SUBMITTAL AM012MNMDCH/AA Page 1 of 3

Samsung DVM S Series, Duct S, Ducted Unit


-RE1DPH /RFDWLRQ
3XUFKDVHU (QJLQHHU
6XEPLWWHGWR 5HIHUHQFH $SSURYDO &RQVWUXFWLRQ
8QLW'HVLJQDWLRQ 6FKHGXOH

Specifications
Cooling (Btu/h) 12,000
Performance Nominal Capacity 1
Heating (Btu/h) 13,500

Voltage ø / V / Hz 1 / 208-230 / 60


Power
Nominal Running Current (A) 0.26 • Compatible with Samsung DVM S, DVM S Water, and DVM S Eco
systems (AM**********AA).
Type Sirocco (2)
• Horizontal discharge airflow
Fan Type BLDC (1)
Motor • The indoor unit shall have a removable EEPROM that stores system
Output (W) 153 programming information, unit name, and other data

CFM (UL) H/M/L 353 / 300 / 247 • All indoor unit addressing and option settings shall be done digitally;
Airflow the indoor unit does not contain rotary dials or setting switches.
Total CFM Range 2 247 - 600
• The indoor unit shall have static pressure scanning for simple setup
and optimized comfort settings for the occupant.
External Static Standard "WC 0.04
Pressure Min. / Max. "WC 0 - 0.6 • The indoor unit shall have smart-tuning function that can provide
optimized comfort by allowing the occupant to offset the fan CFM
Type R410A curve with a wired remote controller (MWR-SH10N, MWR-SH11UN,
Refrigerant MWR-WE13*N, MWR-WG00J*N) to increase or decrease airflow.
Control Method Electronic Expansion Valve
• The indoor unit shall allow service access from four sides (top,
Liquid (flare) Inches 1/4 bottom, left, right).
Piping • The indoor unit shall have an internal condensate pump as standard
Suction (flare) Inches 1/2
Connections with float switch (maximum 29" lift from bottom of unit).
Drain Inches 1 1/16" ID for 3/4" PVC
•High-voltage terminal block temperature sensor to disable unit in
WXHXD Inches 33 7/16 X 9 13/16 X 27 9/16 the event overheating of power connection.
•Discharge air temperature sensor with target discharge temperature
Unit Weight lbs. 69.4
control capability
Dimensions Supply 32 3/16 X 8 11/16
Duct Connections
Construction
(inches) Return 32 3/16 X 8 11/16 The unit shall be constructed of insulated, galvanized steel

Sound Level H/M/L dB(A) 27 / 25 / 23 Heat Exchanger


The heat exchanger shall be mechanically bonded fin to copper tube
Filter Box FB-DS1
Indoor Fan
External Contact Control MIM-B14 Indoor fan is a centrifugal type with a single fan motor
Accessories Wireless Receiver Kit MRK-A10N
Three fan speed settings and auto setting
External Temperature Sensor MRW-TA
Fan output can be configured during commissioning for various
CN83 Pigtail (for 12VDC VENT output) DB39-01263A external static pressure ranges

Safety Certifications ETL (UL 1995) Controls


1
The unit shall be operated via a wireless or wired remote control with
Nominal cooling capacities are based on: Indoor temperature: 80 ⁰F DB, 67⁰F WB. Outdoor temperature: 95⁰F DB, 75°F WB
DDC type signal
Nominal heating capacities are based on: Indoor temperature: 70 ⁰F DB, 60⁰F WB. Outdoor temperature: 47⁰F DB, 43⁰F WB.
2
Refer to technical data book for fan performance details and settings Controls shall integrate with a BMS system
Samsung HVAC maintains a policy of ongoing development, specifications are subject to change without notice.
Control wiring shall be 2 X 16 AWG shielded wire

Air Filtration
The unit shall ship with basic filtration as standard

Pressure drop across the filter must be factored into the total ESP.

