SCD Sec 7
HVAC Load Analysis
for
Prepared By:
C:\ ...\CT-2001 Cto Bently Nevada- Modulo SCD Sector 7.CH8 viernes, 31 de mayo de 2019, 12:08 p. m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
REEISA, SA de CV CT-2001 Cto Bently Nevada Mod. SCD Sec 7
Monterrey, NL 64000 Page 3
Master Roofs
Roof ASHRAE Roof Dark Susp.
No. Roof# U-Fac Color Ceil
1 12 0.192 No No
Roof #1 Description: Flat roof, 6" heavy weight concrete deck with 1" insulation, no ceiling below
Master Walls
Wall ASHRAE Wall Wall
No. Group U-Fac Color
1 E 0.294 D
Wall #1 Description: Concrete wall, 8" thick, 140 lb/ft³, siding, no insulation or finish
2 G 1.124 L
Wall #2 Description: Metal wall, no insulation or finish
Master Partitions
Partition Partition Cool Heat
No. U-Factor T-D T-D
1 0.161 0 0
Partition #1 Description: Concrete partition, 8" thick, 30 lb/ft³, siding, no insulation or finish
Master Glass
Glass Summer Winter Glass Interior Interior
No. U-Factor U-Factor Shd.Coef. Shading Shd.Coef
1 1.040 1.095 1.000 1 0.250
C:\ ...\CT-2001 Cto Bently Nevada- Modulo SCD Sector 7.CH8 viernes, 31 de mayo de 2019, 12:08 p. m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
REEISA, SA de CV CT-2001 Cto Bently Nevada Mod. SCD Sec 7
Monterrey, NL 64000 Page 4
C:\ ...\CT-2001 Cto Bently Nevada- Modulo SCD Sector 7.CH8 viernes, 31 de mayo de 2019, 12:08 p. m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
REEISA, SA de CV CT-2001 Cto Bently Nevada Mod. SCD Sec 7
Monterrey, NL 64000 Page 5
Check Figures
Total Building Supply Air (based on a 20° TD): 1,458 CFM
Total Building Vent. Air (20.58% of Supply): 300 CFM
Total Conditioned Air Space: 187 Sq.ft
Supply Air Per Unit Area: 7.7842 CFM/Sq.ft
Area Per Cooling Capacity: 28.1 Sq.ft/Ton
Cooling Capacity Per Area: 0.0356 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 6.67 Tons
C:\ ...\CT-2001 Cto Bently Nevada- Modulo SCD Sector 7.CH8 viernes, 31 de mayo de 2019, 12:08 p. m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
REEISA, SA de CV CT-2001 Cto Bently Nevada Mod. SCD Sec 7
Monterrey, NL 64000 Page 6
Air Handler #1 - CT-2001 Cto Bently Nevada Mod, SCD Sec 7 - Summary
Loads
Rm Description Area Htg.Loss Sen.Gain Lat.Gain Htg.O.A. Clg.O.A.
No Room Peak Time People Htg.CFM Clg.CFM S.Exh Req.CFM Req.CFM
Volume CFM/Sqft CFM/Sqft W.Exh Act.CFM Act.CFM
CT-2001 Cto Bently
Nevada Mod, SCD 187 0 30,333 440 None Direct
1 Sec 7 2 0 1,458 0 0 300
4pm May 1,966 0.00 7.78 0 0 300
C:\ ...\CT-2001 Cto Bently Nevada- Modulo SCD Sector 7.CH8 viernes, 31 de mayo de 2019, 12:08 p. m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
REEISA, SA de CV CT-2001 Cto Bently Nevada Mod. SCD Sec 7
Monterrey, NL 64000 Page 7
Air Handler #1 - CT-2001 Cto Bently Nevada Mod, SCD Sec 7 - Total Load
Summary
Air Handler Description: CT-2001 Cto Bently Nevada Mod, SCD Sec 7 Constant Volume - Sum of Peaks
Supply Air Fan: Draw-Thru with program estimated horsepower of 0.65 HP
Fan Input: 70% motor and fan efficiency with 2 in. water across the fan
Sensible Heat Ratio: 0.99 --- This system occurs 1 time(s) in the building. ---
Air System Peak Time: 4pm in May.
Outdoor Conditions: Clg: 102° DB, 96° WB, 255.36 grains
Indoor Conditions: Clg: 75° DB, 50% RH
Summer: Ventilation controls outside air, ----- Winter: Exhaust controls outside air.
