Neutral Grounding

Sector Energy PTI NC


Theodor Connor

Copyright © Siemens AG 2008. All rights reserved.


Topics

Introduction

Theoretical background

Methods applied for neutral grounding

Practical aspects

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 1 01.2008 Th. Connor PTD SE PTI
Significance of earth faults for network operation

December
November
October
September
August
July
June
May 1 year
April
March 8760 hours
February
January
31 536 000 seconds

Method of neutral earthing has no influence on behaviour in normal operation

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 2 01.2008 Th. Connor PTD SE PTI
Kaleidoscope of methods available

Isolated neutral
Earth fault compensation KNOSPE

Solid earthing
NOSPE

High-impedance neutral earthing


Arc suppression
Low-impedance neutral earthing

Floating neutral

Effective earthing
Petersen coil
Resonant earthing

Short-time earthing
For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 3 01.2008 Th. Connor PTD SE PTI
Statistical data of German networks

Voltage level 10 kV 20 kV 110 kV 380 kV


Line lengths

Overhead line 28 000 km 111 000 km 60 000 km 17 000 km


Cable 98 000 km 89 000 km 4 000 km 16 km

Amount of faults
6 11 6 3
per 100 km and year

Isolated neutral 23 % - - -

Earth fault compensation 60 % 95 % 78 % -

Low-impedance neutral
8% 2% 22 % 100 %
earthing

Source: VDEW 1993

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 4 01.2008 Th. Connor PTD SE PTI
Display methods for system values

UL1 UL1
UL1(t) = ÛL1 sinωt
t
t Mathematical
equations

Time characteristic Vector display

Positive sequence
Negative sequence
UL1
Zero sequence

Phase-related
display Symmetrical
components

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 5 01.2008 Th. Connor PTD SE PTI
The transient phase of an earth fault

Isolated neutral

Discharge
Charging oscillation

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 6 01.2008 Th. Connor PTD SE PTI
Characteristics of transient phase

Frequency
Discharge 500 Hz . . . 100 000 Hz
Charging oscillation 100 Hz . . . 4 000 Hz

3Û LE max
Overvoltage factor kt = = 1.2...2.7...3.5
2U b

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 7 01.2008 Th. Connor PTD SE PTI
Permanent earth fault

ICE

Isolated neutral

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 8 01.2008 Th. Connor PTD SE PTI
Vector diagram for system with isolated neutral

UL1

UL1 = 0

UL2
Normal operation

UL2
Earth fault

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 9 01.2008 Th. Connor PTD SE PTI
Characteristics of power frequent voltage rise

ULE Max 1
Coefficient of ZE = ... 1
Ub 3
earthing

3 ULE Max
Earth-fault factor cf = 1 ... 3
DIN VDE 0111
Ub
IEC 71-1

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 10 01.2008 Th. Connor PTD SE PTI
Network calculation
3-phase short-circuit

UN
IK =
3⋅ Z

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 11 01.2008 Th. Connor PTD SE PTI
Network calculation
Symmetrical components

U1L1
Positive 1
sequence U1 = 3 (UL1+ a UL2+ a² UL3)

U1L2

UL1
U2 L1

Negative
1
U2 L3 sequence U2 = (UL1+ a² UL2+ a UL3)
3
UL3
UL2

Zero 1
U0 L1
sequence U0 = 3 (UL1 + UL2 + UL3)

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 12 01.2008 Th. Connor PTD SE PTI
Symmetrical components
Example

a2 UT

a US

UR
U1

a UT
a2 US
UR
U2

US
UR U0
UT
For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 13 01.2008 Th. Connor PTD SE PTI
Symmetrical components
Example

a2 UT

a US

UR
U1

U2

U0

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 14 01.2008 Th. Connor PTD SE PTI
Symmetrical components
Line to ground fault

I 1 = I R + I S ⋅ a + I T ⋅ a2

I 2 = I R + I S ⋅ a2 + I T ⋅ a
Boundary requirements at the fault location are
I0 = IR + IS + IT fulfilled by series connection of component
systems

IS = 0
S
~
Positive sequence
R
UR = 0

Negative sequence
Boundary requirements
at the fault location
IS = IT = 0
UR = 0 Zero sequence

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 15 01.2008 Th. Connor PTD SE PTI
Fault current calculation
System with isolated neutral

