Sie sind auf Seite 1von 24

INTERFACE C

MEDIUM VOLTAGE SYMMETRICAL


SEPARABLE CONNECTORS
CATALOGUE 2020
NEXANS NETWORK SOLUTIONS DIV. EUROMOLD

COMPANY PRESENTATION

EUROMOLD International standards Laboratory accreditation


Euromold is the leading All our products meet the Since June 2000, Euromold’s
European specialised designer, International standards like independent ELAB laboratory
manufacturer and distributor of CENELEC HD 629.1, CENELEC obtained the BELAC accreditation
prefabricated cable accessories EN 50180, IEC 60137, no.144-TEST conform with
for medium voltage energy IEC 60502-4… or country the European standards for
distribution. Euromold provides a specifications. Official certificates, laboratories ISO 17025 for
complete range of accessories for CESI, KEMA, ATEX… prove the electrical testing of low and
underground cables: premoulded conformity of our products. medium voltage cable accessories
EPDM rubber connectors for Long duration tests of existing or according to the international
cables and epoxy bushings for new products are continuously standards EN 50393, IEC 60502-
transformers and switchgear, as performed in our test fields. 4, IEC 61442 and HD 629.
well as a large range of cold-
shrinkable terminations and joints
from 12 to 42 kV.
Euromold is also the manufacturer
of electrical components for the
high voltage accessories of the
Nexans group.

ISO 9001 Certificate


Since 1992, Euromold’s
commitment to quality is
demonstrated by its ISO 9001
certification.

While every care is taken to ensure that the information contained in this publication is correct, no legal responsibility
can be accepted for any inaccuracy. Nexans Network Solutions N.V. - Div. Euromold reserves the right to alter or
modify the characteristics of its products described in this catalogue as standards and technology evolve.
SYMMETRICAL SEPARABLE CONNECTORS
INTERFACE C

TABLE OF CONTENTS INTERFACE C1 & C2


(K)400TB - tee connector Dimensions according to European
(M)(P)400TB - tee connector CENELEC EN 50180 and 50181
440TB - tee connector (in mm).
440PB - coupling connector
400PB - XSA - surge arrester
400TR - test rod
400TK and 400SW installation tools
Accessories
Possible arrangements

Dia. 56±0.2

Dia. 46±0.2
Dia. 22 min for C1
Dia. 32 nominal for C2
M16 x 2 - 6H 0
1.5 -0.5

29
min.

90±0.2

11
min.

Dia. 70±0.2

2 In mm.

03/2020
CONNECTING POSSIBILITIES
BUSHINGS / CONNECTION CONNECTORS /
ACCESSORIES ACCESSORIES

Equipment dead-ending
interface of equipment (K)(M)400DR-B
Dead-end receptacle

(K)(M)400AR-3
Equipment bushing

(K)(M)400AR-4
Equipment bushing

cable to
(K)(M)400AR-5 equipment
Equipment bushing

(K)(M)400AR-6
Equipment bushing

(K)(M)400SFR-B
Equipment bushing (K)(M)440PB/G
Coupling connector
(K)(M)(P)400TB/G
Tee connector

400A-24B
In-air bushing

cable
(K)(M)400SOP-B isolation
Stand-off plug

(K)(M)(P)440TB/G 400PB-XSA
Tee connector Surge arrester
cable
400GP-B earthing
Earthing plug

tap-off
(K)400RTPA 630/250A
Reducing tap plug

in-line
junction
(K)(M)400CP-SC
Connecting plug

in-line
junction
(K)(M)440CP
Connecting plug

For information on
bushings please refer to
our bushing catalogue.

03/2020
(K)400TB INTERFACE C
TEE CONNECTOR

APPLICATION TECHNICAL
Separable tee shape connector CHARACTERISTICS
(bolted type) designed to connect • The thick conductive EPDM jacket
polymeric insulated cable provides a total safe to touch
to equipment (transformers, screen which ensures safety for
switchgear, motors, ...). personnel.
Also connects cable to cable when • Each separable connector is
using the appropriate mating tested for AC withstand and
parts. partial discharge prior to leaving
the factory.

