Manual 37615B SPM-D2-10 - Synchronizing Unit

Dead Bus Start


≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡
Closing the circuit breaker may be performed even if synchronization voltage is not present. The close CB com-
mand is issued if the input "Enable CB" (terminal 3) is energized and input "Reply: CB is open" (terminal 4) sig-
nals an open circuit breaker.

Parameter 3432 Dead bus start of power circuit breaker ON/OFF


Gen. circ.break.
Dead bus op. ON ON ................The dead bus operation functions are enabled. The circuit breaker will
be closed onto a dead bus when all dead bus start parameters have
been met (refer to "Closing the CB Without Synchronization (Dead
Bus Start)" on page 26). The subsequent screens of this function are
displayed.
OFF ..............The dead bus operation functions are disabled, and the subsequent
screens of this function are not displayed.

Parameter 5802 Maximum differential frequency for CB dead bus start 0.05 to 5.00 Hz
Dead bus op. GCB
df max = 0.00Hz
The circuit breaker close command is only issued after the measured generator fre-
quency is within the value configured here of the generator rated frequency.
Example: If the generator is rated at 60Hz and 5.00Hz is configured here, the circuit
breaker will be issued a close command when the generator achieves 55Hz.

Parameter 5800 Maximum differential voltage for CB dead bus start 1 to 60 V


Dead bus op. GCB
dV max = 00V
The circuit breaker close command is only issued after the measured generator volt-
age is within the value configured here of the generator rated voltage.
Example: If the generator is rated at 460 Volts and 60V is configured here, the cir-
cuit breaker will be issued a close command when the generator achieves 400 Volts.

Page 54/68 © Woodward