Positive sequence ~

Negative sequence

Zero sequence

3 ⋅ UN
IF =
Z1 + Z2 + Z0

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 16 01.2008 Th. Connor PTD SE PTI
Isolated neutral

ICE
ICE - capacitive earth fault current
ICE = 3 UN⋅ ω ⋅ C0
Isolated neutral

y Transient overvoltages kt ≤ 3.0


y Voltage rise of the fault-free phases cf ≤ 3
y ICE = f (Type of lines, voltage level, size of network)
y Operation under permanent earth fault possible

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 17 01.2008 Th. Connor PTD SE PTI
Estimation of capacitive earth fault current

Line type Voltage level Capacitive earth fault current ICE

Overhead lines
110 kV 0.36 A/km
20 kV 0.06 A/km
10 kV 0.03 A/km

Cables

Oil cable 110 kV 13.3 ... 36.1 A/km


XLPE cable 110 kV 7.5 ... 11.4 A/km

Lead-sheath cable 20 kV 2.2 ... 5.3 A/km


XLPE cable 20 kV 1.6 ... 4.4 A/km

Lead-sheath cable 10 kV 1.2 ... 2.7 A/km


XLPE cable 10 kV 1.2 ... 3.3 A/km

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 18 01.2008 Th. Connor PTD SE PTI
Intermittent earth fault

-0,5

First earth fault Recovery Second earth fault

Ice (t2) = 0

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 19 01.2008 Th. Connor PTD SE PTI
Intermittent earth fault

First earth fault


Recovery

Second earth fault

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 20 01.2008 Th. Connor PTD SE PTI
Ferro resonances

Prerequisite:
Circuit with non linear characteristic
e.g. saturation on reactance

Principle:
Driving voltage UN
From operational point 1 to point 2
But operational point 2 not stable
Current reversal to operational point 3

Types:
Nominal frequency, 3rd harmonic
Trigger: About 2nd harmonic
Switching events About 0.5 nominal frequency (subharmonic)

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 21 01.2008 Th. Connor PTD SE PTI
Ferro resonances

Example in three phase system:


Stable ferro resonance of 2nd harmonic level
No disturbance of phase to phase voltage URS

Possible configurations:
Single phase voltage transformer with bus bar or short cable
Energising reactor via short cable

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 22 01.2008 Th. Connor PTD SE PTI
Earth fault compensation

Petersen
coil Ires Ires - Residual current

Earth fault compensation

• Transient overvoltages kt ≤ 2.7


• Voltage rise of the fault-free phases cf ≤ 3
• Ires = f (Detuning, Harmonics, quality factor of the coil )
• Transient earth faults
• Operation under permanent earth fault possible
• Extinction limit

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 23 01.2008 Th. Connor PTD SE PTI
Fault current calculation
System with earth fault compensation

Positive sequence ~

Negative sequence

Zero sequence

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 24 01.2008 Th. Connor PTD SE PTI
Estimation of residual current

Line type Voltage level Residual current Ires

Overhead lines 110 kV approx. 5 % of ICE


20 kV approx. 8 % of ICE
10 kV approx. 8 % of ICE
i.e. 8 A per 100 A coil current

Cables 110 kV approx. 2 % of ICE


20 kV approx. 3 % of ICE
10 kV approx. 3 % of ICE
i.e. 3 A per 100 A coil current

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 25 01.2008 Th. Connor PTD SE PTI
Reappearing of phase voltage

Exact tuning v = 0

Tuning v = -10

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 26 01.2008 Th. Connor PTD SE PTI
Solid earthing

Ik1
Ik1 – short-circuit current

Solid earthing

y Transient overvoltages kt < 1.8


y Voltage rise of the fault-free phases cf ≤ 1.4
y Ik1 = f (Short-circuit capacity, zero-sequence impedance) Ik1 ~ Ik3
y Selective fault clearing

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 27 01.2008 Th. Connor PTD SE PTI
Fault current calculation
Solid earthing

Positive sequence ~

Negative sequence

Zero sequence

3 ⋅ UN
I k1 = 3I0 =
Z1 + Z2 + Z0

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 28 01.2008 Th. Connor PTD SE PTI
Vector diagram for system with solid earthing

UL1

UL1 = 0

UL2 UL2

Normal operation 1-phase short circuit

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 29 01.2008 Th. Connor PTD SE PTI
Examples for zero-sequence impedances of lines