DESIGN 255 mm
Separable connector 220 mm

comprising: 6/10 (12) kV


1. Conductive EPDM insert. 6.35/11 (12) kV
2. Conductive EPDM jacket. 8.7/15 (17.5) kV
3. Insulating EPDM layer. 12/20 (24) kV
4. Type C interface as described 4 9 12.7/22 (24) kV
by CENELEC EN 50180 and 5
6 8
50181.
1
5. Conductor contact.
Up to 24 kV
6. Basic insulating plug (with 2
630 A - 800 A
VD point). 350 mm
3
7. Cable reducer.
8. Conductive rubber cap.
10
9. Clamping screw.
10. Earthing lead.

The screen break design


enables cable outer sheath 7
testing without removing or
dismantling the connector.

SPECIFICATIONS AND
STANDARDS
The 400TB separable connector
meets the requirements of
CENELEC HD 629.1 S1.

Separable Voltage Current Current Ir (A) Conductor sizes


When using a copper (-11-2) or a (mm2)
connector Um Ir bolted (-14-5) conductor contact
type (kV) (A) min max
400TB/G 12 630 800 35 300
K400TB/G 24 630 800 35 300

03/2020

4
KIT CONTENTS
The complete (K)400TB/G tee The kit also comprises silicone grease,
gloves, wipers, roll adhesive tape and
connector kit comprises the
instalation instructions.
following components:

Conductor
contact TMBC-X
(K)400TB/G-W-X
connector kit

Basic insulating
Clamping plug
Connector housing screw Conductor (K)400BIPA Cable reducer
(K)400BT/G 400TCS contact TBC-X + rubber cap CA0-W

ORDERING INSTRUCTIONS TABLE W


To order the tee connector, select
the ordering part number which Ordering Dia. over core insulation (mm)
gives you the best centring of your part number min max
core insulation diameter and sub- 400TB/G-011-X 12.0 19.0
stitute X using table X, according to 400TB/G-015-X 16.0 26.5
your conductor size and type. 400TB/G-019-X 19.0 32.6
Add a 'K' for use up to 24 kV. 400TB/G-021-X 20.0 34.6
400TB/G-027-X 28.5 37.5

TABLE X
EXAMPLE:
Aluminium and Copper
The copper wire screened cable Aluminium conductor
copper conductor conductor
Conductor
is 12 kV, 150 mm2 stranded sizes (mm2) DIN Deep DIN
Bolted
copper with a diameter over core hexagonal indent hexagonal
insulation of 23.5 mm. 35 35(K)M-10-2 35KM-10-1 35(K)M-11-2
16.95-14-5

Order a 400TB/G-018-150(K) 50 50(K)M-10-2 50(K)M-10-1 50(K)M-11-2


50.150-14-5

M-11-2 tee connector kit. 70 70(K)M-10-2 70(K)M-10-1 70(K)M-11-2


95 95(K)M-10-2 95(K)M-10-1 95(K)M-11-2
95.240-14-5

120 120(K)M-10-2 120(K)M-10-1 120(K)M-11-2


120.300-14-5

150 150(K)M-10-2 150(K)M-10-1 150(K)M-11-2


185 185(K)M-10-2 185(K)M-10-1 185(K)M-11-2
240 240(K)M-10-2 240(K)M-10-1 240(K)M-11-2
300 300(K)M-10-2 – 300(K)M-11-2

IECEx
For use with For use with For applications For use in potentially Components can be When installed on an
copper tape other cable types. outdoors and in explosive atmospheres ordered individually. appropriate equipment
screened cables. Please contact our humid climate. (for 12 kV max). bushing:
Order: Kit MT. representative. Order: +MWS. Order: ATEX-IECEx 800 A continuously

5
(M)(P)400TB INTERFACE C
TEE CONNECTOR

APPLICATION TECHNICAL
Separable tee shape connector CHARACTERISTICS
(bolted type) designed to connect • The thick conductive EPDM jacket
polymeric insulated cable provides a total safe to touch
to equipment (transformers, screen which ensures safety for
switchgear, motors, ...). personnel.
Also connects cable to cable when • Each separable connector is
using the appropriate mating tested for AC withstand and
parts. partial discharge prior to leaving
the factory.

