Sie sind auf Seite 1von 7

Control Strategies for Dynamic Voltage Restorer

Compensating Voltage Sags with Phase Jump


John Godsk Nielsen and Frede Blaabjerg, Institute of Energy Technology,
Aalborg University, Pontoppidanstrzede 101, DK-9220 Aalborg East, Denmark.
Ned Mohan, University of Minnesota, USA

Abstract- Voltage sags a r e a n i m p o r t a n t power quality


problem a n d t h e dynamic voltage restorer is known as a n
effective device t o mitigate voltage sags. I n this p a p e r dif-
ferent control strategies for dynamic voltage restorer a r e
analyzed with emphasis p u t o n t h e compensation of volt-
age sags with phase j u m p . Voltage sags accompanied by
a phase j u m p a r e in some cases more likely t o t r i p loads
a n d a satisfactory voltage compensation a r e more difficult
t o achieve. Different control m e t h o d s t o compensate volt-
age sags with phase j u m p a r e h e r e proposed a n d compared.
Two promising control m e t h o d s a r e tested with simulations Fig. 1. Voltage sag with phase jump. a) Simplified circuit to calcu-
carried out in S a b e r a n d finally tested on a 10 kVA r a t e d late the voltage reduction and phase jump. b) Vector diagram
Dynamic Voltage R e s t o r e r in t h e laboratory. B o t h meth- of voltage sag with the used definition of pre-sag voltage, sag
ods can be used t o reduce load voltage disturbances caused voltage and missing voltage.
by voltage sags with phase j u m p . O n e m e t h o d completely
compensates t h e phase j u m p , which is t h e best solution for
very sensitive loads. T h e second m e t h o d does only partly
compensate t h e phase j u m p , b u t i t is expected t o have of connected load. The DVR must also be able to dis-
a b e t t e r performance in compensating a broader range of tinguish between background power quality problems and
voltage sags. the voltage sags to be compensated. Sags are often non-
symmetrical and accompanied by a phase jump. Control
I. INTRODUCTION strategies for DVR’s have been addressed in [3] and [7].
Significant deviations from the nominal voltage are a In [5] the problems with phase jump have been reported
problem for sensitive consumers in the grid system. In- but no control methods have been proposed. This paper
terruptions are generally considered to be the worst case shortly describes voltage sags with a phase jump and illus-
with the load disconnected from the supply. The num- trate different control strategies for a DVR and some DVR
ber of interruptions, though expensive, can be minimized limitations, which should be included in the control strat-
with parallel feeders and are less likely to occur with the egy. Two control methods are proposed with the ability
transition from overhead lines to cables in the LV and MV to protect the load from a sudden phase shift caused by
distribution system. a voltage sag with phase jump. Finally, the major parts
Voltage Sags are characterized by a reduction in voltage, in the experimental setup are described with the DVR
but the load is still connected to the supply. Sags are in hardware and control system used. Simulations and mea-
most cases considered less critical compared to interrup- surements illustrate how symmetrical voltage sags with
tions, but they typically occur more frequently. Voltage phase jump successfully can be compensated.
sags have in several cases been reported as a threat to sen- 11. VOLTAGE
SAGS WITH PHASE JUMP
sitive equipment and have resulted in shutdowns, loss of
production and a hence a major cost burden. The theory Voltage sags are caused by a short circuit current flow-
of voltage sags and interruptions is thoroughly described ing into a fault, which is shown in Fig. la. Magnitude and
in [I]. phase of the voltage, Usagduring the sag, at the Point of
Sags are so far almost impossible to avoid, because of Common Coupling(PCC), are determined by the fault and
the finite clearing time of the faults causing the voltage source impedances, using the following simplified equa-
sags and the wide propagation of sags from the trans- tion:
mission and distribution system to the low voltage loads.
Equipment can be made more tolerant of sags either via
more intelligent control of the equipment or by storing
more energy in each equipment. Instead of modifying each A fault current somewhere in the grid can lead to a
component in for instance a factory to be very tolerant to reduced magnitude and, in some cases, a phase jump of
voltage sags, a better solution might be to install one dy- the voltage at the point of common coupling. Fig. lb.
namic voltage restorer to mitigate voltage sags. A DVR defines the used definitions of the voltage at the PCC.
can eliminate most sags and minimize the risk of load trip- Usagis the voltage during the sag and cy is the phase
ping at very deep sags. jump at PCC.
The control of a DVR is not straight-forward because The Dynamic voltage restorer injects a voltage in se-
of the requirements of fast response, large variation in the ries with the supply to compensate for voltage sags. The
type of sags to be compensated and variation in the type principle operation of a DVR is illustrated in Fig. 2.

