Beruflich Dokumente
Kultur Dokumente
352 WIRING
Ampacity The IRC specifies the current-carrying capacity
Because all wire has electrical resistance, the flow (ampacity) of wires depending on their size, insu-
of electrons (current) generates heat and raises the lation type, and temperature rating, as shown in
temperature of the conductor, posing a fire danger. the table below.
RHW. THHW RHW-2, THHN, THHW RHW. THHW RHW-2, THHN, THHW
THW, THWN, THW-2, THWN-2 THW, THWN, THW-2, THWN-2
TW, UF XHHW, USE XHHW, XHHW-2, USE-2 TW, UF XHHW, USE XHHW, XHHW-2, USE-2
Size, AWG 5 10 15 20 30 40 50
14 234 117 78 — — — —
12 517 187 124 93 — — —
10 595 298 198 149 99 — —
8 — — — 236 157 118 —
6 — — — — — 183 146
4 — — — — — — 234
Box Dimensions, in Capacity, cu in No. 18 No. 16 No. 14 No. 12 No. 10 No. 8 No. 6
4 × 11⁄4 round or octagonal 12.5 8 7 6 5 5 4 2
4× 11⁄2 round or octagonal 15.5 10 8 7 6 6 5 3
4× 21⁄8 round or octagonal 21.5 14 12 10 9 8 7 4
4 × 11⁄4 square 18.0 12 10 9 8 7 6 3
4 × 11⁄2 square 21.0 14 12 10 9 8 7 4
4× 21⁄8 square 30.3 20 17 15 13 12 10 6
411⁄16 × 11⁄4 square 25.5 17 14 12 11 10 8 5
411⁄16 × 11⁄2 square 29.5 19 16 14 13 11 9 5
411⁄16 × 21⁄8 square 42.0 28 24 21 18 16 14 8
3×2× 11⁄2 device 7.5 5 4 3 3 3 2 1
3 × 2 × 2 device 10.0 6 5 5 4 4 3 2
3 × 2 × 21⁄4 device 10.5 7 6 5 4 4 3 2
3 × 2 × 21⁄2 device 12.5 8 7 6 5 5 4 2
3×2× 13⁄4 device 14.0 9 8 7 6 5 4 2
3×2× 31⁄2 device 18.0 12 10 9 8 7 6 3
4 × 21⁄8 × 11⁄2 device 10.3 6 5 5 4 4 3 2
4 × 21⁄8 × 17⁄8 device 13.0 8 7 6 5 5 4 2
4× 21⁄8 × 21⁄8 device 14.5 9 8 7 6 5 4 2
33⁄4 ×2× 21⁄2 masonry box/gang 14.0 9 8 7 6 5 4 2
33⁄4 × 2 × 31⁄2 masonry box/gang 21.0 14 12 10 9 8 7 4
1
Where no volume allowances are made for clamps, fixture studs, hickeys, etc. as described in IRC Sections
E3805.12.2.2 through E3805.12.2.5.
354 WIRING
Common Electrical Boxes
Box with ears and clamps Wall box with brackets Box with side bracket
Bend radius
greater than 5 times
cable diameter
Staple cable
every 4' 6" min
Staple within
8" of box with
no connector
Nonmetallic
box
Staple within
12" of box
with connector
Metal box
44”-48"
Holes over
1-1/4" from 18-ga steel
stud face over cable if
within 11/4"
of stud face
12”-18"
356 WIRING
Running NM Cable in Floors and Ceilings
Rafter
Exterior wall
Ceiling joist
Across joists
under eaves
Stapled to preferred
sides OK in
all cases
Across joists
OK only if attic
inaccessible
Light
fixture Thru joist OK
in all cases
Interior wall
358 WIRING
Conduit Fittings
Back condulet
Break-apart elbow
Bending Conduit
Length required
x°
1
Length + 2 /4" 2
(for 1/2" EMT)
Finished length
Neutral
(long slot) Ears
Hot
Silver (white (short
wire) slot)
Fault Pickup
sensor coil
Toroid
Hot 1.000 A
15 Amp 20 Amp
120 Volt 120 Volt Neutral 0.995 A
"TEST"
20 Amp 30 Amp
240 Volt 240 Volt
30 Amp 50 Amp
120/240 Volt 120/240 Volt
360 WIRING
Switches
Switch Types
Line
Common Common
In-1 In-2
Position 1
Position 2
Out-1 Out-2
Traveler Traveler
Traveler Traveler
Common
Common
Load
Traveler Traveler
Line In-1 In-2
ON
Switches 361