GUIDE FOR

HYRAULIC CALCULATION
OF
SPRINKLER SYSTEM

MANUAL WORKSHEET METHOD


+
WITH ELITE SOFTWARE

STEP BY STEP PROCEDURE

Prepared by: Mehboob Shaikh


B.E(ME) || CFPS || CFI-1 || AMIE

MITI Consultancy Training|Engineering|Inspections info@mitionline.com


MANUAL CALCULATION

MITI Consultancy Training|Engineering|Inspections info@mitionline.com


The Layout Process

1. Define the Hazard


2. Analyze the Structure
3. Analyze the Water Supply
4. Select the Type of System
5. Select the Sprinkler Type(s) and Locate Them
6. Arrange the Piping
7. Arrange Hangers and Bracing (where needed)
8. Include System Attachments
9. Hydraulic Calculations
9.1 Identify hazard category
9.2 Determine sprinkler spacing
9.3 Determine piping arrangement
9.4 Calculate amount of water needed per sprinkler
9.5 Calculate number and location of open sprinklers in
the hydraulically most demanding area
9.6 Start at most remote sprinkler and work towards the
water supply calculating flows and pressures
9.7 Compare demand with supply
10. Notes and Details for Plans
11. As-Built Drawings

MITI Consultancy Training|Engineering|Inspections info@mitionline.com


Example Project : A Electronic Storage Warehouse
100 FT.

Plan view

200 FT.
18 FT.

Elevation view

MITI Consultancy 200 FT.


Training|Engineering|Inspections info@mitionline.com
Step:1 : Define Hazard
In accordance with NFPA 13,2013- chapter Chapter 5 & Appendix A 5.3.1
Electronic factory is classified as Ordinary Hazard Group -1 Occupancy

Step:2 : Analyzed Structure


Assuming Completed

Step:3 : Analyze water Supply


Based on the Fire Flow test Conducted on Public water mains in
accordance with NFPA 291

MITI Consultancy Training|Engineering|Inspections info@mitionline.com


Step:4 : Select the Type of System
Wet Pipe System

Step:5 : Type of Sprinkler


Standard Spray Quick response upright sprinkler with K factor of 5.6

Step:6,7 & 8 : Arrangement of Piping with


attachments
Sprinkler are 10 ft. apart on the branch lines and 12.5 between branch
lines.
Piping arragment is as shown below,

MITI Consultancy Training|Engineering|Inspections info@mitionline.com


10 ft. between the sprinkler

5 ft. from north wall and 6ft from North


west wall Pipe Layout

z
100 FT.

200 FT.
Mains and branches are Sch 40
pipes

12.5 ft between the branch


18 FT.

15 FT.

All branches are on a 1 ft. riser


ACV
nipple N

200 FT.
Gate Valve

MITI Consultancy Training|Engineering|Inspections info@mitionline.com


Step: 9 : Hydraulic Calculation

Isometric View

10 ft. Standard Quick response


Maximum Area of Operation
Branch lines 12.5 ft. Sprinkler with K-5.6

1
2
5 Area of operation have
3 1-inch been reduced in
1 ½-inch accordance with cl.
1 ¼-inch 6 11.2.3.2.3
4
1 ¼-inch 7
1 ½-inch 8
BL1

3-inch Starting Sprinkler Values :


BL2 9
• Each sprinkler covers an area of 125 ft 2
• Each sprinkler is required to deliver a density of 0.15 gpm/ft 2
3-inch • Minimum flow per sprinkler:
125 ft2 x 0.15 gpm/ft2 = 18.8 gpm
BL3
Minimum pressure for 18.8 gpm:
2
Cross main  18.8 gpm 
p   11.3psi
TOR  5.6 

3-inch
Riser

N Alarm Check valve

15 ft. Gate Valve This is going to be the


Pressure @ Sprinkler -1
FF

MITI Consultancy Training|Engineering|Inspections info@mitionline.com


Select a Design approach
Using Density/Area Curve (NFPA 13, Chapter 11, Fig;11.2.3.1.1)

As per above figure,


Area of operation = 1500 Sq. Ft.
Density = 0.15 gpm/sq ft.