DESIGN 255 mm
Separable connector 220 mm

comprising: 18/30 (36) kV


1. Conductive EPDM insert. 19/33 (36) kV
2. Conductive EPDM jacket. 20.8/36 (42) kV
3. Insulating EPDM layer.
4. Type C interface as described 4 9

by CENELEC EN 50180 and 5


6 8
50181. Up to 42 kV
1
5. Conductor contact. 630 A - 800 A
6. Basic insulating plug (with 2
VD point). 350 mm
3
7. Cable reducer.
8. Conductive rubber cap.
10
9. Clamping screw.
10. Earthing lead.

The screen break design


enables cable outer sheath 7
testing without removing or
dismantling the connector.

SPECIFICATIONS AND
STANDARDS
The 400TB separable connector
meets the requirements of
CENELEC HD 629.1 S1.

Separable Voltage Current Current Ir (A) Conductor sizes


When using a copper (-11-2) or a (mm2)
connector Um Ir bolted (-14-5) conductor contact
type (kV) (A) min max
M400TB/G 36 630 800 35 240
P400TB/G 42 630 800 35 240

03/2020

6
KIT CONTENTS
The complete(M)(P)400TB/G The kit also comprises silicone grease,
gloves, wipers, roll adhesive tape and
tee connector kit comprises the
instalation instructions.
following components:

Conductor
contact TMBC-X
(M)(P)400TB/G-W-X
connector kit

Basic insulating
Clamping plug
Connector housing screw Conductor (M)(P)400BIPA Cable reducer
(M)(P)400BT/G 400TCS contact TBC-X + rubber cap 411CA-W

ORDERING INSTRUCTIONS TABLE W


To order the tee connector, select
the ordering part number which Ordering Dia. over core insulation (mm)
gives you the best centring of your part number min max
core insulation diameter and sub- 400TB/G-11-X 12.0 17.5
stitute X using table X, according to 400TB/G-15-X 16.0 22.0
your conductor size and type. 400TB/G-19-X 20.0 26.5
Add an 'M' for use up to 36 kV, add 400TB/G-22-X 23.5 31.0
a 'P' for use up to 42 kV. 400TB/G-25-X 26.5 32.5
400TB/G-27-X 28.5 37.5

TABLE X
EXAMPLE:
Aluminium and Copper
The copper wire screened cable Aluminium conductor
copper conductor conductor
Conductor
is 36 kV, 150 mm2 stranded sizes (mm2) DIN Deep DIN
Bolted
copper with a diameter over core hexagonal indent hexagonal
insulation of 32.5 mm. 35 35(K)M-10-2 35KM-10-1 35(K)M-11-2
16.95-14-5

Order a M400TB/G-27-150(K) 50 50(K)M-10-2 50(K)M-10-1 50(K)M-11-2


50.150-14-5

M-11-2 tee connector kit. 70 70(K)M-10-2 70(K)M-10-1 70(K)M-11-2


95 95(K)M-10-2 95(K)M-10-1 95(K)M-11-2
95.240-14-5

120 120(K)M-10-2 120(K)M-10-1 120(K)M-11-2


120.300-14-5

150 150(K)M-10-2 150(K)M-10-1 150(K)M-11-2


185 185(K)M-10-2 185(K)M-10-1 185(K)M-11-2
240 240(K)M-10-2 240(K)M-10-1 240(K)M-11-2
300 300(K)M-10-2 – 300(K)M-11-2

For use with For use with For applications Components can be When installed on an
copper tape other cable types. outdoors and in ordered individually. appropriate equipment
screened cables. Please contact our humid climate. bushing:
Order: Kit MT. representative. Order: +MWS. 800 A continuously

7
440TB INTERFACE C
TEE CONNECTOR

APPLICATION TECHNICAL
Separable tee shape connector CHARACTERISTICS
(bolted type) designed to connect • The thick conductive EPDM jacket
polymeric insulated cable provides a total safe to touch
to equipment (transformers, screen which ensures safety for
switchgear, motors, ...). personnel.
Also connects cable to cable when • Each separable connector is
using the appropriate mating tested for AC withstand and
parts. partial discharge prior to leaving
the factory.

