HVAC Load Analysis
for

PEMEX TRANSFORMACIÓN INDUSTRIAL


REFINERIA LAZARO CARDENAS
MINATITLAN, VERACRUZ

Prepared By:

Ing. Alejandro Arenas Solis


REEISA
20 De Noviembre No 600 Col. Maria Luisa
Monterrey Nuevo León CP 64060

viernes, 31 de mayo de 2019


Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
REEISA, SA de CV CT-2001 Cto Bently Nevada Mod. SCD Sec 7
Monterrey, NL 64000 Page 2

General Project Data Input


General Project Information
Project file name: CT-2001 Cto Bently Nevada- Modulo SCD Sector 7.CH8
Project title: CT-2001 Cto Bently Nevada Mod. SCD Sec 7
Project address: Refineria Lazaro Cardenas
Project city, state, ZIP: MINATITLAN, VERACRUZ
Designed by: HC
Project date: Feb 19
Project comment: CT-2001 Cuarto de Bently Nevada Modulo SCD Sector 7
Weather reference city: MINATITLAN, VERACRUZ, MEXICO
Client name: PEMEX TRANSFORMACIÓN INDUSTRIAL
Client address: REFINERIA LAZARO CARDENAS
Client city: MINATITLAN, VERACRUZ
Client comment: CT-2001 Cuarto de Bently Nevada Modulo SCD Sector 7
Company name: REEISA
Company representative: Ing. Alejandro Arenas Solis
Company address: 20 De Noviembre No 600 Col. Maria Luisa
Company city: Monterrey Nuevo León CP 64060
Company e-mail address: aarenas@reeisa.com.mx
Barometric pressure: 29.850 in.Hg.
Altitude: 66 feet
Latitude: 17 Degrees
Mean daily temperature range: 10 Degrees
Starting & ending time for HVAC load calculations: 1am - 12am
Number of unique rooms in this project: 1

Building Default Values


Calculations performed: Cooling loads only
Lighting requirements: 1.50 Watts per square foot
Equipment requirements: 0.00 Watts per square foot
People sensible load multiplier: 250 Btuh per person
People latent load multiplier: 200 Btuh per person
Room sensible safety factor: 10 %
Room latent safety factor: 10 %
Room heating safety factor: 0 %
People diversity factor: 100 %
Lighting profile number: 0
Equipment profile number: 0
People profile number: 2
Building default ceiling height: 10.50 feet
Building default wall height: 10.50 feet

Internal Operating Load Profiles (C = 100)


hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr hr
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 C C C C C C C C C C C C C C C C C C C C C C C C
2 C C C C C C C C C C C C C C C C C C C C C C C C
3 C C C C C C C C C C C C C C C C C C C C C C C C
4 C C C C C C C C C C C C C C C C C C C C C C C C
5 C C C C C C C C C C C C C C C C C C C C C C C C
6 C C C C C C C C C C C C C C C C C C C C C C C C
7 C C C C C C C C C C C C C C C C C C C C C C C C
8 C C C C C C C C C C C C C C C C C C C C C C C C
9 C C C C C C C C C C C C C C C C C C C C C C C C
10 C C C C C C C C C C C C C C C C C C C C C C C C

C:\ ...\CT-2001 Cto Bently Nevada- Modulo SCD Sector 7.CH8 viernes, 31 de mayo de 2019, 12:08 p. m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
REEISA, SA de CV CT-2001 Cto Bently Nevada Mod. SCD Sec 7
Monterrey, NL 64000 Page 3

General Project Data Input (cont'd)


Building-Level Design Conditions

Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor


Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
May 102 96 50% 75 190.04 15
June 102 96 50% 75 190.04 15
July 102 96 50% 75 190.04 15
Winter 50 75

Master Roofs
Roof ASHRAE Roof Dark Susp.
No. Roof# U-Fac Color Ceil
1 12 0.192 No No
Roof #1 Description: Flat roof, 6" heavy weight concrete deck with 1" insulation, no ceiling below

Master Walls
Wall ASHRAE Wall Wall
No. Group U-Fac Color
1 E 0.294 D
Wall #1 Description: Concrete wall, 8" thick, 140 lb/ft³, siding, no insulation or finish
2 G 1.124 L
Wall #2 Description: Metal wall, no insulation or finish

Master Partitions
Partition Partition Cool Heat
No. U-Factor T-D T-D
1 0.161 0 0
Partition #1 Description: Concrete partition, 8" thick, 30 lb/ft³, siding, no insulation or finish

Master Glass
Glass Summer Winter Glass Interior Interior
No. U-Factor U-Factor Shd.Coef. Shading Shd.Coef
1 1.040 1.095 1.000 1 0.250

