Central Engineering Consultancy Bureau

Defence Headquarters Building Complex


MEPI Division

Tel: 0112786560 Fax: 0112054332

Email: …………………………………………………….

Internal Memorandum
To : Archt. W. M. N. P. Weerasinghe Date : 02nd February, 2016
Director - Architectural Services
Copy : - Ref : MEPI-B6-MVAC-244
From : Senior Consultant (Building Services)
Block No.: 6 Level : From LL3 to Roof Level
Subject : Specifications for the doors

Attachments: -

This has reference to your letter DHQC/CECB/ARCHI/MEPI/221216/003 dated 22 nd December, 2016.


We have following comments on the specifications of the doors.

1. Fire resistance rating of 60 minutes is acceptable for the AHU rooms. Same fire resistance rating is
recommended for the chiller plant room door LL3-06-43-D04.
2. We recommend an acoustic rating of Rw 45dB for the following MVAC plant room doors.
(i) Doors of all AHU rooms from LL3 to Roof Level
(ii) Chiller plant room door (Door No. LL3-06-43-D04)
3. Ventilation requirements
(i) Louvered doors for toilet blocks, draught lobbies, directors’ toilets, disabled persons’ toilets,
pantries and janitors rooms, satisfy the ventilation requirements, considering that 50% of the
louvered area is available for ventilation.
(ii) Toilet cubicle doors with 100mm undercut satisfy the ventilation requirements of the areas
concerned.
(iii) There are some rooms (rack unit rooms, store rooms, record rooms, etc.) for which ventilation
to be provided through louvered doors. Please provide louvered doors for the rooms given in
the following table.

Page 1 of 4
MEPI-B6-MVAC-244

FLOOR ROOM NO: ROOM NAME & LOCATION (GRID NOS.) DOOR NO:
6TH-06-01a Rack Unit Room 6TH-06-01a-D-01
6   Record Room / 50-Ne  
6TH-06-06c Rack Unit Room 6TH-06-06c-D-01
5TH-06-01a Rack Unit Room 5TH-06-01a-D-01
  Store Room / 46-Ne  
5   Record Room / 46-Ne  
  Store Room / 53-Nb  
5TH-06-09b Rack Unit Room 5TH-06-09b-D-01
4TH-06-01a Rack Unit Room 4TH-06-01a-D-01
  Record Room / 46-Ne  
  Record Room / 50-Ne  
  Store Room / 45-Ne  
4
  Store Room / 51-Ne  
  Store Room / 53-Nb  
  Store Room / 53-Mc  
4TH-06-13a Rack Unit Room 4TH-06-13a-D-01
3RD-06-01a Rack Unit Room 3RD-06-01a-D-01
  Record Room / 46-Ne  
3
  Store Room / 53-Nb  
3RD-06-11b Rack Unit Room 3RD-06-11b-D-01
2ND-06-01a Rack Unit Room 2ND-06-01a-D-01
  Store Room / 46-Ne  
  Record Room / 46-Ne  
2
  Store Room / 53-Nb  
2ND-06-10b Rack Unit Room 2ND-06-10b-D-01
  CC / 51-Ne  
1ST-06-01a Rack Unit Room 1ST-06-01a-D-01
  G2 / 46-Ne  
1   G2 / 46-Ne  
  Store Room / 53-Nb  
1ST-06-10b Rack Unit Room 1ST-06-10b-D-01
0GF-06-05b Rack Unit Room 0GF-06-05b-D-01
0GF-06-05a / 47-Ne 0GF-06-05a-D-01
GF   Store Room / 53-Nb  
  Store Room / 53-Mc  
0GF-06-14a Rack Unit Room 0GF-06-14a-D-01

Page 1 of 4
MEPI-B6-MVAC-244

FLOOR ROOM NO: ROOM NAME & LOCATION (GRID NOS.) DOOR NO:
LL1-06-01a Rack Unit Room LL1-06-01a-D-01
  Store Room / 46-Ne  
  CC / 46-Ne  
LL1 LL1-06-65b Rack Unit Room LL1-06-65b-D-01
LL1-06-53 RaAncillary Room LL1-06-53-D-01
LL1-06-6a   LL1-06-6a-D-01
LL1-06-25a Rack Unit Room LL1-06-25a-D-01
LL2-06-01a Rack Unit Room LL2-06-01a-D-01
  G2 / 46-Ne  
  CC / 46-Ne  
LL2 LL2-06-65b Rack Unit Room LL2-06-65b-D-01
LL2-06-64a Rack Unit Room LL2-06-64a-D-01
LL2-06-10e Rack Unit Room LL2-06-10e-D-01
LL2-06-26 Rack Unit Room LL2-06-26-D-01
LL3-06-15 Rack Unit Room LL3-06-15-D-01
LL3 LL3-06-14 Utility Storage LL3-06-14-D-01
LL3-06-18 Janitor's Cleaning Storage LL3-06-18-D-01

…………………………………..

Eng. C. K. B. Dissanayake
Senior Consultant (Building Services)

AM