S.L SH Item No Description of Item Quantity Rate Unit Amount
No
.

1 2 4 5 6 7 8 9
1 7 72A.1 Supply, installation, testing & commissioning of split type air-
P-169 cooler with inverter comprising condensing and evaporating
units having following cooling capacity based on indoor
temperature 27º-30ºC DB / 19.5º-22ºC WB and outdoor
temperature 35º-40ºC DB at high fan speed condition suitable
for installation & operation in tropicalized country like
Bangladesh & as per detailed specifications & standard as
mentioned below :

(a). OUTDOOR UNIT / CONDENSING UNIT


(i). Type : Compact weather proof outdoor type condensing unit
(ii). Compressor : Hermitically sealed reciprocating / rotary
compressor.
(iii). Refrigerant : Internationally accepted & recommended and

most commonly used gas (CFC free)


(iv). Blower motor : Well balanced type direct driven centrifugal
type blower fan

(v). Power supply :


(i). 200-250 V, single phase, 50 Hz. AC supply [up to 30000
BTU/HR]
(ii). 400-440 V 3-phase, 50 Hz. AC supply [above 30000
BTU/HR ]
(vi). Condensing pipe / coil : Made of copper
(vii). EER :
Minimum 8.5 [ EER = BTU/HR ]
WATT

(viii). Others features :


(i). Well balanced in all respect having interlock with the
fan coil unit.
(ii). Compressor dully equipped with vibration isolator,
thermostatic
& overload controls, magnetic contactors and all other
standard accessories complete.
(iii). Refrigerant copper pipe [From outdoor to indoor unit]
with thermal insulation, refrigerant charging
arrangement etc.[ Minm length10 mtr.]
(iv). Reqd. size PVC insulated & sheathed cable with ECC
through water grade PVC pipe from outdoor to indoor
unit .

(b). INDOOR UNIT / FAN COIL UNIT


Features : (i). Direct expansion system fan coil unit with well
balanced direct driven centrifugal type fan.
(ii). Fancy & adjustable air circulating louver grill, removable &
washable type filter .
(iii). Condensing water drain out PVC flexible pipe with
necessary
insulation
(iv). Thermostatic switch and remote control switch.
(c). Standard : Major component shall be manufactured as per
relevant international standard & code.
(d). Documents : 01. Manufacturing company shall have the
following certificate :
(i). ISO-9001, 2008
(ii). CE / UL certification
Warranty :
The bidder should provide the guaranty of compressor for at
least 2 years & free service with spares for 2 years from the
date of commissioning & it should be obtained from the air
cooler selling agency.

Any brand manufactured or assembled in JAPAN /


MALAYSIA / SOUTH KOREA / TAIWAN / THAILAND / USA /
EU countries accepted / approved by the Engineer in
accordance with fulfillment of the above specifications and
having relevant certificates as mentioned.

Capacity : 12000 BTU/HR


Wall mounted 3 Nos 79088 /= Each 237264 /=
(S/R)
Capacity : 17000-18000 BTU/HR
Wall mounted 1 Nos 98407 /= Each 98407 /=
(S/R)
2 4 4.10.(ii) Providing & fixing 250 volt single phase 3-pin combined switch
P-99 socket outlet (surface / Concealed type) manufactured and
tested in accordance with relevant IEC / VDE / NEMA / BS / JIS
standards mounted on required size 18 SWG galvanized plain
sheet board / Plastic Board (Self-extinguishing 650oC) of 76.2
mm. (3") depth. (Manufacturer shall have certificate of
standard which they follow).

13 / 15 / 16 / 20 Amps.
Made in HONGKONG / MALAYSIA / SINGAPORE / S
KOREA / THAILAND 4 Nos 586 /= Each 2344 /=
(S/R)
3 1 1.2.3(viii) Surface conduit wiring with the following PVC insulated and
P-7 sheathed cable (BYM) & Green / White colour PVC insulated
ECC wire (BYA) through PVC conduit of reputed
manufacturer complete with 18 SWG GP sheet pull box with 3
mm thick ebonite sheet cover, fixing materials, other
accessories etc. as required including mending the damages
good. All electrical contacts shall be of brass / copper
connected through connector or soldering (no twisting shall be
allowed) and cables shall be manufactured and tested
according to relevant IEC / BDS / BS / VDE standards and as
per detailed specification mentioned in Annexure-1. The work
shall be carried out as per direction & approval of the Engineer.

Cable manufacturer(s) must have valid test certificate from


internationally accrediated laboratory (like CPRI, KEMA
etc) accepted / approved by the Engineer

1C-2x2.5sqmm (BYM) cable with 2.5 sqmm (BYA) ECC wire


through PVC pipe of minimum inner dia 25 mm having wall
thickness of 1.5 mm 635 Mtrs 179 /= P/Mtr 113665 /=
(S/R)
4 4 4.4.1(i) Providing & fixing on a prepared board 250 volt grade following
P-96 single pole miniature circuit breaker (SPMCBS) having
minimum breaking capacity 6-KA with thermal over-current and
instantaneous electromagnetic short circuit release provision.

SPMCBS of DORMAN SMITH / MEM / SIEMENS /


VIRTZRO /HAGER / FEDERAL / KAWAMURA / ABB /
HAVELLS / LEGRAND / MERLIN GERIN / SCHNEIDER or
equivalent brand accepted / approved by the engineer.

5 - 40 Amps. 4 Nos 640 /= Each 2560 /=


(S/R)
5 6 6.A.9.(i). Providing & fixing the Metal halide flood light fitting as of
(b) following manufacturers model & catalogue number consisting
P-144 of black / gray coloured die-cast aluminium body, housing for
control gear, polished aluminium reflector, 4 mm toughened
heatproof glass, universal mounting for ceiling, wall or surface,
hinged front glass for in position lamp replacement,cable entry
gland, U-shaped bracket for pole mounting, brass holder,
ballast (Phillips/ Harmonics /GE), ignitor, capacitor, necessary
wiring with FR cable suitable for use with metal halide lamp,
earth terminal etc. complete with metal halide lamp(Phillips
/Harmonics/GE) sample accepted / approved by the Engineer.

SHWASH cat. no. - SCFL-8 MH- 400W metal


or equiivalent product of CRESCENT, HARMONICS,
GLORIA, ENERGY+ etc. 4 Nos 11169 /= Each 44676 /=
(S/R)

Total Tk. 498916 /=

Humayun Kabir Asiful Islam Bhuiyan Mohammad Lutfus Salam Fahmid Iftekher Ali Md. Ashraful Islam
Sub-Assistant Engineer Sub-Divisional Engineer Sub-Assistant Engineer Assistant Engineer(E/M) Executive Engineer
PWD Bangabhaban PWD Bangabhaban PWD E/M Division-1 PWD E/M Division-1 PWD E/M Division-1
E/M Sub-Division E/M Sub-Division Dhaka Dhaka Dhaka