Rittal – System climate control

Safeguarding our future


with consistent energy efficiency!
Rittal is your value-creating partner for comprehensive

technology packaging solutions. We offer individual

system benefits based on our complete product range,

extensive expertise and global customer service – cross-

sector, value-maximising solutions that are one hundred

percent benefit-focussed.
Rittal system climate control is proven to boost energy

efficiency by up to 45 percent – while ensuring optimum

cooling performance for all control and IT components.

Thanks to the significant reduction in energy consumption,

Rittal’s innovative cooling concepts are major contributors

to cost efficiency in your company, while at the same time

helping to cut CO2 emissions in the environment.


From system to solution:
Comprehensively individual
However individual your business, you can be sure

that all Rittal climate control systems provide a

comprehensive expert package:

● Exemplary energy efficiency

● Plus special project engineering

● Plus permanent innovative strength

● Plus typical Rittal high-quality production.

Rittal never loses sight of a project’s particular

customer requirements. The aim is always the same:

to produce maximum benefits for the customer.

Expertise + Efficiency + Engineering + Innovation + High quality


System solutions from page 15
For mechanical engineering .............................................................15 For various ambient conditions......................................................... 23
For the IT sector ................................................................................19 For final assembly/handling systems................................................ 27

Project planning from page 31


Basic principles for the use of climate control components ............32 Liquid cooling IE/IT ........................................................................... 37
Cooling with ambient air ...................................................................35 Enclosure heaters ............................................................................. 39
Cooling units .....................................................................................36

Cooling with ambient air from page 41


Fan-and-filter units ............................................................................42 Fan systems ...................................................................................... 54
Rack-mounted fans...........................................................................50 Air/air heat exchangers..................................................................... 60
Tangential fans..................................................................................50

Cooling units from page 67


Modular climate control concept ......................................................68 Wall-mounted cooling units .............................................................. 80
Roof-mounted cooling units ..............................................................72 Thermoelectric coolers ..................................................................... 96

Liquid cooling IE from page 99


Air/water heat exchangers, roof-mounted .....................................100 Recooling systems for oil ............................................................... 130
Air/water heat exchangers, wall-mounted .................................... 100 Immersible recooling systems for oil/emulsion ............................. 132
Direct Cooling Package (mounting plate cooling)......................... 110
Recooling systems for water ..........................................................116

Liquid cooling IT from page 135


CRAC systems ................................................................................136 Chillers for IT cooling ...................................................................... 146
Aisle containment........................................................................... 139 Water/water heat exchangers ........................................................ 150
Liquid Cooling Package (rack cooling) ......................................... 140 Piping systems................................................................................ 154

Outdoor climate control from page 157


Cooling units for CS modular enclosures .......................................160 Climate control units for Toptec CR ............................................... 163
Heat exchangers for CS modular enclosures ................................161 Ex-proof climate control systems ................................................... 164

Enclosure heaters from page 167


Enclosure heaters ..........................................................................168

System accessories from page 171


Air routing....................................................................................... 174 Liquid Cooling Package ................................................................ 186
Control/regulation........................................................................... 177 Filter technology ............................................................................ 189
Mounting accessories.................................................................... 181 General .......................................................................................... 192
Cold Plate....................................................................................... 184 Software service........................................................................... 195

Tips and tricks from page 197


Cooling with ambient air .................................................................198 Liquid cooling IT ............................................................................. 230
Cooling units ...................................................................................207 Enclosure heaters ........................................................................... 234
Liquid cooling IE .............................................................................217 Monitoring ....................................................................................... 235

Technical details from page 239


Cooling with ambient air .................................................................240 Liquid cooling IT ............................................................................. 266
Cooling units ...................................................................................245 Enclosure heaters ........................................................................... 267
Liquid cooling IE .............................................................................251 System accessories ........................................................................ 268

Overview of products and approvals from page 271


Overview of products and approvals .............................................272

Service .......................................................................................... 298


List of model numbers................................................................. 300
Index.............................................................................................. 303

Rittal System Climate Control 3


Rittal climate expertise

4
Rittal climate expertise –

Outstanding breadth and quality.

Rittal cooling concepts are

synonymous with guaranteed

quality, from the product itself

right through to customer service.

Global availability, globally sought-

after. International approvals are

just as much part of the Rittal

“system concept” as uniform

system platforms for cooling units

and heat exchangers. Rittal’s

winning formula for climate control

expertise centres around one

basic idea, with infinite

possibilities. Flexible, inexpensive,

and exceptionally efficient. Rittal

cooling concepts are complete

solutions, precisely tailored to

your requirements and offering

exceptional added-value.

5
Total efficiency

6
Rittal efficiency – A fresh take on

creativity and value-added.

Thanks to its intensive research

and development work with

Pro Ozone cooling units, Rittal

has helped to focus the world’s

attention on “efficiency”. With a

host of innovative ideas such as

nano surface protection, the

Liquid Cooling product family and

coolants based on environmentally

neutral CO2, Rittal is renowned as

a world leader in this field.

Less is more, is our guiding

principle: Less consumption of

energy and resources on the

one hand, and more cost-

effectiveness and productivity

for customers on the other. Rittal’s

solutions successfully unite these

two principles.

7
Engineering partners
Rittal engineering – Building on

cooperation for a shared future.

Whether you require analysis of an

existing climate control concept,

or help planning a new one, Rittal

is a partner you can rely on. As

well as manufacturing system com-

ponents, Rittal also collaborates

closely with customers in the

research and development field.

We act as engineering partners

to our clients. A combination of

practical experience and project

planning leads to innovative,

comprehensive climate control

concepts.

Rittal’s customer service and main-

tenance divisions guarantee com-

plete customer satisfaction from

start to finish.

9
Innovative strength

10
Rittal’s innovative strength –

Deriving fresh growth from

ideas.

Innovation cannot be planned,

but it can be continuously re-

evaluated. This is Rittal’s approach

when tackling any new task. In an

instant, an idea is born, which the

Rittal laboratories then develop

into a new product solution. The

thermoelectric cooler, which cuts

energy consumption by more than

60 % compared with conventional

systems, is just one innovative

high-end example among many.

Rittal’s engineers are encouraged

to think outside the box and come

up with new solutions. These ideas

add value and help to make our

customers more competitive.

11
High quality production

12
Rittal high quality production –

Top quality begins with the

tiniest detail.

Rittal achieves outstanding high-

quality at its own production sites

and in-house research depart-

ments, development units and test

laboratories. This in turn enables

us to guarantee outstanding pro-

duct quality, because our process

quality is second to none. Every

department is broken down into

individual process units, each of

which plays a vital role in Rittal’s

overall quality. High quality pro-

duction relies on a perfect quality

assurance chain. This quality

standard reflects Rittal’s 100 %

customer dedication.

13
14
Rittal system climate control for mechanical engineering

System solutions/Mechanical engineering


Precision scores
an ace
Whenever a higher enclosure protection category is required due to hot, metal dust-

laden or oily ambient conditions, Rittal liquid cooling concepts really come up

trumps.

Precise temperature control of machine and process cooling is another priority.

When cooling spindles with 40,000 rpm, for example, Rittal recooling systems

supply volumetric flows and coolant temperatures at precisely the required level.

Rittal system climate control is the key to a high level of dimensional accuracy,

consistently perfect workpieces, and stable production conditions.

Rittal recooling systems Air/water heat exchangers Rittal DCP –


Energy-efficient cooling of liquid The classic liquid cooling solution Direct Cooling Package
cooling media. ● For extremely hot and dusty ambient Direct cooling of power electronics
● A high level of temperature conditions inside the enclosure
accuracy. ● To dissipate high heat loads without putting ● Using liquid-cooled mounting
● Powerful performance. thermal pressure on the ambient air. plates, with or without fans
● Individual system solutions. ● No impairment to the protection
category
● With efficient frequency converter
cooling.

Rittal System Climate Control 15


System example
Rittal system climate control for mechanical engineering
System example

29
C 31

32

35

B 26 27 28 23 25 21 24 22

30

33

34
7

3 2 1

17

18

19 20

16

4 11 12 10 8 9

5 13 14 16 15
A

Example: Rittal system climate high speed, thanks to the immersion Machine controller, low-voltage distributor B
control for mechanical and plant recooling system (7).
● Bayed Top enclosure system TS 8 (24).
● Process heat from the welding robot and
engineering ● Rittal DCP: Liquid-cooled mounting plates
heat loss from the PC case of the robot
(Cold Plate) (21) for efficient frequency
The air inside the hall is contaminated with controller (18) – case based on TS 8,
converter cooling and
metal swarf and oil mist, and is unable to equipped with air/water heat exchanger
● TopTherm air/water heat exchangers, roof-
absorb waste heat from the controllers and (17) – is effectively dissipated via Rittal
mounted (23) and wall-mounted (22), with
machine cooling system. A comprehensive recooling systems (1).
internal controllers for monitoring and
Rittal liquid cooling concept with central ● The twin-doored enclosure ES 5000 with
control, reliably dissipate the heat loss.
recooling (1) provides a particularly efficient air/water heat exchanger, wall-mounted
● The modular power supply is type-tested
solution. (8), is integrated into the design of the
for global use (28).
machines.
All function and safety-relevant components
● Rittal thermoelectric coolers (16) are a Industrial IT and control room C
are remotely monitored with Rittal CMC-TC
particularly compact, efficient solution
(3). The benefit to you: Added perfection and ● Network enclosures are effectively climate-
for cooling the Rittal Comfort Panel (13)
increased productivity. controlled with a special, low-noise office
command panels.
cooling unit (29).
Machining centre, welding robot A The enclosure is custom-built and
● EMC fan-and-filter units (30) cool the
equipped to order, with a support arm
● The coolant temperature of the process command controller in the pedestals of the
system (15) tailored to your individual
emulsion is precisely coordinated with the TopConsole systems (33).
requirements.
machining cycle of the spindle rotating at

16 Rittal System Climate Control


System example
Rittal system climate control for mechanical engineering
System-wide Ex overpressure enclosure with
integral enclosure cooling unit

System example
Components Page
Central recooling system for for zone II, gas (6)
1 148
enclosure and machine cooling
2 Piping systems 154
CMC-TC for monitoring
3 Cat. 32, p. 808
access, climate, power supply
Test workstation: Rittal Industrial Workstation
4 with support arm CP-S, TFT screen, membrane Cat. 32, p. 172
keyboard
5 Air/water heat exchanger on the IW pedestal 63
6 Ex overpressure enclosure, climate-controlled 164