0 2001 IEEE
0-7803-6618-2/01/$10.00 1267
RBSt01ed

Fig. 4. The flow of active and reactive power with a DVR inserted.

The discussed three methods are illustrated in Fig. 3


and by studying Fig. 3 it appears like the energy storage
Fig. 2. Principle operation of the Dynamic Voltage Restorer can be reduced applying the DVR voltage perpendicular
t o the load current, but the current will change phase
according to the new load voltage applied to it and energy
will be drawn from the DVR. Fig. 4 illustrates how the
power flows in the system. The voltage generated which
is perpendicular to the load current can be used to bring
the current in-phase with the supply voltage or make the
DVR and load appear as a capacitive load. A capacitive
load current tends to raise the supply voltage usupply
and
by raising the supply voltage more power can be taken
from the grid and hence saved from the energy storage.
Fig. 3. Control strategies for the DVR.,,,Q
,, the pre-sag com-
Before selecting a control method to be used further is-
pensation, ,,,,Q
the in-phase compensation and , the sues have to be addressed, which are closely linked to the
energy optimal control chosen control strategy. A DVR has limited capabilities
and the DVR will most likely face a sag outside the range
of full compensation. Three important limitations for a
111. CONTROL
STRATEGY
DVR are:

The possibility of compensation of voltage sags can be Voltage limit; The design of the DVR is limited in the
limited by a number of factors including finite DVR power injection capability to keep the cost down and reduce the
rating, different load conditions, background power qual- voltage drop across the device in normal operation.
ity problems and different types of sags. If the DVR Power limit; Power is stored in the DC-link, but the
should be a successful device, the control may be able bulk power is often converted from the supply itself or
to handle most sags and the performance must be max- from a larger DC storage. An additional converter is used
imized according to the equipment inserted. Otherwise, t o maintain a constant DC-link voltage and the rating of
the DVR may not be able to avoid load tripping and even the converter introduces a power limit to the DVR.
cause additional disturbances to the load. Energy limit; Energy is used to maintain the load volt-
A control strategy for voltage sags with phase jump age fixed and it is normally sized as low as possible in
should be included, to be able to compensate this partic- order to reduce cost. Some sags will deplete the storage
ular type of sag. The control strategy can depend on the fast and the control can reduce the risk of load tripping
type of load connected. Some loads are very sensitive t o caused be insufficient energy storage.
phase jump and the load should be protected from them.
Other type of loads are more tolerant to phase jump and All the limits should be included in the control to fully
the main task is to maintain the nominal voltage on all utilize the investment of a DVR. Fig. 5 illustrates a single
three phases. Three basic control strategies for a DVR phase phasor diagram for one load case. The phasor of the
can be stated as: pre-sag voltage is shown with a lagging load current. The
phase jump is negative with a reduced during-sag voltage.
Method 1: Pre-sag compensation; The supply voltage The voltage and power limits are indicated and the
is continuously tracked and the load voltage is compen- hatched region illustrates the region within the DVR can
sated to the pre-sag condition. The method gives a nearly operate. The pre-sag voltage cannot be maintained in the
undisturbed load voltage, but can often exhaust the rating case illustrated in Fig. 5. In-phase control to nominal
of the DVR. voltage is also not obtainable if the current phasor stays,
0 Method 2: In-phase compensation; The generated DVR because of the power limit.
voltage is always in phase with the measured supply volt- A phase jump could be initiated by certain voltage sags
age regardless of the load current and the pre-sag voltage. with phase jump, or by the DVR itself t o reduce the power
Method 3: Energy optimal compensation; To fully uti- drain or maximize the load voltage a t severe sags. In both
lize the energy storage, information about the load current cases a phase jump may be undesirable for the load and
is used to minimize the depletion of the energy storage. may initiate transient currents in capacitors, transformers,
motors etc. The operation of line commutated converters

