Sie sind auf Seite 1von 5

24th International Conference & Exhibition on Electricity Distribution (CIRED)

12-15 June 2017

Session 2: Power quality and electromagnetic compatibility

Influence of grounding transformer on


ground fault current in MV networks
ISSN 2515-0855
doi: 10.1049/oap-cired.2017.0653
Hrvoje Opačak ✉, Tihomir Čalic´, Siniša Jergovic´ www.ietdl.org

HEP ODS, Zagreb, Croatia


✉ E-mail: hrvoje.opacak@hep.hr

Abstract: Medium voltage (MV) networks have numerous of solutions how to perform a neutral point grounding according
to demanded characteristic of a ground fault current for relay terminals and safety of people and utilities. Solution with
grounding over partial compensation is widely spread in networks with significant capacitive current IC (though not too
high) and where network is mostly in a steady state often without change in its configuration. In networks where
secondary side of the transformer is in delta connection grounding transformer forms an artificial neutral point through
its grounding bank. Use of grounding transformer changes ground fault in a way presented in this article. Through
Thevenin’s symmetrical component model of a related circuit is possible to validate currents and voltages in network
during a ground fault.

Nomenclature types of connection and depends on whether that transformer


should be used only for providing a neutral point or also as an
I ′′ k1 ground fault current, A auxiliary transformer. Grounding transformer used in the observed
IL inductive current, A network effects the decrease of a resistive fault current and
IC capacitive current, A increase of a remaining reactive current. Neglecting grounding
In.p. current towards neutral, A transformer’s zero impedance (R0 and X0) can bring the
unexpected ground fault current which can have negative impact
Iremain remaining reactive current, A on relay protection and fatal effect on people and utility. Beside
IR resistive current, A ground fault calculation this study brings the procedure of
Ubd broken delta voltage, V choosing thermal current for grounding system elements. Both are
Zd /Zt direct/inverse impedance, Ω the base for making technical enquires of such equipment.
Z0eq zero equivalent impedance, Ω
Zeq Thevenin’s equivalent impedance, Ω
Z0PT /phase power transformer’s zero impedance, Ω 2 Types of grounding system in MV networks
Z0GT /phase grounding transformer’s zero impedance, Ω
There are several grounding system types in distribution network.
ZL impedance of reactor, Ω What will be applied depends firstly on a permitted touch voltage
Rn neutral grounding resistor, Ω [1]. In a case of high ground fault current it is necessary to equalise
RF ground fault resistance, Ω a voltage potential on the place of plausible touch with fault. Very
Csn /phase capacitance of the network, F often is more reasonable to design a grounding system that will
SAIFI system average interruption frequency index decrease ground fault current so that there is no more problem with
SAIDI system average interruption duration index high soil resistivity. Secondly, it depends on configuration of the
network. Generally, it refers to the length of a network, but ratio
between cable and overhead lines is also crucial [2]. It is well
known that 1 km of cable in MV network has more than 10 times
1 Introduction higher capacitance than 1 km of overhead line. In a past, grounding
was not needed because networks were not much developed hence
Firstly, in the time of undeveloped electrical networks and especially capacitive current was not very high. Thereupon, networks could be
because of the small cable ratio all distribution networks had isolated fully operated while having a fault because arc self-extinction
neutral point. By increasing cable ratio and size of the networks, happened. When arc self-extinction point is crossed, isolated neutral
neutral point grounding started to be dominant. Since there is a system is left. Since then came into existence various types of
high restriction due to people’s safety, grounding systems are grounding. Every grounding type is suitable for specific
constructed to limit a ground fault magnitude. One of the characteristic of the network and is described in the following sections.
grounding solutions is grounding over partial compensation. It is
performed over parallel connection of resistor and reactor whose
taps are regulated only in the off state. Grounding like this one is 2.1 Isolated neutral system
applied especially in networks with high capacitive current where
regulations according to the safety of people and utility as well as At the beginning, all MV networks were isolated because conditions
relay terminal’s demand of a current characteristic cannot be for arc self-extinction were fulfilled. Therefore, networks could be
achieved in solutions without compensation. When power operated during a fault without additional risk for people and
transformer has a delta connection on its medium voltage (MV) utility. Internal overvoltages in such systems can be up to 2.7Un.
side, an artificial neutral point is created by grounding transformer. Intermittent can happen after opening operation of the interrupter
By using this kind of grounding, the regular model for ground and inability of extinction an arc. The factor of overvoltage in that
fault calculation can be omitted. Grounding bank can be in various case can be up to 3.5Un [3] (Fig. 1).

