Item Description Unit Total Quantity 3x7.5 MVA

LOT1

SUBSTATION
POWER TRANSFORMER, step down 7500 KVA, 33/11.55KV, DYN 11
ONAN /ONAF& 3 Phase 50 Hz, oil immersed, core type, With CTs, furnished
1 Lot 3
with Off-Load, Tap changer + 5% in steps of 4x+ 1.25 % Altitude- from sea
level 2300M.
Suspstation Equimpent, with 4 feeders 400 Amp each - R.H. 80% ref. cont.
2 Lot 3
from item 1.1 to Item 13 Suspstation Equimeptn.
3 Spare for items (1 + 2) (ref. cont. from Item No. 1 to 13. Lot 3
4 Building (2 Room + Toilet) Lot 3
Cost Of Inspection Company &2 PARE Engineers
1 INSULATORS & INSULATOR FITTINGS
1.1 33 kV INSULATOR STRING , COMPRISING : sets 3 9
A. BALL ENDED STRUCTURE ATTACHMENT
B. SUSPENSION INSULATOR, ANSI 52-3 [4 PCS]
C. SOCKET EYE
D. STRAIN CLAMP FOR 170mm sq. ACSR
1.2 11 KV MAIN BUS BAR INSULATOR STRING sets 6 18
A. EYE ENDED STRUCTURE ATTACHMENT
B. SUSPENSION INSULATOR, ANSI 52-1 [3PCS]
C. STRAIN CLAMP FOR 170 - 185 mm. sq. Al.
1.3 11 KV FEEDER INSULATOR STRING sets 12 36
A. EYE ENDED STRUCTURE ATTACHMENT
B. SUSPENSION INSULATOR, ANSI 52-1 [3 PC]
C. STRAIN CLAMP FOR 100 mm sq. ACSR
1.4 11 KV NEUTRAL STRING, COMPRISING: sets 6 18
A. EYE ENDED STRUCTURE ATTACHMENT
B. SUSPENSION INSULATOR, ANSI 52-1 [1PC]
C. STRAIN CLAMP
1.5 SHIELD WIRE STRING, COMPRISING: sets 5 15
A. EYE ENDED STRUCTURE ATTACHMENT
B. STRAIN CLAMP
1.6 33 KV BUS SUPPORT INSULATOR sets 3 9
A. STATION POST INSULATOR, 33 KV
B. AL. ALLOY BUS SUPPORT W/ MOUNTING HARDWARE
1.7 11 KV BUS SUPPORT INSULATOR sets 6 18
A. STATION POST INSULATOR, 11 KV as
B. AL. ALLOY BUS SUPPORT W/ MOUNTING HARDWARE requir
as as required
C. CU BUS SUPPORT W/ MOUNTING HARDWARE ed
requir as required
2 SURGE ARRESTERS: ed

2.1 36 KV SURGE ARRESTER INTERMEDIATE CLASS PCS 3 9


2.2 12 KV SURGE ARRESTER, INTERMEDIATE CLASS PCS 3 9

1
12KV SURGE ARRESTER, DISTRIBUTION CLASS with isolate mounting
2.3 PCS 12 36
base / without mounting bracket
3 MEDIUM VOLTAGE SWITCHES & FUSES
3.1 34.5 KV GROUP OPERATED AIR BREAK SWITCHES, 3 Poles PCS 1 3
3.1a MOUNTING PEDESTAL FOR 34.5 KV AIR BREAK SWITCH PCS 1 3
3.2 34.5 KV, 16 KA BREAKING CAPACITY POWER FUSE c/w connectors PCS 3 9
3.2a FUSE UNIT FOR 34.5 KV POWER FUSE PCS 3 9
SINGLE PHASE VOLTAGE REGULATOR BY-PASS SWITCH, 400A,
3.3 PCS 3 9
15 KV WITH MOUNTING BRACKET
SINGLE PHASE HOOK STICK OPERATED DISCONNECT SWITCH,
3.4 PCS 30 90
600A, 15KV, W/MOUNTING BRACKET
SINGLE PHASE HOOK STICK OPERATED DISCONNECT SWITCH,
3.5 600A, 15KV, FOR TRANSFORMER RECLOSER BYPASS, WITH PCS 3 9
MOUNTING BRACKET
15KV SINGLE PHASE FUSE CUTOUT, 100 A 12 KV INTERRUPTING
3.6 PCS 4 12
CAPACITY, C/W MOUNT BRACKET
3.7 6 A FUSE LINK, TYPE K PCS 9 27
3.7a 1 A FUSE LINK, TYPE K PCS 3 9
4 VOLTAGE REGULATORS
VR-32 6600V, 50Hz, c/w CL-5C control with 1RCT on backpanel, elevating
4.1 0
structure 27-43" height for 35" thru 38" diameter tank, unassembled.
4.1a Elevating structure 27-43" height for 35" thru 38" diameter tank, unassembled. 0
5 SUBSTAION RECLOUSERS:
5.1 Main Reclouser Equipped With PCS 1 3
a Electronic Over current trip
b Electronic groud trip
c Fast Operation module
d S/S Mounting Farme
5.2 Feeders Reclouser Equipped With PCS 4 12
a Electronic Over current trip
b Electronic groud trip
c Fast Operation module
d S/S Mounting Farme
6 SUBSTATION AUXLIARY EQUIPMENT
6.1 50KVA ,50HZ 33/0.4KV,170KV BIL ,3-PH,Transformer PCS 1 3
INSULATOR LEVEL 15/34/11 KV ,MIN.CREEPAGE DISTACE
6.2 820MM,VOLTAGE TRANSFORMER 6350 /230 V SINGLE PHASE PCS 3 9
POTENTIAL TRANSFORMER
6.3 STRUCTURE MOUNTED, OUTDOOR Mercury LUMINAIRE, 250W PCS 6 18
STRUCTURE MOUNTED, OUTDOOR POWER SOCKET OUTLET WITH
6.4 MATCHING PLUG, 250V, 15A MOUNTED ON LUMINAIRE Set 4 12
STRUCTURE
POWER AND LIGHTING WEATHER PROOF CABINET
6.5 PCS 1 3
INCORPORATING LIGHTING & PHOTOCELL CONTROL
6.6 11kv CAPACITOR BANK 450KVAR COMPLETE Set 1 3
7 SUBSTATION METERING
7.1 COMBINED TRANSFORMER & FEEDER METERING CABINET PCS 1 3
8 CONDUCTORS & WIRES
Meter
8.1 400 A CAPACITY AL. CONDUCTOR FOR 11KV MAIN BUS BAR 250 750
s
8.2 HARD DRAWN COPPER CONDUCTOR FOR 11 KV CONNECTIONS, Meter 500 1500
NEUTRAL BUS- BAR AND SUBSTATION GROUNDING s