Room Space sensible loss: 0 Btuh
Infiltration sensible loss: 0 Btuh 0 CFM
Outside Air sensible loss: 0 Btuh 0 CFM
Supply Duct sensible loss: 0 Btuh
Return Duct sensible loss: 0 Btuh
Return Plenum sensible loss: 0 Btuh
Total System sensible loss: 0 Btuh
Heating Supply Air: 0 / (.998 X 1.08 X 0) = 0 CFM
Winter Vent Outside Air (0.0% of supply) = 0 CFM
Room space sensible gain: 30,333 Btuh
Infiltration sensible gain: 0 Btuh
Draw-thru fan sensible gain: 1,659 Btuh
Supply duct sensible gain: 0 Btuh
Reserve sensible gain: 0 Btuh
Total sensible gain on supply side of coil: 31,992 Btuh
Cooling Supply Air: 31,992 / (.998 X 1.1 X 20) = 1,458 CFM
Summer Vent Outside Air (20.6% of supply) = 300 CFM
Return duct sensible gain: 0 Btuh
Return plenum sensible gain: 0 Btuh
Outside air sensible gain: 8,889 Btuh 300 CFM
Blow-thru fan sensible gain: 0 Btuh
Total sensible gain on return side of coil: 8,889 Btuh
Total sensible gain on air handling system: 40,880 Btuh
Room space latent gain: 440 Btuh
Infiltration latent gain: 0 Btuh
Outside air latent gain: 38,679 Btuh
Total latent gain on air handling system: 39,119 Btuh
Total system sensible and latent gain: 79,999 Btuh
Check Figures
Total Air Handler Supply Air (based on a 20° TD): 1,458 CFM
Total Air Handler Vent. Air (20.58% of Supply): 300 CFM
Total Conditioned Air Space: 187 Sq.ft
Supply Air Per Unit Area: 7.7842 CFM/Sq.ft
Area Per Cooling Capacity: 28.1 Sq.ft/Ton
Cooling Capacity Per Area: 0.0356 Tons/Sq.ft
Heating Capacity Per Area: 0.00 Btuh/Sq.ft
Total Heating Required With Outside Air: 0 Btuh
Total Cooling Required With Outside Air: 6.67 Tons
C:\ ...\CT-2001 Cto Bently Nevada- Modulo SCD Sector 7.CH8 viernes, 31 de mayo de 2019, 12:08 p. m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
REEISA, SA de CV CT-2001 Cto Bently Nevada Mod. SCD Sec 7
Monterrey, NL 64000 Page 8
C:\ ...\CT-2001 Cto Bently Nevada- Modulo SCD Sector 7.CH8 viernes, 31 de mayo de 2019, 12:08 p. m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
REEISA, SA de CV CT-2001 Cto Bently Nevada Mod. SCD Sec 7
Monterrey, NL 64000 Page 9
C:\ ...\CT-2001 Cto Bently Nevada- Modulo SCD Sector 7.CH8 viernes, 31 de mayo de 2019, 12:08 p. m.
Chvac - Full Commercial HVAC Loads Calculation Program Elite Software Development, Inc.
REEISA, SA de CV CT-2001 Cto Bently Nevada Mod. SCD Sec 7
Monterrey, NL 64000 Page 10
Air System #1 (CT-2001 Cto Bently Nevada Mod, SCD Sec 7) Psychrometric
Analysis
System Load Analysis Latent Grains Sensible Temp CFM
Leaving Coil Condition 64.327 55.000
Draw-Thru Fan 1,659 1.037 76
Misc Load on Supply Side 0 0.000 0 0.000 0
Supply Air Duct 0 0.000 0
Room Loads 440 0.445 30,333 18.963 1,382
Sensible Reserve 0 0.000 0
Room Condition 440 64.772 31,992 75.000 1,458
Return Air Duct 0 0.000
Return Air Plenum 0 0.000
Misc Load on Return Side 0 0.000 0 0.000
Vent Air 300 CFM 38,679 39.121 8,889 5.557
Blow-Thru Fan 0 0.000
Entering Coil Condition 39,119 103.893 40,880 80.557 1,458
C:\ ...\CT-2001 Cto Bently Nevada- Modulo SCD Sector 7.CH8 viernes, 31 de mayo de 2019, 12:08 p. m.