil inlet temperature Min temperature.
7.
1: < 25°C 􀁸 Before generator rotor turn circulate oil in system by
means of seal oil pump or Pumps until seal oil temperature
reaches start-up limit. Oil temperature self-rise due to
circulation is more efficient if generator is pressurized.
Float valve does not open
Level degassing tanks
10MKW14AA001, 10MKW15AA001 & 10MKW16AA001
8. 10MKW14/15/16BB001 Max
Adjust level manually by using of valve:
1
10MKW14AA003, 10MKW15AA003 & 10MKW16AA003
Float valve does not close
10MKW14AA001, 10MKW15AA001 & 10MKW16AA001
Level degassing tanks Close valve:
9.
10MKW14/15/16BB001 Min 1 10MKW14AA002, 10MKW15AA002 & 10MKW16AA002
and adjust level manually by using of valve:
10MKW14AA003 ,10MKW15AA003 & 10MKW16AA003
Very low vacuum pressure because of defective vacuum
pumps, for example,
Influences the oil flow between 10MKW14BB001 and
10MKW20BB001. In this
Level in air seal oil tank High Consequence, the oil level in the air seal oil tank increases
10. because of very low vacuum and, simultaneously, the oil level in the vacuum tank
pressure Max 1 decreases. This situation stabilizes when the increasing oil
level above the air seal oil tank reaches the height of the
vacuum tank inlet. The oil flows from the air seal oil tank
into the vacuum seal oil tank through the connection pipe.
Repair or replace the vacuum pumps as soon as possible.
Float valve 10MKW14AA001 does not open
Air seal oil return pipe
11. Close valve 10MKW14AA002 and adjust level manually by
10MKW13BR010 level Max 1
using valve 10MKW14AA003
Hydrogen seal oil return pipe Float valve 10MKW15AA001 does not open
12. DE 10MKW15BR010 level Close valve 10MKW15AA002 and adjust level manually by
Max 1 using valve 10MKW15AA003
Hydrogen seal oil return pipe Float valve 10MKW16AA001 does not open
13. NDE 10MKW16BR010 level Close valve 10MKW16AA002 and adjust level manually by
Max 1 using valve 10MKW16AA003
14. Pressure in vacuum tank Max Vacuum pump 10MKQ11AN001 or 10MKQ12AN001 is

Page 2|7
Doc. Ref. No.
BOILER AIR & GAS PASS 10HLA/
Revision: 01

S. No. Alarm Description Actions Remarks


defective or not working properly
1 > 200 mbar abs Automatic switch over function to second vacuum pump is
activated
Differential pressure controller 10MKW33AA002 defective
or
Differential pressure controller 10MKW34AA002 defective
Close valves 10MKW33AA001 and 10MKW33AA003
Repair or replace controller 10MKW33AA002
Differential pressure between or
15. seal oil and gas Max 1 > 0,8 Close valves 10MKW34AA001 and 10MKW34AA003
bar Repair or replace controller 10MKW34AA002
Standby pump and/or emergency pump (10MKW21AP001
and/or 10MKW23AP001) or
(10MKW22AP001 and/or 10MKW23AP001) is running.
Switch off manually if the differential pressure is re-
established – Set point 0,5 bar
Differential pressure controller 10MKW33AA002 defective
or
Differential pressure controller 10MKW34AA002 defective
Close valves 10MKW33AA001 and 10MKW33AA003
Repair or replace controller 10MKW33AA002
or
Close valves 10MKW34AA001 and 10MKW34AA003
Repair or replace controller 10MKW34AA002
Clearance of shaft seal ring is too large.
Shutdown the turboset, release the gas pressure and purge
Differential pressure between
the generator Major oil leakage to surroundings If it is not
16. seal oil and gas Min 1 < 0.3
possible to stop the leakage, all necessary actions must be
bar
taken to stop the turboset and purge the generator.
Oil leakage into cooling water
Check open position of isolating valves in cooling water
system
Change over to standby cooler 10MKW25AC001 or
10MKW26AC001 using valve 10MKW24AA001
Seal oil pumps have failed 10MKW21AP001,
10MKW22AP001& 10MKW23AP001
Check power supply of pumps Check pressure at
10MKW24CP001
Automatic start-up of reserve seal oil pump
Differential pressure between
If differential pressure between seal oil and gas is not
17. seal oil and gas Min 2 < 0.2
improved after reserve pump start up, turbo set will be
bar
automatically tripped.
Pressure in air seal oil tank Failure of oil vapor fan 10MKQ21AN001 or
18. 10MKW14BB001 Min 1 10MKQ22AN001.
1mbar Automatic switch over to stand by oil vapor fan
19. Lube oil storage vessels level Oil consumption of vacuum pumps 10MKQ11AN001,

Page 3|7
Doc. Ref. No.
BOILER AIR & GAS PASS 10HLA/
Revision: 01

S. No. Alarm Description Actions Remarks


10MKQ12AN001
Low <30 % Refill lube oil storage vessels 10MKQ11BB001,
10MKQ12BB001
Oil consumption of vacuum pumps 10MKQ11AN001,
Lube oil storage vessels level 10MKQ12AN001
20.
Min <20 % Refill lube oil storage vessels 10MKQ11BB001,
10MKQ12BB001
Lube oil storage vessel is full
Collection of seal oil coming from vacuum tank
10MKW20BB001 in case of a formation of oil foam in
vacuum seal oil tank
Open drain connection of lube oil storage
Lube oil storage vessels level vessel10MKQ11BB001/10MKQ12BB001
21.
High >95 % Reduce the vacuum pressure at 10MKQ10CP001 to 150-200
mbar abs.
Verify that the prerequisites for starting the vacuum pumps
are fulfilled, refer to
section "Starting up operational vacuum pump
10MKQ11AN001"
Open valve 10MKQ11AA202 and drain the excess
Condensation water level condensation water in water trap approx. to the central line
22.
Max 1 of sight glass 10MKQ11AX001
Close valve 10MKQ11AA202 after draining.
Over pressure in vacuum tank10MKW20BB001 due to seal
oil system Malfunction
Vacuum pump 10MKQ11AN001 failure.
Pressure in oil box of vacuum
Pressure increase caused by explosive combustion in
23. pump 10MKQ11AN001 Max 1
vacuum pump 10MKQ11AN001.
>0,5 barg
Automatic switch off of operational vacuum pump
10MKQ11AN001 and switch over to
Standby vacuum pump 10MKQ12AN001.
Resistance temperature detector 10MKW20CT001
Seal oil heater temperature defective.
24.
Max 1 > 120°C “Heaters TRIP Temperature sensor 10MKW20CT311/321 defective.
Replace resistance temperature detector 10MKW20CT001.

Page 4|7