1268
I I TABLE I
MAINSYSTEM PARAMETERS FOR THE EXPERIMENTAL DVR SETUP.

Description Rated value Per unit value


Load rating 20 kVA 1 PU
DVR rating 10 kVA 0.5 pu
Load voltage 230 V 1 PU
DVR voltage 0 - 115 V 0 - 0.5 PU
DC-link voltage 560 V
:.‘ vower limit
Supply frequency 50 Hz 1 PU
Switchine: freauencv 5 kHz 100 DU
Fig. 5. A deep voltage sag with a phase jump. The hatched region
indicates the region the DVR can operate.
n 3

B2

Line filter

Auxiliaiy AC supply Fig. 7. DVR control in the rotating dq-reference frame.


Fig. 6. Prototype DVR in the laboratory including a three phase
supply and load
storage or from the grid itself. The different topologies
for DVR’s are treated in [6]. In this setup the DVR is
may also be disturbed by a sudden change in the phasor of powered by an auxiliary AC Supply and the AC is recti-
the load voltage. Because of the potential problems with fied by a passive diode bridge and fed in to the DC-link.
a phase shift at the load, the control of a DVR is tested, The setup correspond to a system with energy storage and
emphasis is put on the voltage sags with phase jump and a constant DC-link voltage. During a voltage sag the DC-
how to avoid the phase shift to propagate to the load. link voltage is only slightly reduced because of the active
Two methods are tested, which could protect phase shift power drawn by the series converter.
sensitive loads from phase jumps. They are here charac- Each injection transformer for the DVR are magneti-
terized as: cally decoupled in order to have the maximum test pos-
sibilities. To minimize the voltage drop across the DVR
In-phase compensation with a smooth compensation of and to take the full advantage of the leakage inductance in
the phase jump. the transformer, the converter switches directly into the
Pre-sag compensation. transformer also used in [ 2 ] . The line filter sinks the main
part of the switching harmonics.
The first method continually tracks the supply voltage Calculations for the control is carried out in a Digital
and information about the pre-sag condition is initially Signal Processor (DSP) and the switchings are performed
used, but it changes slowly to inject a voltage in phase by a Micro Controller (MC). The main hardware param-
with the new supply voltage. The second method uses the eters for the DVR are listed in Table I.
pre-sag condition and in the ideal case the load voltage is
undisturbed by the voltage sag. B. Control Method

I v . DVR TEST SYSTEM


The two main control methods applied to DVR’s are the
open loop control and the closed loop control [7]. Closed
To test and verify the control of the DVR a prototype loop control have the potential of the best performance,
has been built in the laboratory. but changes in the load leads to a varying system model
and the voltage controller must be designed with caution.
A . Hardware Open loop load voltage control is often used and combined
In the laboratory the DVR converter is based on three with feed forward compensation of the voltage drop caused
full-bridge Voltage Source Converters with a common DC- by the line filter and the injection transformer. In this
link. Fig. 6 illustrates the DVR setup. paper open loop control is used and Fig. 7 illustrates the
The power needed, when injecting a voltage in phase control used.
with the load current is usually taken from an energy Space vector control has been applied to the DVR,

1269
-400'20 40 60 80 100 120 140 160 180
I

Fig. 8. Phase locked loop(PLL) to synchronize the DVR to the


supply voltage.