Check for Area Adjustment :


Quick response sprinklers (in light hazard or ordinary hazard with wet pipe
system, reduce design area based on maximum ceiling height, where it is
less than 20 ft) ----NFPA 13,2013,11.2.3.2.3 excerpt,

MITI Consultancy Training|Engineering|Inspections info@mitionline.com


“Area of Operation shall be permitted to be reduced withtout revising the
density as indicated in the below figure when all of the following
conditions are satified.

1. Wet Pipe System


2. Light Hazard or Ordinary hazard Occupancy
3. 20 ft. Maximum ceiling height
4. There are no Protected ceiling pockets as allowed by 8.6.7 and 8.8.7
exceeding 32 sq. ft.

- 3x
y  55
2
 3(18)
y  55
2
 54
y  55  28%
2

MITI Consultancy Training|Engineering|Inspections info@mitionline.com


Design area = 1500 Sq ft.
Applying the 28% reduction in area
100% - 28% = 72%
Therefore, 1500 Sq ft. X 0.72 = 1080 Sq. Ft.

New Area of Operation = 1080 Sq .ft.


Density remains same = 0.15 gpm/Sq.ft.

Spacing between the Sprinkler (S) = 10 ft.


Spacing between the branch (L) = 12.5 ft.

Area of Coverage = S x L
Area of Coverage = 10 x 12.5
Area of Coverage = 125 Sq. ft.

𝐷𝑒𝑠𝑖𝑔𝑛 𝐴𝑟𝑒𝑎
No. of Sprinklers in the design area =
𝐴𝑟𝑒𝑎 𝑜𝑓 𝐶𝑜𝑣𝑒𝑟𝑎𝑔𝑒
1080
No. of Sprinklers in the design area =
125
No. of Sprinklers in the design are = 9 Sprinklers

MITI Consultancy Training|Engineering|Inspections info@mitionline.com


No. of Sprinkler Along the branch Line = 1.2√𝐴𝑟𝑒𝑎 𝑜𝑓 𝑜𝑝𝑒𝑟𝑎𝑡𝑖𝑜𝑛 ÷ 10
No. of Sprinkler Along the branch Line = 1.2 √1080 ÷ 10
No. of Sprinkler Along the branch Line = 3.94 Say 4 Sprinklers

Check if Area Increase is required ….?


30% for dry pipe (NFPA 13,2013-11.2.3.2.5)
30% for double interlock (NFPA 13,2013-11.2.3.2.5)
30% for Pitched Ceiling (NFPA 13,2013-11.2.3.2.4)

Starting Sprinkler Values :

• Each sprinkler covers an area of 125 ft2


• Each sprinkler is required to deliver a density of 0.15 gpm/ft2
• Minimum flow per sprinkler:
125 ft2 x 0.15 gpm/ft2 = 18.8 gpm
• Minimum pressure for 18.8 gpm:
2
 18.8 gpm 
p   11.3psi
 5.6 

MITI Consultancy Training|Engineering|Inspections info@mitionline.com


Check :

 What is minimum required pressure by code ? ( 7 psi)


 What is minimum pressure required by manufacturer? (specs)
 Is minimum calculated pressure greater than minimums?

11.3 > 7 Psi or Specs ? (Yes)

Data Summary :

Water Supply Information


Static Pressure 90 psi @ 0 gpm
Residual Pressure 60 psi @ 1000 gpm
Hazard Classification OH - 1
System Type Wet
Ceiling Height 18 feet
Density/Area 0.15 gpm/ft2 / 1500 ft2
Adjusted to 0.15 gpm/ft2 / 1080 ft2
Sprinkler Type Quick Response – Standard Spray
K – Factor K =5.6
Area Per Sprinkler 125 ft2
Minimum Sprinkler Flow 18.8 gpm
Minimum Pressure 11.3 psi

MITI Consultancy Training|Engineering|Inspections info@mitionline.com


Calculation Paths :

Main Path :

1 2 3 4 BL1 BL2

BL3 TOR

Auxillary Paths-1 :

5 6 7 8 BL2

Auxillary Paths-2 :

6 BL3

MITI Consultancy Training|Engineering|Inspections info@mitionline.com


Branch wise Calculation :

