Hex Dec Size Content

0x00AA 170 1 UPS Mode inquiry


0x00AB 171 1 The input R voltage
0x00AC 172 1 The input S voltage
173 1 The input T voltage
174 1 The input frequency
175 1 The output R voltage
176 1 The output S voltage
177 1 The output T voltage
178 1 The output frequency
179 1 The output R current
180 1 The output S current
181 1 The output T current
182 1 The output load R percent
183 1 The output load S percent
184 1 The output load T percent
185 1 The output load total percent
186 1 The max temperature
187 1 Ups status
188 1 The bypass R voltage
189 1 The bypass S voltage
190 1 The bypass T voltage
191 1 The bypass R current
192 1 The bypass S current
193 1 The bypass T current
194 1 The bypass frequency
195 1 The P bus voltage
196 1 The N bus voltage
197 1 Temperature of heat sinks 1
198 1 Temperature of heat sinks 2
199 1 Temperature of heat cabinet
200 1 Temperature of battery
Units Type
Note2 ReadOnly 2402
0.1V ReadOnly 2404
0.1V ReadOnly 2406
0.1V ReadOnly 2408
0.1Hz ReadOnly 2410
0.1V ReadOnly
2412
0.1V ReadOnly 2414
0.1V ReadOnly 2416
0.1V ReadOnly 2418
0.1A ReadOnly 2420
0.1A ReadOnly 2422
0.1A ReadOnly 2424
0.1% ReadOnly 2426
0.1% ReadOnly 2428
0.1% ReadOnly 2430
0.1% ReadOnly 2432
0.1 ℃ ReadOnly 2434
Note1 ReadOnly 2436
0.1V ReadOnly 2438
0.1V ReadOnly 2440
0.1V ReadOnly 2442
0.1A ReadOnly 2444
0.1A ReadOnly 2446
0.1A ReadOnly 2448
0.1HZ ReadOnly 2450
0.1V ReadOnly 2452
0.1V ReadOnly 2454
1 ℃ ReadOnly 2456
1 ℃ ReadOnly 2458
1 ℃ ReadOnly 2460
1 ℃ ReadOnly 2462
350 1 Battery voltage P 0.1V
351 1 Battery voltage N 0.1V
352 1 Battery charging current P 0.1A
353 1 Battery charging current N 0.1A
354 1 Battery discharging current P 0.1A
355 1 Battery discharging current N 0.1A
356 1 Battery capacity 1%
357 1 Battery remain time Min.

Note
1. Note1
Note 1:
Bit15 1 Online UPS(fixed )
Bit14 0
Bit13 Utility Fail 0:FALSE/1:TRUE

Bit12 Battery Low 0:FALSE/1:TRUE


Bit11 Bypass Active 0:FALSE/1:TRUE
Bit10 UPS Failed 0:FALSE/1:TRUE
Bit09 EPO active 0:FALSE/1:TRUE
Bit08 Test in Progress 0:FALSE/1:TRUE
Bit07 Shutdown Active 0:FALSE/1:TRUE
Bit06 Bzon /Bzoff 0:FALSE/1:TRUE
Bit05 Bat test OK 0:FALSE/1:TRUE
0.1V ReadOnly 2502
0.1V ReadOnly
2504
0.1A ReadOnly 2506
0.1A ReadOnly 2508
0.1A ReadOnly 2510
0.1A ReadOnly 2512
1% ReadOnly 2514
Min. ReadOnly 2516
Note 2:
MODE_POWERON 1
MODE_STANDBY 2
MODE_BYPSS 3
MODE_LINE 4
MODE_BATTERY 5
0x00D0H
MODE_BATTEST 6
MODE_FAULT 7
MODE_CONVERT 8
MODE_ECO 9
MODE_SHUTDOWN 10

3. Note3
Fault Fault Name
Fault Kind Number

0x01 Bus start fail


0x02 Bus volt over
0x03 Bus volt under
Bus fault
0x04 Bus volt unbalance
0x05 Bus short
0x06 PFC over current
0x11 Inverter soft fail
0x12 Inverter volt high
0x13 Inverter volt low
0x14 L1 inverter short
0x15 L2 inverter short
Inverter 0x16 L3 inverter short
fault 0x17 L1L2 inverter short
0x18 L2L3 inverter short
0x19 L3L1 inverter short
0x1A L1 inverter negative power
0x1B L2 inverter negative power
0x1C L3 inverter negative power
Electric link 0x21 Bat SCR short fault
fault 0x22 Line SCR short fault
0x23 Inverter relay open fault
0x24 Inverter relay short fault
0x25 Wiring fault
0x26 Battery reverse fault
0x27 Battery too high
0x28 Battery too low
0x29 Battery Fuse
0x30 Open-Circuit Fault
0x31 CAN communication fault
0x32 Host line fault
Parallel 0x33 Synchronization line fault
system fault
Parallel
system fault 0x34 Synchronization pulse line fault
0x35 Parallel communication line loss
0x36 Output circuit fault
0x41 Over temperature
0x42 CPU communication fault
Others 0x43 Overload fault
0x44 Fan fault
0x45 Charger fault
2502 2402
2504 2404
2506 2406
2508 2408
2510 2410
2512 2412
2514 2414
2516 2416
2518 2418
2520 2420
2522 2422
2524 2424
2526 2426
2528 2428
2530 2430
2532 2432
2534 2434
2536 2436
2538 2438
2540 2440
2542 2442
2544 2444
2546 2446
2548 2448
2550 2450
2552 2452
2554 2454
2556 2456
2558 2458
2560 2460
2562 2462
2564
2566
2568
2570
2572
2574
2576
2578
2580
2582
2584
2586
2588
2590
2592
2594
2596
2598
2600
2602
2604
2606
2608