C:\ ...\CT-2001 Cto Bently Nevada- Modulo SCD Sector 7.CH8 viernes, 31 de mayo de 2019, 12:08 p. m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
REEISA, SA de CV CT-2001 Cto Bently Nevada Mod. SCD Sec 7
Monterrey, NL 64000 Page 4

Air Handler Input


Air Handler Number 1 Input Data
Name: CT-2001 Cto Bently Nevada Mod, SCD Sec 7
Terminal type: Constant Volume
Method for CV Sum of Peaks
Supply fan type: Draw-thru fan
Calculations performed: Cooling loads only
Excess supply air: Reserve
Occurrences: 1
People profile number: 0
Lighting profile number: 0
Equipment profile number: 0
Exhaust may not exceed supply air: Yes
Leaving heating coil temp (deg.F): 96.0
Leaving cooling coil temp (deg.F): 51.0
Cooling coil CFM 0
Misc. Btuh gain - supply side: 0
Misc. Btuh gain - return side: 0
Combined fan & motor efficiency: 70
Static pressure across fan (in.wg.): 2.00
Summer supply duct temp rise (deg.F): 0.000
Summer return duct temp rise (deg.F): 0.000
Winter supply duct temp drop (deg.F): 0.000
Winter return duct temp drop (deg.F): 0.000
Chilled water temp difference (deg.F): 0.000
Hot water temp difference (deg.F): 0.000
Cooling ventilation: 0 Direct
Cooling infiltration: 0 Direct
Heating ventilation: 0 Direct
Heating infiltration: 0 Direct
Pretreated outside air: none
Pretreated air Summer DB (deg.F): 0
Pretreated air Summer WB (deg.F): 0
Pretreated air Winter DB (deg.F): 0

Design Outdoor Outdoor Indoor Indoor Grains In/Outdoor


Month Dry Bulb Wet Bulb Rel.Hum Dry Bulb Diff Correction
May 102 96 50% 75 190.04 15
June 102 96 50% 75 190.04 15
July 102 96 50% 75 190.04 15
Winter 50 75

C:\ ...\CT-2001 Cto Bently Nevada- Modulo SCD Sector 7.CH8 viernes, 31 de mayo de 2019, 12:08 p. m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
REEISA, SA de CV CT-2001 Cto Bently Nevada Mod. SCD Sec 7
Monterrey, NL 64000 Page 5

Building Summary Loads


Building peaks in May at 4pm.
Bldg Load Area Sen %Tot Lat Sen Net %Net
Descriptions Quan Loss Loss Gain Gain Gain Gain
Roof 187 0 0.00 0 1,387 1,387 1.73
Wall 419 0 0.00 0 5,871 5,871 7.34
Glass 187 0 0.00 0 11,674 11,674 14.59
Floor Slab 0 0 0.00 0 0 0 0.00
Skin Loads 0 0.00 0 18,932 18,932 23.67
Lighting 281 0 0.00 0 1,054 1,054 1.32
Equipment 2,610 0 0.00 0 9,796 9,796 12.25
Pool Latent 0 0 0.00 0 0 0 0.00
People 2 0 0.00 440 550 990 1.24
Partition 0 0 0.00 0 0 0 0.00
Cool. Pret. 0 0 0.00 0 0 0 0.00
Heat. Pret. 0 0 0.00 0 0 0 0.00
Cool. Vent. 300 0 0.00 38,679 8,889 47,567 59.46
Heat. Vent. 0 0 0.00 0 0 0 0.00
Cool. Infil. 0 0 0.00 0 0 0 0.00
Heat. Infil. 0 0 0.00 0 0 0 0.00
Draw-Thru Fan 0 0 0.00 0 1,659 1,659 2.07
Blow-Thru Fan 0 0 0.00 0 0 0 0.00
Reserve Cap. 0 0 0.00 0 0 0 0.00
Reheat Cap. 0 0 0.00 0 0 0 0.00
Supply Duct 0 0 0.00 0 0 0 0.00
Return Duct 0 0 0.00 0 0 0 0.00
Misc. Supply 0 0 0.00 0 0 0 0.00
Misc. Return 0 0 0.00 0 0 0 0.00
Building Totals 0 0.00 39,119 40,880 79,999 100.00

Building Sen %Tot Lat Sen Net %Net


Summary Loss Loss Gain Gain Gain Gain
Ventilation 0 0.00 38,679 8,889 47,567 59.46
Infiltration 0 0.00 0 0 0 0.00
Pretreated Air 0 0.00 0 0 0 0.00
Room Loads 0 0.00 440 30,333 30,773 38.47
Plenum Loads 0 0.00 0 0 0 0.00
Fan/Duct/Misc Loads 0 0.00 0 1,659 1,659 2.07
Building Totals 0 0.00 39,119 40,880 79,999 100.00