CIRED, Open Access Proc. J., 2017, Vol. 2017, Iss. 1, pp. 733–737
This is an open access article published by the IET under the Creative Commons 733
Attribution License (http://creativecommons.org/licenses/by/3.0/)
Fig. 1 Ground fault phasor diagram in a network with isolated neutral

Fig. 3 Ground fault phasor diagram in partial compensated network


2.2 Low-ohm grounding of neutral point

The safety of people and utilities was the reason of letting isolated an arc self-extinction point and assured ground resistance in MV/
neutral system go and shifting to low-ohm grounding. It manifests LV (low-voltage) substations (Fig. 4).
itself in having a ground fault current which has a dominant
resistive component, 3IR > IC [4]. It affects lower internal
overvoltages and intermittent cannot even happen. Overvoltages 3 Grounding over grounding transformer
rise up to 1.9Un. MV equipment in HV/MV substations such as
interrupters and relay protection reacts reliable on mainly resistive When a network is supplied from delta connection of the
ground fault current. In a contrary to isolated neutral systems, transformer, the only way for grounding a system is the use of
network with low-ohm grounding cannot be operated while having grounding bank. Grounding bank can be connected in variates of
a fault. Thus, any line in a fault has to be interrupted and connections. The most generic design is the Y-Δ connection which
consumers stay without electricity (Fig. 2). provides the neutral point on its primary side. There are couple of
designs of grounding bank, but the most used one is of the form
ZNyn(d) which is used in the actual network. In contrary to
2.3 Partial compensation grounding of neutral point connection Z or Y-Δ this connection can be applied for supplying
consumption of the utility. Tertiary of the grounding transformer
Resistor and reactor connected in parallel create a partial provides a path for current I0 in the case of ground fault on LV
compensation grounding system. Advantage of using this side. The most important electrical parameters when ordering a
grounding is the reduction of a ground fault current with grounding transformer are: nominal apparent power Sn, thermal
compensating capacitive current. Overvoltages seem to be small current Ith(s) and zero impedance Z0GT. Nominal apparent power Sn
too. Without lots of network changes it looks like a good way of is determined according to utility needs. While thermal current Ith
grounding. Disadvantages of this solution lay in the reactor’s (s) determines current which is permitted to flow through neutral
inability to adjust its inductance to the network’s capacitance. If during a certain period, zero impedance Z0GT changes ground fault
changes in the network capacitance are often it can lead to the current and voltages on which this study mostly orientates.
state where compensation is not assured. Then, use of this type of
grounding brings risk to the people and equipment (Fig. 3).
3.1 Grounding transformer variates

As mentioned before, the most generic form of creating an artificial


2.4 Resonant grounding (arc suppression coil)
neutral point is Y-Δ and an interconnected star (Z connection). They
Arc suppression coil with automatic adjustment of inductance is used are applied only for providing an artificial neutral point of the
in the resonant grounding systems. The biggest advantage of this network.
type of grounding is the improvement of SAIDI and SAIFI Following types can serve for feeding the utility with electricity as
indexes without bringing people and utilities in danger. well as for creating a neutral system [5]:
Overvoltages go up to 2.5Un and intermittent voltages do not
exist. [3] Ground fault current has inductive character and has the † ZNyn is a connection often used despite its disadvantage. This
value according to the U0 set on regulator. Value is determined to grounding provider serves as an auxiliary transformer too and
be high enough for fault detection but still low enough to satisfy feeds the utility.

