Our InD, OutD and HelpD series are designed to complement each
other. InD stands for indoor power systems, while OutD solutions
are created for demanding outdoor use. HelpD is our global support
team; its task is to make everything easy for you.

3791363100_00
www.deltapowersolutions.com Smarter. Greener. Together.
Table of contents
1 UIM – User Interface Module / UIL – User Interface Local ................................ 2
1.1 UIM / UIL keys .......................................................................................... 2
1.2 Default password ..................................................................................... 3
2 General ............................................................................................................... 4
3 Implementation setup ......................................................................................... 5
3.1 Defining event thresholds ......................................................................... 5
3.2 Defining event delays ............................................................................... 5
3.3 Defining battery functions ......................................................................... 6
3.4 Defining rectifier functions ........................................................................ 7
3.5 Save setup ............................................................................................... 7

Controller PSC 3 Table of contents


1 UIM – User Interface Module / UIL – User
Interface Local

1.1 UIM / UIL keys

Press the ENTER key to:

• activate functions
• change parameters
• confirm changes
• move the control one level down on the menu tree

Press the EXIT key to:

• exit a menu
• break an input
• move the control one level up on the menu tree

2 Controller PSC 3 UIM – User Interface Module / UIL – User Interface Local
UIL

Press the arrow buttons to:

• move the cursor


• get a new menu
• get new menu options
• decrease a parameter value
• increase a parameter value

1.2 Default password

The default password is the following key sequence:

arrow up – arrow up – arrow down – EXIT – EXIT – ENTER

Controller PSC 3 UIM – User Interface Module / UIL – User Interface Local 3
2 General
The PSC 3 controller is preconfigured at the Delta Energy Systems factory according to
the system configuration. The following step-by-step instructions show how to modify the
basic configuration from the beginning with UIM/UIL. The configuration order is the
following:

3.1 Defining event thresholds


- Psys high
- LVD
- PLDx

3.2 Defining event delays


- PLDx
- MF delay

3.3 Defining battery functions


- Float Charge
- System Voltage Supervision
- Battery Test
- Middle Point Measurement

3.4 Defining rectifier functions


- Rectifier number

3.5 Save setup


- Save

4 Controller PSC 3 General


3 Implementation setup

3.1 Defining event thresholds


From the main menu select 6. Configuration / 6.1 Event / 6.1.1 Thresholds.

6. CONFIGURATION 6.1 EVENT 6.1.1 THRESHOLDS

From the 6.1.1 Thresholds menu select the menu that you want to modify.

From Psys high menu select Up Thres. Define the value (n + x number of rectifiers).

From the LVD [U] menu select Low Thres. Define the LVD open value.

From the PLD1 [U] and / or PLD2 [U] menu select Low Thres. Define the PLDx open
value. Set the hysteresis value so that PLDx will not be closed below 50V.

6.1.1 THRESHOLDS Psys high Up Thres: 6000W

LVD [U] Low Thres: 42.00V

PLD1 [U] Hysteresis: 8.00V

PLD2 [U]

3.2 Defining event delays


From the main menu select 6. Configuration / 6.1 Event / 6.1.2 Delays.

6. CONFIGURATION 6.1 EVENT 6.1.2 DELAYS

From the PLD1 [t] and / or PLD2 [t] menu select True for. Define the PLDx open delay
time.

From the MF delay menu select True for. Define the Mains failure alarm delay time.

6.1.2 DELAYS PLD1 [t] Inp: S Mainsfailure

PLD2 [t] TRUE for: 00:10:00

MF delay FALSE for: 00:00:00

Controller PSC 3 Implementation setup 5


3.3 Defining battery functions
From the main menu select 7. Battery funct / 7.1 Float charge.

From the 7.1 Float charge menu select Usys @ 20 °C. Define the value (Float charge
level).

From the 7.1 Float charge menu select Tcoeff. Define the value (Temperature
compensation coefficient).

From the 7.1 Float charge menu select Tc_low. Define the value (Temperature
compensation low level).

From the 7.1 Float charge menu select Tc_high. Define the value (Temperature
compensation high level).

From the 7.1 Float charge menu select Utc_high. Define the value (Highest
compensation voltage level).

7. BATTERY FUNCT 7.1 FLOAT CHARGE Usys @ 20 ºC 53.5V

Tcoeff: -96mV/ ºC

Tc low: 0 ºC

Tc_high: 45 ºC

Utc high: 57.5V

From the main menu select 7. Battery funct / 7.4 Usys supervis.

From the 7.4 Usys Supervis menu select Ua max (max. voltage of system).

From the 7.4 Usys Supervis menu select Ua min (min. voltage of system).

From the 7.4 Usys Supervis menu select Us max (+ 1 % of float charge).

From the 7.4 Usys Supervis menu select Us min (- 1 % of float charge).

7. BATTERY FUNCT 7.4 USYS SUPERVIS Ua max: 57.00V

Ua min: 46.00V

Us max: 54.10V

Us min: 52.90V

6 Controller PSC 3 Implementation setup


From the main menu select 7. Battery funct / 7.5 Battery test / 7.5.1 Parameters.

From the 7.5.1 Parameters menu select Usupport (battery test support voltage level).

From the 7.5.1 Parameters menu select Duration (battery test duration).

7.5 BATTERY TEST 7.5.1 PARAMETERS Usupport: 46.5V

Duration: 60min

From the main menu select 7. Battery funct / 7.6 Middle point / 7.6.1 Parameters.

From the 7.6.1 Parameters menu select Ud chrg (difference with recharge or charge
mode).

From the 7.6.1 Parameters menu select Ud dichrg (difference with discharge mode).

7.6 MIDDLE POINT 7.6.1 PARAMETERS Ud chrg: 0.50V

Ud dichrg: 0.50V

3.4 Defining rectifier functions


From the main menu select 8. Rectifier funct / 8.1 Configuration / 8.1.2 Setup.

8. RECTIFIER FUNCT 8.1. CONFIGURATION 8.1.2 SETUP

From the 8.1.2 Setup menu select 1. RM NUMBER (define correct number of rectifiers).

8.1.2 SETUP .1 RM NUMBER Number: 5

3.5 Save setup


From the main menu select 9. Setup / 9.1. Save setup.

From the 9.1 Save setup menu select Save.

9. SETUP 9.1 SAVE SETUP Setup: saved

Save

Controller PSC 3 Implementation setup 7