2
Meter
8.3 L.V. insulated stranded copper wire 20 60
s
Meter
8.4 L.V. insulated solid copper wire as follows: 400 1200
s
8.5 Black 200 600
8.6 white 200 600
Meter
8.7 Control Cable 6 core for CT's & PT's 150 450
s
Meter
8.8 Steel shield wire 50 150
s
Meter
8.9 Hard Drawn Copper for S/S Grounding 100 300
s
Meter
8.1 Rigid 1/2" copper 20 60
s
9 CONNECTOR & CONDUCTOR ACCESSORIES
9.1 Ground rod, 2.4 m x 16 mm, heavy copper bonded to a rigid steel core PCS 25 75
9.2 Bolted ground connector, 2x95 mm2 copper conductors to flat PCS 29 87
9.3 Bolted ground connector, 95 mm2 copper conductors to flat PCS 40 120
9.4 Parallel clamp for 2x95 mm2 copper conductors PCS 15 45
9.5 Parallel clamp for 95 mm2 and 50 mm2 copper conductors PCS 20 60
9.6 Parallel clamp for 95 mm2 copper and 50 mm2 steel conductors PCS 5 15
9.7 Ground clamp, for 50 mm2 copper to fence post PCS 4 12
9.8 Ground clamp, for 50 mm2 copper to fence post - gate PCS 4 12
9.9 Ground clamp, for 50 mm2 copper to fence post - corner PCS 5 15
9.10 Ground clamp, for 50 mm2 flexible copper straps to gate post PCS 4 12
9.11 Ground clamp, for 50 mm2 flexible copper straps to fence post PCS 4 12
9.12 Flexible copper straps, 50 mm2 and 24” (600mm) long PCS 4 12
Tinned split bolts, strands of 50 mm2 copper conductor to fence fabric or
9.13 PCS 150 450
barbed wire
Ground clamp, for 95 mm2 stranded copper conductor and steel ground pad
9.14 PCS 3 9
0.5”-13 UNC tapped holes .75” deep
9.15 Ground cable lug, for 95 mm2 stranded copper conductor to M12 bolt PCS 5 15
9.16 Handle Clamp PCS 1 3
Mold, for connection copper conductor 95 mm2 to copper clad grounding
9.17 PCS 1 3
rod dia 16 mm,
9.18 Weldmetal for GTC-95-16 PCS 25 75
9.19 Mold, for connection copper conductor 95 mm2 to copper conductor 95 mm2 PCS
9.20 Weldmetal for XAC-95.95 PCS
Mold, for connection run copper conductor 95 mm2 to tap copper conductor 95
9.21 PCS 1 3
mm2,
9.22 Weldmetal for TAC-95.95 PCS 59 177
9.23 Mold, for connection run copper conductor 95 mm2 to tap conductor 50mm2 PCS 1 3
9.2 Weldmetal for TAC-95.50 PCS 18 54
9.25 Toolset (gloves, flint ignitor with spare flints and brushes) Set 1 3
9.26 Ground clamp, for 50 mm2 copper to 2” steel tube PCS 4 12
10 CONNECTOR & CONDUCTOR ACCESSORIES
Aluminium compression or bolted tee, 157.90 mm2 AAAC to 157.90 mm2
10.1 PCS 18 54
AAAC
Aluminium compression or bolted tee, 170 mm2 ACSR to 157.90 mm2
10.2 PCS 3 9
AAAC
10.3 Parallel groove bolted clamp, 13 mm2 Cu to 100 mm2 ACSR PCS 12 36
10.4 Cable lug, for 50 mm2 stranded copper conductor to M12 bolt PCS 3 9
10.5 Aluminium compression or bolted tee, 157.90 mm2 AAC to 50 mm2 Copper PCS 4 12
10.6 Bronze compression or bolted tee, 95 mm2 copper to 95 mm2 copper PCS 6 18
11 MISC. INSTALLATION MATERIALS
11.1 Intermediate metallic conduit – IMC with ¾” diameter meters 210 630
11.2 Galvanized bushing with locknuts PCS 23 69
11.3 Condulets, for IMC with ¾” diameter,with covers and gaskets Type “T” PCS 5 15