Fig. 2 Ground fault phasor diagram in low-ohm grounding network Fig. 4 Ground fault phasor diagram in resonant grounding network

CIRED, Open Access Proc. J., 2017, Vol. 2017, Iss. 1, pp. 733–737
734 This is an open access article published by the IET under the Creative Commons
Attribution License (http://creativecommons.org/licenses/by/3.0/)
† ZNyn(d) is a connection which has an advantage compared to the 4 Theoretical and practical analysis of the model
previous one because in the case of ground fault on LV side, ground
fault current is around three times lower without delta in grounding 4.1 Calculation and scheme model
transformer than with it [6].
† ZNzn is a connection that fulfils all the requirements for Thevenin’s equivalent scheme of affected symmetrical components
grounding transformer with adequate secondary winding which is the base for calculation. Scheme consists of direct, inverse and
supplies consumption of the utility. zero impedance. Zero impedance has the biggest impact. In a
conventional grounding, there is a Z0 of a power transformer
which is apparently low and can almost be neglected due to
3.2 Determination of electrical parameters transformer’s big apparent power. When using power transformer
in Yd5 connection, grounding on the MV side can be performed
The most important technical parameters except apparent power are only over grounding transformer. In the system of zero sequence
thermal current Ith(s) and zero impedance Z0GT. When making an components, Z0GT has impedance three times smaller in a
inquiry for thermal current Ith(s) of grounding transformer, the calculation model than Z0 of the grounding elements:
buyer has to know in what spectrum of currents this element
might be exposed. Thermal current Ith(s) of grounding transformer uk% UB2
is often specified for 5 s, 10 min and permanent or in a similar ZdTR = ZiTR = (4)
100 sn
way. Besides setting delay time on ground fault protection relay,
automatic reclosing and operational time of interrupter are taken Zdeq = Zieq = ZdTR + Zdline (5)
into consideration. By using the law of conservation of energy
thermal current can easily be determined. Energy that current I1    
(9Rn ZL /(3(Rn + ZL ))) + Z0GT × −jkC
has produced for period t1 is equal to the energy that current I2 Z0eq = + 3RF + Z0line (6)
has produced for period t2: (9Rn ZL /(3(Rn + ZL ))) + Z0GT − jkC

Zeq = Zdeq + Zieq + Z0eq (7)


2
Ith1 Z1 t1 = 2
Ith2 Z 2 t2 (1)
Equations describe a procedure of calculating an influence of
grounding transformer on ground fault variables. In the model, the
main focus should be on Z0GT which affect a voltage drop in the
Z1 = Z2 = Zx (2) zero sequence circuit. Therefore, parallel connection of the resistor
and reactor get diminished voltage and leads to lower inductive IL
and resistive current IR.
 First step after calculating equivalent impedance Zeq is to calculate
t1
Ith2 = Ith1 (3) a ground fault current I′′ k1:
t2
√
′′ 3UL
I k1 = (8)
While there is almost a negligible zero impedance Z0 of power Zdeq + Zieq + Z0eq
transformer, grounding transformer makes it difficult to
compensate a capacitive current IC. However, it has a similar As model scheme denotes, capacitive current leads the voltage and
influence on the resistive current in observed network, although does not flow towards grounding system [8].
using grounding transformer with other characteristic can have Therefore, current that flow towards grounding system has
totally opposite influence. Distribution company is responsible for particularly inductive character. According to the model, these two
determination of a zero impedance Z0GT which should suit currents compensate each other just in the neutral point. Following
requirements of a certain network. Grounding transformer’s Z0GT equations explain statement:
depends not only on the form, used material and dimensions of the
core and windings, but also on the type of the connection between
wounds [7] (Fig. 5). In.p. = I ′′ k1 − IC (9)