DESIGN 255 mm
220 mm
Separable connector
comprising: 6/10 (12) kV
1. Conductive EPDM insert. 6.35/11 (12) kV
2. Conductive EPDM jacket. 8.7/15 (17.5) kV
3. Insulating EPDM layer 12/20 (24) kV
moulded between the insert 4 9
and the jacket.
12.7/22 (24) kV
4. Type C interface as described 5 6 8 18/30 (36) kV
by CENELEC EN 50180 and 1
19/33 (36) kV
50181. 20.8/36 (42) kV
2
5. Conductor contact.
6. Basic insulating plug (with 355 mm 3 Up to 42 kV
VD point). 630 A - 1250 A
7. Cable reducer.
10
8. Conductive rubber cap.
9. Clamping screw.
10. Earthing lead.

The screen break design 7


enables cable outer sheath
testing without removing or
dismantling the connector.

SPECIFICATIONS AND
STANDARDS
The 440TB separable connector
meets the requirements of
CENELEC HD 629.1.

Separable Voltage Current Current Conductor sizes


connector Um Ir Ir (A) (mm2)
type (kV) (A) min max
440TB/G 12 630 1250 185 630
K440TB/G 24 630 1250 185 630
M440TB/G 36 630 1250 185 630
P440TB/G 42 630 1250 185 630
03/2020

8
KIT CONTENTS
The complete (K)(M)(P)440TB/G The kit also comprises silicone grease, field
tee connector kit comprises the control mastic, installation instructions and
crimp chart.
following components:

Conductor
contact TMBC-X
(K)(M)(P)440TB/G-W-X
connector kit

Basic insulating
Clamping plug
Connector housing screw Conductor (K)(M)(P)400BIPA Cable reducer
(K)(M)(P)440BT/G 400TCS contact TBC-X + rubber cap 611CA-W

ORDERING INSTRUCTIONS TABLE W


To order the tee connector, select
the ordering part number which Ordering Dia. over core insulation (mm)
gives you the best centring of your part number min max
core insulation diameter and sub- 440TB/G-22-X 23.5 31.0
stitute X using table X, according 440TB/G-27-X 28.5 37.5
to your conductor size and type. 440TB/G-32-X 34.0 42.5
Add a 'K' for use up to 24 kV, add 440TB/G-37-X 39.0 48.5
an 'M' for use up to 36 kV, add a 'P' 440TB/G-43-X 45.5 56.0
for use up to 42 kV. TABLE X

EXAMPLE: Aluminium and copper Copper


Conduc- Aluminium conductor
The copper wire screened cable conductor conductor
tor sizes
is 36 kV, 240 mm2 stranded (mm2) DIN Deep DIN
Bolted
aluminium with a diameter over hexagonal indent hexagonal
core insulation of 37.0 mm. 185 185(K)M-12-2 185KM-12-1 185(K)M-11-2
Order a M440TB/G-32-240(K)
240 240(K)M-12-2 240KM-12-1 240(K)M-11-2
M-12-2 tee connector kit.
300 300(K)M-12-2 300KM-12-1 300(K)M-11-2

400 400(K)M-12-2 400KM-12-1 400(K)M-11-2

500 500(K)M-12-2 500KM-12-1 500(K)M-11-2

630 – 630KM-12-1 630(K)M-11-2

IECEx
For use with For use with For applications For use in potentially Components can be When installed on an
copper tape other cable types. outdoors and in explosive atmospheres ordered individually. appropriate equipment
screened cables. Please contact our humid climate. (for 12 kV max). bushing:
Order: Kit MT. representative. Order: +MWS. Order: ATEX-IECEx 1250 A continuously

9
440PB COUPLING CONNECTOR FOR
400TB AND 440TB

APPLICATION TECHNICAL
Separable coupling connector CHARACTERISTICS
(bolted type) for dual cable • A thick conductive EPDM jacket
arrangement. It has been provides a total safe to touch
designed to be used with 400TB screen.
and 440TB separable tee • Each separable connector is
connector. tested for AC withstand and
partial discharge prior to leaving
the factory.

