Control Loop
Control Loop in
Controlled Parameter Actuator Target Comments Available in PCS Reason for run in Manual Mode Comments [if any]
Auto/Manual
(Y/N)
Total mill feed (Fresh feed + separator Optimized production and power To provide constant material flow through the mill, target mill throughput is given
Fresh Feed Weigh feeders
rejects) or elevator power consumption by operator in t/h
Constant gas flow through the separator ensures constant lift of material and
Raw Mill fan Variable Speed Drive or
Separator Gas Flow Consistent particle size distribution separator performance constant, gas flow measurement by venturi before mill fan,
adjustable Damper
pressure loss across the mill cyclones can also be used.
Inlet damper, bypass damper, second Excessively high temperatures affect bearings of mill & separator and
Adequate drying of raw material and to
Mill Outlet Gas Temperature compartment water injection or Hot performance of a downstream electro-static precipitator (if fitted). Outlet
protect mill bearing and separator
gas generator damper/fan speed temperature should be controlled by hot gas/ recycle gas flow.
Mill Inlet static Pressure Recirculation Damper Optimization of pressure load on fan
Air flow through the separator must be maintained constant to achieve constant
Fineness Final Product Separator Variable Speed Drive Constant product fineness
product fineness at the same speed
Proportions of Raw Mill Feed and QMC can be used to control the proportions of corrective material according to
Raw Meal Chemistry Consistent quality results
corrective material quality results
Corrective Material 2 Feed Bin digital Level Sensor Not activated Activated 3 Avoid overfilling
Mill Filter Hopper Level Sensor Not activated Activated 5*60 Trip Mill Filter Fan. If the mill has its own filter
Mill Filter & Fan (Normally with Mill Filter DP/Filter Outlet Pressure >HH 3 Trip Mill Filter Fan. If the mill has its own filter
Pyro system)
Mill filter outlet pressure >HH 3 Trip Mill Filter Fan. If the mill has its own filter
*Delay for stop:- 3 seconds is proposed in order to avoid stoppage due to signal perturbation (can be increased/reduced according to site conditions)
In general, delays can be adjusted according to site conditions/circuit configuration/OEM recommendation.
Some limit values mentioned in comments are for ultimate safety. Operational limits needs to be
Note:-
set based on supplier/OEM recommendation or circuit configuration.