Line type Voltage level Zero sequence Zero sequence


resistance R'0 reactance X'0

Overhead lines

110 kV 0.4 ... 0.2 Ω /km 1.0 ... 1.5 Ω /km


20 kV 0.6 ... 0.2 Ω /km 1.5 Ω /km
10 kV 0.6 ... 0.2 Ω /km 1.6 Ω /km

Cables

Oil cable 110 kV 0.8 ... 0.4 Ω /km 0.4 ... 0.2 Ω /km
XLPE cable 110 kV 0.6 ... 0.5 Ω /km 0.3 ... 0.2 Ω /km

Lead-sheath cable 20 kV 0.6 ... 0.4 Ω /km 0.4 ... 0.3 Ω /km
XLPE cable 20 kV 0.6 ... 0.4 Ω /km 0.3 ... 0.2 Ω /km

Lead-sheath cable 10 kV 2.0 ... 1.1 Ω /km 0.5 ... 0.2 Ω /km
XLPE cable 10 kV 3.2 ... 1.4 Ω /km 0.9 ... 0.3 Ω /km

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 30 01.2008 Th. Connor PTD SE PTI
Low-impedance neutral earthing

Ik1
Ik1 – 1-phase short-circuit current

Low-impedance neutral earthing

y Transient overvoltages for earthing via resistor kt ≤ 1.8


y Transient overvoltages for earthing via reactor kt ≤ 2.7
y Voltage rise of the fault-free phases cf ≤ 3
y Ik1 = f (Neutral impedance, fault location) Ik1 << Ik3
y Selective fault clearing

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 31 01.2008 Th. Connor PTD SE PTI
Fault current calculation
Low-impedance neutral earthing

Positive sequence ~

Negative sequence

Zero sequence

3 ⋅ UN
I k1 = 3I0 =
Z1 + Z2 + Z0

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 32 01.2008 Th. Connor PTD SE PTI
High-impedance neutral earthing

IF
IF - Earth fault
current
High-impedance neutral earthing

y Transient overvoltages kt ≤ 2.7


y Voltage rise of the fault-free phases cf ≤ 3
y IF = IR ≥ ICE
2 2
I +I
R CE

y Selective fault clearing possible

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 33 01.2008 Th. Connor PTD SE PTI
Fault current calculation
System with high-impedance neutral earthing

Positive sequence ~

Negative sequence

Zero sequence

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 34 01.2008 Th. Connor PTD SE PTI
Practical aspects

Methods applied

Criteria for comparison

High voltage systems

Medium voltage systems


Isolated neutral
Resonant grounding
Low impedance neutral grounding

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 35 01.2008 Th. Connor PTD SE PTI
Neutral earthing practice in Germany

380/220 kV Interconnected systems NE IK1 ≤ IK3

110 kV Regional systems EFC (Bavaria NG)


City system (cable) NE with limitation IK1 = 5 ... 10 kA

20 kV Regional & urban network EFC or EFC with SE


Urban cable network NE IK1 = 1.5 ... 2 kA

10 kV Small network IS ICE = 20 ... 100 A


Large network EFC or EFC with SE ICE ≤ 500 A
Urban cable network NE IK1 = 1 ... 2 kA

Industry Small systems IS ICE = 5 ... 30 A


5 ... 20 kV Large systems EFC ICE ≤ 300 A

NE = Low-impedance neutral earthing IS = Isolated neutral SE = Short time earthing EFC = Earth fault compensation

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 36 01.2008 Th. Connor PTD SE PTI
Criteria for comparison of methods

– Voltage stress

– Current stress
y Destruction at the fault location
y Potential rise
y Inductive interference; EMC

– Operational aspects
y Fault detection
y Fault localisation
y Amount of switching required
y Fail safe situation

– Investment costs

– Development in the future

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 37 01.2008 Th. Connor PTD SE PTI
Earth fault transients and voltage rise

Isolated neutral
Earth fault compensation

ICE = 100 A

Fault duration min ... h

Low-impedance neutral earthing

Ik1 = 1.5 kA Neutral resistor

Fault duration ms

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 38 01.2008 Th. Connor PTD SE PTI
Fault current and voltage rise during earth fault

U / ULE
1.8 3
IK1 / IK3
1.6

1.4

1.2 Voltages of the fault-free phases


U / ULE
1.0

0.8

0.6

0.4 Fault current


IK1 / IK3
0.2

0
0 2 4 6 8 10 ∞ Z0 / Z1

Solid Isolated neutral


Low-impedance Earth fault compensation
Effective neutral neutral earthing
earthing
High-impedance neutral earthing