Check Figures
Total Building Supply Air (based on a 20° TD): 1,458 CFM
Total Building Vent. Air (20.58% of Supply): 300 CFM
Total Conditioned Air Space: 187 Sq.ft
Supply Air Per Unit Area: 7.7842 CFM/Sq.ft
Area Per Cooling Capacity: 28.1 Sq.ft/Ton
Cooling Capacity Per Area: 0.0356 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 6.67 Tons

C:\ ...\CT-2001 Cto Bently Nevada- Modulo SCD Sector 7.CH8 viernes, 31 de mayo de 2019, 12:08 p. m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
REEISA, SA de CV CT-2001 Cto Bently Nevada Mod. SCD Sec 7
Monterrey, NL 64000 Page 6

Air Handler #1 - CT-2001 Cto Bently Nevada Mod, SCD Sec 7 - Summary
Loads
Rm Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Room Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
CT-2001 Cto Bently
Nevada Mod, SCD 187 0 30,333 440 None Direct
1 Sec 7 2 0 1,458 0 0 300
4pm May 1,966 0.00 7.78 0 0 300

Room Peak Totals: 187 0 30,333 440


Total Rooms: 1 2 0 1,458 0 0 300
Unique Rooms: 1 1,966 0.00 7.78 0 0 300

C:\ ...\CT-2001 Cto Bently Nevada- Modulo SCD Sector 7.CH8 viernes, 31 de mayo de 2019, 12:08 p. m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
REEISA, SA de CV CT-2001 Cto Bently Nevada Mod. SCD Sec 7
Monterrey, NL 64000 Page 7

Air Handler #1 - CT-2001 Cto Bently Nevada Mod, SCD Sec 7 - Total Load
Summary
Air Handler Description: CT-2001 Cto Bently Nevada Mod, SCD Sec 7 Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.65 HP
Fan Input: 70% motor and fan efficiency with 2 in. water across the fan
Sensible Heat Ratio: 0.99 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 4pm in May.
Outdoor Conditions: Clg: 102° DB, 96° WB, 255.36 grains
Indoor Conditions: Clg: 75° DB, 50% RH
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Room Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.998 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Room space sensible gain: 30,333 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 1,659 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 31,992 Btuh
Cooling Supply Air: 31,992 / (.998 X 1.1 X 20) = 1,458 CFM
Summer Vent Outside Air (20.6% of supply) = 300 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 8,889 Btuh 300 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 8,889 Btuh
Total sensible gain on air handling system: 40,880 Btuh
Room space latent gain: 440 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 38,679 Btuh
Total latent gain on air handling system: 39,119 Btuh
Total system sensible and latent gain: 79,999 Btuh

Check Figures
Total Air Handler Supply Air (based on a 20° TD): 1,458 CFM
Total Air Handler Vent. Air (20.58% of Supply): 300 CFM
Total Conditioned Air Space: 187 Sq.ft
Supply Air Per Unit Area: 7.7842 CFM/Sq.ft
Area Per Cooling Capacity: 28.1 Sq.ft/Ton
Cooling Capacity Per Area: 0.0356 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 6.67 Tons

C:\ ...\CT-2001 Cto Bently Nevada- Modulo SCD Sector 7.CH8 viernes, 31 de mayo de 2019, 12:08 p. m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
REEISA, SA de CV CT-2001 Cto Bently Nevada Mod. SCD Sec 7
Monterrey, NL 64000 Page 8

Zone Detailed Loads (At Zone Peak Times)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Room 1-CT-2001 Cto Bently Nevada Mod, SCD Sec 7 - Air Handler 1 (CT-2001 Cto Bently Nevada
Mod, SCD Sec 7), Zone 0 peaks (sensible) in May at 4pm.
Roof-1-12-No.Clg-L 187 0.50 35.1 0.192 1,261 4.800 899
Wall-1-N-E-D 176 1 35.6 0.294 1,845 7.350 1,295
Wall-2-E-E-D 10 1 48.1 0.294 139 7.350 72
Wall-3-S-E-D 200 1 40.1 0.294 2,357 7.350 1,469
Wall-4-W-E-D 10 1 41.1 0.294 119 7.350 72
Door-5-N-G-L 24 0.65 33.0 1.124 877 28.100 665
Gls-E-1-90-Tran 93.5 1.000 29 1.040 2,819 27.375 2,559
0%S-0-WS-Solar 93.5 0.250 215 0.170 854
Gls-W-1-90-Tran 93.5 1.000 29 1.040 2,819 27.375 2,559
0%S-0-WS-Solar 93.5 0.250 215 0.820 4,120
Lights-Prof=0 281 1.000 958
Equipment-Prof=0 2,610 1.000 8,906 0
People-Prof=2 2.0 1.000 500 400
Sub-total 27,575 400 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 30,333 440 0