A Machining centre, welding robot More compact, lightweight and


efficient.
Components Page The powerful thermoelectric
7 Immersible recooling system for process emulsion 132 cooling unit in a lightweight
8 Air/water heat exchanger, wall-mounted 104 design (16).
9 Free-standing enclosure ES 5000, twin-door Cat. 32, p. 155
The eco-friendly climate control
solution for command panels
10 Cable entry, cable routing Cat. 32, p. 1045 and small enclosures – an
11 Interior installation, mounting levels Cat. 32, p. 988 energy saving of more than
12 Signal pillar (in conjunction with CMC-TC) Cat. 32, p. 1125 60 % compared with conven-
13 Rittal Comfort Panel command panel Cat. 32, p. 192 tional industry systems.
14 Monitors, keyboards, handles for the Comfort Panel Cat. 32, p. 1133
15 CP-L support arm system for Comfort Panel Cat. 32, p. 250
16 Thermoelectric cooler for Comfort Panel 97
Air/water heat exchanger, space-saving
17 74
accommodated on the roof of the PC case
18 PS enclosure system, based on TS 8 Cat. 32, p. 168
19 Base/plinth for PC case system Cat. 32, p. 892
20 Bus enclosure Cat. 32, p. 120

B Machine controller, low-voltage distributor Rittal DCP Cold Plate – Liquid-


cooled mounting plates (21)
Components Page
Rittal DCP Cold Plate – Liquid-cooled mounting
21 112
plates
22 Air/water heat exchanger, wall-mounted 104
23 Air/water heat exchanger, roof-mounted 102
24 Baying enclosure system TS 8 Cat. 32, p. 136
System accessories (base/plinth, walls, baying
25 Cat. 32, p. 926
technique, locks, interior installation, cable routing)
26 Ri4Power Form 1, heavy current power distributor Cat. 32, p. 438
Ri4Power Form 2-4, form separation for low-voltage
27 Cat. 32, p. 472
switchgear
28 RiLine60, busbar systems Cat. 32, p. 350

C Industrial IT and control room Quiet performance: Office


cooling units for network
Components Page enclosures (29)
29 Office cooling units for network enclosures 76
30 EMC fan-and-filter units for console systems 48
31 Network enclosures, based on TS 8 Cat. 32, p. 745
System accessories for IT (patch panels,
32 Cat. 32, p. 1013
component shelves)
33 TopConsole system Cat. 32, p. 156
System accessories for consoles (base/plinth,
34 Cat. 32, p. 890
interior installation)
System accessories for the human/machine
35 interface (keyboard drawers, TFT monitors, Cat. 32, p. 1115
keyboards)

Rittal System Climate Control 17


Rittal system climate control for data centres and IT

System solutions/IT sector


Cool and efficient!
A high performance server in the data centre or in the middle of the office? Without

putting additional thermal pressure on the air-conditioning system? Without the

irritating noise of high-speed fan-and-filter units? All that can now be achieved very

easily!

Because Rittal Liquid Cooling concepts offer new framework conditions for your

IT infrastructures in terms of flexibility, safety and cost-efficiency. Independent of the

room situation, with almost zero heat and noise emissions, individual server CPUs

and complete server units or electronic components receive direct, highly effective

cooling.

Modular concepts, tailored precisely to your current requirements, and easily

scalable to meet future needs.

Rittal CRAC systems LCP – Liquid Cooling Package Piping systems


By using Rittal aisle containment, Rittal solves the problem of climate control for The Rittal piping system provides the
high heat losses per rack with this system link between the equipment and the
● you can optimise air-conditioning of
family. refrigeration system.
the room
● in conjunction with the Rittal CRAC ● Extremely high heat loads are dissipated ● An optimum design and targeted
system from the rack via the LCP (air/water heat media supply ensure efficient oper-
● in terms of energy efficiency and exchanger). ation of all cooling components.
cooling output. ● Additionally, this system also allows
temperature-neutral expansion of the
data centre.

Rittal System Climate Control 19


System example
Rittal system climate control for the IT sector
System example

5
7
4

1.1

22

21
B
19 1

20

A 12
14 3
13
17
11
18
10

15

16
8

30

24 28 29 25 26 27 23

Example: Rittal system climate ● Other LCP-cooled (11) computer cases Administration, monitoring C
control for data centres and IT also operate without dissipating heat to
● All function and safety-relevant
the ambient air.
High heat loads in modern data centres, components are remotely monitored with
maximum availability, and the most energy- Development server room, UPS B Rittal CMC-TC. Messages and controls
occur centrally in the control room (23).
efficient climate control system available. ● The server systems are cooled via LCPs
To accommodate all three requirements, you ● Super-low-noise roof-mounted fans (23)
(14), without a raised floor and without
will need an individual concept: cool the network enclosures in the office.
putting pressure on the climate control
Rittal liquid cooling IT. Redundant chillers An even quieter alternative are air/water
system. The heat is dissipated completely
(1), free cooling (1.1) and heat recovery (7). heat exchangers integrated into the
silently via the piping system.
coolant cycle.
Piping systems are designed on a project- ● All server racks are based on the TS 8
specific basis. ● EMC fan-and-filter units with speed
enclosure platform (15).
control (24) ensure fault-free operation
Data centre A ● The dissipation of heat loss from the UPS
and cooling of the control room consoles.
is also integrated into the liquid cooling
● At the heart of this concept are server The result: Targeted, low-noise, energy
concept via the air/water heat exchanger.
efficient!
racks (9) with the option of aisle ● Alternative recooling via LCP Inline or
containment (8). LCP Extend.
● The cold air required is blasted in via the
raised floor by two CRAC systems (10).

20 Rittal System Climate Control


System example
Rittal system climate control for the IT sector
System-wide IT chiller, redundant
configuration, also with

System example
Components Page
IT chiller, redundant configuration, free cooling (1).
1 146
also with free cooling device
1.1 or external free cooling function 147
2 Double pump unit 147
3 Water/water heat exchanger 152
4 Buffer store
5 Water/water heat exchanger 152
6 Emergency water supply
7 Heat recovery

A Data centre with raised floor CRAC systems for raised floor
and aisle flooding (10)
Components Page
8 Rittal aisle containment 139
9 Server racks for aisle containment
10 CRAC systems for raised floor and aisle flooding 138
Room temperature-neutral server extension,
11 Cat. 32, p. 726
cooling with LCP Standard, Plus or Smart
12 Server racks, based on TS 8, bayed with LCPs Cat. 32, p. 777
System accessories for server racks (cable
management devices, monitor/keyboard unit,
13 KVM switch, power distribution, plug-in modules, Cat. 32, p. 890
component shelves, base/plinths and much more
besides)

B Server room without raised floor, UPS Ambient air-neutral server


cooling with LCP air/water
Components Page heat exchangers (14)
Separate servers in the development department,
14 140
cooling with LCP Standard, Plus or Smart
15 LCP Inline 145
16 LCP Extend 143
17 Server racks, based on TS 8, bayed with LCPs Cat. 32, p. 777
18 System accessories for server racks Cat. 32, p. 787
19 Air/water heat exchangers for UPS cooling 104
UPS: Power Modular Concept PMC,
20 Cat. 32, p. 786
rack basis TS 8
21 Power distribution: Power Distribution Rack PDR Cat. 32, p. 787
22 Socket strips: Power System Module PSM Cat. 32, p. 789

C Server and network administration, video monitoring Roof-mounted fan for the office
sector (23)
Components Page
23 Roof-mounted fan for the office sector 76
EMC fan-and-filter units for console systems
24 48
with speed control
CMC-TC, modular system for monitoring
25 Cat. 32, p. 806
climate, access and power supply
26 Network enclosures, based on TS 8 Cat. 32, p. 745
System accessories for IT (patch panels,
27 Cat. 32, p. 1013
component shelves)
28 TopConsole system Cat. 32, p. 156
System accessories for consoles (base/plinth,
29 Cat. 32, p. 890
interior installation)
System accessories for the human/machine
30 interface (keyboard drawers, TFT monitors, Cat. 32, p. 1115
keyboards)

Rittal System Climate Control 21


Rittal system climate control for various ambient conditions

System solutions/Various ambient conditions


TopTherm-Plus
Cleaning, phosphating, dipcoat-priming, spray-finishing, drying. The process

chain in a spray-finishing plant creates extremely varied ambient conditions – and

this also affects climate control of the controllers. Whether humidity, paint dust or

drying heat – these varying requirements are met by a single product range:

Rittal TopTherm-Plus cooling units.

With nano-coating of the heat exchanger surfaces, this ensures a high level of

efficiency and exceptional durability.

Rittal cooling units – Masters of energy efficiency

TopTherm-Plus cooling units Electronic condensate evaporation Master/slave mode


Cooling units keep the enclosure Any condensate incurred is effectively In open bayed enclosure systems,
internal temperature at a constant evaporated and doesn’t need to be cooling units or air/water heat
level, even to below room tempera- collected or dissipated. exchangers with Comfort control
ture, with the air routing being tai- are set to master/slave mode via a
Your value-added:
lored to individual requirements. Two bus cable:
● Enhanced safety – No condensate drips
separate circuits prevent the ingress
onto the floor. ● Even temperature distribution
of dust into the enclosure.
● Time savings – No need to empty across all sections of the enclosure.
● Climate control doors condensate containers. ● Simultaneous activation and
● Roof-mounted cooling units ● Cost benefits – No need to lay condensate deactivation of the devices.
● Wall-mounted cooling units tubing. ● Parallel system and door limit
switch function.

Rittal System Climate Control 23


System example
Rittal system climate control for various ambient conditions
System example

D
20

B 11 8 12 9 7 21

23

22

24

19

13

10

17
A
18

1 2 5 6

14

15 4
16

Example: Rittal system climate ● Wall-mounted cooling units (2) may be Control and inspection workstations C
control for various ambient internally mounted, partially internally
● Test workstation with mini-cooling units
mounted or externally mounted.
conditions ● Design variants: Standard, stainless steel
(14).
● Individual configuration from IW modules
Rittal TopTherm-Plus cooling units define (4), NEMA 4x, all including RiNano
(15) (Industrial Workstation).
the performance class of the future. Even coating and condensate management.
● Command Panel (Optipanel) (17) with
under extremely varied ambient conditions,
Control of the spray-finishing and drying thermoelectric cooler (18) and individual
the control electronics are climate-controlled
line – paint dust and heat B panel design.
at a stable level and with a high degree of
Support arm system CP-XL.
reliability. ● Perfection in cooling and design with the
Configured entirely to your requirements.
This is supplemented by plant-wide remote modular climate control concept (7). The
monitoring with Rittal CMC-TC (23) – this enclosure door and climate components Control room for the entire production
ensures availability and also saves money. are combined into one – no need for time- process D
consuming assembly.
Control of the cleaning and ● Server enclosures – based on TS 8 (21) –
● Comfort controller (8) – the ideal control
priming line – high humidity A in the control room, bayed with LCP
and safety electronics.
cooling (20).
● Roof-mounted cooling units (1) and wall- ● Bayed EMC systems TS 8 (9) with a high
● The central recooling system (19).
mounted cooling units (2) in master/slave level of RF attenuation.
supplies cooling medium in a particularly
mode (3). The cooling output of several
energy-efficient manner.
cooling units in a bayed enclosure suite is
carefully coordinated to boost efficiency.