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 39 01.2008 Th. Connor PTD SE PTI
Fault current and voltage rise during earth fault

N Neutral earthing with voltage


rise below 1.4
S Neutral earthing with voltage
rise exceeding 1.4
W Low impedance neutral
earthing
K Earth fault compensation
I Isolated neutral

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 40 01.2008 Th. Connor PTD SE PTI
Neutral earthing in high voltage networks

IK1 ≥ IK3

IK1< IK3

IK1< IK3

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 41 01.2008 Th. Connor PTD SE PTI
Required protection for transmission systems

Low-impedance neutral earthing (110 kV ... 380 kV)

Overhead line
Distance protection, Overcurrent protection (Back-up)
1-phase auto reclosure

Cable
Differential protection, Distance protection ,
Overcurrent protection (Back-up)

Earth fault compensation (110 kV)

Overhead line
Transient earth fault relay

Cable
-
For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 42 01.2008 Th. Connor PTD SE PTI
Operational aspects
System with isolated neutral

3I0A

3I0B
ICE

3I0C

3I0E

3I0D

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 43 01.2008 Th. Connor PTD SE PTI
Determination of zero sequence voltage

L1
L2
L3

UN
3

UL1 + UL2 + UL3 = 3 · U0


100V
3
58 V Normal operation
100 V Earth fault
3 U0

100V
Open delta winding 3

100 V Earth fault

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 44 01.2008 Th. Connor PTD SE PTI
Determination of earth fault current
Holmgreen

L1

L2

L3

IL1 + IL2 + IL3= 3 · I0 Relay

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 45 01.2008 Th. Connor PTD SE PTI
Operational aspects
System with earth fault compensation

Icoil

3I0A

3I0B
Ires

3I0C
3I0E
Icoil 3I0D

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 46 01.2008 Th. Connor PTD SE PTI
Petersen coil details

Type of coil Connection point to network neutral


Fixed coil • Feeding transformer

Tapped coil 1:3 • Neutral busbar

Plunger coil 1:10 • Earthing transformer

Plunger coil with controller

Location of coil in the network


Central compensation

Distributed coils in the network

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 47 01.2008 Th. Connor PTD SE PTI
Earth fault compensation
Types of Petersen coil

Plunger coils for medium voltage

Fixed coil for 110 kV

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 48 01.2008 Th. Connor PTD SE PTI
Tuning of Petersen coil

IE Earth fault current


in case of fault
Uneutral

Overhead line
Voltage of neutral point
in normal operation
Cable

under-compensated over-compensated tuning

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 49 01.2008 Th. Connor PTD SE PTI
Double earth fault current distribution

L3
L2
L1

L3
L2
L1

L3
L2
L1

3
IEE ≤ IK2 = 2
IK3

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 50 01.2008 Th. Connor PTD SE PTI
Directional earth fault relay

U0 U0

Ires

ICE ICE Icoil

Capacitive Wattmetric
directional earth fault relay directional earth fault relay

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 51 01.2008 Th. Connor PTD SE PTI
Required protection relays for earth fault detection

y Signalling relay for zero sequence voltage

y Central earth fault detection relay

y Directional earth fault relay

Overcurrent relay with directional earth fault relay


Distance relay with directional earth fault relay
Differential relay + Back-up overcurrent relay with directional earth fault relay

y Transient earth fault relay

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 52 01.2008 Th. Connor PTD SE PTI
Determination of residual current
Window type current transformer

3 · I0 = IL1 + IL2 + IL3

L1 L2 L3

I Fault I Sheath

I Earth

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 53 01.2008 Th. Connor PTD SE PTI
Transient earth fault relay

L1

L2

L3

t [ms]

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 54 01.2008 Th. Connor PTD SE PTI
Transient earth fault relay
Fault indication survey

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 55 01.2008 Th. Connor PTD SE PTI
Increase of residual current

3I0ZA 3I0ZA

3I0ZB 3I0ZA
IAdditional

Ires + IAdditional

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 56 01.2008 Th. Connor PTD SE PTI
Pulsating residual current

Icoil

ICE

Ires + IPulse

IPulse

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 57 01.2008 Th. Connor PTD SE PTI
Detection by 5th harmonic

