Estimate for Suplly, Installation, Testing & Commissioning of 320 KVA Sub-Station of Tongi Govt.

Colleg
Tongi, Gazipur-1711
LOCAL PART:
Sl Description Qty Unit

1 HT SWITCHGEAR (LBS): 1 Set


item no. 2.A.1(a), page no. 55
PWD Schedule of Rate 2018
for Electrical-Mechanical Works

2 300/315 KVA Oil type Distribution Transformer: 1 Set


3 Phase, 11/.4 KV,
item no. 2.A.5.6), page no. 56
PWD Schedule of Rate 2018
for Electrical-Mechanical Works
3 190 KVAr PFI Plant: 1 Set
item no. 2.A.8.5, page no. 57
PWD Schedule of Rate 2018
for Electrical-Mechanical Works
4 L.T. Switchgear for 300/315 KVA: 1 Set
Specification: 630 A MCCB
item no. 2.A.7.5, page no. 56 PWD Schedule of Rate 2018
for Electrical-Mechanical Works
5 HT Metering Unit: 1 Set
Specifications: Metering upto 3000KVA
item no. 2.A.9.0, page no. 56 PWD Schedule of Rate 2018
for Electrical-Mechanical Works
6 LIGHTNING ARRESTOR: 1 Set
item no. 2.A.10.1, page no. 57 PWD Schedule of Rate 2018
for Electrical-Mechanical Works
7 H.T. DROUP OUT FUSE: 1 Set
11 KV Dofc with rated fuse link for 3 phase, 3pcs/set
item no. 2.A.10.2, page no. 57 PWD Schedule of Rate 2018
for Electrical-Mechanical Works
8 IRON Channel 20 m
specification: HT cable MS channel rack.
item no. 2.A.11 page no. 57 PWD Schedule of Rate 2018
for Electrical-Mechanical Works
Installation Materials:

9 HT Switchgear 1 Set
With LBS
item no. 2.A.12.1 page no. 57 PWD Schedule of Rate 2018
for Electrical-Mechanical Works
10 HT Meter 1 Set
11KV meter intallation with all accessories
item no. 2.A.12.4 page no. 57 PWD Schedule of Rate 2018
for Electrical-Mechanical Works
11 Transformer on CC pad 1 pcs
11/.4 KV, 200-315 KVA, 3phase transformer intallation on CC pad
item no. 2.A.13.3 (c) page no. 58 PWD Schedule of Rate 2018
for Electrical-Mechanical Works
12 Installation of LT & PFI 1 set
200-400 KVA
item no. 2.A.14.2 page no. 58 PWD Schedule of Rate 2018
for Electrical-Mechanical Works
13 Installation of DoFC /LA
Drop Out Fuse, item no. 2.A.15.1 3 set
Lightening Arrester, Item no.2.A.15.2 1 set
page no. 58 PWD Schedule of Rate 2018
for Electrical-Mechanical Works
14 HT Cable (XLPE) 30 m
3C X 120sq mm XLPE cable, In pucca ground/ pucca road
item no. 1.5.6 (b) page no. 52 PWD Schedule of Rate 2018
for Electrical-Mechanical Works
15 Installation of on Grid Solar-Panel 3 KW
5KW ongrid solar -panel supply and Installation including all accessories
item no. 12.4 page no. 105 PWD Schedule of Rate 2018
for Electrical-Mechanical Works
16 LT Cable (PVC) 100 m
1C-4 X 70sq mm NYY cable, In pucca floor
item no. 1.3.15 (ii) page no. 48 PWD Schedule of Rate 2018
for Electrical-Mechanical Works
17 LT Cable (PVC) 25 m
1C-4 X 95sq mm NYY cable, In pucca floor
item no. 1.3.16 (ii) page no. 48 PWD Schedule of Rate 2018
for Electrical-Mechanical Works
18 Supply & Installation of Emergency Diesel Generator With ATS 1 Set
10 KVA Diesel Generator, made in USA/Japan
item no. 2B.3(a).1 page no. 48 PWD Schedule of Rate 2018
for Electrical-Mechanical Works
19 Necessary Civil Works 1 L.S
300/315 KVA transformer, 10KV Generator, HT switch gear, LT switch
gear, PFI panel Foundation preparation including Earthing works and
necessary civil works as per direction of engineering Incharge
VA Sub-Station of Tongi Govt. College,