24 Rittal System Climate Control


System example
Rittal system climate control for various ambient conditions

A Control of the cleaning and priming line Cooling units also available in
stainless steel. TopTherm-Plus

System example
Components Page
1 TopTherm-Plus cooling units, roof-mounted 74 cooling units (1, 2) ensure
constant temperatures for
2 TopTherm-Plus cooling units, wall-mounted 83
control electronics, regardless
3 Master/slave mode 235 of variations in the ambient
4 Cooling units in stainless steel 74 conditions.
5 Bayed Top enclosure system TS 8 Cat. 32, p. 136
System accessories for TS 8 (base/plinth, walls,
6 doors, baying system, rail systems for interior Cat. 32, p. 926
installation, cable entry and much more besides)

B Control of the spray-finishing and drying line TopTherm-Plus climate control


doors combined with TS 8
Components Page enclosure system: Optimum
7
TopTherm-Plus climate control doors combined with
70 airflow, no assembly work (7)
TS 8
8 Comfort controller 70
Bayed Top enclosure system TS 8 with EMC
9 Cat. 32, p. 329
shielding
Base/plinth (100/200 mm) for TS 8, compulsory
10 when using climate control doors (modular climate Cat. 32, p. 893
control concept)
11 EMC system accessories Cat. 32, p. 572
12 Signal pillars Cat. 32, p. 1125
13 Recooling system to cool the robot controller 127

C Control and inspection workstations Mini-cooling unit, wall-mounted


for efficient cooling of small
Components Page control and computer units (14)
Mini-cooling unit, wall-mounted, on IW and
14 83
TopConsole
15 Industrial Workstation (IW) Cat. 32, p. 172
TopConsole system (pedestal, desk unit) with TFT
16 Cat. 32, p. 156
monitor in the Optipanel (CP-S support arm system)
Comfort-Panel command panel
17 Cat. 32, p. 192
on CP-XL support arm system
18 Thermoelectric cooler 97

D Control room for the entire production process Server cooling with LCP:
Horizontal cold air routing, no
Components Page thermal pressure on the room,
19 IT chiller with integral free cooling device 148 cost-effective, central recooling
20 Server cooling with LCP 141 (19)
21 Server racks, based on TS 8, bayed with LCPs Cat. 32, p. 774
22 System accessories for server racks Cat. 32, p. 890
CMC-TC, modular system for monitoring climate,
23 Cat. 32, p. 806
access and power supply
System accessories for the human/machine
24 interface (keyboard drawers, TFT monitors, Cat. 32, p. 1115
keyboards)

Rittal System Climate Control 25


System climate control for final assembly and handling systems

System solutions/final assembly, handling systems


Air versus heat
Even in apparently non-critical ambient conditions, for example when there is an

adequate supply of clean, cool air, it is still worthwhile to provide climate control.

Here too, the aim is to achieve maximum reliability with exceptional efficiency.

Reliability and efficiency with fan-and-filter units: Temperature-dependent speed

control plus temperature and airflow monitoring.

Reliability and efficiency with air/air heat exchangers: Thanks to separate air

circuits (external/internal), dust remains excluded, while a micro-controller

provides temperature-dependent control and monitoring of key parameters.

The benefit to you: Efficient reliability at all times.

Fan-and-filter units Air/air heat exchangers Machine, process and


Fan-and-filter units are ideal for The requirement for using air/air heat enclosure cooling
dissipating heat loads cost-effectively. exchangers is that the ambient temperature ● Operational reliability thanks
must be below the required enclosure internal to liquid cooling e.g. of high-
● The prerequisite is that the ambient
temperature. frequency motor spindles and
air must be relatively clean with a
temperature below the desired ● Dust and contaminated ambient air is
other drive technology.
● Precise workpiece machining
enclosure internal temperature. unable to ingress the enclosure, thanks
● The entire range of fan-and-filter to the two separate air circuits. thanks to precise, constant
units is also available with EMC temperatures of the cooling media.
● In this way, temperature peaks
shielding.
inside enclosures – for example,
in summer – can be effectively
dissipated via air/water heat
exchangers.

Rittal System Climate Control 27


System example
Rittal system climate control for final assembly/handling systems
System example

A
1 2

5 13 B
12

15

14

11

8
18

10

9
23

17 22

16
24 D 18 20
25
19 21
26

31
C
30

28

27

29

B 7

System climate control Robot: Effective liquid cooling of Control room D


for final assembly and handling controller and process B
The aim is to minimise the level of noise
systems A central recooling system (7) “kills two pollution in offices:
birds with one stone”:
Air versus heat – Even in non-critical ● This can be achieved with Office roof-
ambient conditions, it is still worthwhile ● Effective cooling of the PC case (8) mounted fans (24) and speed-controlled
providing systematic climate control. via air/water heat exchangers (6). fan-and-filter units (27).
Here too, the aim is to achieve maximum ● Precise cooling of machine spindles ● Zero emissions of heat and noise, thanks
reliability with exceptional efficiency. and/or welding heads. to a liquid cooling concept.
Control of production plant and handling Machine operation,
systems A quality assurance C
Reliability and efficiency with air/air heat Reliability and efficiency thanks to fan-and-
exchangers (1) to cool the free-standing filter units (21) for Industrial Workstations IW
enclosures ES 5000 (3). (20):
● Thanks to separate air circuits (external/ ● Temperature-dependent speed control.
internal), dust is unable to ingress. ● Temperature and airflow monitoring.
● A high operating ratio and minimal Exceptionally energy-efficient cooling of
cleaning required. command panels with thermoelectric
● Monitoring of key parameters via a micro- coolers (17).
controller.
28 Rittal System Climate Control
System example
Rittal system climate control for final assembly/handling systems

A Control of production plant and handling systems Platform concept:


Air/air heat exchangers, wall-

System example
Components Page
1 Air/air heat exchangers, wall-mounted 62 mounted, have the same
mounting interface as
Alternatively or additionally: Rittal TopTherm-Plus
2
cooling units, wall-mounted
83 TopTherm-Plus (1, 2)
3 Free-standing enclosure ES 5000 Cat. 32, p. 154
4 Viewing window Cat. 32, p. 944
System accessories (base/plinth, cable entry and
5 Cat. 32, p. 890
interior installation)

B Robot control and process cooling Recooling system for


central enclosure and
Components Page process cooling (7)
Air/water heat exchanger, wall-mounted
6 104
on the rear door of the PC case
Recooling system for central enclosure and process
7 116
cooling
8 PS enclosure system, based on TS 8 Cat. 32, p. 168
9 Base/plinth for PC case system Cat. 32, p. 892
10 Bus enclosure Cat. 32, p. 120
11 Signal pillar (in conjunction with CMC-TC) Cat. 32, p. 1125
12 Rittal Comfort Panel command panel Cat. 32, p. 192
13 Monitors, keyboards, handles for Comfort Panel Cat. 32, p. 1133
14 CP-L support arm system for Comfort Panel Cat. 32, p. 250
15 Thermoelectric cooler for Comfort Panel 97

C Machine operation, quality assurance Thermoelectric cooler for


Comfort Panel (15, 17)
Components Page
16 Rittal Comfort Panel command panel Cat. 32, p. 192
17 Thermoelectric cooler for Comfort Panel 97
18 Monitors, keyboards, handles for Comfort Panel Cat. 32, p. 1133
19 CP-L support arm system for Comfort Panel Cat. 32, p. 250
20 Industrial workstation IW Cat. 32, p. 172
21 Fan-and-filter unit, speed-controlled 44
Optipanel with TFT monitor, CP-S support arm
22 Cat. 32, p. 204
system
23 Compact Panel, CP-S support arm system Cat. 32, p. 231

D Control room Effective cooling, on request


with RF shielding:
Components Page EMC fan-and-filter unit (27)
24 Office roof-mounted fans for network enclosures 55
25 Network enclosures, based on TS 8 Cat. 32, p. 745
System accessories for IT (patch panels,
26 Cat. 32, p. 1013
component shelves)
27 EMC fan-and-filter units for console systems 48
28 TopConsole system Cat. 32, p. 156
System accessories for consoles (base/plinth,
29 Cat. 32, p. 890
interior installation)
System accessories for the human/machine
30 interface (keyboard drawers, TFT monitors, Cat. 32, p. 1115
keyboards)
CMC-TC for monitoring
31 Cat. 32, p. 806
access, climate, power supply

Rittal System Climate Control 29


30
Project planning

Basic principles for the use of climate control components from page 32
Guide to selecting suitable units.......................................................32 Project planning software ................................................................. 34
Heat dissipation ................................................................................33 Interactive performance diagrams ................................................... 34

Project planning
Calculation basis for enclosure climate control ................................34

Cooling with ambient air from page 35


Fan-and-filter units ............................................................................35
Air/air heat exchangers.....................................................................35

Cooling units from page 36


Condensation and dehumidification of the enclosure air .................36
Practical tips .....................................................................................36

Liquid cooling IE/IT from page 37


Air/water heat exchangers ................................................................37 Cooling water .................................................................................... 38
Notes on water quality ......................................................................37 Form for designing recooling systems ............................................. 38
Recooling systems/chillers ...............................................................38

Enclosure heaters from page 39


Heating performance diagram..........................................................39

Rittal System Climate Control 31


Project planning
Basic principles for the use of climate control components

Guide to selecting suitable units


As electronic components become ever smaller and are
more densely packed in enclosures and electronic cases,
systems are becoming increasingly sensitive to external
factors such as dust, oil, moisture and temperature.
Heat in particular is a deadly enemy of sensitive
microelectronics.
Project planning

For example, a general rule of thumb for semi-conductors


is that an increase in the operating temperature of 10°C,
Heat conduction
in relation to the maximum permissible operating
temperature, will shorten its service life by half.
In order to guarantee proper functioning of the electronics,
this heat needs to be dissipated.

Convection Radiation

Ambient conditions Enclosure interior There are three basic forms of heat transfer:
problems Thermal conduction:
Heat is transported by matter, without the matter itself being
moved. The energy is passed from particle to particle.
Convection:
Energy flows with the matter. The transport medium, e.g. a
liquid or gas, takes up energy in the form of heat and
dissipates energy as heat.
Radiation:
Heat is passed from one body to another in the form of
Heat Heat loss
radiation energy, without a medium material.
The decisive factor for the type of heat dissipation to be used
in enclosures is whether they are open (air-permeable) or
closed (air-tight). Whereas in open enclosures, the heat is
dissipated by means of air circulation, in closed enclosures
the heat can only be dissipated via the enclosure wall.
Rittal cooling units provide the ideal system solution for
ensuring an optimum operating temperature inside an air-
tight enclosure, even at high external temperatures.
Dust Condensate

On the following pages, you will find a chrono-


logical guide to help you to easily find the most
suitable climate control solution.