DESIGN 410 mm

1. Interface designed to fit


400TB/440TB connector. 6/10 (12) kV
2. Contact rod for 440PB. 6.35/11 (12) kV
3. Conductive EPDM insert. 11 2 8.7/15 (17.5) kV
4. Insulating EPDM layer 1 8
6
12/20 (24) kV
moulded between the
12.7/22 (24) kV
7
400TB or 3
insert and the jacket. 440PB
18/30 (36) kV
440TB
connector 4 coupling
5. Conductive EPDM jacket. connector

6. Conductive EPDM cap.


355 mm
5 19/33 (36) kV
7. Basic insulating plug. 20.8/36 (42) kV
8. Conductor contact.
10
9. Cable reducer. Up to 42 kV
10. Earthing lead. 9 800 A
11. Threaded M16 stud for the
equipment bushing.
The screen break design 155 mm

enables cable outer sheath


testing without removing or
dismantling the connector.

SPECIFICATIONS AND
STANDARDS
The 440PB coupling connector
meets the requirements of
CENELEC HD 629.1.

Separable Voltage Current


Conductor sizes (mm2)
connector Um Ir
type (kV) (A) min max
440PB/G 12 800 185 630
K440PB/G 24 800 185 630
M440PB/G 36 800 185 630
P440PB/G 42 800 185 630

03/2020

10
KIT CONTENTS The kit also comprises silicone grease, field
The complete control mastic, installation rod, installation
(K)(M)(P)440PB/G coupling instructions and crimp chart.

connector kit comprises 3 x the


following components:

Conductor
contact TMBC-X
3 x (K)(M)(P)440PB/G-W-X
coupling connector kit

Contact rod
Connector housing 440PB-CR Conductor Cable reducer
(K)(M)(P)440BP/G + M16 stud contact TBC-X 611CA-W

ORDERING INSTRUCTIONS TABLE W


To order the coupling connector,
select the ordering part number Ordering Dia. over core insulation (mm)
which gives you the best centring part number min max
of your core insulation diameter 3 x 440PB/G-22-X 23.5 31.0
and substitute X using table X, ac- 3 x 440PB/G-27-X 28.5 37.5
cording to your conductor size and 3 x 440PB/G-32-X 34.0 42.5
type. 3 x 440PB/G-37-X 39.0 48.5
Add a 'K' for use up to 24 kV, add 3 x 440PB/G-43-X 45.5 56.0
an 'M' for use up to 36 kV,
TABLE X
add a 'P' for use up to 42 kV.
Aluminium and copper Copper
EXAMPLE: Conduc- Aluminium conductor
conductor conductor
The copper wire screened cable tor sizes
(mm2) DIN Deep DIN
is 36 kV, 240 mm2 stranded Bolted
hexagonal indent hexagonal
aluminium with a diameter over
185 185(K)M-12-2 185KM-12-1 185(K)M-11-2
core insulation of 37.0 mm.
Order 3 x M440PB/G-32-240(K) 240 240(K)M-12-2 240KM-12-1 240(K)M-11-2
M-12-2 coupling connector kit. 300 300(K)M-12-2 300KM-12-1 300(K)M-11-2

400 400(K)M-12-2 400KM-12-1 400(K)M-11-2

500 500(K)M-12-2 500KM-12-1 500(K)M-11-2

630 – 630KM-12-1 630(K)M-11-2

For use with For use with fabric tape For use with For use with copper For use with For outdoor
copper tape (graphite) screened cables. easy strip semi-conductive wire screened cables. other cable types. applications.
screened cables. Order additional screened cables. Order: No earthing Please contact our Order: +MWS.
Order: Kit MT. semi-conductive tape Field control mastic device is representative.
(type TSC). (type MFC). necessary.
11
400PB-10SA INTERFACE C
SURGE ARRESTER