U  
Uac = √L − In.p. Z0GT − I ′′ k1 Zdeq + Zieq + Z0line + RF (10)
3
 
U 
ac
IL = (11)
Zreactor
 
U 
IR = ac (12)
Rn
 
Uab = I ′′ k1 Zdeq + Zieq + Z0line + RF (13)
 
U 
ab
IC = (14)
−jXC

By neglecting ground fault resistance, impedance of lines and


transformers, capacitive current is calculated as
√  
IC = 3 × UL  × w × Csn (15)

Broken delta voltage is the vector addition of all three


Fig. 5 Thevenin’s equivalent model for grounding over artificial neutral phase-to-ground voltages. As more emphasised line impedances
point are less, voltage will be on broken delta. Broken delta is the most

CIRED, Open Access Proc. J., 2017, Vol. 2017, Iss. 1, pp. 733–737
This is an open access article published by the IET under the Creative Commons 735
Attribution License (http://creativecommons.org/licenses/by/3.0/)
Table 3 Comparison between results from calculation model and
ground fault in network for RF = 0 and 350 Ω

Grounding over grounding transformer’s artificial NP

Ground fault calculation Ground fault in the


model analysed network

RF = 0 Ω RF ≃350 Ω RF = 0 Ω RF≃350 Ω
 
 ′′ 
I k1 , A 51.39 21.73 51.3 21.9
IR , A 41.48 21.04 41.4 21.3
Ireactor , A 147.70 69.84 141.3 66.7
 
 
In.p. , A 153.42 72.94 157.1 75.8
Ubd , V 105.55 49.84 — —

Fig. 6 The influence of grounding transformer’s Z0GT on ground fault


current (taken value 100% X0GT) output rated voltage on the broken delta of voltage transformer in
the analysed case is 100/3 V per phase. In a case of fault-free state
reliable detector of the ground fault. Even when relay protection phase, voltage of every winding is 33.3 V and voltage of broken
cannot detect a fault concerning small current or its unsuitable delta is 0 V (Fig. 6) (Tables 1–3).
characteristic, broken delta voltage warns on the ground fault. The
4.2 Testing the model in 20 kV network
Table 1 Comparison between ground faults in grounding over power In TS 110/20 kV Vincent in HEP, Elektroistra test of the ground fault
transformer (PT)’s and grounding transformer (GT)’s neutral point (RF = 0 Ω)
was made to prove a testing model and to set a relay terminal and a
Grounding over reactor’s tap in the right position. During the test, tap on the reactor
was on seventh position, with inductance XL = j74.83 Ω. The first test
Power transformer’s Grounding transformers was performed without ground fault resistance and the second one
neutral point (NP) artificial NP
with resistance RF = 350 Ω.
Un , V 21,000 21,000
Current clamps were used on every location for which ground
Csn , F 1.55819 × 10−5 1.55819 × 10−5 fault was previously calculated. ABB relay terminal REF 543 was
RF , Ω 0 0 measuring ground fault current I′′ k1. Automatic reclosing was shut
 
Z0PT Z0GT , Ω j2.07 j24 down and relay protection was set on t = 0.4 s.
ZL , Ω j74.83 j74.83
Rn , Ω 240 240
Zeq , Ω 653.25 − j224.60 571.17 − j417.87 5 Conclusion
IC , Ω j178.05 j178.05
I ′′ k1 , A 52.65└ 18.97° 51.39└ 36.19° Grounding transformer which was considered in this model has
IR , A 49.79 41.48 predominantly inductive impedance which is not always a case.
IL , A −j160.93 −j147.70 Since there are different application purposes, that is,
Iremain , A j17.12 j30.35 generator grounding etc. it can have different characteristic.
In.p. , A 168.47└ − 72.81° 153.42└ − 74.31 Hence, distribution operator company has to have
 