18.8 gpm @
11.3 psi
19.95 gpm
@ 12.69 psi

84..36 gpm
@ 27.28 psi

28.33 gpm
21.3 gpm @
@ 27.71psi
14.4 psi

84.36 gpm
@ 24.38 psi

N 197.07 gpm
@ 41.41 psi

MITI Consultancy Training|Engineering|Inspections info@mitionline.com


SPRINKLER HYDRAULIC CALCULATION(Manual Worksheet)

Reference : NFPA 13,2013, Chapter 23, 23.3 & 23.4


Fittings-
Node- Elev- K- Flow added
Nominal ID Quantity L- ft C Factor Total(Pt)
1 1 Factor this step(q)
and Length Remarks
(Density Notes
F-ft Pf per foot (psi)( Elev(Pe) Verificat
Node- Elev- Total Flow
Actual ID 4.52*Q^1.85*/C^1.8
2 2 (Q) ion)
T- ft 5/d^4.87) Frict( Pf)
10.00 120.000 11.300 0.15
1 17 5.6 18.800 1.00 1E
2.00 0.116 Q1 = 18.8 gpm & P1 = 11.3
2 17 18.800 1.05 12.00 1.393
10.00 120.000 12.693 0.16
2 17 5.6 19.951 1.25 1T
6.00 0.116 Q2 =19.95 gpm & P2 = 12.69
3 17 38.751 1.38 16.00 1.862
10.00 120.000 14.554 0.17
3 17 5.6 21.364 1.25 1T
6.00 0.262 Q3 =21.3 gpm & P3 = 14.54
4 17 60.115 1.38 16.00 4.195
2T 19.00 120.000 18.749 0.19
4 17 5.6 24.248 1.50
16.00 0.232 0.433 Q4 =24.248 gpm & P4 = 18.74
BL1 16 84.363 1.61 35.00 8.107
0 12.50 120.000 27.289 0.67 QBL1 =84.363 gpm & PBL1 =
BL1 16 16.15 84.363 3.00
- 0.007 0.000 27.289, balaning flow @ BL1 &
BL2 | Keq @ BL1 & BL2 =
BL2 16 84.363 3.26 12.50 0.093 84.363/(27.289)^(0.5) = 16.15
0 12.50 120.000 27.382 0.67
BL2 16 84.363 3.00
- 0.027 0.000
BL3 16 168.726 3.26 12.50 0.336
3.00 1ACV 182.80 120.000 27.718 0.23
BL3 16 5.38 28.337 Keq @ BL3 = 5.38 ( Keq =
1E 18.00 0.036 6.495
18.8/12.2^0.5)
FF 16 197.063 3.26 1GV 200.80 7.196
41.409

MITI Consultancy Training|Engineering|Inspections info@mitionline.com


Pressure (psi)

System Demand
197 gpm @ 41.40 psi

With Hose Stream


447 gpm @ 41.0 psi

Flow (gpm)

Min. Density Vertification :

The value in the hydraulic calculations should be higher than the


minimum density times area due to pressure losses in the system

MITI Consultancy Training|Engineering|Inspections info@mitionline.com


ELITE SOFTWARE
CALCULATION

MITI Consultancy Training|Engineering|Inspections info@mitionline.com


Step :1 - General Project Data(client,Company & building data) :

Select Hazard, NFPA 13, Ch.05


Step-2 : System data:

Adjusted area of operation

City water mains flow test result


as per NFPA 291
MITI Consultancy Training|Engineering|Inspections info@mitionline.com
Step -3 : Pipe Data Nodes, Pipe Length & Dia. Along
with details of fittings

Final Node will be the inflow


node

MITI Consultancy Training|Engineering|Inspections info@mitionline.com


Select Calculation Mode
Step-4 : Calculation
Smallter imbalance will take more
time and result will be more accurate

Press “Calculate” upon filling


all details
Step-5 : Solution

MITI Consultancy Training|Engineering|Inspections info@mitionline.com


Report :

Print Report

MITI Consultancy Training|Engineering|Inspections info@mitionline.com


ELECTRONIC STORAGE WAREHOUSE
Fire Sprinkler Reports

for

ABC Brothers

Mumbai
Maharastra-400083

Prepared By:

Mehboob Shaikh
ABC Pvt. Ltd
Mumbai
Maharastara 400083
+919146861270
10/6/2020
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Electronic Storage Warehouse
Hell Page 2

