as to diminish the solar heat without much 7) For a total area of openings (inlet and outlet)
reduction in air motion indoors. of 20 percent to 30 percent of floor area, the
2) Inlet openings in the buildings should be well average indoor wind velocity is around
distributed and should be located on the 30 percent of outdoor velocity. Further
windward side at a low level, and outlet increase in window size increases the available
openings should be located on the leeward velocity but not in the same proportion as
side. Inlet and outlet openings at high levels shown in Fig. 6. In fact, even under most
may only clear the top air at that level without favourable conditions the maximum average
producing air movement at the level of indoor wind speed does not exceed 40 percent
occupancy. of outdoor velocity.
3) Maximum air movement at a particular plane 8) Where the direction of wind is quite constant
is achieved by keeping the sill height of the and dependable, the size of the inlet should
opening at 85 percent of the critical height be kept within 30 to 50 percent of the total
(such as head level) for the following area of openings and the building should be
recommended levels of occupancy: oriented perpendicular to the incident wind.
a) For sitting on chair 0.75 m, Where direction of the wind is quite variable
the openings may be arranged so that as far as
b) For sitting on bed 0.60 m, and
possible there is approximately equal area on
c) For sitting on floor 0.40 m. all sides. Thus no matter what the wind
4) Inlet openings should not as far as possible direction be, there would be some openings
be obstructed by adjoining buildings, trees, directly exposed to wind pressure and others
sign boards or other obstructions or by to air suction and effective air movement
partitions inside in the path of air flow. through the building would be assured.
5) In rooms of normal size having identical 9) Windows of living rooms should open directly
windows on opposite walls the average indoor to an open space. In places where building
air speed increases rapidly by increasing the sites are restricted, open space may have to
width of window up to two-third of the wall be created in the buildings by providing
width; beyond that the increase is in much adequate courtyards.
smaller proportion than the increase of the 10) In the case of rooms with only one wall
window width. The air motion in the working exposed to outside, provision of two windows
zone is maximum when window height is on that wall is preferred to that of a single
1.1m. Further increase in window height window.
promotes air motion at higher level of window,
11) Windows located diagonally opposite to each
but does not contribute additional benefits as
other with the windward window near the
regards air motion in the occupancy zones in
upstream corner give better performance than
buildings.
other window arrangements for most of the
6) Greatest flow per unit area of openings is building orientations.
obtained by using inlet and outlet openings of
12) Horizontal louvers, that is, sunshades atop
nearby equal areas at the same level.
windows deflect the incident wind upward and
reduce air motion in the zone of occupancy. A
horizontal slot between the wall and horizontal
louver prevents upward deflection of air in the
interior of rooms. Provision of inverted L type
(Γ) louver increases the room air motion
provided that the vertical projection does not
obstruct the incident wind (see Fig. 7).
13) Provision of horizontal sashes inclined at an
angle of 45° in appropriate direction helps to
promote the indoor air motion. Sashes
projecting outward are more effective than
projecting inward.
14) Air motion at working plane 0.4 m above the
FIG . 6 EFFECT OF AREA OF OPENING ON AVERAGE floor can be enhanced by 30 percent using a
INDOOR WIND VELOCITY pelmet type wind deflector (see Fig. 8).