Beruflich Dokumente
Kultur Dokumente
Line data:
Z1 =0.5 + j5.0 ohm
Z 0=2.0 + j15.0 ohm
Z<
Line data:
Z1 =2.5 + j15.0 ohm
Z 0=10.0 + j60.0 ohm
Z m0=8.0 + j45.0 ohm
132
3
VT :
0.11
3
Z< IT : 1500 /1
The fault resistance for phase to phase faults is limited to the arc
resistance, which can be estimated (minimum phase to phase fault current:
3 kA) by use of the van Warrington formula. The arc resistance is less
than 1.6 ohm. With the double end fault current to the fault the arc
resistance will be enlarged. A setting of 5 ohm (primary) is therefor
chosen.
The fault resistance for phase to ground faults is dependent on the
resistance between the fault point and real ground (tower footing
resistance). An effective tower footing resistance of 5 ohm is assumed. In
addition to this there will be some arcing resistance. With the double end
fault current to the fault the arc resistance will be enlarged. A setting of 15
ohm (primary) is therefor chosen.
Zone 2
The time delay of zone 2 is set to 0.4 s. Zone 2 is also used as the
overreach zone for the permissive overreach communication scheme. Zone
2 will in addition to this serve as back-up protection for faults at the remote
busbar.
The first requirement is that zone 2 shall overreach the remote busbar. For
the phase to phase loops a first attempt is to chose a setting of 125 % of
the line impedance:
Positive sequence:
Z1, set = 1.25 ⋅ (2.5 + j15.0) = 3.12 + j18.75 ohm( primary )
Zero sequence:
Z 0, set = 1.25 ⋅ (12.50 + j 75.00 − (10.0 + j 60.0 )) = 3.12 + j18.75 ohm( primary )
Zone 4
Zone 4 shall serve as remote back-up protection for other objects in the
system (lines, transformers, etc.). The apparent impedance seen by the
protection for faults at other objects can be calculated. Here it is assumed
that a 60 MVA transformer at the remote substation shall be covered by
zone 3. The apparent impedance, seen by the distance protection at a fault
at the low voltage side of the transformer in the remote substation, is
calculated to about 60 ohm (primary). This corresponds to 400 % of the
line reactance. The settings must not give unwanted limitations of the
power transfer of the line at normal operation. We assume the following
settings:
Positive sequence:
Z1, set = 4.00 ⋅ (2.5 + j15.0) = 10.00 + j 60.00 ohm( primary )
Zero sequence:
Z 0, set = 4.00 ⋅ (10.0 + j 60.0 ) = 40.00 + j 240.00 ohm( primary )
For the fault resistance a setting of 30 ohm is chosen both for the phase-
phase loop and the phase-ground loop.
The maximum power to be transferred on the line is 300 MVA. With a
minimum operational voltage of 130 kV the minimum apparent impedance
at normal operation will be:
130 2
Z load min = = 56.3 ohm( primary )
300
The resistive reach should be limited to about 45 ohm (primary).
General Fault Criterion
The setting of the general fault criterion shall be done so that all other
zones are covered.
Positive sequence: Reactive setting both phase-phase and phase-ground
loop: X 1, set ≥ 60.00 ohm( primary )
Setting of Current reversal and Weak end infeed logic for distance
protection.
For the current reversal the timers’ tPickUp and tDelay shall be given.
tPickUp is chosen to 20 ms to assure shorter time than the breaker time.
T Delay is chosen to 50 ms to assure that the communication has time to
reset.
Setting of the phase overcurrent protection function:
The Instantaneous function is given a current setting to assure rapid
tripping of line faults close to the substation. The maximum phase current
through the bay is calculated for faults at the remote busbar and at the
home busbar. This current is found to be 6000 A at a three phase short
circuit at the remote busbar. The instantaneous phase overcurrent function
is therefor given a current setting of 8500 A (primary)
The delayed phase overcurrent function shall, if possible, cover the own
line for all faults. The setting must not endanger the normal operation. The
current setting must therefor be larger than the highest possible load
current. The largest load current can be calculated:
300
I load max = ≈ 1.3 kA
3 ⋅130
The time delay must be longer than the longest trip time for objects within
the reach of the delayed phase overcurrent protection.
The following settings are therefor chosen:
2000 A (primary), 1.2 s
Setting of Current reversal and Weak end infeed logic for residual
overcurrent protection.
For the current reversal the timers tPickUp and tDelay shall be given.
tPickUp is chosen to 20 ms to assure shorter time than the breaker time.
T Delay is chosen to 50 ms to assure that the communication has time to
reset.
Setting of autoreclosing.
The autoreclosing shall be a three-phase autoreclosing for all faults. The
dead time shall be 0.5 s to assure the arcing fault to extinguish.