General Project Data Report

General Data
Project Title: Electronic Storage Warehouse Project File Name: Demo Project..fiw
Designed By: Mehboob Shaikh Date: 10/6/2020
Code Reference: NFPA 13,2013 Approving Agency: Civil Defense

Client Name: ABC Brothers Phone: +919146861270


Address: Mumbai City, State Zip Code: Maharastra-400083
Company Name: ABC Pvt. Ltd Representative: Mr. George
Company Address: Mumbai City And State: Maharastara 400083
Phone: +919146861270
Building Name: Ms. Electronic Store Building Owner: Mr. George
Contact at Building: Mr. David Phone at Building: +919146861270
Address Of Building: Mumbai City, State Zip Code: Maharastra-400083

Project Data
Description Of Hazard: Ordinary 1 Sprinkler System Type: Wet
Design Area Of Water Application: 1080 ft² Maximum Area Per Sprinkler: 130 ft²
Default Sprinkler K-Factor: 5.60 K Default Pipe Material: SCHED 40 WET STEEL
Inside Hose Stream Allowance: 0.00 gpm Outside Hose Stream Allowance: 250.00 gpm
In Rack Sprinkler Allowance: 0.00 gpm

Sprinkler Specifications
Make: TYCO Model: QR
Size: 0.5" Temperature Rating: 155 F

Water Supply Test Data


Source Of Information:
Test Hydrant ID: XYZ001 Date Of Test:

Hydrant Elevation: 0 ft Static Pressure: 90.00 psi


Test Flow Rate: 1000.00 gpm Test Residual Pressure: 60.00 psi
Calculated System Flow Rate: 474.96 gpm Calculated Inflow Residual Pressure: 40.53 psi
Available Residual Pressure At
82.43 psi
System Flow:

Calculation Project Data


Calculation Mode: Demand
HMD Minimum Residual Pressure: 7.00 psi Minimum Desired Flow Density: 0.15 gpm/ft²
Maximum Water Velocity: 10.00 ft/s Maximum Frictional Loss / 100 feet: 0.00 psi
Number Of Active Nodes: 8
Number Of Active Pipes: 7 Number Of Inactive Pipes: 1
Number Of Active Sprinklers: 7 Number Of Inactive Sprinklers: 0

C:\Users\USER\Desktop\Demo Project..fiw Thursday, October 8, 2020, 12:52 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Electronic Storage Warehouse
Hell Page 3

Fire Sprinkler Input Data

Node Input Data


Sprinkler Pressure Node Elev (ft) Non-Sprinkler
Area Group
Node Node Description KFactor (K) Estimate (psi) Branch Non- Flow (gpm)
Branch Dia.
No. Branch Description Branch Len. Branch Stnd Stnd Fittings Branch Sprk
(in)
(ft) Fittings (ft) KFactor (K)

Sprinkler ---- 5.60 11.21 17.00 0.00


1
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.60 12.60 17.00 0.00


2
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.60 14.45 17.00 0.00


3
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.60 18.62 17.00 0.00


4
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 16.15 27.11 16.00 0.00


5
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.38 27.56 16.00 0.00


6
---- 0.000 0.0 ---- 0.0 0.00

Sprinkler ---- 5.38 28.16 16.00 0.00


7
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 40.53 16.00 0.00


8
---- 0.000 0.0 ---- 0.0 0.00

C:\Users\USER\Desktop\Demo Project..fiw Thursday, October 8, 2020, 12:52 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Electronic Storage Warehouse
Hell Page 4

Fire Sprinkler Input Data

Pipe Input Data


Nominal Nominal Fitting Total CFactor
Beg. End. Type Fitting
Pipe Description Diameter Length Length Length (gpm/inch-
Node Node Group Data
(inch) (feet) (feet) (feet) psi)

1 2 SCHED 40 WET STEEL 1.000 0 E 10.00 2.00 12.00 120

2 3 SCHED 40 WET STEEL 1.250 0 T 10.00 6.00 16.00 120

3 4 SCHED 40 WET STEEL 1.250 0 T 10.00 6.00 16.00 120

4 5 SCHED 40 WET STEEL 1.500 0 2T 19.00 16.00 35.00 120

5 6 SCHED 40 WET STEEL 3.000 0 12.50 0.00 12.50 120

6 7 SCHED 40 WET STEEL 3.000 0 12.50 0.00 12.50 120

7 8 SCHED 40 WET STEEL 3.000 0 EBG 182.80 18.00 200.80 120

C:\Users\USER\Desktop\Demo Project..fiw Thursday, October 8, 2020, 12:52 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Electronic Storage Warehouse
Hell Page 5