APPLICATION TECHNICAL
Surge arrester designed to protect CHARACTERISTICS
medium voltage components, • This surge arrester is a metal
including transformers, oxide varistor surge arrester in an
equipment, cable and accessories elbow configuration.
from high voltage surges resulting • Each arrester is tested for AC
from lightning or switching. withstand, partial discharge and
critical voltage prior to leaving the
factory.
DESIGN
Surge arrester comprising: 247 mm
1. Conductive EPDM insert. 145 mm
2. Conductive EPDM jacket.
3. Insulating EPDM layer
Dia.
moulded between the insert 80 mm
6/10 (12) kV
and the jacket. 6.35/11 (12) kV
4. Contact rod. 4
8.7/15 (17.5) kV
5. Earthing lead. 1 12/20 (24) kV
9
6. Earth connection. 2 12.7/22 (24) kV
7. Steel cap. 5 18/30 (36) kV
3
8. Metal oxide valve elements. L2
19/33 (36) kV
L1
9. Type C interface as described 20.8/36 (42) kV
8
by CENELEC EN 50180 and
50181.
Dia. Up to 42 kV
70 mm
SPECIFICATIONS AND 7
STANDARDS
6
The 400PB-10SA surge arresters
meet the test requirements of IEC
60099-4.

Nominal Max. continuous Dimensions


Surge Rated
discharge operating (mm)
arrester voltage
current voltage
type Ur (kV)
In (kA) Uc (kV) L1 L2
400PB-10SA-15L 10 15 12.0 270 310
400PB-10SA-18L 10 18 14.4 270 310
400PB-10SA-22L 10 22 17.6 370 410
400PB-10SA-24L 10 24 19.2 370 410
400PB-10SA-30L 10 30 24.0 370 410
400PB-10SA-6N 10 6 4.8 270 310
400PB-10SA-9N 10 9 7.2 270 310
400PB-10SA-12N 10 12 9.6 270 310
400PB-10SA-15N 10 15 12.0 270 310
400PB-10SA-18N 10 18 14.4 270 310
400PB-10SA-22N 10 22 17.6 270 310
400PB-10SA-24N 10 24 19.2 370 410
400PB-10SA-30N 10 30 24.0 370 410
400PB-10SA-33N 10 33 26.4 370 410
400PB-10SA-36N 10 36 28.8 370 410
400PB-10SA-45N 10 45 36.0 470 510
400PB-10SA-51N 10 51 40.8 470 510 03/2020

12
TYPICAL APPLICATIONS AND ORDERING INSTRUCTIONS
DIMENSIONS To order the surge arrester,
specify the surge arrester type, as
410 mm described on previous page.
220 mm 185 mm
EXAMPLE:
For a maximum continuous
operating voltage (r.m.s.) of
24 kV and a nominal discharge
current of 10 kA.
Order a 400PB-10SA-30N surge
arrester.

Type
400TB
or 440TB Type 400PB-10SA
tee connector surge arrester

NOTES:
• The surge arrester body needs
to be positioned vertically after
installation.
• Prior to cable testing, the surge
arrester shall be removed.

TECHNICAL DATA

Steep current Lightning current Switching impulse High current


Surge residual voltage residual voltage
residual impulse
arrester [8/20 µs] (kV) [36/90 µs] (kV)
voltage @ 10 kA withstand
type
[1/20 µs] (kV) (kA)
@ 5 kA @ 10 kA @ 20 kA @ 125 A @ 500 A

400PB-10SA-15L 47.1 38.9 42.3 47.4 29.8 31.8 100


400PB-10SA-18L 56.5 46.7 50.8 56.9 35.8 38.2 100
400PB-10SA-22L 69.2 57.1 62.2 69.7 43.8 46.7 100
400PB-10SA-24L 75.2 62.1 67.6 75.8 47.7 50.8 100
400PB-10SA-30L 94.0 77.6 84.5 94.7 59.6 63.5 100
400PB-10SA-6N 20.4 16.8 18.3 20.5 12.9 13.7 100
400PB-10SA-9N 28.5 23.5 25.6 28.7 18.0 19.2 100
400PB-10SA-12N 38.0 31.4 34.2 38.3 24.1 25.7 100
400PB-10SA-15N 48.1 39.7 43.2 48.4 30.5 32.5 100
400PB-10SA-18N 58.1 48.0 52.2 58.5 36.8 39.2 100
400PB-10SA-22N 70.1 57.9 63.0 70.6 44.4 47.3 100
400PB-10SA-24N 77.0 63.6 69.2 77.6 48.8 52.0 100
400PB-10SA-30N 97.0 80.1 87.2 97.7 61.5 65.5 100
400PB-10SA-33N 103.4 85.4 93.0 104.2 65.6 69.9 100
400PB-10SA-36N 115.9 95.7 104.2 116.8 73.5 78.3 100
400PB-10SA-45N 144.1 119.0 129.5 145.1 91.3 97.3 100
400PB-10SA-51N 166.0 137.1 149.2 167.2 105.2 112.1 100

13
400TR TEST ROD

APPLICATION TECHNICAL
• The test rod can be used for: CHARACTERISTICS
- cable fault location • The 400TR test rod can be used
- cable testing with 400TE, 400TB and 440TB
- phasing checks, etc. connectors.
• Connections may be made with
a cable lug, a 4 mm plug or
spring clips.