Unit Price Total


in Tk in Tk
348,499.40 348,499.40

850,646.45 850,646.45

284,595.27 284,595.27

303,069.21 303,069.21

312,125.06 312,125.06

15,093.09 15,093.09

30,789.90 30,789.90

724.47 14,489.40

6,701.33 6,701.33
8,457.13 8,457.13

5,044.47 5,044.47

4367.46 4,367.46

724.27 2,172.81
724.27 724.27

7134.00 214,020.00

132725.00 398,175.00

5078.00 507,800.00

6832.00 170,800.00

882750.00 882,750.00

250000.00 250,000.00
4,610,320.25
TECHNICAL SPECIFICATIONS FOR 11KV HT PANEL WITH LBS

HT SWITCHGEAR :Type: LBS/FN7


Origin: F&G/German.
Supply of sheet steel clad, dust and vermin proof , floor mounting, indoor type, factory
assembled according to IEC298/694 and VDE 0670.11KV, 3-Phase, 630A,50Hz, 20KA
(Breaking Capacity) safe to touch and hermitically sealed, Air Insulated switchgear
as per technical specification and drawings complete with 630 A, TP Hard Drawn Copper Bar.
diagram on the doors, isolator & circuit breaker position indicators, all internal wiring
and comprising of three LBS panel. The HT switchgear must comply with the upto-date
requirements of DESA. The rate includes supply of all consumable including termination
kit, Elastomould etc. for termination of cables (3c-185 mm2 PVC/XLPE insulated) to
LBS of the HT Switchgear.

1 No. Incoming feeder shall be equipped with the following:


1 No. 630A, 11KV, 50HZ, 20KA (3 sec), triple pole, completely maintenance free
neither greasing nor adjustment will be required) fixed type Load Break Switch(LBS)
On/OFF indicators, Auto Trippins System etc.Origin : F&G / Germany

2 Nos. 11KV cast resin insulated, single pole potential transformer having ratio 11000:√3 V/
110:√3 V , class 0.5, burden 50VA each for metering and protection. Origin: Siemens / Germany.

1 No. TP MCB for PT secondary protection.


3 Nos. of cast resin insulated 11 KV double core current transformer having ratio 30/5A
Core 1: 15 VA, Class 0.5M5 for Metering
1 No. of 0-15KV voltmeter with selector switch
1 No. of 0-30A Ammeter with selector switch

1 No. Operating handle


2 x Panel heater.

1 x Set TP Busbar suitably sized and insulated.

TECHNICAL OF 300/315 kVA OIL IMMERSED TRANSFORMER: 1 SET

Three phase transformer, Step down Type with normal Accessories. Indoor on ONAN Type, Natural
Cooling, Oil Immersed. Design, manufacturing, routine tests & tolerances according to IEC 726, IEC76
and NFC92100 (Normal Test). Design, manufacturing, routine tests & tolerances according to IEC 76
& 726 standards.
Painting are in accordance with International Standard.

Standard Accessories:-
Lifting lugs.
Earthing terminals.
rating plate (on HV side).
Temperature Meter
Oil Level Indication
Drane Vulbe
Oil Conservator
Tap Changer

Terminations:-

HV = Connection from top onto flat bar terminals.


LV = Connection from top onto flat bar terminals.

Rated power in KVA: 500


Frequency 50 Hz
High voltage 11 KV
HV tapping by links (off-circuit) in: +/-2.5%,+-5%
LV in volts: 415V
HV insulation level in KV: 12
HV impulse KV peak in KV: 75
Power frequency KV rms: 28
Vector group: DYN11
Max. Ambient temp.in Deg.C.: 45
Winding Temperature rise Deg.K: 100
Altitude lower than in meter: 1000
No load loss: 680Watt
Load loss at 120 Deg.C: 4200Watt
Impedence voltage at.75 Deg.C: 4%
Winding material (HV/LV): Cu/Cu

Routine Tests:

* Applied voltage dielectric Test (50Hz-mm)


* Oil Test
* Mesurement Of:
# no load loses and no load current
# MV & LV winding resistance
# impedance voltage and load loses
# The transformer ration & vector group.

Brand of Materials:
Silicon Core: Nippon, Japan
Winding Copper: BRB, Banglasesh
Insulation Oil: Sovita, India.
Lather Paper: Volt Amp, India
Lather Board: Volt Amp, India
Tap Changer: ABB, Italy.
Origin: GEM Plant/Bangladesh

190 kVAr AUTO / MANUAL PFI PLANT: 1 SET

Automatic power factor improvement plant, 300 KVAR in 8 steps sheet steel fabricated, floor mounting,
tropicalised design indoor type, low tension switchgear for 3 phase, 4 wire, 50 Hz 380 /415V AC system and
shall be supplied complete with TP + N Busbars suitably sized and properly insulated arrange to withstand
and short circuit current of 50KA for 1 sec.

