Sie sind auf Seite 1von 31

Optoelectronics Skills

a Promising Skill that Changes Life

Specifics of installation and Implementation


of optoelectronic applications
content

1. Introduction of lighting system

2. Installation process of lighting system

3. Trial operation and acceptance of lighting system

CQCET 2
01 Introduction of lighting system

CQCET 3
01
03 Introduction of lighting system

Lighting system can utilize the distributed wireless telemetry and


energy-saving electrical control technology to realize the safety,
convenience, comfort and artistry of lighting application.

CQCET 4
01
03 Introduction of lighting system

Composition of lighting system


Lamps Wiring Lamps

Wiring Switches
Switches CQCET 5
01
03 Introduction of lighting system

LED bulb

CQCET 6
01
03 Introduction of lighting system

Light stripe

CQCET 7
02 Installation process of lighting system

CQCET 8
02
03 Installation process of lighting system

Stages of lighting installation

Preparation for Installation of lighting wire


construction distribution box connection

Our Focus

Acceptance of Trial operation of Installation of


lighting system lighting power supply lamps

CQCET 9
02
03 Installation process of lighting system

Installation of lamps

Assembly of
lamps Wiring of lamps
Check the Integrity Install the lamp with
and appearance of corresponding Connect lamps
Assemble lamps
according to the installation method. according to
according to lamp
list. specifications and
assembly technical
document. requirements.
Check lamps Installation of
lamps

CQCET 10
02
03 Installation process of lighting system

Installation of T5

1 2 3

CQCET 11
02
03 Installation process of lighting system

Installation of split T8
1 2 3

4 5 5

CQCET 12
02
03 Installation process of lighting system

Installation of integral T8

1 2

3 4

CQCET 13
02
03 Installation process of lighting system

Installation of light stripe

1 2 3

4 5

CQCET 14
02
03 Installation process of lighting system

Notes for lamp installation

CQCET 15
02
03 Installation process of lighting system

4m

3m

2m

1m

CQCET 16
02
03 Installation process of lighting system

Ceiling

deviation <= 5 mm Lamp

deviation <= 5 mm

CQCET 17
02
03 Installation process of lighting system

Wiring of lamps

Insulation pad at the entrance of conductor Insulation pad at the internal metal opening

CQCET 18
02
03 Installation process of lighting system

×: No flexible fixing holder in non- √: Stress relief with flexible fixing


detachable soft cable holder

CQCET 19
02
03 Installation process of lighting system

Unqualified item: only contacted with the metal parts of the lamp body by the
conductor of basic insulation protection
Rectification measures: internal wiring adopts double insulation
CQCET 20
03 Trial operation and acceptance of lighting system

CQCET 21
03
03 Trial operation and acceptance of lighting system

Completion
Insulation Lamp control Illumination
of acceptance
inspection inspection detection
records

CQCET 22
03
03 Trial operation and acceptance of lighting system

• One is the calculation software of professional lighting manufacturers (such as


GE, Philips, DiSano, etc.).
• The other is professional illuminance calculation software (such as Dialux, etc.)

Simulation effect of Dialux evo CQCET 23


03
03 Trial operation and acceptance of lighting system

100 h

10 h

without external light source


CQCET 24
03
03 Trial operation and acceptance of lighting system

Central point method


The illuminance measurement area is divided into square grid and measured
vertically at the center of the rectangular grid.

1
𝐸𝑎𝑣 = 𝐸𝑖
𝑀∙𝑁

𝐸𝑎𝑣 - average illuminance in lx;


𝐸𝑖 - illuminance on the i-th side in lx;
M- longitudinal measuring points ;
N- horizontal measuring points ;
CQCET 25
03
03 Trial operation and acceptance of lighting system

Measurement example
Measure the illuminance of the kitchen.

4m
5m

2m 4m CQCET 26
03
03 Trial operation and acceptance of lighting system

4m
5m

2m 4m
CQCET 27
03
03 Trial operation and acceptance of lighting system

E1=292 lx E9=299 lx E18=425 lx


E1 E6 E11 E15 E19 E23 E10=319 lx E19=431 lx
E2=307 lx
E20=403 lx
E2 E7 E12 E16 E20 E24 E3=345 lx E11=326 lx
4m E =310 lx E12=336 lx E21=301 lx
5m E3 E8 E13 E17 E21 E25 4
E22=359 lx
E5=412 lx E13=363 lx
E4 E9 E14 E18 E22 E26 E14=387 lx
E23=333 lx
E6=451 lx
E24=297 lx
E5 E10 E7=389 lx E15=342 lx
E25=323 lx
E8=395 lx E16=355 lx
2m 4m E26=389 lx
E17=367 lx

1 1
𝐸𝑎𝑣 = 𝐸𝑖 = 𝐸1 + 𝐸2 + ⋯ + 𝐸25 + 𝐸26 = 356 lx
𝑀∙𝑁 26 CQCET 28
04 Review

CQCET 29
Review

• Introduction of lighting system

• Installation process of lighting system

• Trial operation and acceptance of lighting system

CQCET 30
Thanks

Das könnte Ihnen auch gefallen