Sie sind auf Seite 1von 8

REPUBLIC OF THE PHILIPPINES

NUEVA ECIJA UNIVERSITY OF SCIENCE AND TECHNOLOGY


COLLEGE OF ENGINEERING
DEPARTMENT OF ELECTRICAL ENGINEERING

ASSIGNMENT IN EE 423
Transformer loading characteristics

Submitted by: Abdifatah M. Abdi


Submitted to: Engr.Erbert Alison J.Benedicto
Date : February 20,2020
A. PRIMARY VOLTAGE VS LOAD

Primary Voltage vs Load Current


2,360.00

2,340.00

2,320.00
Vp in (V)

2,300.00

2,280.00

2,260.00

2,240.00
0 1 2 3 4 5 6 7 8 9
current in (A)
VP UNITY
VP 0.9
LAGGING

LOAD VP UNITY VP 0.9 VP 0.9


(A) LAGGING LEADING
2,300.0
0 2,300.00 0 2,300.00
2,308.4
2 2,303.43 8 2,297.69
2,317.0
4 2,306.93 1 2,295.45
2,325.5
6 2,310.50 7 2,293.28
2,334.1
8 2,314.13 8 2,291.18
2,342.8
10 2,317.83 2 2,289.15
2,351.5
12 2,321.59 1 2,287.19
B. PRIMARY VOLTAGE VS PF

Primary voltage vs pf
2,371
2,352
2,333
2,314
2,295
2,276
2,257
2,238
2,219
2,200
-0.1 -0.2 -0.3 -0.4 -0.5 -0.6 -0.7 -0.8 -0.9 1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1
PF

LOAD (PF) VP (volts) RESPONSE

-0.1 2234.93
-0.2 2237.89
-0.3 2241.57
-0.4 2246.05
-0.5 2251.42 LEADING
-0.6 2257.85
-0.7 2265.61
-0.8 2275.28
-0.9 2288.29
1 2319.46 UNITY
0.9 2346.6
0.8 2355.61
0.7 2361.31
0.6 2365.14
0.5 2367.67 LAGGING
0.4 2369.18
0.3 2369.83
0.2 2369.73
0.1 2368.93
C. SECONDARY VOLTAGE VS LOAD

Secondary Voltage vs LOAD


232

230

228
VS (V)

226

224

222

220
0 1 2 3 4 5 6 7 8 9
IS (A)

Vs UNITY Vs 0.9 LAGGING Vs 0.9 LEADING

LOAD Vs at Vs 0.9 Vs 0.9


(A) UNITY LAGGING LEADING
0 230 230 230
20 229.66 229.15 230.23
40 229.31 228.31 230.45
60 228.95 227.46 230.67
80 228.59 226.61 230.88
100 228.22 225.77 231.08
120 227.84 224.92 231.28
D. SECONDARY VOLTAGE VS PF

Secondary voltage vs PF
240
238
236
234
232
230
VS

228
226
224
222
220
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
PF

LOAD Vs
(volts) RESPONSE
(PF)
-0.1 236.41
-0.2 236.13
-0.3 235.77
-0.4 235.55
-0.5 234.81 LEADING
-0.6 234.18
-0.7 233.41
-0.8 232.46
-0.9 231.17
1 228.05 UNITY
0.9 225.40
0.8 224.48
0.7 223.89
0.6 223.50
0.5 223.24 LAGGING
0.4 223.08
0.3 223.02
0.2 223.03
0.1 223.11
E. REGULATION VS LOAD

Voltage regulati on vs Load


3

2.5

1.5
%VR

0.5

0
0 2 4 6 8 10 12

-0.5

-1
LOAD (IP)
VR UNITY VR LAGGING VR LEADING

LOAD VR VR VR
(IP) UNITY LAGGING LEADING
0 0 0 0
2 0.15 0.37 -0.1
4 0.3 0.74 -0.2
6 0.46 1.11 -0.29
8 0.61 1.49 -0.38
10 0.78 1.86 -0.47
12 0.94 2.24 -0.56
F. REGULATION VS PF

Regulati on vs PF
4.00

3.00

2.00

1.00
%VR (%)

0.00
-0.1 -0.2 -0.3 -0.4 -0.5 -0.6 -0.7 -0.8 -0.9 1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1
-1.00

-2.00

-3.00

-4.00
PF

LOAD
VR (%) RESPONSE
(PF)
-0.1 -3
-0.2 -3.03
-0.3 -3.04
-0.4 -3.01
-0.5 -2.94 LEADING
-0.6 -2.82
-0.7 -2.64
-0.8 -2.38
-0.9 -2.04
1 0.85 UNITY
0.9 2.03
0.8 2.42
0.7 2.67
0.6 2.83
0.5 2.94 LAGGING
0.4 3.01
0.3 3.01
0.2 3.03
0.1 3.00