The boards are designed & constructed in accordance with BS5486/ IEC 439.

Busbars & other live parts are spaced & insulated in accordance with European standards IEC 158,UTE
C20-040,VDE-C 110 for 660V.
The boards are factories assembled complete with all wiring, metal parts bonded ground points and finished
with two coats of antirust paint.
The panel shall fully comply regulations of the 15th edition IEE wiring regulation for isolation & switching.

The panel comprising of


1 x 12.5 kVAr (Fixed),415V,50 Hz, 3 phase, dry type, self healing compact PF capacitors bank with discharge
rsistor(fixed), ZEZ SILKO /Czech Republic.Product: Made in Germany.
3 x 60A,HRC fuse with base as required.

1 x 12.5 KVAR ,415V,50 Hz, 3 phase, dry type, self healing compact PF capacitors bank with discharge
rsistor(fixed), ZEZ SILKO /Czech Republic.Product: Made in Germany.
1 x NC1-3201, triple phase air contactor for 12.5 KVAR capacitor. Chint.
3 x 60A,HRC fuse with base as required.

2 x 25kVAr (Fixed),415V,50 Hz, 3 phase, dry type, self healing compact PF capacitors bank with discharge
rsistor(fixed), ZEZ SILKO /Czech Republic.Product: Made in Germany.
2 x NC1-6511, triple phase air contactor for 25 KVAR capacitor. Chint
6 x 80A,HRC fuse with base as required.

2 x 37.5kVAr (Fixed),415V,50 Hz, 3 phase, dry type, self healing compact PF capacitors bank with discharge
rsistor(fixed), ZEZ SILKO /Czech Republic.Product: Made in Germany.
2 x NC1-6511, triple phase air contactor for 37.5 KVAR capacitor. Chint
6 x 100A,HRC fuse with base as required.

3 x 50kVAr (Fixed),415V,50 Hz, 3 phase, dry type, self healing compact PF capacitors bank with discharge
rsistor(fixed), ZEZ SILKO /Czech Republic.Product: Made in Germany.
6 x NC1-6511, triple phase air contactor for 25 KVAR capacitor. Chint
9 x 120A,HRC fuse with base as required.

8 x Start pushbutton as required.


Telemecanique of France.
8 x Stop pushbutton as required.
Telemecanique of France.
1 x Auto/manual selector switch with adder block. Telemecanique of France.
4 x CA2-DN22 Control relay. Telemecanique of France.

1 x LAl-DN22 2NO+2NC auxiliary contact block. Telemecanique of France.


8 x XB2-EV163 Indicating lamp.Telemecanique of France.
3 x Fuse carrier with fuse for control circuit.

1 x 8 steps reactive power regulator which performs the switching of capacitor bank in automatic power factor
correction equipments depending on charges of reactive power complete with p.f.luminecent indicators &
digital power factor meter.Mikro/D-Lab/Malaysia

Features of PFC Controllers:-


1) Automatic Programming
2) Display of V, I, f, Q, P, S, CosΦ
3) Display of all odd Harmonics of 1 to 19 Current & Voltage values.
4) Display of capacitor current.
5) Display of switching operations per capacitor stage
6) Display of total on time of each capacitor stage.
7) No-volt release within 20ms
8) Degree of detuning programmable for each stage from 0 to 20%
9) Setting of discharge time for all capacitor stages.
10) Individual programming of Capacitor power.
11) Current Transformer input for ../1A, ../5A
12) Password Protection
13) Externally switching target CosΦ
14) Alarm output programmable for
: Under Voltage detection
: Over Voltage Protection
: Low measurement current
: exceeded measurement current
: insufficient capacitor output
: harmonics limits
: Over temperature.

LT SWITCHGEAR 630A MCCB: 1 SET


Sheet steel fabricated, floor mounting, tropicalised design, indoor type, low tension switchgear for
800 Amp, 3 phase, 4 wire, 50 Hz, 380/415V AC system and shall be supplied complete with 1000A
TPN+PE Busbar suitably sized & properly insulated arrange to withstand & short circuit current of
50KA for 1 sec.
The boards are designed & constructed in accordance with BS 5486/IEC 439.