hence the RST voltages have been transformed in to a 20 40 60 80 100 120 140 160 180
space vector representation:

The space vector -are transformed in to a rotating dq- -400


reference frame according to 3: 20 40 60 80 100 120 140 160 180
c) Time [ms]

ud +ju, = (U, +jup)e-Je (3) Fig. 9. The associated supply voltages during a voltage sag with a
phase jump. a) Supply voltage phase R, b) supply voltage phase
A voltage sag is detected by measuring the error between S and c ) supply voltage phase T.
the dq-voltage of the supply and the reference values:

IUerror,dql= J(Uref,d - u,upply,d)2 + (Uref,q - % L P P l Y , q ) 2 A . In-phase compensation with smooth compensation of


the phase j u m p
(4)
The d-reference component is set to rated voltage and the A PLL with a response time of approximately 10 ms is
q-reference component is set to zero. used for this method Fig. loa. illustrates how the PLL is
able to track the fundamental component during a 70 %
C. Synchronzzation voltage sag with a 30" negative phase jump. The PLL has
The synchronization of the DVR to the supply is shown a fast response time and it starts tracking the new angle
in Fig. 8, which is further described in [4]. The angle y in- of the supply. The associated dq-voltages of the supply
dicates the instantaneous angle of the supply space voltage is shown in Fig. lob. and c. A reduction in the d- and
and 6' is the angle of the PLL. The PLL tracks the positive q-component can-initially-be seen and the missing voltage
sequence component of the supply voltage and the PLL must be injected to avoid disturbing the load. In case of a
angle is used for transformation to the dq-system. The symmetrical voltage sag without a phase jump the supply
angle 0 is filtered from most harmonics, non-symmetry would only have a reduction in the d-component.
and transients from the supply voltages. The PLL above The u,,f,, is set to zero (0 v) and the u,,f,d is set
is processed in the DSP with the same sampling time as to nominal voltage (325 V) and the effect is a smooth
the switching frequency. compensation of the phase jump from instantaneous wave
compensation to in-phase compensation. In Fig. 11 the
V. SIMULATIONS generated load voltages are shown. With this method the
The control system, converter, supply and load are DVR is also injecting a voltage after the supply voltage
modelled and written-for implementation in Saber to test is restored, because the positive phase jump,. that occurs
the different control strategies for the DVR. Fig. 9 illus- when the supply voltage is restored, is-smoothed by the
trates the supply voltage with a 70 % voltage sag and a DVR.
30" negative phase jump. The sag is symmetrical with a
duration of 100 ms. At time, t = 40 ms the voltage sag is
initiated and the supply voltage is restored 100 ms later:
At time t = 140 ms the supply voltage jumps back to the
pre-sag condition, which correspond to a positive phase
jump .

1270
II= r-
40-

E;;;r!
z
3 20:
0. go
2-20
3-20 -

1-
-40- I -40'
20 40 60 80 100 120 140 160 180 20 40 60 80 100 120 140 160 180

, , a' ,

g:
aQoo

2 i
E 100

s -100
20
I
40 60 80 100 120 140 I60
,
180
150
20 40 60 80 100
b)
120 140 160 180

-200
20 40 60 80 I00 I20 140 160 I80
c)Tunc[ms] c ) Time [SI

Fig 10 Simulation of a 70% voltage sag with in-phase compen- Fig. 12. Simulation of a 70% voltage sag with pre-sag compensation
sation a) Angle between the supply and the PLL. (y - e), b) a) Angle between the supply and the PLL (y - e), b) d-supply
d-supply voltage and c) q-supply voltage voltage and c) q-supply voltage.

.""