Cool

32 Rittal System Climate Control


Project planning
Fast selection

Heat dissipation
Before you start, please consider your peripheral
conditions such as external temperature, internal
temperature and protection category.
In order to achieve targeted, effective cooling, it is important
to ensure correct calculation of the required climate control
components and possible thermal analysis using computer-

Project planning
assisted flow models (CFD – Computational Fluid Dynamics).

Basic selection:

Ti target > Tu max.


No Integrated louvres, air inlet/outlet grille
Protection category
IP 54 important
Roof ventilation, fan-and-filter unit
Yes
Air/air heat exchanger
Ti target < or = Tu max.

Cooling water cycle Yes


available at the Air/water heat exchanger
installation site
Recooling system
No
Cooling unit

Ti = Required internal temperature of enclosure [°C]


Tu = Ambient temperature of enclosure [°C]
The following pages contain detailed calculation formulae for your chosen option.

Calculation of effective enclosure surface area An enclosure which stands in a room unobstructed on all
Of the variables required for calculation purposes, the effec- sides may dissipate more heat than one sited against a wall
tive enclosure surface area A requires special explanation. or in a niche. For this reason, there are precise specifications
The thermal output dissipated by the enclosure not only on how to calculate the effective enclosure surface area
depends on its actual surface area; the installation type of depending on the type of installation site. The formulae
the enclosure also plays a decisive role. for calculating A are specified in DIN 57 660, part 500 and
IEC 890 (see table below).

Enclosure installation type to IEC 890

Single enclosure, free-standing on all sides First or last enclosure in a suite, for wall Enclosure within a suite, for wall mounting
Single enclosure for wall mounting mounting Enclosure within a suite, for wall mounting,
First or last enclosure in a suite, free-standing Enclosure within a suite, free-standing covered roof surfaces

Installation type
Formula for calculating A [m2]
to IEC 890
A = 1.8 x H x (W + D) + 1.4 x W x D
A = 1.4 x W x (H + D) + 1.8 x D x H
A = 1.4 x D x (H + W) + 1.8 x W x H
A = 1.4 x H x (W + D) + 1.4 x W x D
A = 1.8 x W x H + 1.4 x W x D + D x H
A = 1.4 x W x (H + D) +DxH
A = 1.4 x W x H + 0.7 x W x D + D x H
A = Effective enclosure surface area
W = Enclosure width [m]
H = Enclosure height [m]
D = Enclosure depth [m]

Rittal System Climate Control 33


Project planning
General information

Calculation basis for enclosure climate .


QV = Heat loss installed in the enclosure [W]
control .
QS = Heat
. emitted by the enclosure surface [W]
In natural convection, heat loss is dissipated to the outside Q
. S > 0: Radiation (Ti > Tu)
via the enclosure panels. The prerequisite for this is that the QS < 0: Irradiation (Ti < Tu)
ambient temperature must be lower than the temperature .
inside the enclosure. The maximum temperature increase QE = Required cooling output of an enclosure cooling unit [W]
(ΔT)max. which may occur inside an enclosure compared with .
Project planning

QH = Required thermal output of an enclosure heater [W]


the ambient air is calculated as follows:
qw = Specific thermal output of a heat exchanger [W/K]
.
. V = Required volumetric air flow of a fan-and-filter unit to
QV maintain the maximum permissible temperature difference
(ΔT)max. = between the extracted air and the emitted air [m3/h]
kA
ΔT = Ti – Tu = Max. admissible temperature difference [K]

Note: A = Effective, heat loss-dissipating enclosure surface area to


IEC 890 [m2]
If the heat loss inside the enclosure is not known, this
basic formula can be used to calculate actual heat loss, k = Heat transfer coefficient [W/m2K]
by measuring the ambient temperature Tu and the en- for sheet steel k = 5.5 W/m2K
closure internal temperature Ti

.
QS = A  k  ΔT (watts)

Project planning software


Rittal Therm
Make calculation even easier and faster by using our project
planning software Rittal Therm.
Model No. see page 195.

EPLAN Cabinet
Tool for the planning of enclosures and defining data for
climate control calculations.
Order information see page 195.

Interactive performance diagrams


Interactive performance diagrams may be found on the
Internet at www.rittal.com on the respective component data
sheets in the “Downloads” section, under the heading
“Characteristic curve”.

Enter your required interior temperature and the maximum


exterior temperature in the relevant boxes, then click on
“Calculate”. The heat loss that may be dissipated under
these conditions will be displayed.

34 Rittal System Climate Control


Project planning
Fan-and-filter units, air/air heat exchangers

Fan-and-filter units
The following applies when calculating the volumetric air flow:
.
. QV
V=f
ΔT

Project planning
Performance diagram SK 3325. . . .
140 50 Hz
60 Hz
120

100

80
ΔPst
60

40

20
.
0 V = Volumetric flow (m3/h)
0 100 200 300
. ΔPst = Stat. pressure difference
V
(Pa) Selection diagram
3000
2500
The styling of the
2000
vent louvres in Rittal
fan-and-filter units
1500
guarantees exemplary
1000 stability of the air vol-
umes in relation to

Δ T 2 30 0 K
800

Δ T2 5 K
Δ T 4
pressure loss. The

15 0 K K
Δ T
. 600

Δ
QV
correct fan-and-filter

K
500
K

K
400 unit has been chosen
35

T
10
T

if the specified heat


T
Δ

300
Δ

5K
f = 3.1 m3  K/Wh at loss is dissipated
T
h=( 0 to 100)
Δ
200
whilst complying with
f = 3.2 m3  K/Wh at h = (100 to 250)
the desired maximum
f = 3.3 m3  K/Wh at h = (250 to 500) enclosure internal
100
f = 3.4 m3  K/Wh at h = (500 to 750) 10 20 40 60 80 100 200 400 600800 temperature.
30 50 70 90 300 500 700
f = 3.5 m3  K/Wh at h = (750 to 1000) V
.
.
f = Compensating factor V = Volumetric flow (m3/h)
h = Height above sea level [m] .
QV = Heat loss (W)

Air/air heat exchangers


Calculate the specific thermal output
of the heat exchanger:
.
QV – (A  ΔT  k)
qw =
ΔT

Selection diagram
25 20 15 10 5 0
12
30 10
8
A
6
ΔT
40 4
2
50 0
60
70

Note:
For ambient temperatures that are lower than the desired
enclosure internal temperature, the use of air/air heat
3000 2000 1000 0 10 20 30 40 50 60 70 80
.
exchangers may be appropriate, particularly in cases where
QV qw there are dust, oil and aggressive substances in the ambient
ΔT = Temperature difference (K) air which must not be allowed to ingress the enclosure under
. any circumstances.
QV = Heat loss (W)
qw = Specific thermal output (W/K)
A = Enclosure surface area to IEC 890 (m2)
k = Heat transfer coefficient (W/m2 K)
for sheet steel k = 5.5 W/m2 K

Rittal System Climate Control 35


Project planning
Cooling units

Cooling units Mollier h-x diagram


for calculating the water content of air.
x

0 5 10 15 20 25 30 35 40
x2 x1
50

45

10%
Project planning

40

%
20

%
35

30

%
40
%
30 50 %
60 %
70 0%
10
%
25 90
%
80
20
Calculate your required cooling output.
T 15
. .
QE = QV – k  A  ΔT 10

Condensation and dehumidification of enclosure air 0

when using cooling units


–5
One unavoidable side-effect of using cooling units is the
dehumidification of the enclosure’s interior air. As it cools – 10
down, part of the humidity contained in the air condenses
on the evaporator coil. This condensate must be reliably – 15
discharged from the enclosure. The amount of condensate
occurring depends on relative humidity, the air temperature – 20
0 5 10 15 20 25 30 35 40 45 50 55 60
inside the enclosure and on the evaporator coil, and the air Pd
volume present in the enclosure. The Mollier h-x diagram
shows the water content of air depending on its temperature Pd = Water vapour partial pressure (mbar)
and relative air humidity. T = Air temperature (°C)
x = Water content (g/kg dry air)
➀ = Relative humidity

Practical tips The quantity of condensation is calculated from the following


In all situations where optimum operating temperatures equation:
are required inside an enclosure, even at high external
temperatures, a Rittal enclosure cooling unit can provide W = V  ρ  Δx
the right solution. It is even possible to cool the interior
temperature of the enclosure to well below the ambient
temperature.
The favourable aerodynamic arrangement of the air inlet and W = Water quantity in g
V = Volume of the enclosure in m3
outlet openings in the internal and external circuits ensures ρ = Density of air kg/m3
optimum air circulation inside the enclosure. This sample Δx = Difference of water content in g/kg dry air
calculation will show you a quick, time-saving method for (from the Mollier h-x diagram)
calculating a cooling unit.
Enclosure door closed:
For example: Only the enclosure volume is dehumidified.
A cooling unit with a refrigeration output of 1500 watts
commences operation with a temperature setting of V = width  height  depth = 0.6 m  2 m  0.5 m
Ti = 35°C. V = 0.6 m3
The relative ambient air humidity is 70 %. If air at 35°C is W = V  ρ  Δx
passed over the evaporator coil, the surface temperature
= 0.6 m3  1.2 kg/m3  11 g/kg
of the evaporator coil (evaporation temperature of the
refrigerant) is approximately 18°C. W = 7.92 g 8 ml
At the boundary layer adhering to the surface of the
evaporator coil, water is deposited at the dew point. The Poorly sealed cable designs, damaged door seals and the
difference Δx = x1 – x2 indicates how much condensation is attachment of display media to enclosure surfaces lead to
incurred per kg of air with complete dehumidification. The increased rates of leakage in the enclosure. Hence, with a
leak-tightness of the enclosure has a decisive effect on the leakage rate of, say, 5 m3/h, a continuous condensate
quantity of condensation. volume of up to 80 ml/h may occur.