DESIGN
1. Insulating shroud. 400TR
2. Threaded rod for test
connection.
3. Two nuts M12.
4. Insulation.
5. Copper test rod stem.
6. Wing nut.
An insulating shroud is 1
provided to allow the M12
application of test voltages 2
when bushings are closely
3 40
spaced.

INSTALLATION 480

The test rod is mounted on


to the clamping screw in the type
C interface tee and coupling
connectors. The test cable is
connected to the threaded stem 4 280
and the insulating shroud moved
to its final position over the end of
5
the test rod.

ORDERING INSTRUCTIONS
Simply specify:
400TR test rod.
In mm.

Maximum A.C. Maximum D.C. Impulse voltage


Test rod
test voltage test voltage (1.2 x 50 µs)
type
(50 Hz - 1 min) (8 x U0 - 30 min) min
400TR 36 kV 96 kV 95 kV
03/2020

14
400TK AND 400SW
INSTALLATION TOOL

APPLICATION
• The box spanner and box
spanner key are designed to
facilitate assembly of 400TE,
400TB and 440TB connectors.
• The 400TK box spanner is used
to install the 400TEF clamping 400SW
pin contact or 400TCS clamping
400TK
screw.
• The 400SW box spanner key fits
on the hex nut of the 400BIPA
basic insulating plug.

ORDERING INSTRUCTIONS
Simply specify:
- 400TK box spanner
- 400SW box spanner key.

15

01/2020

15
ACCESSORIES

APPLICATION TECHNICAL 6/10 (12) kV


For use with connectors and CHARACTERISTICS 6.35/11 (12) kV
bushings with an interface C as All these products, except the 8.7/15 (17.5) kV
described by CENELEC EN 50180 earthing plugs, are tested for 12/20 (24) kV
and 50181. AC withstand and partial 12.7/22 (24) kV
discharge prior to leaving 18/30 (36) kV
the factory. 19/33 (36) kV
20.8/36 (42) kV

Up to 36 kV

400DR-B/G ORDERING INSTRUCTIONS


DEAD-END RECEPTACLE Order
Fits over a bushing with a type C 400DR-B/G for 12 kV,
interface to provide 'dead-end' K400DR-B/G for 24 kV or
facility. The dead-end receptacle is M400DR-B/G for 36 kV
supplied with an earth lead. applications.

400SOP-B ORDERING INSTRUCTIONS


STAND-OFF PLUG Order
Is designed to support and 'dead- 400SOP-B for 12 kV,
end' connectors with a type C K400SOP-B for 24 kV,
interface when removed from M400SOP-B for 36 kV or
equipment. P400SOP-B for 42 kV
applications.

400GP-B ORDERING INSTRUCTIONS


EARTHING PLUG Order
Is designed to support and earth 400GP-B for 12, 24, 36 or
connectors with a type C interface 42 kV applications.
when removed from equipment.

03/2020

16
400BIPA ORDERING INSTRUCTIONS
BASIC INSULATING PLUG Order
Acts as a tightening nut for the 400BIPA for 12 kV,
400TB and 440TB tee connector K400BIPA for 24 kV
kits. M400BIPA for 36 kV or
The plug contains a voltage P400BIPA for 42 kV
detection point. applications.
The conductive rubber protection
cap is included.

400CP-SC ORDERING INSTRUCTIONS


CONNECTING PLUG Order
For connecting two or more 400CP-SC for 12 kV,
connectors with a type C interface K400CP-SC for 24 kV or
together, thus creating a separable M400CP-SC for 36 kV
cable joint or a multiple cable applications.
connection to equipment.

For use up to 630 A.

