Beruflich Dokumente
Kultur Dokumente
NOTE: The balanced twisted-pair cable and coaxial cable do not have to be terminated at the same
location (e.g., wall telephone location). However, a minimum of one 4-pair balanced twisted-pair cable
and one 75-ohm Series-6 coaxial cable shall be installed to all other outlets.
Grade 2 residential telecommunications cabling provides a generic cabling system that meets the requirements
for current and developing basic, advanced, and multimedia telecommunications services.
The cabling associated with both grades of residential cabling is to be placed in a star topology. In addition, the
length of each outlet cable is not to exceed ≈90 meters (m [300 feet (ft)]). This length allows an operational
length of ≈100 m (328 ft), including an ≈10 m (33 ft) allowance for patch cords or jumper wire and equipment
cords.
NOTES: Each living area should be cabled with at least one telecommunications outlet.
A living area is defined as any room in which voice/data/video applications may be used.
Coaxial backbone cable may be implemented using a star, bus, or star and bus topology.
Balanced Twisted-Pair
The tenant’s needs will determine the proper number of pairs required for the ADO cable.
The ADO and DD usually are collocated and can be combined in a single unit. Install the ADO
in the end user’s (e.g., tenant’s) premises at a readily accessible location. Consider allowing
for growth of additional ADOs.
Note: for the installation of a surge protection device for each conductive cable entering or leaving
the building. Provide access to the building electrical ground within ≈1.52 m (5 ft) of the DD
and in accordance with applicable codes.
Chapter 20: Residential Cabling BICSI 13th ed
Terminate balanced
twisted-pair outlet
cable and ADO cable
on insulation
displacement
contact (IDC)
termination blocks
or with 8-position,
8-contact (8P8C)
plugs to facilitate
quick disconnect and
line of demarcation.
Coaxial cable is
typically terminated
with F-connectors.
guidance for planning the wall space that should be allocated for the DD and associated equipment.
Many DDs are sized to fit within the stud spacing in a wall ≈368 millimeters (mm [14.5 inches (in)]) and
may be as tall as ≈1370 mm (54 in).
A dedicated 15-ampere (A), 120 volt alternating current (Vac) nominal, no switchable duplex electrical
outlet shall be provided within ≈1.52 m (5 ft) of the DD.
Recommended Cables
Recommended outlet cable includes:
• 4-Pair 100-ohm balanced twisted-pair category 5e, although category 6 is recommended.
• Multimode optical fiber. • Singlemode optical fiber. • Series-6 coaxial.
Install outlet cable according to star topology (see Figure 20.2), in which:
• One or more outlet cable runs extend from the DD to each telecommunications outlet.
• A tenant located on more than one floor is cabled from a single DD serving that tenant.
Chapter 20: Residential Cabling BICSI 13th ed
EF. Access to the building electrical ground shall be provided within ≈1.52 m (5 ft) of the
conductive cable terminations in the EF in accordance with applicable codes.
NOTE: All of the design and construction of EFs for residential cabling shall meet or exceed
applicable codes, standards, regulations, and authority having jurisdiction rulings.
If active equipment is placed within the CTR, dedicated, unstitched electrical power
outlet(s) shall be provided within ≈1.52 m (5 ft) in the CTR. The height of the electrical
outlet(s) should be suitable for the equipment being installed and shall be in compliance with
applicable codes.
Chapter 20: Residential Cabling BICSI 13th ed
NOTES:
1. One 27 metric designator (1 trade size) electrical metallic tubing conduit to each unit. Conduit
may be in slab or ceiling space.
2. One 27 metric designator (1 trade size) rigid PVC Type 2 or metallic conduit.
3. All conduits are to be limited to two 90-degree sweeping bends.
4. Size and location are to be determined by the AP.
5. Provide and install all ducts and conduits with a pull cord.
6. CATV is in a separate conduit system to mitigate potential pulling problems.
7. One 27 metric designator (1 trade size) PVC conduit to accepted ground grid.
Chapter 20: Residential Cabling BICSI 13th ed
• Wall-mounted telephone jacks ≈1220 mm to ≈1320 mm (48 in to 52 in) above the floor.
NOTE: Adjust the locations of wall-mounted jacks to accommodate elderly tenants or thers with special
needs.
To minimize electrical interference, do not place long runs of outlet or ADO cable close or
parallel to electrical power cabling.
Install plastic bushings on holes drilled through metal studs to prevent damage to the cable
sheath. Pull cable through joists and studs carefully to avoid damaging the cable.
Do not run cable on the exterior of buildings.
Connect all auxiliary equipment (e.g., transformers used for electrical power on otherwise vacant outlet
cable pairs) at the DD. The DD cabling shall ensure that external voltage sources are not applied to the
network interface through the ADO cable.
Telecommunications Outlets
For balanced twisted-pair cabling, terminate the connector-pin configurations as shown in Figure 20.11.
Using the T568A configuration will accommodate many telecommunications services, including one-line
and two-line telephone sets.
Chapter 20: Residential Cabling BICSI 13th ed
NOTE: Performing either a qualification test or certification of data cable generally negates
the need for verification testing during the trim-out stage.
Verification testing of the cabling shall be performed to ensure proper end-to-end connectivity.
Coaxial cable shall be verified to ensure continuity.
The permanent link refers to the permanent part of the cabling installed (e.g., cable up to ≈90 m [300
ft] from the DD to the outlet and the connectors) without patch cords installed on each end of the cable.
At a minimum, provide a label within the DD denoting each cable run. Identify each cable
run by room and wall locations. For example, B1-N could denote a telecommunications
outlet/connector on the north wall of bedroom one. If telecommunications outlets/connectors
are not labeled, consider including simple floor plans at the DD that provide a graphic
correlation between physical telecommunications outlet locations and outlet designations.