-400' I -N"
20 40 60 80 100 120 140 160 I80 20 40 60 80 100 120 140 160 180
a)

-400' I
20 40 60 80 100 120 140 160 180

20 40 60 80 100 120 140 160 180 20 40 60 80 100 120 140 160 180
c) Time [ms] c ) Time [ms]

Fig. 11. The associated load voltages for each phase during a voltage Fig. 13. The associated load voltages for each phase during a voltage
sag with a phase jump. sag with a phase jump.

B. Pre-sag compensation VI. EXPERIMENTAL


RESULTS

To have pre-sag compensation the angular velocity of The two methods have been tested on an experimen-
the pre-sag voltage is used during the sag and the PLL tal setup, the DVR system has been described under test
output is used again, when the sag is over. Fig. 12a. system and the test conditions is in both cases a voltage
illustrate again the angle between the supply voltage and sag down to 80 % with a 15" negative phase jump. The
the used transformation angle. Both the dq-component of stationary values for the two control methods are:
the supply voltage (Fig. 12b. and c. are reduced and the
DVR injects d-component up to 325 V and q-component
upre-sag
- = 1L15"-0.8 = 0.31L57"
~ s u p p ~ y - ~ s a g (5)
up to 0 V. The load voltage in Fig. 13 seems almost
undisturbed and the phase jump remain unseen by the - usupply
Uin-phase - Usag= 1LO" - 0.8 = 0.2LO" (6)
load. This means the pre-sag compensation require a 50 %
higher rated DVR compared with the in-phase compensa-
tion method.
The load applied for these tests is a symmetrical star
connected load with resistors (16 a)paralleled with in-
ductors (168 mH). The load conditions are approximate
11 kVA with a power factor of 0.96, hence the load current
is lagging the load voltage by 17".

1271
q 250
20
& ,

40 60 80 100 120 140 160 180 20 40 60 80 100 120 I40 160 180

I &

-4001 I
20 40 60 80 100 I20 140 160 180 20 40 60 80 100 120 140 160 180
c) T i m [m] E) T i m [m]

Fig. 14. Measurement of a 80% voltage sag with in-phase compen- Fig. 15. Measured response during a 80 % voltage sag from 230 V
sation a) Angle between the supply and the PLL. (y - e), b) to 184 V with in-phase compensation. a) Supply voltage phase
d-supply voltage and c ) q-supply voltage R, b) DVR voltage phase R and c) load voltage phase R.

A . In-phase compensatzon wzth smooth compensataon of


the phase j u m p
The in-phase compensation with smooth compensation
of the phase jump avoid a large phase jump seen by the
30 35 40 45 50 55 60 65
load, but within a certain time the PLL synchronize with
the new supply frequency and generate a voltage in phase Fig. 16. Zoomed view of the measured response during a 80 % volt-
with the supply voltage. Applying the smoothing method age sag from 230 V to 184 V. The Supply voltage drops, the
DVR voltage goes from a low standby voltage drop to an injec-
the DVR still require a high rating. Fig. 14a. illustrate tion value and the load voltage is almost maintained constant.
the measured angular difference between the PLL angle
and the actual supply angle. The deviation disappear fast
with a time constant of approximate 10 ms. In 14b. and c.
the associated d- and q-voltages for the supply voltage can
B. Pre-sag Compensation
be seen. The parameters in Fig. 14 have been recorded The pre-sag condition is here locked and the load is
by the DSP at 5 kHz sampling frequency with no pre- compensated for the phase jump. Fig. 17 illustrate the
triggering. measured angle difference and the associated dq-voltages
The DVR response and performance for one phase can for the supply. In the RST reference frame the response
be seen in Fig. 15, which illustrate the supply voltage is shown in Fig. 18 with the supply voltage, DVR voltage
with the phase jump, the injected DVR voltage and the and the load voltage.
resulting load voltage. The parameters have here been A zoomed view of the initial response of a voltage sag is
measured with an oscilloscope at 50 kHz sampling fre- illustrated in Fig. 19, which clarify that the original phase
quency. From the zoomed view of the the initial response of the supply voltage is maintained by the DVR.
in Fig. 16 the phase jump can be seen and how the DVR
in time starts to inject a voltage in-phase with the new
supply voltage. The phase of the load voltage is with this
method changed two times at the beginning of the sag and
at the end of the sag. These phase shifts can still disturb
the load and induce a transient current according to the
new phase of the load voltage.