Fire Sprinkler Output Data

Overall Node Groupings Output Data


Pipe Segment Pipe Pipe Sprinkler Flow Non-Sprinkler Flow Beg. Node Imbalance
Beg. End. Type Flow Rate At Beg. Node Out (+) In (-) Residual Flow At Beg.
Node Node Group (gpm) (gpm) (gpm) (gpm) Pressure (psi) Node (gpm)

1 2 0 -18.75 18.75 0.00 0.00 11.21

2 1 0 18.75 19.88 0.00 0.00 12.60 0.00000


2 3 0 -38.63

3 2 0 38.63 21.29 0.00 0.00 14.45 0.00000


3 4 0 -59.91

4 3 0 59.91 24.16 0.00 0.00 18.62 0.00000


4 5 0 -84.08

5 4 0 84.08 84.09 0.00 0.00 27.11 0.00000


5 6 0 -168.17

6 5 0 168.17 28.24 0.00 0.00 27.56 0.00000


6 7 0 -196.41

7 6 0 196.41 28.55 0.00 0.00 28.16 0.00000


7 8 0 -224.96

8 7 0 224.96 0.00 0.00 -224.96 40.53

C:\Users\USER\Desktop\Demo Project..fiw Thursday, October 8, 2020, 12:52 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Electronic Storage Warehouse
Hell Page 6

Fire Sprinkler Output Data

Overall Pipe Output Data


q (gpm) F. L./ft Pipe-Len.
Beg. Nodal Spk/Hose Residual Nom. Dia. PF-(psi)
Elevation Q (gpm) (psi/ft) Fit-Len.
End. KFactor Discharge Pressure Inside Dia. PE-(psi)
(feet) Velocity Fittings Tot-Len.
Node (K) (gpm) (psi) C-Value PT-(psi)
(fps) Type-Grp (ft)

1 5.60 17.00 18.75 11.21 1.00 18.75 0.11553 10.00 1.386


2 5.60 17.00 19.88 12.60 1.049 18.75 E 2.00 0.000
SCHED 40 WET STEEL 120 6.96 0 12.00 1.386

2 5.60 17.00 19.88 12.60 1.25 19.88 0.11571 10.00 1.851


3 5.60 17.00 21.29 14.45 1.380 38.63 T 6.00 0.000
SCHED 40 WET STEEL 120 8.29 0 16.00 1.851

3 5.60 17.00 21.29 14.45 1.25 21.29 0.26067 10.00 4.171


4 5.60 17.00 24.16 18.62 1.380 59.91 T 6.00 0.000
SCHED 40 WET STEEL 120 12.85 0 16.00 4.171

4 5.60 17.00 24.16 18.62 1.50 24.16 0.23031 19.00 8.061


5 16.15 16.00 84.09 27.11 1.610 84.08 2T 16.00 0.433
SCHED 40 WET STEEL 120 13.25 0 35.00 8.494

5 16.15 16.00 84.09 27.11 3.00 84.09 0.03594 12.50 0.449


6 5.38 16.00 28.24 27.56 3.068 168.17 ----- 0.00 0.000
SCHED 40 WET STEEL 120 7.30 0 12.50 0.449

6 5.38 16.00 28.24 27.56 3.00 28.24 0.04790 12.50 0.599


7 5.38 16.00 28.55 28.16 3.068 196.41 ----- 0.00 0.000
SCHED 40 WET STEEL 120 8.52 0 12.50 0.599

7 5.38 16.00 28.55 28.16 3.00 0.00 0.06157 182.80 12.364


8 0.00 16.00 0.00 40.53 3.068 224.96 EBG 18.00 0.000
SCHED 40 WET STEEL 120 9.76 0 200.80 12.364

C:\Users\USER\Desktop\Demo Project..fiw Thursday, October 8, 2020, 12:52 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Electronic Storage Warehouse
Hell Page 7