440CP ORDERING INSTRUCTIONS


CONNECTING PLUG Order
For connecting two or more 440CP for 12 kV,
connectors with a type C interface K440CP for 24 kV or
together, thus creating a separable M440CP for 36 kV
cable joint or a multiple cable applications.
connection to equipment.
Order (K)(M)440CP + 676SA
stud for connection to an already
For use up to 1250 A.
installed connector.

400RTPA ORDERING INSTRUCTIONS


REDUCING TAP PLUG Order
Provides a type A interface to 400RTPA for 12 kV or
connectors with a type C interface. K400RTPA for 24 kV
A 'C' spanner, 600SW, is used to applications.
tighten the reducing tap plug on to
its mating part. Order 600SW for the 'C'
spanner.

KIT MT ORDERING INSTRUCTIONS


EARTHING KIT FOR COPPER Order
TAPE SCREENED CABLES Kit MT for 12 kV, 24 kV
Contains a tinned copper braid 36 kV or 42 kV applications.
(25 mm² - L = 500 mm), a tinned
copper wire for cleating and some
water sealing mastic.

400BE/G ORDERING INSTRUCTIONS


BUSHING EXTENDER Order 400BE/G for 12 kV,
Provides an extension piece to K400BE/G for 24 kV,
allow cables to stand away from M400BE/G for 36 kV or
equipment. P400BE/G for 42 kV
Is used in conjunction with the applications. 17
400CP, 440CP or 440PB. The
bushing extender is supplied with
an earth lead.
POSSIBLE ARRANGEMENTS

400TB/G 400TB/G-P2
Single cable arrangement. Dual cable arrangement.
Order 400TB/G for 12 kV, Order 400TB/G-P2 for 12 kV,
K400TB/G for 24 kV, K400TB/G-P2 for 24 kV or
M400TB/G for 36 kV or P400TB/G M400TB/G-P2 for 36 kV
for 42 kV applications. applications.

250 500

basic
insulating
plug
tee
connector connecting basic
plug insulating
plug

110 110 245

400TB/G-L2 400BE+440PB
2-way connection. Connector standing away from
Order 400TB/G-L2 for 12 kV, equipment.
K400TB/G-L2 for 24 kV or Order 400BE+440PB for 12 kV,
M400TB/G-L2 for 36 kV K400BE+440PB for 24 kV,
applications. M400BE+440PB for 36 kV or
P400BE+440PB for 42 kV
applications.
410

400BE
bushing extender
400

265
In mm.

03/2020

18
400TB/G-L3
3-way connection.
Order 400TB/G-L3 for 12 kV,
K400TB/G-L3 for 24 kV or
M400TB/G-L3 for 36 kV
applications.

400TB/G-L4
Disconnectable tap-off.
Order 400TB/G-L4 for 12 kV,
K400TB/G-L4 for 24 kV or
M400TB/G-L4 for 36 kV
applications.

400TB/G-L5 505
2-way connection with tap-off.
Order 400TB/G-L5 for 12 kV
or K400TB/G-L5 for 24 kV
applications.

In mm.

19
440TB+440PB-P2
Dual cable arrangement.
410
Order 440TB/G+440PB/G-P2 for
12 kV, K400TB/G+K440PB/G-P2
for 24 kV, M400TB/G+M440PB/
G-P2 for 36 kV, P400TB/
G+P440PB/G-P2 for 41,5 kV.
400

155

CONNECTOR ON STAND- CONNECTOR ON EARTHING


OFF PLUG PLUG
Order 400SOP-B for 12 kV, Order 400GP-B for 12 kV,
K400SOP-B for 24 kV or 24 kV and 36 kV applications.
M400SOP-B for 36 kV
applications.

400BIPA
basic
insulating
plug

400TB/G tee
stand-off connector
plug

CABLE AND EQUIPMENT


TESTING

20

In mm.

03/2020
Nexans Network Solutions N.V. - Div. Euromold
Zuid III, Industrielaan 12, B-9320 Erembodegem
Tel.: +32(0)53 85 02 11 • sales.euromold@nexans.com • www.euromold.be

Catalogue also available on Website and Mobile Apps

Find out more about Nexans Power Accessories.


03/2020