Summary:
Enclosure cooling units should only operate with the door
closed.
● Seal the enclosure on all sides.
● Use a door limit switch.
● Use TÜV-tested equipment.
● Only set the enclosure internal temperature as low as is
actually needed.
36 Rittal System Climate Control
Project planning
Air/water heat exchangers

Air/water heat exchangers


Calculate your required cooling output:
. .
QE = QV – k  A  ΔT

Project planning
e.g. performance diagram
Air/water heat exchanger 1000 W

1750
.
VW = 400 l/h
.
45 VW = 200 l/h
1500 °C .
VW = 100 l/h

1250
35
°C
.
QK 1000

750 25°
C

500

250 Ti
5 10 15 20 25 30
TW

Tw = Water inlet temperature (°C)


.
QK = Continuous useful cooling output (W)
Ti = Enclosure internal temperature (°C)

Notes on water quality Material of the water-carrying parts


For safe operation of the equipment, it is essential to observe Hydrological data CuAl V4A1)
the VGB guidelines on cooling water (VGB-R 455 P). pH value 7 – 8.5 6–9
Cooling water must not contain any limescale deposits or Calcium hardness > 3 < 8° dH 1 – 12° dH
loose debris; in other words, it should have a low level of Free carbonic acid 8 – 15 mg/dm3 1 – 100 mg/dm3
hardness, particularly a low level of calcium hardness. For Accompanying carbonic acid 8 – 15 mg/dm3 free
recooling within the plant, the calcium hardness should not Aggressive carbonic acid 0 mg/dm3 0 – 400 mg/dm3
be too high. On the other hand, however, the water should Sulphides free free
not be so soft that it attacks the operating materials. When Oxygen < 10 mg/dm3 < 10 mg/dm3
recooling the cooling water, the salt content should not be
Chloride ions < 50 mg/dm3 < 200 mg/dm3
allowed to increase excessively due to the evaporation of
Sulphate ions < 250 mg/dm3 < 500 mg/dm3
large quantities of water, since electrical conductivity
increases as the concentration of dissolved substances Nitrates and nitrites < 10 mg/dm3 < 100 mg/dm3
rises, and the water thereby becomes more corrosive. For COD < 7 mg/dm3 < 40 mg/dm3
this reason, not only is it always necessary to add a Ammonia < 5 mg/dm3 < 20 mg/dm3
corresponding quantity of fresh water, but also to remove Iron < 0.2 mg/dm3 free
part of the enriched water. Manganese < 0.2 mg/dm3 free
Conductivity < 2200 μS/cm < 4000 μS/cm
Gypsiferous water is unsuitable for cooling purposes
because it has a tendency to form boiler scale, which is Residue on evaporation < 500 mg/dm3 < 200 mg/dm3
particularly difficult to remove. Furthermore, cooling water Potassium permanganate
< 25 mg/dm3 < 40 mg/dm3
consumption
should be free from iron and manganese, because otherwise
deposits may occur which settle in the pipes and block them. <3 mg/dm3
At best, organic substances should only be present in small > 3 < 15 mg/dm3 partial current
Suspended matter purification recommended
quantities, because otherwise sludge deposits and
> 15 mg/dm3 continuous purification
microbiological contamination may occur. recommended
1)The complete absence of corrosion under experimental conditions suggests
that solutions with a significantly higher salt content and greater corrosion
potential (such as seawater) may still be tolerated.

Rittal System Climate Control 37


Project planning
Recooling systems/chillers

Recooling systems/chillers
Recooling systems may be used in all situations where a
high cooling load is required, e.g. in process and machine
cooling, in media cooling or when dissipating heat loss from
enclosures via air/water heat exchangers.

Our project engineers will be happy to help you design


Project planning

a recooling system for your specific application area. An


overview of the planning data required for this purpose
can also be found on the Internet at www.rittal.com in the
section on system climate control/process and machine
cooling.

Cooling water Contamination of the water Procedure


Preparation and maintenance of the water in recooling Filtering of water via
– Mesh filter
systems Mechanical contamination – Gravel filter
Depending on the type of installation to be cooled, certain – Cartridge filter
requirements are placed on the cooling water with respect – Precoated filter
to purity. According to the level of contamination and the size Excessive hardness
Water softening via
ion exchange
and design of the recooling systems, a suitable process is
used to prepare and/or maintain the water. Moderate content of mechanical Addition of stabilisers and/or
contaminants and hardeners dispersing agents to the water
The most common types of contamination and most
Moderate content of chemical Addition of passifiers and/or
frequently used techniques to eliminate them in industrial contaminants inhibitors to the water
cooling are: Biological contaminants, slime
Addition of biocides to the water
bacteria and algae

Form for designing recooling systems


Simply tick the type of system, and select or enter the criteria
to suit your requirements. Please also include your name,
company and address. Once you have completed the form,
you can generate a PDF to print out or send via e-mail as an
enquiry. The form for the design of recooling systems may be
found on the Internet at:
www.rittal.com
–> Products
–> System climate control
–> Product portfolio
–> Process and machine cooling
–> Recooling systems
–> Form for designing recooling systems

38 Rittal System Climate Control


Project planning
Enclosure heaters

Enclosure heaters
The required thermal output is calculated from:
.
QH = A  ΔT  k

Project planning
Heating performance diagram
2 5 7.
5 10
10
8 15 ΔT
6 20
5
4
30
A 3

2
1.5

1
10 15 20 30 40 50 60 80 100 150 200 300 500
.
QH

.
QH = Thermal output (W)
A = Enclosure surface area to IEC 890 (m2)
ΔT = Temperature difference (K)

Based on:
Interior siting, static air, heat transfer coefficient k = 5.5 W/m2 K
For exterior siting (moving air):
Double the determined thermal output

Rittal System Climate Control 39


Cooling with ambient air

Fan-and-filter units from page 42


  Fan-and-filter units . . . . . . . . . . . . . . . . . . . . . . . . . . 20/55 m3/h. . . . . . . . 44
  Fan-and-filter units . . . . . . . . . . . . . . . . . . . . . . . . 105/180 m3/h. . . . . . . . 45
  Fan-and-filter units . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230 m3/h. . . . . . . . 46
  Fan-and-filter units . . . . . . . . . . . . . . . . . . . . . . . . 550/700 m3/h. . . . . . . . 47
   Fan-and-filter units . . . . . . . . . . . . . . . . . . . . . . . . 20 – 105 m3/h. . . . . . . . 48
   Fan-and-filter units . . . . . . . . . . . . . . . . . . . . . . . 180 – 700 m3/h. . . . . . . . 49

Cooling with ambient air


Rack-mounted fans from page 50
  for 482.6 mm (19˝) . . . . . . . . . . . . . . . . . . . . . . . . 320/480 m3/h. . . . . . . . 52

Tangential fans from page 50


  for 482.6 mm (19˝) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 320 m3/h. . . . . . . . 53

Fan systems from page 50


  RTT roof-mounted fan and vent attachment. . . . . 400/800 m3/h. . . . . . . . 54
  Roof-mounted fan. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 360 m3/h. . . . . . . . 54
 Roof-mounted fan for the office sector. . . . . . . . . . . 1500 m3/h. . . . . . . . 55
 Enclosure internal fan . . . . . . . . . . . . . . . . . . . . . . . . . 160 m3/h. . . . . . . . 55
 Fan mounting plate. . . . . . . . . . . . . . . . . . . . . . . . . . . 180 m3/h. . . . . . . . 56
Fan expansion kit . . . . . . . . . . . . . . . . . . . . . . . . 108/184 m3/h. . . . . . . . 56
 Fan mounting plate DC . . . . . . . . . . . . . . . . . . . . . . . 990 m3/h. . . . . . . . 57
 Fan roof, modular, two-piece . . . . . . . . . . . . . . . . . . . . 180 m3/h. . . . . . . . 58
 Fan unit, active . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160 m3/h. . . . . . . . 58
  Door-mounted fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . 600 m3/h. . . . . . . . 59
 Fan expansion kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300 m3/h. . . . . . . . 59

With EMC shielding Standardised installation 482.6 mm (19˝) installation

Interchangeable airflow Passive ventilation


direction

Air/air heat exchangers from page 60


   Wall-mounted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12/62 W/K. . . . . . . . 62
  Wall-mounted with controller . . . . . . . . . . . . . . . 17.5 to 90 W/K. . . . . . . . 63
  Wall-mounted, railway-compatible version . . . . . .27 to 98 W/K. . . . . . . . 64
 Roof-mounted. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 W/K. . . . . . . . 65

Standardised installation Wall-mounted 24 V DC and 110 V DC

Suitable for command panels Roof-mounted

Rittal System Climate Control 41


Fan-and-filter units
Fan-and-filter units

Fan-and-filter units are ideal for dissipating heat loads desired enclosure internal temperature. The entire

cost-effectively. The prerequisite is that the ambient air range of fan-and-filter units is now also available with

must be relatively clean with a temperature below the EMC shielding and all required rated voltages.

42 Rittal System Climate Control


Application diversity and
functions
Particularly for applications in the food
industry, the hose-proof hood prevents the
ingress of damp. The protection category
of IP 56 is achieved in conjunction with filter
mats.
Not always full power!
At lower ambient temperatures, the air
throughput may be reduced. By adapting
the fan-and-filter speed to match the
temperature using a controller, noise
generation is reduced.
Also available with EMC shielding

Fan-and-filter units
All fan-and-filter units and outlet filters are
alternatively available with EMC shielding.
The required conductive connection is
achieved via a metallic coating on the fan-
and-filter unit housing and a special sealing
frame.

Fast assembly
Super-fast clip-on mounting
This guarantees fast, completely secure
attachment of the fan-and-filter unit. The
prerequisites for protection category
IP 54 are met as standard. Screws are not
required. Removal of the louvred grille, like-
wise without any screws, means that filter
mat changes can be achieved in next to no
time.
Draw-in or extract?
The air direction may be quickly reversed
from draw-in (default setting) to extracting.
Simply rotate the fan through 180°.

Aesthetics and
function
Typical of the Rittal fan-and-filter
unit design is the extremely low
build height. The super-slimline
vent grille guarantees optimum
air throughput with low noise
generation. Combined with the
technical features, Rittal fan-and-
filter units meet all application
requirements.

Benefits at a glance Important Tips and tricks


● Air throughput from 20 m3/h to 700 m3/h ● The prescribed heat loss and the Applications see page 198
● Super-fast assembly maximum anticipated ambient
Selection criteria see page 199
● IP 54 as standard temperature define the required
● Air flow direction may be reversed from volumetric flow Assembly see page 200
draw-in (default setting) to extracting ● Always use the fan-and-filter units
● All fans also available with EMC shielding and outlet filters together
● Minimal installation depth
● Fan also bayable

Rittal System Climate Control 43


Fan-and-filter units
Air throughput 20/55 m3/h

B2

T2

T1

H2
H1
B1

B = Width
T = Depth
Fan-and-filter units

Supply includes: German registered design Approvals,


Fan-and-filter units ready for no. M 93 04 846 see page 272.
installation, including filter mats.
Performance diagrams,
available on the Internet.

