Controller PSC 3
Our InD, OutD and HelpD series are designed to complement each
other. InD stands for indoor power systems, while OutD solutions
are created for demanding outdoor use. HelpD is our global support
team; its task is to make everything easy for you.
3791363100_00
www.deltapowersolutions.com Smarter. Greener. Together.
Table of contents
1 UIM – User Interface Module / UIL – User Interface Local ................................ 2
1.1 UIM / UIL keys .......................................................................................... 2
1.2 Default password ..................................................................................... 3
2 General ............................................................................................................... 4
3 Implementation setup ......................................................................................... 5
3.1 Defining event thresholds ......................................................................... 5
3.2 Defining event delays ............................................................................... 5
3.3 Defining battery functions ......................................................................... 6
3.4 Defining rectifier functions ........................................................................ 7
3.5 Save setup ............................................................................................... 7
• activate functions
• change parameters
• confirm changes
• move the control one level down on the menu tree
• exit a menu
• break an input
• move the control one level up on the menu tree
2 Controller PSC 3 UIM – User Interface Module / UIL – User Interface Local
UIL
Controller PSC 3 UIM – User Interface Module / UIL – User Interface Local 3
2 General
The PSC 3 controller is preconfigured at the Delta Energy Systems factory according to
the system configuration. The following step-by-step instructions show how to modify the
basic configuration from the beginning with UIM/UIL. The configuration order is the
following:
From the 6.1.1 Thresholds menu select the menu that you want to modify.
From Psys high menu select Up Thres. Define the value (n + x number of rectifiers).
From the LVD [U] menu select Low Thres. Define the LVD open value.
From the PLD1 [U] and / or PLD2 [U] menu select Low Thres. Define the PLDx open
value. Set the hysteresis value so that PLDx will not be closed below 50V.
PLD2 [U]
From the PLD1 [t] and / or PLD2 [t] menu select True for. Define the PLDx open delay
time.
From the MF delay menu select True for. Define the Mains failure alarm delay time.
From the 7.1 Float charge menu select Usys @ 20 °C. Define the value (Float charge
level).
From the 7.1 Float charge menu select Tcoeff. Define the value (Temperature
compensation coefficient).
From the 7.1 Float charge menu select Tc_low. Define the value (Temperature
compensation low level).
From the 7.1 Float charge menu select Tc_high. Define the value (Temperature
compensation high level).
From the 7.1 Float charge menu select Utc_high. Define the value (Highest
compensation voltage level).
Tcoeff: -96mV/ ºC
Tc low: 0 ºC
Tc_high: 45 ºC
From the main menu select 7. Battery funct / 7.4 Usys supervis.
From the 7.4 Usys Supervis menu select Ua max (max. voltage of system).
From the 7.4 Usys Supervis menu select Ua min (min. voltage of system).
From the 7.4 Usys Supervis menu select Us max (+ 1 % of float charge).
From the 7.4 Usys Supervis menu select Us min (- 1 % of float charge).
Ua min: 46.00V
Us max: 54.10V
Us min: 52.90V
From the 7.5.1 Parameters menu select Usupport (battery test support voltage level).
From the 7.5.1 Parameters menu select Duration (battery test duration).
Duration: 60min
From the main menu select 7. Battery funct / 7.6 Middle point / 7.6.1 Parameters.
From the 7.6.1 Parameters menu select Ud chrg (difference with recharge or charge
mode).
From the 7.6.1 Parameters menu select Ud dichrg (difference with discharge mode).
Ud dichrg: 0.50V
From the 8.1.2 Setup menu select 1. RM NUMBER (define correct number of rectifiers).
Save
D0126867_02