3
11.4 Condulets, for IMC with ¾” diameter,with covers and gaskets Type “C” PCS 3 9
11.5 Condulets, for IMC with ¾” diameter,with covers and gaskets Type “X” PCS 1 3
11.6 Clamp/support for intermediate metallic conduit ¾” with screw PCS 40 120
11.7 Coupling for IMC with ¾” diameter PCS 39 117
11.8 Watertight service entries for IMC with ¾” diameter PCS 1 3
11.9 Terminal Strips for up to 35 mmsq Cu. Wire PCS 100 300
11.10 Electrical joint compound PCS 1 3
11.11 Intermediate metallic conduit – IMC with 1-1/2" diameter, L=1.75 meters meters 1 3
11.12 Service entrance fitting, 1-1/2” IPS PCS 1 3
11.13 Watertight service entries, for 1-1/2” IPS - Cable outlet bushing PCS 1 3

11.14 Intermediate metallic conduit – IMC with ¾” diameter and treaded on both PCS
ends length 1 m
11.15 Cover bushing for item 12.15 PCS 6 18
12 STEEL STRUCTURES:
STEEL STRUCTURE FOR SUBSTATION GANTRIES tons 9 27
13 OTHER WORKS SUPPLIES AND SERVICES :
13.1 FENCING MATERIALS (30 x 11 meters) lot 1 3
13.2 DESIGN lot 1 3
14 Transformer Spares
14.1 Primary Bushing PCS 1 3
14.2 Secondary Bushing PCS 1 3
14.3 Secondary Bushing CT PCS 1 3
14.4 Packing / Gasket set PCS 1 3
14.5 Dial Thermometer PCS 1 3
14.6 Dial Oil Guage PCS 1 3
14.7 Touch up paint littre 1 3
15 Substation Spares
15.1 Suspension insulator, ANSI 52-3 PCS 3 9
15.2 Suspension Insulator - ANSI 52-1 PCS 6 18
15.3 33 kV Station Post Insulator PCS 1 3
15.4 11 kV Station Post Insulator PCS 3 9
15.5 Spare insulator for 3 phase disconnect switch (Item 3.1) PCS 1 3
15.6 Spare set of fixed and moving contacts for Overhead switch (Item 3.1) PCS 1 3
15.7 Spare fuse for power fuse switch (item 3.2) PCS 3 9
15.8 Spare insulators for VR bypass switch (item 3.3) PCS 2 6
15.9 Lower contact Assembly for item 3.3 - PCS 1 3
15.10 Upper contact Assembly for item 3.3 PCS 1 3
15.10a Upper contact Assembly for item 3.3 PCS 1 3
15.11 Spare insulator for single phase disconnect switch (item 3.4) PCS 2 6
15.12 Spare set of fixed and moving contacts for item 3.4 PCS 2 6
15.13 Spare insulator for item 3.4 PCS 1 3
15.14 Spare set of fixed and moving contacts for item 3.4 PCS 1 3
15.15 Spares for 11 KV fuse link
a 6 Amp type K Fuse Link PCS 11 33
b 1 amp type K Fuse Link PCS 7 21
15.16 Voltage Regulator Spares
a.1 Bushing Assembly for voltage regulator (VR) item 4.1 - PCS 1 3

4
a.2 Bushing Hardware package - PCS 1 3
a.3 Bushing Hardware package - PCS 1 3
b Series arrester for VR - PCS 1 3
c Shunt arrester for VR - PCS 1 3
d.1 Lid cover seal for VR - PCS 1 3
d.2 Hand hole cover seal for VR - PCS 1 3
e Reverse moveable contact for VR - PCS 1 3
f Right Reverse Stationary moveable contact for VR - PCS 1 3
g Left Reverse Stationary moveable contact for VR - PCS 1 3
h Main stationary contact for VR - PCS 1 3
i&j Left and Right Main stationary contact for VR - PCS 1 3
k Motor Capacitor for VR - PCS 1 3
1.1 Set of fuses for control for VR - PCS 1 3
1.2 Fuses for Control PCS 2 6