© 2019 Samsung HVAC www.SamsungHVAC.com


SHA-DVMS-08012019 888-699-6067
SUBMITTAL AM012MNMDCH/AA Page 2 of 3

Samsung DVM S Series, Duct S, Ducted Unit


AM012MNMDCH/AA Dimensional Drawing

1 1/8"

7 1/4”
6 1/4”
5 3/4”
30 - Ø0.13" hole
32 3/16"
[ Air around ]
Return air flange Return air flange
Inspection
700 X P100 = 700 2 1/4” opening

[ Top View ]

Anchor position

27 9/16"
29 1/4”

23 3/4”
27 1/2”

32 3/16"
5
33 1/2” 33 7/16"
35 1/4” (Suspension position) 37 3/8" 19 11/16"
37 1/2”

Supply air direction


9 1/4"
5 3/4" 4
2 1
Suspension bolt
( 4 x M8 ~ M10 )
8 11/16"

9 3/4"
Discharge side
Suction side
14 3/16" 3 3"

3 3/4"
[ Front View ]
[Right View]

NO Name Description
1 Liquid pipe connection Ø1/4"
2 Gas pipe connection Ø1/2"
3 Drain pipe connection 1 1/16" ID for 3/4" PVC
4 Power supply connection -
5 Air discharge flange -
6 Air filter -
7 Suspension point 5/16" ~ 3/8"

Inspection Opening Requirements Unit Clearance From Structure


Structure
Unit Depth + 2"

13/16" or more

Unit
Unit Width (W)
A=W+4" B=19 11/16" min.
13/16" or more
Ceiling
In applications where there is not a tile ceiling, an inspection hole is required.
If height between ceiling and structure is 1.64' or more, inspection opening "B" is
Service Access

recommended. If height between ceiling and structure is less than 1.64', inspection
opening "A" and "B" is recommended.(verify state and local codes).

www.SamsungHVAC.com
SUBMITTAL AM012MNMDCH/AA Page 3 of 3

Samsung DVM S Series, Duct S, Ducted Unit


Fan Characteristics (P-Q Curve)

External Static Pressure (inWC) Option Code External Static Pressure (inWC) Option Code
1 2
0≤ SP ≤0.04 010054-1E5072-202323-331102 0.04≤ SP ≤0.12 010054-1E50D6-202323-331102
0.8 0.8

0.7 0.7

External Static Pressure (inWC)


External Static Pressure (inWC)

0.6 0.6

0.5 0.5

0.4 0.4

HIGH HIGH
0.3 0.3
MID MID
0.2 LOW 0.2 LOW Upper limit of
external
Upper limit of static pressure
0.1 external Lower limit of 0.1
static pressure external 2 Lower
externallimit of
1 static pressure static pressure
0 0
200 300 400 500 600 700 800 900 200 300 400 500 600 700 800 900
Airflow Rate (CFM) Airflow Rate (CFM)

External Static Pressure (inWC) Option Code External Static Pressure (inWC) Option Code
3 4
0.12< SP ≤0.20 010054-1E5449-202323-331102 0.20< SP ≤0.30 010054-1E54BD-202323-331102

0.8 0.8

0.7 0.7
External Static Pressure (inWC)

External Static Pressure (inWC)


0.6 0.6

0.5 0.5

0.4 0.4 Upper limit of


HIGH external
static pressure
0.3 Upper limit of 0.3
4
HIGH external
static pressure MID
0.2 0.2
MID 3
Lower limit of
0.1 Lower limit of 0.1 external
external LOW static pressure
LOW static pressure
0 0
200 300 400 500 600 700 800 900 200 300 400 500 600 700 800 900
Airflow Rate (CFM) Airflow Rate (CFM)

External Static Pressure (inWC) Option Code External Static Pressure (inWC) Option Code
5 6
0.30< SP ≤0.40 010054-1E5911-202323-331102 0.40< SP ≤0.50 010054-1E5976-202323-331102

0.8 0.8

0.7 0.7
External Static Pressure (inWC)
External Static Pressure (inWC)

0.6 0.6 Upper limit of


HIGH external
static pressure
0.5 Upper limit of 0.5 6
HIGH external
static pressure
0.4 0.4
5 MID

0.3 MID 0.3 Lower limit of


external
static pressure
Lower limit of
0.2 external 0.2
static pressure LOW
LOW
0.1 0.1

0 0
200 300 400 500 600 700 800 900 200 300 400 500 600 700 800 900
Airflow Rate (CFM) Airflow Rate (CFM)

External Static Pressure (inWC) Option Code


7
0.50< SP ≤0.60 010054-1E59CA-202323-331102

0.8

0.7 Upper limit of


HIGH external
static pressure
External Static Pressure (inWC)

0.6
7

0.5
MID
0.4 Lower limit of
external
static pressure
0.3

0.2 LOW

0.1

0
300 400 500 600 700 800 900
Airflow Rate (CFM)