EQp2 - Tracking Sheet for Smoking Room Differential Air Pressure Testing

OPTION 2Pressure
Negative - Non Residential
in SmokingProjects
Room must average 5 Pa (0.02 inches of water gauge)

with a minimum of 1 Pa (0.004 inches of water gauge) when the doors to the smoking room are closed

ROOM NUMBER/NAME _______________________________ Enter room name that is being tested

Take air pressure samples at 10 minuite intervals for 15 minuites and record pressure in the time slots
TIME: DIFFERENTIAL PRESSURE: DIFFERENTIAL PRESSURE: DIFFERENTIAL PRESSURE:
:10 3:40 6:40
:20 3:50 6:50
:30 4:00 7:00
:40 4:10 7:10
:50 4:20 7:20
1:00 4:30 7:30
1:10 4:40 7:40
1:20 4:50 7:50
1:30 5:00 8:00
1:40 5:10 8:10
1:50 5:20 8:20
2:00 5:30 8:30
2:10 5:40 8:40
2:20 5:50 8:50
2:30 6:00 9:00
2:40 5:40 9:10
2:50 5:50 9:20
3:00 6:00 9:30
3:10 6:10 9:40
3:20 6:20 9:50
3:30 6:30 10:00

10:10 11:50 13:30


10:20 12:00 13:40
10:30 12:10 13:50
10:40 12:20 14:00
10:50 12:30 14:10
11:00 12:40 14:20
11:10 12:50 14:30
11:20 13:00 14:40
11:30 13:10 14:50
11:40 13:20 15:00
Conduct the above samples for any adjacent rooms or chases and record the average room pressure here.
Air Pressure Air Pressure Smoking Room Requirements (Y/N)
Adjacent Room 1: ______________ Adjacent Chase 1: ________________ Exhausted to the Outdoors? _________
Adjacent Room 2: ______________ Adjacent Chase 2: _______________ No recirculation to Non-smoking areas? _________
Adjacent Room 3: ______________ Adjacent Chase 3: _______________ Deck to Deck Partitions? _________
Adjacent Room 4: ______________ Adjacent Chase 4: _______________ Compliant Pressure Test Completed? _________ (see below)
Adjacent Room 5: ______________ Adjacent Chase 5: ____________

Enter the avg. pressure for the current room tested by adding up all the 10 second pressure samples and dividing by 93 (the # 10 second of air samples)
DIFFERENTIAL PRESSURE AVERAGE ______________

DIFFERENTIAL PRESSURE AVERAGE with doors closed______________

DIFFERNTIAL PRESSURE AVERAGE compared with adjacent rooms ______________

COMPLIANT? ________________ (Y/N)


EQp2 - Tracking Sheet for Smoking Room Differential Air Pressure Testing
OPTION
Negative 2Pressure
- Non Residential
in SmokingProjects
Room must average 5 Pa (0.02 inches of water gauge)

with a minimum of 1 Pa (0.004 inches of water gauge) when the doors to the smoking room are clos

ROOM NUMBER/NAME ______Room 101: Designated Smoking room_________

TIME: DIFFERENTIAL PRESSURE: DIFFERENTIAL PRESSURE:


:10 5 3:40
:20 4 3:50
:30 4 4:00
:40 4 4:10
:50 4.5 4:20
1:00 4.5 4:30
1:10 4.5 4:40
1:20 4.5 4:50
1:30 4.5 5:00
1:40 4.5 5:10
1:50 4 5:20
2:00 4 5:30
2:10 4 5:40
2:20 4 5:50
2:30 4 6:00
2:40 4 5:40
2:50 4 5:50
3:00 4 6:00
3:10 4.5 6:10
3:20 4.5 6:20
3:30 5 6:30

10:10 6.5 11:50


10:20 6.5 12:00
10:30 6 12:10
10:40 6 12:20
10:50 6 12:30
11:00 6.5 12:40
11:10 6.5 12:50
11:20 6.5 13:00
11:30 6 13:10
11:40 5.5 13:20
Air Pressure Air Pressure
Adjacent Room 1: ________ 11 Adjacent Chase 1: __________ 11
Adjacent Room 2: ________ 11 Adjacent Chase 2: __________ 11
Adjacent Room 3: ________ 11 Adjacent Chase 3: __________ 11
Adjacent Room 4: ________ 11 Adjacent Chase 4: __________ 11
Adjacent Room 5: ________ 11 Adjacent Chase 5: __________ 11

DIFFERENTIAL PRESSURE AVERAGE _______5_______

DIFFERENTIAL PRESSURE AVERAGE with doors closed_______2_______

DIFFERNTIAL PRESSURE AVERAGE compared with adjacent rooms ______________

COMPLIANT? ____yes____________ (Y/N)

Credit Requirements
If the occupants are permitted to smoke, provide 1 or more designated smoking
rooms designed to contain, capture, and remove ETS from the building. At a
minimum, each smoking room must be directly exhausted to the outdoors,
with no recirculation of ETS-containing air to nonsmoking areas, enclosed with
impermeable deck-to-deck partitions, and operated at a negative pressure compared
with surrounding spaces of at least an average of 5 Pa (0.02 inches of water gauge)
and with a minimum of 1 Pa (0.004 inches of water gauge) when the doors to the
smoking rooms are closed.

Verify performance of the smoking rooms’ differential air pressure by conducting 15


minutes of measurement, with a minimum of 1 measurement every 10 seconds, of
the differential pressure in the smoking room with respect to each adjacent area and
in each adjacent vertical chase with the doors to the smoking rooms closed. Conduct
the testing with each space configured for worst-case conditions of transport of air
from the smoking rooms (with closed doors) to adjacent spaces.
f water gauge)

o the smoking room are closed

DIFFERENTIAL PRESSURE:
5 6:40 5.5
5 6:50 5.5
5 7:00 5.5
5 7:10 5
5 7:20 5
5 7:30 5.5
5 7:40 5.5
5 7:50 5.5
5 8:00 6
5 8:10 6
5 8:20 6
5 8:30 6
5 8:40 6
5 8:50 6
5 9:00 6
5.5 9:10 6
5.5 9:20 6
5.5 9:30 6
5.5 9:40 6
5.5 9:50 6
5 10:00 6.5

5.5 13:30 4.5


5.5 13:40 4.5
5 13:50 4.5
5 14:00 4.5
5 14:10 4.5
5 14:20 4.5
5 14:30 4.5
5 14:40 5
4.5 14:50 5
4.5 15:00 5
Smoking Room Requirements (Y/N)
Exhausted to the Outdoors? _____Y____
Recirculation to Non-smoking areas? ____N_____
Deck to Deck Partitions? ____Y_____
Compliant Pressure Test Completed? _____Y____ (see below)