Fire Sprinkler Output Data

Overall Sprinkler Output Data


Flowing Sprinkler Residual Flowing Sprinkler
Area Group Sprinkler Flowing Area
Sprinkler Elevation Pressure Density Discharge
Code KFactor (K) (ft²)
Node No. (feet) (psi) (gpm/ft²) (gpm)

1 5.60 17.00 11.21 125.00 0.150 18.75


Sub Totals For Non-Group 125.00 0.150 18.75

2 5.60 17.00 12.60 125.00 0.159 19.88


Sub Totals For Non-Group 125.00 0.159 19.88

3 5.60 17.00 14.45 125.00 0.170 21.29


Sub Totals For Non-Group 125.00 0.170 21.29

4 5.60 17.00 18.62 125.00 0.193 24.16


Sub Totals For Non-Group 125.00 0.193 24.16

5 16.15 16.00 27.11 125.00 0.673 84.09


Sub Totals For Non-Group 125.00 0.673 84.09

6 5.38 16.00 27.56 125.00 0.226 28.24


Sub Totals For Non-Group 125.00 0.226 28.24

7 5.38 16.00 28.16 125.00 0.228 28.55


Sub Totals For Non-Group 125.00 0.228 28.55

Totals For All Groups 875.00 0.257 224.96

C:\Users\USER\Desktop\Demo Project..fiw Thursday, October 8, 2020, 12:52 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Electronic Storage Warehouse
Hell Page 8

Fire Sprinkler Output Summary

Hydraulically Most Demanding Sprinkler Node


HMD Sprinkler Node Number: 1
HMD Actual Residual Pressure: 11.21 psi
HMD Actual GPM: 18.75 gpm

Sprinkler Summary
Sprinkler System Type: Wet
Specified Area Of Application: 1080.00 ft²
Minimum Desired Density: 0.150 gpm/ft²
Application Average Density: 0.208 gpm/ft²
Application Average Area Per Sprinkler: 154.29 ft²
Sprinkler Flow: 224.96 gpm
Average Sprinkler Flow: 32.14 gpm

Flow Velocity And Imbalance Summary


Maximum Flow Velocity ( In Pipe 4 - 5 ) 13.25 ft/sec
Maximum Velocity Pressure ( In Pipe 4 - 5 ) 1.18 psi

Allowable Maximum Nodal Pressure Imbalance: 0.0000 psi


Actual Maximum Nodal Pressure Imbalance: 0.0000 psi
Actual Average Nodal Pressure Imbalance: 0.0000 psi
Actual Maximum Nodal Flow Imbalance: 0.0000 gpm
Actual Average Nodal Flow Imbalance: 0.0000 gpm

Overall Network Summary


Number Of Unique Pipe Sections: 7
Number Of Flowing Sprinklers: 7

Pipe System Water Volume: 83.81 gal

Sprinkler Flow: 224.96 gpm


Non-Sprinkler Flow: 0.00 gpm
Demand Flow Excluding Exterior Hose Flow: 224.96 gpm
Exterior Hose Flow: 250.00 gpm

Minimum Required Residual Pressure At System Inflow


40.53 psi
Node:
Demand Flow At System Inflow Node: 474.96 gpm

C:\Users\USER\Desktop\Demo Project..fiw Thursday, October 8, 2020, 12:52 PM


Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Electronic Storage Warehouse
Hell Page 9

Fire Sprinkler Output Data

Hydraulic Supply/Demand Graph

100

90
90

80

70
Pressure psi

60
60

50

40

30

20

10

0
1 2 3 4 5 6 7 8 9 10
Flowrate(x100) gpm

Supply Curve Data


Static Pressure: 90 psi
Test Residual Pressure: 60 psi
Test Flow Rate: 1000 gpm

Demand Curve Data


Calculated Residual Pressure: 40.53 psi
Calculated Flow Rate: 474.96 gpm
Exterior Hose Flow: 250.00 gpm
Excess Available Residual Pressure At Calculated Flow: 41.91 psi
Pressure Required For First Sprinkler Downstream From Inflow Node To Flow: 0.00 psi

C:\Users\USER\Desktop\Demo Project..fiw Thursday, October 8, 2020, 12:52 PM