Sie sind auf Seite 1von 4

Totally Integrated

Automation Portal

Projet7 / PLC_1 [CPU 1212C AC/DC/Rly] / Blocs de programme


Main [OB1]
Main Propriétés
Général
Nom Main Numéro 1 Type OB Langage CONT
Numéroration Automatique
Information
Titre "Main Program Sweep (Cy‐ Auteur Commentaire Famille
cle)"
Version 0.1 ID utilisateur

Main
Nom Type de données Valeur par déf. Surveillance Commentaire
Temp
Constant

Réseau 1 :

%DB4
"MC_Power_DB_2"
MC_Power

EN ENO
Axis_1 Axis Status ...
true Enable Error ...
0 StopMode

Réseau 2 :

%DB5
"MC_MoveJog_
DB"

%M0.1 MC_MoveJog
"X1"
EN ENO
Axis_1 Axis InVelocity ...
true JogForward Error ...
false JogBackward
%MD2
"vitesse" Velocity

Réseau 3 :

%DB6
"MC_MoveJog_
DB_1"

%M0.5 MC_MoveJog
"X5"
EN ENO
Axis_1 Axis InVelocity ...
false JogForward Error ...
true JogBackward
%MD2
"vitesse" Velocity

Réseau 4 :

%M0.1
"X1" MOVE
EN ENO
300 IN %MD2
%M0.5 OUT1 "vitesse"
"X5"

Réseau 5 :

%M0.2
"X2" MOVE
EN ENO
0 IN %MD2
%M0.6 OUT1 "vitesse"
"X6"
Totally Integrated
Automation Portal

Réseau 6 :

%M0.0 %I1.5 %I1.6 %M0.1


"X0" "BA0M" "Pos_1" "X1"
S

%M0.0
"X0"
R

Réseau 7 :

%M0.1 %I1.7 %M0.2


"X1" "Pos_0" "X2"
S

%M0.1
"X1"
R

Réseau 8 :

%DB9
"t1"
%M0.2 TON %M0.3
"X2" Time "X3"
IN Q S
T#2s PT ET ...
%M0.2
"X2"
R

Réseau 9 :

%DB8
"t2"
%M0.3 TON %M0.4
"X3" Time "X4"
IN Q S
T#4s PT ET ...
%M0.3
"X3"
R

Réseau 10 :

%DB10
"t3"
%M0.4 TON %M0.5
"X4" Time "X5"
IN Q S
T#2s PT ET ...
%M0.4
"X4"
R

Réseau 11 :

%M0.0 %I2.0 %I1.7 %M0.5


"X0" "BA1D" "Pos_0" "X5"
S

%M0.0
"X0"
R

Réseau 12 :
Totally Integrated
Automation Portal

%M0.5 %I1.6 %M0.6


"X5" "Pos_1" "X6"
S

%M0.5
"X5"
R

Réseau 13 :

%DB11
"t4"
%M0.6 TON %M0.7
"X6" Time "X7"
IN Q S
T#2s PT ET ...
%M0.6
"X6"
R

Réseau 14 :

%DB12
"t5"
%M0.7 TON %M1.0
"X7" Time "X8"
IN Q S
T#4s PT ET ...
%M0.7
"X7"
R

Réseau 15 :

%DB13
"T6"
%M1.0 TON %M0.0
"X8" Time "X0"
IN Q S
T#2s PT ET ...
%M1.0
"X8"
R

Réseau 16 :

%M0.2 %Q1.3
"X2" "OuvP0"

Réseau 17 :

%M0.4 %Q1.1
"X4" "FeP0"

Réseau 18 :

%M0.6 %Q1.4
"X6" "OuvP1"

Réseau 19 :

%M1.0 %Q1.2
"X8" "FeP1"
Totally Integrated
Automation Portal

Réseau 20 :

%M0.0 %M0.1 %M0.2 %M0.3 %M0.4 %M0.5 %M0.6 %M0.7 %M1.0 %M0.0
"X0" "X1" "X2" "X3" "X4" "X5" "X6" "X7" "X8" "X0"
S