Busbar & other live parts are spaced & insulated in accordance with European standards IEC 158,
UTE C20-040, VDE-C 110 for 660V.
All MCCB units & panel boards shall fully comply regulations of the 15th edition IEE wiring regulation
for isolation & switching.
INCOMING:

The Panel comprising of


Incoming:

1 x 630A,50KA,414V,50Hz,3P,Moulded Case Circuit Breaker (MCCB) Complete with thermal Overload


and Magnetic short circuit and release protection.Origin: Chint

4 x Current transformer ratio: 800/5A with suitable accuracy and burden.

1 x Ammeter scaled (0-800A) with selector switch.

1 x Voltmeter scaled (0-600V) with selector switch.

3 x Phase indicating lamp RED/YELLOW/BLUE.


1 x Set Modular Fuse with Control wirings.

OUTGOING

7 x 160A TP MCCB, Chint.

(ALL MCCB’ s are thermal overload and magnetic short circuit protection)

TECHNICAL SPECIFACTION DROPOUT FUSE


Rated Voltage (Normal): 11 kV
Rated Voltage (Max): 15 kV
Rated Frequency: 50 Hz
BIL: 75 kV
Rated Current (rms): 100 Amps
Interrupting Current (rms): 10 kA
Withstand Test Voltage :
·        Dry, 1 Min: 35 kV
·        Wet, 10 Sec.: 30 kV

Origin: Korea/Brazil

TECHNICAL SPECIFICATIONS LIGHTNING ARRESTOR

Rated Voltage (RMSl): 11 kV


Rated SystemVoltage: 12 kV
Rated Frequency: 50 Hz
Minimum Spark Over(RMS): 14KV
Maximum Spark Over(RMS): 40KV
Maximum Impulse Spark (Crest): 45KV
Withstand Test Voltage:
·        Dry, 1 Min: 28 kV
·        Wet , 10 Sec: 24 kV
Discharge 33KV (Crest): 5KV
Impulse Current Withstand: 55KA

Origin: Korea/Brazil

INSTALLATION,TESTING & COMMISSIONING OF SUBSTATION EQUIPMENTS:


Installation, testing and commissioning of 500kVA transformer excluding supply of consumables like
Angle frame
Cable support
U channels
Foundation nuts, bolts, etc. and
Performing oil test

LT Swtichgear:
Installation, testing and commissioning of 415 Volt LT pannel excluding supply of consumables like
Angle frame
Cable support
Control cable
U-channels
Foundation nuts, bolts, etc.

PFI plant:
Installation, testing and commissioning of 300 KVAR PFI plant excluding supply of consumables like
Angle frame
Control cable
U-channels
Foundation nuts, bolts, etc.

Earthing:
Supply, installation, testing and commissioning of copper earthing block with required
Nos. of ¼” hole for ECC connection. Size 254mm x 40mm x 10mm.

Earthing lead:
Supply, installation of earthing lead, 1x4/0 SWG copper wire through 1'' dia GI pipe from earthing
block to earth electrode including inter connection between two electrodes.

Earthing lead by insulated cable:


Supply installation of single core 95rm PVC insulated cable as earthing lead from transformer neutral
in the earth electrode.

Earthing continuity conductor:


Supply, installation of 25WG copper earth continuity conductor running from the bodies of substation
equipment to the earthing block.

Earth electrode:
Supply, installation of 1” dia GI pipe having 1” hole at 4 interval buried upto the depth of 100’-0”
(with connecting copper link) in the damp soil including 4x4 SWG copper wire from bottom of GI
pipe upto connecting link.

Earthing inspection PIT:


Constriction of 1 ½” x 1 ½” x 1 ½” earth inspection Pit of 5” Sit class brick wall of both side plastering
including 3” thick CC cover 3” thick brick flat soling 2 ½” thick RCC slab with ½” dia M.S lifting hook.

TECHNICAL SPECIFICATIONS OF EMERGENCY GENERATOR

GENERATOR OUTPUT 10KVA


GENERATING VOLTAGE 380-415 VOLT
FREQUENCY 50HZ
TYPE: 4 POLE, ROTATING FIELD
INSULATION: CLASS H
TEMPERATURE RISE 125 DEG C (CLASS H)
COUPLING: FLEXIBLE DICS CLOSE COUPLE
UNBALACE LOAD CAPACITY:25% OF RATED CURRENT
EXITING TYPE: BRUSHLESS