U , V 105.31 105.55 well-educated engineers so that they can answer on challenges
bd
in such networks.
Modifier Letter-small capital L that take place in the expressions where In this model of partial compensating network, the influence of
complex numbers are written in a polar form. grounding transformer results in the reduction of resistive and
inductive current. As a consequence, it can have unreliableness of
Table 2 Comparison between ground faults in grounding over PT’s and relay protection, too high ground fault current and high capacitive
GT’s neutral point (RF = 350 Ω) current. Therefore, not knowing or neglecting Z0GT in calculation
model causes danger to people, utilities and consequently
Grounding over interruption of electrical energy.
In resonant grounding networks this influence is even
Power transformer’s NP Grounding transformers
artificial NP more 4emphasized. There are a number of examples where arc
suppression coils ‘ARC’ with their nominal current IL cannot
Un , V 21,000 21,000 compensate much lower nominal IC of network. In these cases only
Csn , F 1.55819 × 10−5 1.55819 × 10−5 solution is operating a system with both ARCs in parallel which
RF , Ω 350 350 actually has a negative effect on the safety of people, utility and
 
Z0PT Z0GT , Ω j2.07 j24 energy supply.
ZL , Ω j74.83 j74.83 Distribution operator company has to bring a standard for
Rn , Ω 240 240
selecting grounding transformers depending on their purpose and
Zeq , Ω 1703.25 − j228.74 1621.17 − j417.87
according to this model. Model is suitable for partial compensated
IC , Ω j71.59 j75.27 network as well as for other types of grounding (low-ohm,
I ′′ k1 , A 21.17└ 7.51° 21.73└ 14.45° resonant and static) networks.
IR , A 20.99 21.04
IL , A −j68.83 −j69.84
Iremain , A j2.77 j5.42
In.p. , A 71.95└ − 73.04° 72.94└ − 73.24° 6 References
 
U , V 42.34 44.62
bd
1 Lakevri, E., Holmes, E.J.: ‘Electricity distribution network design’ (IEE, London,
United Kingdom, 1995), pp. 40–68
Modifier Letter-small capital L that take place in the expressions where 2 Castor, W., Fenkel, R., Grünert, H.: ‘Umstellung der Sternpunkterdung im 20-kV
complex numbers are written in a polar form. Kabelnetz’ (EW Sonderdruck, Erlangen, Germany, 2009)

CIRED, Open Access Proc. J., 2017, Vol. 2017, Iss. 1, pp. 733–737
736 This is an open access article published by the IET under the Creative Commons
Attribution License (http://creativecommons.org/licenses/by/3.0/)
3 Böckenfel, B.: ‘Der Erdschluss im Netzbetrieb’ (Siemens AG, Nürnberg, Germany, 6 Kelemen, T., Tomšic,´ I., Boras, M.: ‘Earthing and auxiliary transformer’. CIGRE
1996) Conf., 2007
4 Obkircher, C.: ‘Ausbaugrenzen gelöscht betriebener Netze’ (TU Gratz, Institut für 7 Krajcar, S., Delimar, S.: ‘Električna postrojenja’, Faculty of electrical engineering
Elektrische Anlagen, Graz, Austria, 2008) and computing, UNIZG, Zagreb, Croatia, 2007
5 Winders, J.J. Jr.: ‘Power transformers, principles and applications’ (Marcel Dekker, 8 Druml, G.: ‘Wischerrelais für hochohmige, intermittierende und wiederzündende
New York, USA, 2002) Erdschlüsse’ (A. Eberle GmbH & Co., Nürnberg, Germany, 2013)

CIRED, Open Access Proc. J., 2017, Vol. 2017, Iss. 1, pp. 733–737
This is an open access article published by the IET under the Creative Commons 737
Attribution License (http://creativecommons.org/licenses/by/3.0/)

Das könnte Ihnen auch gefallen