C:\ ...\CT-2001 Cto Bently Nevada- Modulo SCD Sector 7.CH8 viernes, 31 de mayo de 2019, 12:08 p. m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
REEISA, SA de CV CT-2001 Cto Bently Nevada Mod. SCD Sec 7
Monterrey, NL 64000 Page 9

Room Detailed Loads (At Room Peak Times)


Load Unit -SC- CLTD U.Fac Sen. Lat. Htg. Htg.
Description Quan CFAC SHGF -CLF- Gain Gain Mult. Loss
Room 1-CT-2001 Cto Bently Nevada Mod, SCD Sec 7 peaks (sensible) in May at 4pm, Air Handler 1
(CT-2001 Cto Bently Nevada Mod, SCD Sec 7), Zone 0, 19.0 x 9.8, Construction Type: 1 (Light)
Roof-1-12-No.Clg-L 187 0.50 35.1 0.192 1,261 4.800 899
Wall-1-N-E-D 176 1 35.6 0.294 1,845 7.350 1,295
Wall-2-E-E-D 10 1 48.1 0.294 139 7.350 72
Wall-3-S-E-D 200 1 40.1 0.294 2,357 7.350 1,469
Wall-4-W-E-D 10 1 41.1 0.294 119 7.350 72
Door-5-N-G-L 24 0.65 33.0 1.124 877 28.100 665
Gls-E-1-90-Tran 93.5 1.000 29 1.040 2,819 27.375 2,559
0%S-0-WS-Solar 93.5 0.250 215 0.170 854
Gls-W-1-90-Tran 93.5 1.000 29 1.040 2,819 27.375 2,559
0%S-0-WS-Solar 93.5 0.250 215 0.820 4,120
Lights-Prof=0 281 1.000 958
Equipment-Prof=0 2,610 1.000 8,906 0
People-Prof=2 2.0 1.000 500 400
Sub-total 27,575 400 0
Safety factors: +10% +10% +0%
--------- --------- ---------
Total w/ safety factors: 30,333 440 0

C:\ ...\CT-2001 Cto Bently Nevada- Modulo SCD Sector 7.CH8 viernes, 31 de mayo de 2019, 12:08 p. m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
REEISA, SA de CV CT-2001 Cto Bently Nevada Mod. SCD Sec 7
Monterrey, NL 64000 Page 10

Air System #1 (CT-2001 Cto Bently Nevada Mod, SCD Sec 7) Psychrometric
Analysis
System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 64.327 55.000
Draw-Thru Fan 1,659 1.037 76
Misc Load on Supply Side 0 0.000 0 0.000 0
Supply Air Duct 0 0.000 0
Room Loads 440 0.445 30,333 18.963 1,382
Sensible Reserve 0 0.000 0
Room Condition 440 64.772 31,992 75.000 1,458
Return Air Duct 0 0.000
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000 0 0.000
Vent Air 300 CFM 38,679 39.121 8,889 5.557
Blow-Thru Fan 0 0.000
Entering Coil Condition 39,119 103.893 40,880 80.557 1,458

General Psychrometric Equations Used In Analysis:


PR = (Barometric pressure of site / Standard ASHRAE pressure of 29.921)
TSH = PR x 1.10 x CFM x (DB entering - DB leaving)
TLH = PR x 0.68 x CFM x (Grains entering - Grains leaving)
GTH = PR x 4.50 x CFM x (Enthalpy entering - Enthalpy leaving)

TSH = 0.998 x 1.10 x 1,458 x( 80.6 - 55.0 )= 40,880 Btuh


TLH = 0.998 x 0.68 x 1,458 x( 103. - 64.3 )= 39,124 Btuh
9
----------
SUM = 80,004 Btuh
GTH = 0.998 x 4.50 x 1,458 x( 35.6 - 23.2 )= 81,392 Btuh
Total System Load = 79,999 Btuh

Chilled and Hot Water Flow Rates and Steam Requirement


Cooling GPM = 81,392 / ( 0.00 x 500 ) = 0.0 GPM
Heating GPM = 0 /( 0.00 x 500 ) = 0.0 GPM
Steam Req. = 0 / 970 = 0.0 lb./hr

Entering Cooling Coil Conditions Entering Heating Coil Conditions


Dry bulb temperature: 80.56 Dry bulb temperature: 75.00
Wet bulb temperature: 71.88
Relative humidity: 66.16
Enthalpy: 35.61 Btu/lbm

Leaving Cooling Coil Conditions Leaving Heating Coil Conditions


Dry bulb temperature: 55.00 Dry bulb temperature: 75.00
Wet bulb temperature: 54.96
Relative humidity: 99.73
Enthalpy: 23.18 Btu/lbm

C:\ ...\CT-2001 Cto Bently Nevada- Modulo SCD Sector 7.CH8 viernes, 31 de mayo de 2019, 12:08 p. m.