Model No. SK fan-and-filter unit 3321.107 3321.117 3321.027 3321.0471) 3322.107 3322.117 3322.027 3322.0471)
Rated operating voltage V/Hz 230, 50/60 115, 50/60 24 (DC) 48 (DC) 230, 50/60 115, 50/60 24 (DC) 48 (DC)
B1/H1 116.5 148.5
Dimensions in mm B2/H2 92 + 0.82) 1242)
T1 10 10.5
Max. installation depth mm T2 42 57
Air throughput, unimpeded air flow 20/25 m3/h 20 m3/h 55/66 m3/h 55 m3/h
Air throughput with outlet filter
1 x SK 3321.207: 15/18 m3/h 1 x SK 3322.207: 43/50 m3/h
including standard filter mat

Self-starting Self-starting
Axial fan DC motor DC motor
shaded pole motor shaded pole motor
69 mA 138 mA 0.12 A 0.24 A
Rated current max. 125 mA 90 mA 170 mA 90 mA
58 mA 115 mA 0.11 A 0.23 A
Power 12.5 W/10.3 W 3.0 W 4.1 W 19.0 W/18.0 W 4.0 W 4.4 W
Noise level 41/46 dB (A) 41 dB (A) 46/49 dB (A) 42 dB (A)
Temperature range –10°C to +55°C
Colour RAL 70353)
IP 54 standard
Protection category to EN 60 529
IP 56 when using a hose-proof hood
Model No. SK outlet filter 3321.207 3322.207
Accessories Packs of Page
Spare filter mats 5 3321.700 3322.700 191
Thermostat 1 3110.000 178
Temperature indicator 1 3114.100 3114.115 3114.024 – 3114.100 3114.115 3114.024 – 177
Speed control 1 3120.000 3120.115 – – 3120.000 3120.115 – – 179
Hose-proof hood 1 3321.800 3322.800 193
1) Delivery times on request.
2) For metal thickness > 2.5 mm the cut-out B2/H2 must be 1 mm larger.
3) RAL7032 on request.
Special voltages available on request. We reserve the right to make technical modifications.

Accessories Page 171 EMC-protected design Page 48 Configuration software Page 195

44 Rittal System Climate Control


Fan-and-filter units
Air throughput 105/180 m3/h

B2

T2

T1

H2
H1
B1

B = Width
T = Depth

Fan-and-filter units
Supply includes: German registered design Approvals,
Fan-and-filter units ready for no. M 93 04 846 see page 272.
installation, including filter mats.
Performance diagrams,
available on the Internet.

Model No. SK fan-and-filter unit 3323.107 3323.117 3323.027 3323.0471) 3324.107 3324.117 3324.027 3324.0471)
Rated operating voltage V/Hz 230, 50/60 115, 50/60 24 (DC) 48 (DC) 230, 50/60 115, 50/60 24 (DC) 48 (DC)
B1/H1 204 255
Dimensions in mm B2/H2 1772) 2242)
T1 12.5 12.5
Max. installation depth mm T2 82.5 105
Air throughput, unimpeded air flow 105/120 m3/h 105 m3/h 180/160 m3/h 180 m3/h
1 x SK 3323.207: 71/82 m3/h 1 x SK 3325.207: 115/95 m3/h
Air throughput with outlet filter
2 x SK 3323.207: 85/98 m3/h 2 x SK 3325.207: 165/140 m3/h
including standard filter mat
1 x SK 3325.207: 78/90 m3/h 1 x SK 3326.207: 155/130 m3/h

Self-starting Self-starting
Axial fan DC motor DC motor
shaded pole motor shaded pole motor
0.12 A 0.24 A 0.19 A 0.38 A
Rated current max. 170 mA 90 mA 0.3 A 0.34 A
0.11 A 0.23 A 0.20 A 0.40 A
Power 19.0 W/18.0 W 4.0 W 4.3 W 30.0 W/35.0 W 7.2 W 14.0 W
Noise level 46/49 dB (A) 42 dB (A) 52/48 dB (A) 52 dB (A)
Temperature range –10°C to +55°C
Colour RAL 70353)
IP 54 standard
Protection category to EN 60 529 IP 55 when using an additional fine filter mat
IP 56 when using an additional fine filter mat and hose-proof hood
Model No. SK outlet filter 3323.207 3325.207
Accessories Packs of Page
Spare filter mats 5 3171.100 3172.100 191
Fine filter mats 5 3181.100 3182.100 191
Thermostat 1 3110.000 178
Temperature indicator 1 3114.100 3114.115 3114.024 – 3114.100 3114.115 3114.024 – 177
Speed control 1 3120.000 3120.115 – – 3120.000 3120.115 – – 179
Hose-proof hood 1 3323.800 3324.800 193
1) Deliverytimes available on request.
2) For metal thickness > 2.5 mm, the cut-out B2/H2 must be 1 mm larger.
3) RAL 7032 on request.
Special voltages available on request. We reserve the right to make technical modifications.

Accessories Page 171 EMC-protected design Page 48 Configuration software Page 195

Rittal System Climate Control 45


Fan-and-filter units
Air throughput 230 m3/h

B2

T2

T1

H2
H1
B1

B = Width
T = Depth
Fan-and-filter units

Supply includes: German registered design Approvals,


Fan-and-filter units ready for no. M 93 04 846 see page 272.
installation, including filter mats.
Performance diagrams,
available on the Internet.

Model No. SK fan-and-filter unit 3325.107 3325.117 3325.027 3325.0471)


Rated operating voltage V/Hz 230, 50/60 115, 50/60 24 (DC) 48 (DC)
B1/H1 255
Dimensions in mm B2/H2 2242)
T1 12.5
Max. installation depth mm T2 105
Air throughput, unimpeded air flow 230/265 m3/h 230 m3/h
1 x SK 3325.207: 170/205 m3/h
Air throughput with outlet filter
2 x SK 3325.207: 200/230 m3/h
including standard filter mat
1 x SK 3326.207: 190/215 m3/h

Axial fan Self-starting shaded pole motor DC motor


0.28 A 0.53 A
Rated current max. 0.59 A 0.31 A
0.24 A 0.49 A
Power 41.0 W/38.0 W 14.0 W 15.0 W
Noise level 54/56 dB (A) 54 dB (A)
Temperature range –10°C to +55°C
Colour RAL 70353)
IP 54 standard
Protection category
IP 55 when using an additional fine filter mat
to EN 60 529
IP 56 when using an additional fine filter mat and hose-proof hood
Model No. SK outlet filter 3325.207
Accessories Packs of Page
Spare filter mats 5 3172.100 191
Fine filter mats 5 3182.100 191
Thermostat 1 3110.000 178
Temperature indicator 1 3114.100 3114.115 3114.024 – 177
Speed control 1 3120.000 3120.115 – – 179
Hose-proof hood 1 3324.800 193
1) Delivery
times available on request.
2) Formetal thickness > 2.5 mm, the cut-out B2/H2 must be 1 mm larger.
3) RAL 7032 on request.
Special voltages available on request. We reserve the right to make technical modifications.

Accessories Page 171 EMC-protected design Page 48 Configuration software Page 195

46 Rittal System Climate Control


Fan-and-filter units
Air throughput 550/700 m3/h

B2

T2

T1

H2
H1
B1

B = Width
T = Depth

Fan-and-filter units
Supply includes: German registered design Approvals,
Fan-and-filter units ready for no. M 93 04 846 see page 272.
installation, including filter mats.
Performance diagrams,
available on the Internet.

Model No. SK fan-and-filter unit 3326.107 3326.117 3327.107 3327.117 3327.147


Rated operating voltage V/Hz 230, 50/60 115, 50/60 230, 50/60 115, 50/60 400/460, 3~, 50/60
B1/H1 323
Dimensions in mm B2/H2 2921)
T1 12.5
Max. installation depth mm T2 129 145
Air throughput, unimpeded air flow 550/600 m3/h 700/720 m3/h
Air throughput with outlet filter 1 x SK 3326.207: 360/390 m3/h
1 x SK 3326.207: 525/575 m3/h
including standard filter mat 2 x SK 3326.207: 440/495 m3/h

Axial fan Capacitor motor Rotary current motor


0.29 A 0.58 A 0.65 A 1.5 A 0.27 A
Rated current max.
0.35 A 0.70 A 0.95 A 2.0 A 0.37 A
Power 64.0 W/80.0 W 115.0 W/212.0 W 167.0 W/230.0 W 146.0 W/220.0 W
Noise level 59/61 dB (A) 75/76 dB (A)
Temperature range –10°C to +55°C
Colour RAL 70352)
IP 54 standard
Protection category
IP 55 when using an additional fine filter mat
to EN 60 529
IP 56 when using an additional fine filter mat and hose-proof hood
Model No. SK outlet filter 3326.207
Accessories Packs of Page
Spare filter mats 5 3173.100 3327.700 191
Fine filter mats 5 3183.100 191
Thermostat 1 3110.000 – 178
Temperature indicator 1 3114.100 3114.115 3114.100 3114.115 – 177
Speed control 1 3120.000 3120.115 3120.000 – – 179
Hose-proof hood 1 3326.800 193
1) For metal thickness > 2.5 mm, the cut-out B2/H2 must be 1 mm larger.
2) RAL 7032 on request.
Special voltages available on request. We reserve the right to make technical modifications.

Accessories Page 171 EMC-protected design Page 48 Configuration software Page 195

Rittal System Climate Control 47


Fan-and-filter units – EMC
Air throughput 20 – 105 m3/h

B2

T2

T1

H2
H1
B1

B = Width
T = Depth
Fan-and-filter units – EMC

Supply includes: Approvals,


Complete fan-and-filter units see page 273.
ready for installation,
Performance diagrams,
including drilling template, filter
available on the Internet.
mat and assembly parts.

Model No. SK fan-and-filter unit 3321.607 3321.6171) 3322.607 3322.6171) 3323.607 3323.6171)
Rated operating voltage V/Hz 230, 50/60 115, 50/60 230, 50/60 115, 50/60 230, 50/60 115, 50/60
B1/H1 116.5 148.5 204
Dimensions in mm B2/H2 92 + 0.82) 1242) 1772)
T1 10 10.5 12.5
Max. installation depth mm T2 42 57 82.5
Air throughput, unimpeded air flow 20/25 m3/h 55/66 m3/h 105/120 m3/h
1 x 3322.267: 43/50 m3/h 1 x 3323.267: 71/82 m3/h
Air throughput with outlet filter
1 x 3321.267: 15/18 m3/h 2 x 3322.267: 48/55 m3/h 2 x 3323.267: 85/98 m3/h
including standard filter mat
1 x 3323.267: 48/55 m3/h 1 x 3325.267: 78/90 m3/h

Axial fan Self-starting shaded pole motor


69 mA/ 138 mA/ 0.12 A/ 0.24 A/ 0.12 A/ 0.24 A/
Rated current max.
58 mA 115 mA 0.11 A 0.23 A 0.11 A 0.23 A
Power 12.5 W/10.3 W 19.0 W/18.0 W
Noise level 41/46 dB (A) 46/49 dB (A)
Temperature range –10°C to +55°C
Colour RAL 70353)
Protection category to EN 60 529 IP 54 standard
Model No. SK outlet filter – EMC 3321.267 3322.267 3323.267
Accessories Packs of Page
Spare filter mats 5 3321.700 3322.700 3171.100 191
Fine filter mats 5 – 3181.100 191
Thermostat 1 3110.000 178
Temperature indicator 1 3114.100 3114.115 3114.100 3114.115 3114.100 3114.115 177
Speed control 1 3120.000 3120.115 3120.000 3120.115 3120.000 3120.115 179
Hose-proof hood 1 3321.800 3322.800 3323.800 193
1) Deliverytimes available on request.
2) For metal thickness > 2.5 mm, the cut-out B2/H2 must be 1 mm larger.
3) RAL 7032 on request.
Special voltages available on request. We reserve the right to make technical modifications.