ICoil

ICE

Ires

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 58 01.2008 Th. Connor PTD SE PTI
Combined method
Earth fault compensation with phase grounding

Icoil

3I0A

3I0B
Ires

3I0C
3I0E
Icoil 3I0D

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 59 01.2008 Th. Connor PTD SE PTI
Combined method
Earth fault compensation with phase grounding

3I0A

3I0B

3I0C
3I0E
Icoil 3I0D

Ires Icoil 3I0

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 60 01.2008 Th. Connor PTD SE PTI
Combined method
Earth fault compensation with phase grounding

L3
L2
L1
Load current

L3
L2
L1

L3
L2
L1

Induced loop current

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 61 01.2008 Th. Connor PTD SE PTI
Combined method
Residual current compensation

Icoil

3I0A

3I0B
Ires = 0

3I0C
3I0E
Icoil 3I0D

~
~
Ires

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 62 01.2008 Th. Connor PTD SE PTI
Earth fault trial in 20 kV network

System circuit 150 2

3I0 in A
110/20kV 0

0.40 0.45 0.50 0.55 t/sec.

Residual current

1.6

1.2
150 2 1 pu

3I0 in A 0.8

0
0.4

0.0
0.40 0.45 0.50 0.55 t/sec. 0 1 2 3 4 5 6 7 8 9 10 12 14
f/fg

3I0 in the feeding cable Harmonic analysis of residual current

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 63 01.2008 Th. Connor PTD SE PTI
Earth fault trial in compensated network
Voltages and current at the fault location

U [kV]

20 kV

110 kV

t [ms]

Ires

Ires [A]

Ires [A]

t [ms]

t [ms]

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 64 01.2008 Th. Connor PTD SE PTI
Operational aspects
System with low-impedance neutral earthing

3I0 = IK1

IK1

Ineutral

IK1 >> ICE

Fault current indicator

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 65 01.2008 Th. Connor PTD SE PTI
Comparison of neutral resistor and reactor

UR UR

US US

UT UT

IR IR

t t

Neutral resistor Neutral reactor

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 66 01.2008 Th. Connor PTD SE PTI
Short circuit trial
Voltages at medium- and low-voltage level
U [kV]

t [ms]

10 kV

U [V]

0.4 kV
t [ms]

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 67 01.2008 Th. Connor PTD SE PTI
Low-impedance neutral earthing
Design types of neutral resistors

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 68 01.2008 Th. Connor PTD SE PTI
Low-impedance neutral earthing
Connection possibilities for a neutral resistor

110 kV 110 kV 110 kV

10 (20) kV 10 (20) kV 10 (20) kV

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 69 01.2008 Th. Connor PTD SE PTI
Low-impedance neutral earthing
Design types of earthing transformers

Earthing transformer for 6 kV

Earthing transformer with increased


zero sequence impedance for 10 kV

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 70 01.2008 Th. Connor PTD SE PTI
Required protection for low-impedance neutral
earthing

y 3phase protection equipment necessary

• Overcurrent relay
sensitive earth fault detection 0.1 IN

• Distance protection
Overcurrent pick-up
Earth fault for loop selection
Impedance pick-up
in meshed networks

y Transformer differential protection


Suppression of neutral current

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 71 01.2008 Th. Connor PTD SE PTI
Test circuit for measurements

Current source
Remote station Feeding station

Test
voltage

Active power
Test
UE current

V
Sheath
current

Earth
current
Uind
Z0

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 72 01.2008 Th. Connor PTD SE PTI
Combined method
Short term neutral earthing for detection

Fault current indicator


IK1

Ires/ IK1/ Ires

Short term earthing for detection tSE < tprotection

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 73 01.2008 Th. Connor PTD SE PTI
Combined method
Reverse short term neutral earthing

Fault current indicator


IK1

IK1/ Ires

Short term earthing for detection tSE < tprotection

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 74 01.2008 Th. Connor PTD SE PTI
Combined method
Short term neutral earthing for trip

Fault current indicator


IK1

Ires/ IK1

Short term earthing for trip tSE > tprotection

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 75 01.2008 Th. Connor PTD SE PTI
Comparison of neutral earthing schemes
France - Germany

Cable system Overhead line system

France Germany France Germany

Ik1 max = 1000A


Ik1 max = 300A

Ik1 max = 2000A

Trip

For internal use only. / Copyright © Siemens AG 2008. All rights reserved.
Page 76 01.2008 Th. Connor PTD SE PTI