WIRING DIAGRAM, MILLENNIUM ®


MODEL YK (STYLE E) LIQUID CHILLERS
PRODUCT DRAWING
OPTIVIEW CONTROL CENTER
YORK INTERNATIONAL CORPORATION
P.O. Box 1592, York, PA 17405
WITH STYLE B SOLID STATE STARTER
CONTRACTOR ________________________ PURCHASER ____________________________________________
ORDER NO. __________________________ JOB NAME _______________________________________________
YORK CONTRACT NO. _________________ LOCATION _______________________________________________
YORK ORDER NO. _____________________ ENGINEER ______________________________________________

REFERENCE DATE ________ APPROVAL DATE ________ CONSTRUCTION DATE ________

JOB DATA:

CHILLER MODEL NO. YK ________________________________________________________


NO. OF UNITS _____________
COMPRESSOR MOTOR ______________ VOLTS, 3-PHASE, _____________ Hz
OIL PUMP MOTOR _____________ VOLTS, 3-PHASE, _____________ Hz, _____________FLA

REMARKS:
2
DWG. 035-17157 (REV. –)
ELEMENTARY DIAGRAM

YORK INTERNATIONAL
FORM 160.54-PW2.1 FORM 160.54-PW2.1

LD05500
YORK INTERNATIONAL 3 YORK INTERNATIONAL 3A
FORM 160.54-PW2.1

ELEMENTARY DIAGRAM (Cont’d)

YORK INTERNATIONAL 3B 4 YORK INTERNATIONAL


FORM 160.54-PW2.1

LD05504

YORK INTERNATIONAL 5
FORM 160.54-PW2.1

TIMING DIAGRAM

LD05502

** This function is not for all shutdowns. See Operations Manual, Form 160.54-O1.

NOTES:
1. This wiring diagram describes the standard electronic 9. ____________________
control scheme for use with a YORK Solid State Starter.
10. For wiring diagram of Solid State Starter, refer to Prod-
For details of standard modifications, refer to Product
uct Form 160.04-PW1.
Form 160.54-PW7.
11. To check motor rotation on initial start-up, install mo-
2. Field wiring to be in accordance with the National Elec-
mentary switch between terminals 24 & 25 (line 41).
trical Code as well as all other applicable codes and
Depress start switch. After approx. 30 seconds, jog mo-
specifications. See Product Form 160.54-PW5.1 for field
tor with momentary switch. When proper rotation is ob-
wiring connections.
tained, replace momentary switch with jumper. Switch
3. Numbers along the left side of diagram are line identifica- must have a minimum contact rating of 2 FLA., 10 LRA
tion numbers. The numbers along the right side indicate at 115 Volts A.C.
the line number location of relay contacts. An underlined
12. Solid State Starter motor overload contact (CM) on Solid
contact location signifies a normally closed contact.
State Starter Logic Board is set to trip at 105% FLA.
4. Main control panel Class 1 field wiring terminal connec-
13. Contact rating is 5 Amps resistive @ 250 Volts A.C. &
tion points are indicated by numbers within a rectangle,
30 Volts D.C., 2 Amp inductive (.4 PF) @ 250 Volts A.C.
i.e. 15 . Main control panel factory wiring terminal con-
& 30 Volts D.C.
nection points are indicated by numbers within a triangle,
i.e. 5 . Component terminal markings are indicated by 14. Field connected control power supply is not required,
numbers within a circle, i.e. C1 . Numbers adjacent to as control transformer is supplied on the Solid State
circuit lines are the circuit identification numbers. Starter.
5. To cycle unit on and off automatically with contacts other 15. ____________________
than those shown, install a cycling device between ter-
16. Each 115VAC field-connected inductive load: i.e. relay
minals 1 & 13 (line 37) (see note 7). If a cycling device
coil, motor starter coil, etc., shall have a transient sup-
is installed, jumper must be removed between termi-
pressor wired in parallel with its coil, physically located
nals 1 & 13 .
at the coil. Spare transient suppressors and control
6. To stop unit and not permit it to start again, install a stop circuit fuses are supplied in a bag attached to green
device between terminals 1 & 8 (Line 33) (see note 7). ground screw in lower left corner of control panel.
A remote start-stop switch may be connected to termi-
17. For units with Flash Miniature Software Card Version
nals 1 , 7 & 8 (Lines 32 & 33) (see note 7). Remote
C.MLM.01.00 through C.MLM.01.03, the condenser
start-stop switch (Line 32) is operative only in the “re-
water pump should be wired to terminal 164 of TB2
mote” operating mode.
instead of terminal 151, and the wire from terminal 22
7. Device contact rating to be 5 milliamperes @ 115 volts of TB5 to terminal 150 of TB2 shall not be installed. For
A.C. software version C.MLM.01.04 and higher, the con-
denser pump connection should be as shown in the
8. Contact rating is 5A resistive @ 120 volts A.C. or 240
figure.
volts A.C.

YORK INTERNATIONAL 5A
FORM 160.54-PW2.1

LEGEND

LD05503

YORK INTERNATIONAL 5B 6
CONNECTION DIAGRAM

6 YORK INTERNATIONAL
FORM 160.54-PW2.1

LD05506

YORK INTERNATIONAL 7
CONNECTION DIAGRAM (Cont’d)

8 YORK INTERNATIONAL
FORM 160.54-PW2.1

YORK INTERNATIONAL 9
WIRING FOR 230V AND 460V UNITS

LD05508

10 YORK INTERNATIONAL
FORM 160.54-PW2.1

WIRING FOR 346V AND 600V UNITS

LD05509

OIL PUMP MOTOR OIL PUMP FUSING


FULL DUAL
VOLTS-PH-HZ LOAD ELEMENT*
AMPS FUSE SIZE
230-3-60 6.7 15
460-3-60 3.35 7.5
575-3-60 2.6 8#
* Oil pump motor fuses located in Solid State Starter.
#
Single element fuse size.

YORK INTERNATIONAL 11
INSIDE VIEW OF FRONT DOOR

LD05505

12 YORK INTERNATIONAL
FORM 160.54-PW2.1

PRESSURE TEMPERATURE CHART

LD05501

YORK INTERNATIONAL 13
14 YORK INTERNATIONAL
FORM 160.54-PW2.1