1272

U,
-20 I
20 40 60 80 I00 I20 140 160 180 30 35 40 45 50 55 60 65

Fig. 19. Zoomed view of the measured response during a 80 % volt-


Zq age sag from 230 V to 184 V. The Supply voltage drops, the
+
2250
DVR voltage goes from a low standby voltage drop to an injec-
tion value and the load voltage is almost maintained constant.
225

$1 1
20 40 60 80 100 I20 140 160 180

VII. CONCLUSION
3 -50

The DVR could be a important device in the future to


-75’
20 40 60 80 100 120 140 160
I
180
protect sensitive loads from voltage sags. Often voltage
c ) T i m [msl
dips are accompanied with phase jumps, which challenges
the DVR rating and the control of a DVR. A good com-
Fig. 17. Measured response during a 80 % voltage sag from 230 V to pensation of voltage sags with phase jump is essential to
184 V with pre-sag compensation a) Angle between supply and protect very sensitive loads.
the PLL. (y - O ) , b) d-supply voltage and c) q-supply voltage
The control of a dynamic voltage have been analyzed
and it is stated that that to protect sensitive loads it is
pursued to preserve a load voltage without sudden phase
shift.
Two methods have been proposed to compensate a volt-
age sag with a phase jump. The first method called ”in-
phase compensation” smoothes the phase jump and after
20 40 60 80 100 1%) 140 160 180
approximately 10 ms generates an in-phase voltage with
the during-sag voltage. The second method called ”pre-
sag compensation” compensate for the phase jump and
protects thereby fully the load from the phase jump. Sim-
V I ulations indicate that the methods are feasible and ex-
20 40 60 80 100 I20 140 160 180
periments with a 10 kVA rated DVR verifies, that both
methods are applicable in the control of a dynamic voltage
restorer.
REFERENCES
20 40 60 80 100 120 140 160 180
c) T i m (MI M. Bollen. Understanding Power Quality Problems, voltage sags
and intermptions. IEEE press, 1999.
T. Jauch, Kara A., Rahmani M., and Westermann D. Power
Fig. 18. Measured response during a 80 % voltage sag from 230 V quality ensured by dynamic voltage correction. ABB Review,
to 184 V. with pre-sag compensation a) Supply voltage phase Vol. 4:pp. 25 - 36, 1998.
R, b) DVR voltage phase R and c) load voltage phase R G. Jobs. Three-phase static series voltage regulator control al-
gorithms for dynamic sag compensation. Proc. of ISIS’99, Vol.
2:pp. 515 - 520, 1999.
J. Kolar, H. Ertl, K. Edelmoser, and F. Zach. Analysis of the
The method gives minimum disturbances to the load control behavior of a bidirectional three-phase pwm rectifier sys-
tem. Proc. of EPE’91, pp.:2-095 - 2-loo., 1991.
and no transient currents will be initiated if the pre-sag S. Middlekauff and E. Collins. System and customer impact.
phase and voltage are maintained. Freezing to the pre-sag IEEE Transactions o n Power Delivery, Vol. 13, No. 1:pp. 278 -
condition can be difficult, when the duration of the voltage 282., January 1998.
J.G. Nielsen. Topologies for dynamic voltage restorer. Proc. of
. sag are long. In this case small deviations between actual N O R D A C 2000, 2000.
supply angular velocity and pre-sag angular velocity can M. Vilathgamuwa, R. Perera, S. Choi, and K . Tseng. Control of
give a degraded performance. energy optimized dynamic voltage restorer. Proc. of IECON’99,
Vol. 2:pp. 873 - 878, 1999.

1273

Das könnte Ihnen auch gefallen