Specifications
Cooling (Btu/h) 12,000
Performance Nominal Capacity 1
Heating (Btu/h) 13,500
CFM (UL) H/M/L 353 / 300 / 247 • All indoor unit addressing and option settings shall be done digitally;
Airflow the indoor unit does not contain rotary dials or setting switches.
Total CFM Range 2 247 - 600
• The indoor unit shall have static pressure scanning for simple setup
and optimized comfort settings for the occupant.
External Static Standard "WC 0.04
Pressure Min. / Max. "WC 0 - 0.6 • The indoor unit shall have smart-tuning function that can provide
optimized comfort by allowing the occupant to offset the fan CFM
Type R410A curve with a wired remote controller (MWR-SH10N, MWR-SH11UN,
Refrigerant MWR-WE13*N, MWR-WG00J*N) to increase or decrease airflow.
Control Method Electronic Expansion Valve
• The indoor unit shall allow service access from four sides (top,
Liquid (flare) Inches 1/4 bottom, left, right).
Piping • The indoor unit shall have an internal condensate pump as standard
Suction (flare) Inches 1/2
Connections with float switch (maximum 29" lift from bottom of unit).
Drain Inches 1 1/16" ID for 3/4" PVC
•High-voltage terminal block temperature sensor to disable unit in
WXHXD Inches 33 7/16 X 9 13/16 X 27 9/16 the event overheating of power connection.
•Discharge air temperature sensor with target discharge temperature
Unit Weight lbs. 69.4
control capability
Dimensions Supply 32 3/16 X 8 11/16
Duct Connections
Construction
(inches) Return 32 3/16 X 8 11/16 The unit shall be constructed of insulated, galvanized steel
Air Filtration
The unit shall ship with basic filtration as standard
Pressure drop across the filter must be factored into the total ESP.
1 1/8"
7 1/4”
6 1/4”
5 3/4”
30 - Ø0.13" hole
32 3/16"
[ Air around ]
Return air flange Return air flange
Inspection
700 X P100 = 700 2 1/4” opening
[ Top View ]
Anchor position
27 9/16"
29 1/4”
23 3/4”
27 1/2”
32 3/16"
5
33 1/2” 33 7/16"
35 1/4” (Suspension position) 37 3/8" 19 11/16"
37 1/2”
9 3/4"
Discharge side
Suction side
14 3/16" 3 3"
3 3/4"
[ Front View ]
[Right View]
NO Name Description
1 Liquid pipe connection Ø1/4"
2 Gas pipe connection Ø1/2"
3 Drain pipe connection 1 1/16" ID for 3/4" PVC
4 Power supply connection -
5 Air discharge flange -
6 Air filter -
7 Suspension point 5/16" ~ 3/8"
13/16" or more
Unit
Unit Width (W)
A=W+4" B=19 11/16" min.
13/16" or more
Ceiling
In applications where there is not a tile ceiling, an inspection hole is required.
If height between ceiling and structure is 1.64' or more, inspection opening "B" is
Service Access
recommended. If height between ceiling and structure is less than 1.64', inspection
opening "A" and "B" is recommended.(verify state and local codes).
www.SamsungHVAC.com
SUBMITTAL AM012MNMDCH/AA Page 3 of 3
External Static Pressure (inWC) Option Code External Static Pressure (inWC) Option Code
1 2
0≤ SP ≤0.04 010054-1E5072-202323-331102 0.04≤ SP ≤0.12 010054-1E50D6-202323-331102
0.8 0.8
0.7 0.7
0.6 0.6
0.5 0.5
0.4 0.4
HIGH HIGH
0.3 0.3
MID MID
0.2 LOW 0.2 LOW Upper limit of
external
Upper limit of static pressure
0.1 external Lower limit of 0.1
static pressure external 2 Lower
externallimit of
1 static pressure static pressure
0 0
200 300 400 500 600 700 800 900 200 300 400 500 600 700 800 900
Airflow Rate (CFM) Airflow Rate (CFM)
External Static Pressure (inWC) Option Code External Static Pressure (inWC) Option Code
3 4
0.12< SP ≤0.20 010054-1E5449-202323-331102 0.20< SP ≤0.30 010054-1E54BD-202323-331102
0.8 0.8
0.7 0.7
External Static Pressure (inWC)
0.5 0.5
External Static Pressure (inWC) Option Code External Static Pressure (inWC) Option Code
5 6
0.30< SP ≤0.40 010054-1E5911-202323-331102 0.40< SP ≤0.50 010054-1E5976-202323-331102
0.8 0.8
0.7 0.7
External Static Pressure (inWC)
External Static Pressure (inWC)
0 0
200 300 400 500 600 700 800 900 200 300 400 500 600 700 800 900
Airflow Rate (CFM) Airflow Rate (CFM)
0.8
0.6
7
0.5
MID
0.4 Lower limit of
external
static pressure
0.3
0.2 LOW
0.1
0
300 400 500 600 700 800 900
Airflow Rate (CFM)