Site located 120Km east of Colombo in one of the most scenic areas in the hills
of sabaragamuwa. Namely Gadadessa Estate. (50Arcre)
Building
2 storied Resort Bungalow.
Height : 30ft
Structure : Wooden
Rooftop : Wood/Metal
Situation : Hill Top
Usage : Guest Bungalow/2 Luxury rooms, ONLY for the VVIP s
Item List
1. Solar Panel – 8 Nos
2. UNIRAC Solar Panel Mounting System.
3. PV Fuse Box (15 A)
4. DC Surge Protector – Delta Brand
5. Safety Switch – 30A 3Pole -Squre D – 2 Nos
6. Charge Controller – Out Back – FLEXmax 60
7. 2000VA /24V-230V Outback Inverter
8. 740Ah Battery Bank – 6V/370Ah 8nos- 4X2 Series Parallel combination
9. AC Out Distribution Box
10. 160A Merlin Gerin Breaker Switch
11. HRC Fuse 200A-2 Nos
12. Wires /Lugs /Conduits/casing/Silicone glue and other fixing accessories
Programmed for 24V DC system & Battery Bank Absorb Voltage set
point 29.6V/Float Voltage set point 27.6V
Installation
Panels Faced to South Side. Angle 10-15 degrees. For all joints/connections used
Stainless Steel / Galvanized Nut & Bolts. Used Waterproof Silicone for Roof Mounting L
Foot base.
Panel Mounting Brackets
Suggestion,
If panels directly mount to AL bar using
S/S nut and Bolts we can away from this
doubt.
2. Panel Wiring & Down Conductor
Used 4X2 method. Two sets of 4 panels. This 4 panel connected is Series And
parallel connected to other 4 panel set.
Down Conductor
Wire Size :Used 6mm2 two core copper wire and 6mm single core Standard
copper Earth wire
Wire Length : 22Meters*
*No any Joints
*40 A / 3.08Ohms per 1Km- Kelani Cable –Sri Lanka
4. Used Safety switches for Charge controller input side (6mm2 Wire 1.5Ft) & out put
Side(18mm2 Copper wire 6Ft).
• Safety Switch rated Ampere is 30A. For the Battery Bank Side interconnected
all 3 Poles for disconnect Positive Terminal. Negative terminal directly
interconnected(Battery Bank and Charge controller)
5. Battery Bank
6V/370Ah- 8 nos Flooded type Battery. Inverter Input Voltage is 24V so battery bank
also interconnected 4X2 method. Used 50mm2 wire and 50mm Lugs for interconnect
battery bank/HRC Fuse/Main Breaker and Inverter.
8. All Items are connected to the Wooden Sheet. And finally double checked all
Connections, Polarity, Eathing system (6mm Wire/6ft 1.5Dia GI Pipe) and others.