Accessories Page 171 Configuration software Page 195

48 Rittal System Climate Control


Fan-and-filter units – EMC
Air throughput 180 – 700 m3/h

B2

T2

T1

H2
H1
B1

B = Width
T = Depth

Fan-and-filter units – EMC


Supply includes: Approvals,
Complete fan-and-filter units see page 273.
ready for installation,
Performance diagrams,
including drilling template, filter
available on the Internet.
mat and assembly parts.

Model No. SK fan-and-filter unit 3324.607 3324.6171) 3325.607 3325.6171) 3326.607 3326.6171) 3327.607 3327.6171)
Rated operating voltage V/Hz 230, 50/60 115, 50/60 230, 50/60 115, 50/60 230, 50/60 115, 50/60 230, 50/60 115, 50/60
B1/H1 255 323
Dimensions in mm B2/H2 2242) 2922)
T1 12.5 12.5
Max. installation depth mm T2 105 129 145
Air throughput, unimpeded air flow 180/160 m3/h 230/265 m3/h 550/600 m3/h 700/720 m3/h
1 x 3325.267: 1 x 3325.267: 1 x 3325.267:
115/95 m3/h 170/205 m3/h 170/205 m3/h
Air throughput with outlet filter 2 x 3325.267: 2 x 3325.267: 2 x 3325.267: 1 x 3326.267:
including standard filter mat 165/140 m3/h 200/230 m3/h 200/230 m3/h 525/575 m3/h
1 x 3326.267: 1 x 3326.267: 1 x 3326.267:
155/130 m3/h 190/215 m3/h 360/390 m3/h

Axial fan Self-starting shaded pole motor Capacitor motor


0.19 A/ 0.38 A/ 0.28 A/ 0.53 A/ 0.29 A/ 0.58 A/ 0.65 A/ 1.50 A/
Rated current max.
0.20 A 0.40 A 0.24 A 0.49 A 0.35 A 0.70 A 0.95 A 2.00 A
30.0 W/ 41.0 W/ 64.0 W/ 155.0 W/ 167.0 W/
Power
35.0 W 38.0 W 80.0 W 212.0 W 230.0 W
Noise level 52/48 dB (A) 54/56 dB (A) 59/61 dB (A) 75/76 dB (A)
Temperature range –10°C to +55°C
Colour RAL 70353)
Protection category to EN 60 529 IP 54 standard
Model No. SK outlet filter – EMC 3325.267 3326.267
Accessories Packs of Page
Spare filter mats 5 3172.100 3173.100 3327.700 191
Fine filter mats 5 3182.100 3183.100 191
Thermostat 1 3110.000 178
Temperature indicator 1 3114.100 3114.115 3114.100 3114.115 3114.100 3114.115 3114.100 3114.115 177
Speed control 1 3120.000 3120.115 3120.000 3120.115 3120.000 3120.115 3120.000 3120.115 179
Hose-proof hood 1 3324.800 3326.800 193
1) Delivery times available on request.
2) For metal thickness > 2.5 mm, the cut-out
B2/H2 must be 1 mm larger.
3) RAL7032 on request.
Special voltages available on request. We reserve the right to make technical modifications.

Accessories Page 171 Configuration software Page 195

Rittal System Climate Control 49


Rack-mounted/tangential fans,
fan systems
Rack-mounted/tangential fans, fan systems

All rack-mounted climate control components are fitted Ready-to-use, wired modules equipped with fans for

directly onto the 482.6 mm (19˝) mounting level for numerous Rittal enclosure system platforms offer

subracks. Positioning directly beneath the electronic effective air throughput and minimal assembly work.

components ensures effective cooling, and prevents Fan roofs, door-mounted fans for server enclosures,

the formation of hot-spots. internal fan mounting panels and enclosure internal

fans are all available.

50 Rittal System Climate Control


Tangential fans
320 m3/h air throughput, 2 U
The high air throughput means that Rittal

Rack-mounted/tangential fans, fan systems


tangential fans are capable of dissipating
large heat losses from the enclosure. The
minimal noise generation of 52 dB creates a
pleasant working environment. Front outlet
grille 2 U for hot air outlet to the outside in
the upper section of the enclosure.

Rack-mounted fan
module
The rack-mounted fan slides into
the guide frame like a drawer.
Connectors on the rear ensure
immediate contact. Installation
options for the guide frame:
Directly in the subrack, via
two mounting brackets on the
482.6 mm (19˝) mounting angles.
Ideal for avoiding hot-spots in fully
populated enclosures.

For the office sector:


Roof-mounted fan
Low noise generation and high performance
for sensitive office areas.
Unit consisting of TS roof plate and fan.

Benefits at a glance Tips and tricks


Rack-mounted/tangential fans Applications see page 201
● Rapid installation on 482.6 mm (19˝)
mounting levels
● Direct, effective dissipation of heat loss,
thanks to positioning beneath the
assemblies
● No externally mounted equipment to
disrupt the aesthetic appearance of
the enclosure
Fan systems
● Fast assembly
● Targeted air routing to avoid hot-spots
● Perfect system integration

Rittal System Climate Control 51


Rack-mounted fans
for 482.6 mm (19˝), air throughput 320/480 m3/h

4
21 6
20
2 00
180 43
2
41
0 55
73 12
0
10
0
48
2.6 48 42
(19 2.6 6
˝) (19
˝)

1 HE
1 HE
1 2
Rack-mounted fans

Rack-mounted fan/Vario rack- Guide frame supply includes: Approvals,


mounted fan supply includes: Guide frame including connec- Also required: see page 273.
Wired unit ready for connection, tor and fitted connection cable Remember to order the Detailed drawing,
including terminal strip and (3 m), bracket for optional appropriate guide frame for your see page 240.
assembly parts. attachment to the 482.6 mm
chosen application.
(19˝) system, assembly parts. Performance diagrams,
available on the Internet.

1 Rack-mounted fans 2 Vario rack-mounted fans


Model No. SK Model No. SK
2 fans
3340.0241) 3340.1151) 3340.230 – – 3350.0241) 3350.1151) 3350.2301) –
Distance between axes 85 mm
3 fans
3341.0241) 3341.115 3341.230 – 9769.0021)2) 3351.0241) 3351.1151) 3351.230 –
Distance between axes 85 mm
3 fans
3342.024 3342.1151) 3342.230 3342.5002)3) – 3352.0241) 3352.1151) 3352.230 3352.5003)
Distance between axes 105 mm
24 V (DC) 36 V (DC) 24 V (DC)
Rated operating voltage V 24 V (DC) 115 V (AC) 230 V (AC) 115 – 230 V up to 24 V (DC) 115 V (AC) 230 V (AC) 115 – 230 V
(AC) 72 V (DC) (AC)
Model No. SK
– – – – – 3356.1001) 3355.100 3355.100 3357.100
matching guide frame
Accessories Page
Temperature indicator
714 3114.100 3114.115 3114.100 3114.024 – 3114.100 3114.115 3114.100 3114.024
230 V (AC)
Thermostat 715 3110.000
Speed control 716 3120.000 3120.115 3120.000 – – 3120.000 3120.115 3120.000 –

Technical specifications
3341.230 3341.115 3341.024
3340.230 3340.115 3340.024 3351.230 3351.115 3351.024 3342.5002)
Model No. SK/CS 9769.002
3350.230 3350.115 3350.024 3342.230 3342.115 3342.024 3352.5002)
3352.230 3352.115 3352.024
AC 230 V AC 115 V DC 24 V AC 230 V AC 115 V DC 24 V DC 24 V 36 V (DC)
Rated operating voltage
AC 115 – 230 V up to
V, Hz
50/60 Hz 50/60 Hz – 50/60 Hz 50/60 Hz – 50/60 Hz 72 V (DC)
0.24 A/ 0.46 A/ 0.36 A/ 0.69 A/
Rated current max. 0.49 A 0.74 A 0.85 A 0.28 A
0.22 A 0.46 A 0.33 A 0.69 A
Pre-fuse T 6.0 A 6.0 A
Number of fans 2 3 3
Air throughput, unimpeded air flow 320 m3/h 480 m3/h 250 m3/h
–33°C to
Temperature range –10°C to +55°C
+55°C
Noise level 51 dB (A) 52 dB (A) 51 dB (A) 51 dB (A) 52 dB (A) 51 dB (A) 52 dB (A)
1) Deliverytimes available on request.
2) Rack-mounted fan for metric mounting angles available on request.
3) Version with monitoring

Accessories Page 171 Configuration software Page 195

52 Rittal System Climate Control


Tangential fans
for 482.6 mm (19˝), air throughput 320 m3/h
17
3
16

38

88
0

48
2.6
(19
˝)

Tangential fans
Supply includes: Approvals,
Fully assembled and wired unit, see page 274.
ready for connection, including
Detailed drawing,
filter mat.
see page 240.
Performance diagrams,
available on the Internet.

Model No. SK 3145.000 3144.000


Rated operating voltage V/Hz 115, 50/60 230, 50/60
W 482.6 (19˝)
Dimensions in mm H 88 (2 U)
D 158
Air throughput, unimpeded air flow 320 m3/h

Rated current max. 0.32 A 0.16 A


Power 37 W
Noise level 52 dB (A)
Speed 2245 rpm–1
Temperature range –10°C to +55°C
Maximum static pressure difference 65 – 70 Pa
Accessories Packs of Page
Temperature indicator 1 3114.115 3114.100 177
Thermostat 1 3110.000 178
Filter mats 5 3177.000 189
Front outlet grille 2 U 1 3176.000 193
Roof vent 1 3148.007 54
Speed control 1 3120.115 3120.000 179
Special voltages available on request. We reserve the right to make technical modifications.

Accessories Page 171 Configuration software Page 195

Rittal System Climate Control 53


Fan systems

RTT roof-mounted fan TS roof plates with prepared mounting cut-outs


are additionally available.
and vent attachment
Roof-mounted fan supply includes:
for TS
The active roof-mounted fan and the passive vent Unit ready to connect with built-in radial fan,
sealing material and assembly parts.
attachment (TS 8801.380) integrate perfectly into
the system-wide mounting concept of the Rittal Vent attachment:
TopTherm platform. They fit precisely onto the cut- see page 182.
outs of the small and medium performance cate-
Protection category:
gory of TopTherm roof-mounted cooling units.
IP 43 to EN 60 529
Of course, they may also be mounted on any suffi-
Detailed drawing,
37
0
55 ciently large roof surface.
0 see page 240.
125

50
0 0
29
Fan systems

B
T

B = Width
T = Depth

Model No. SK 3149.410 3149.420 3149.440 3149.810 3149.820 3149.840 8801.380 Page
400, 3~, 50/60 400, 3~, 50/60
Rated operating voltage V/Hz 115, 50/60 230, 50/60 115, 50/60 230, 50/60 Roof vent
460, 3~, 60 460, 3~, 60
Without
Air throughput, unimpeded air flow 400 m3/h 800 m3/h
motor
Required mounting cut-out W x D mm 475 x 260 490 x 390
Power consumption of fan 120 W/170 W 95 W/140 W 170 W/225 W 180 W/310 W
Rated current of fan 1.1/1.6 A 0.55/0.88 A 0.35/0.35 A 1.5/2.2 A 0.75/1.1 A 0.35/0.55 A
Temperature range –10°C to +55°C
Noise level 68/69 dB (A) 69/70 dB (A)
Weight 10 kg 11 kg 6 kg
Colour shade RAL 7035
Accessories
Roof plate 600 x 600 mm for TS 8 with cut-out 8801.300 8801.310 181
Roof plate 600 x 800 mm for TS 8 with cut-out 8801.320 8801.330 181
Roof plate 1200 x 600 mm for TS 8 with cut-out – 8801.350 181
Temperature indicator 3114.115 3114.100 – 3114.115 3114.100 – – 177
Speed control 3120.115 3120.100 – 3120.115 3120.100 – – 179

Roof-mounted fan Protection category:


IP 43 to EN 60 529. By additionally installing the
● The roof-mounted fan is easily installed using filter holder with filter mat SK 3175.000, with roof
6 screws. The sealing tape supplied can be vent SK 3148.007 a protection category of IP 44 is
used to seal it against the enclosure. achieved.
● The attachment screws are invisible from the
outside. Fully wired unit ready for connection with built-in
● The roof-mounted fan casing has a large air radial fan, sealing material and assembly parts,
outlet surface and labyrinth air ducting. connection cable (3 m), drilling template.

Accessories:
34
0 42
0
Filter holder,
see page 194.
50

Detailed drawing,
see page 240.
34
5 5
26

Model No. SK 3149.007 3169.007 3148.007


Rated operating voltage V/Hz 230, 50/60 115, 50/60 Without fan motor
Air throughput 360 m3/h
Rated current max. 0.2 A 0.55 A
Power consumption 42 W 65 W
Temperature range –10°C to +60°C
Noise level 53 dB (A)
Weight 7.8 kg
Colour1) RAL 7035, textured enamel
1) To
order the version in RAL 7032, please add extension .000 to the Model No.
Special voltages available on request. We reserve the right to make technical modifications.

54 Rittal System Climate Control


Fan systems

Roof-mounted fan Technical specifications:


● Fitted onto a roof plate based on TS.
for TS/FR(i) for the office sector ● Easy assembly; mounting cut-outs have been
This new roof ventilation concept offers a wealth provided.
of performance, assembly and cost benefits ● Radial fan.
associated with the use of integrated ventilation
systems. This roof-mounted fan may be ordered Supply includes:
with and without a roof plate. Another outstanding Fully wired ready for connection,
feature is the enormous volumetric flow in propor- including assembly parts.
tion to exceptionally low noise levels, making it
ideal for use in sensitive office areas.

Model No. SK 3164.610 3164.620 3164.810 3164.820 3164.115 3164.230 Page

Fan systems
Rated operating voltage V/Hz 115, 50/60 230, 50/60 115, 50/60 230, 50/60 115, 50/60 230, 50/60
Air throughput (unimpeded air flow) 1500 m3/h1)
Version With roof plate without roof plate
W 800 800 511
Dimensions in mm H 240 240 227
D 800 900 511
Power consumption 68 W/81 W
Rated current 0.6 A/0.7 A 0.3 A/0.35 A 0.6 A/0.7 A 0.3 A/0.35 A 0.6 A/0.7 A 0.3 A/0.35 A
Radial fan –
Noise level 40 dB (A)
Temperature range +20°C to +55°C
Colour RAL 7035
Accessories
Temperature indicator in 1 U patch panel 7109.035 177
Temperature indicator 3114.115 3114.100 3114.115 3114.100 3114.115 3114.100 177
Thermostat 3110.000 178
1) 800
m3/h at 40 Pa counterpressure using two integrated louvres, type DK 7825.801, in the enclosure base/plinth.
Special voltages available on request. We reserve the right to make technical modifications.

Mounting cut-out
only required for fans wtihout roof plate
1 51 T B
51 1
20
H

24
H

Ø
6.5
13.5

450

(8x
B )
T
225

41 0
45 0 41 0
0 45
205
410

B = Width
T = Depth

Enclosure internal fan Air through- Power


Rated Rated
put (unim- consump- Model No.
for TS current voltage
peded air tion SK
To prevent hot-spots and support the air routing A V, Hz
flow) W
of active enclosure climate control components. 160 m3/h 19.0/18.0 0.12/0.11 230, 50/60 3108.100
Adjustable in two axes. Attached to the TS 8
frame section. Several fans may be cascaded 160 m3/h 19.0/18.0 0.24/0.23 115, 50/60 3108.115
using the quick-release clamping strip. 160 m3/h 3.5 0.15 24 V (DC) 3108.024

Supply includes:
Fully wired unit ready for connection with radial 213.5

fan and lockable swivel device, as well as


assembly parts.
120
100
Ø 6 (2x)

Rittal System Climate Control 55


Fan systems

Fan mounting plate For enclosures


Number
Max.
Model No.
for TS Width Depth number of
of fans DK
mm mm fans
The fan mounting plate may be retro-fitted in all
TS 8 network enclosures from above. The plate 600 600 2 4 7966.035
is mounted at the front of the enclosure, whilst the 800
rear section is left free for cable entry. A rubber 600
900
2 6 7968.035
cable clamp strip is supplied loose for optional 1000
sealing at the rear. 1200
800 600 2 6 7986.035
The following combinations are also possible:
800
● Solid roof plate raised with 20 or 50 mm roof 800
900
2 6 7988.035
spacers. 1000
● Roof plate for cable entry raised with 20 or 1200
50 mm roof spacers.
● Vented roof plate for cable entry. The air throughput can be increased with the fan
Fan systems

In conjunction with the large swing frame, usage expansion kit DK 7980.000.
is only possible from an enclosure depth of Technical specifications for one fan:
800 mm, in conjunction with a roof plate for cable Rated operating voltage: 230 V
entry from 900 mm. Power consumption: 15/14 W at 50/60 Hz
Note: Air throughput (unimpeded air flow):
Not suitable for crane transportation. Not suitable 160/180 m3/h, 50/60 Hz
for combination with 482.6 mm (19˝) mounting Temperature range: –10°C to +55°C
frame. Technical specifications of thermostat:
Rated operating voltage: 250 V
Temperature range: +5°C to +55°C
Colour:
RAL 7035
40

Supply includes:
2 fans, 2/4 cut-outs to extend to 4/6 fans,
52
5/7 thermostat, rubber cable clamp strip.
25
5/5
85 Thermostat and fan fully wired to connection
38
cable (2.5 m).

Accessories:
Fan expansion kit,
see page 56.
Rubber cable clamp strip SZ 2573.000 for sealing
at the sides and targeted air routing when bayed,
see Cat. 32 page 1047.

Fan expansion kit Dimensions


Packs of Model No. DK
W x H x D mm
For retro-fitting various fan units or to supplement
the fan mounting plate and modular fan roof. 119 x 119 x 38 1 set 7980.000
119 x 119 x 25 1 set 7980.100
Technical specifications DK 7980.000:
Rated operating voltage: 230 V~ 119 x 119 x 25 1 set 7980.148
Power consumption: 15/14 W at 50/60 Hz
Air throughput (unimpeded air flow): Supply includes:
160/180 m3/h, 50/60 Hz Fan, including assembly parts and connection
Noise level (unimpeded air flow): 37 dB (A) cable (0.61 m).
Temperature range: –10°C to +55°C
Technical specifications DK 7980.100:
Rated operating voltage: 230 V~
Power consumption: 14/12 W at 50/60 Hz
Air throughput (unimpeded air flow):
108/120 m3/h, 50/60 Hz
Noise level (unimpeded air flow): 34 dB (A)
Temperature range: –20°C to +70°C
Technical specifications DK 7980.148:
Rated operating voltage: 48 V (DC)
Power consumption: 7.7 W
Air throughput (unimpeded air flow): 184 m3/h
Noise level (unimpeded air flow): 43 dB (A)
Temperature range: –20°C to +70°C

56 Rittal System Climate Control


Fan systems

Cover plates for fan panels Packs of Model No. DK


for FlatBox 6 7507.760
To cover unused fan panels when using fans in
the FlatBox.
Material:
Sheet steel
Surface finish:
Powder coated in RAL 7035
Supply includes:
Assembly parts.

Fan systems
Fan mounting plate DC For For
enclosures enclosures Number of Model No.
for TS width depth DC fans DK
Super-low noise thanks to FCS speed control, mm mm
fully fitted 800
Suitable for TS 8 enclosures with a raised roof 800 900 6 7858.488
(> 20 mm) or TS 8 roof plate, vented. The fan 1000
mounting plate may be used as an alternative to
fan mounting plate 7988.035. It is installed from Technical specifications:
above. Cable entry is prepared in the rear section Power pack rated voltage:
of the plate. 100 – 240 V AC, 50/60 Hz
Not suitable for combination with 482.6 mm (19˝) Power supply rated current: max. 1.5 A
mounting frame. Power supply secondary range: 24 V DC, 3 A
Advantages of the DC fan mounting plate with Temperature range: +5°C to +40°C
FCS technology: Total air throughput (unimpeded air flow):
● Super-low noise thanks to speed control. 6 x 175 m3/h = 990 m3/h
● All fans are monitored for failure. Technical specifications for one fan:
● High air throughput thanks to DC technology Rated voltage: 24 V DC
(unimpeded airflow 6 x 175 m3/h = 990 m3/h). Rated current: max. 0.3 A
● EMC compatibility. Air throughput (unimpeded air flow): 175 m3/h
● Temperature monitoring and control. Speed: 2650 rpm
● High level of safety (low safety voltage with Noise level: up to 45 dB (A)
24 V DC power supply). at maximum speed activation
● Visual and acoustic alarm messages, plus relay
alarm output.
● Freely selectable installation location for the Also required:
FCS control unit (included with the supply of the Connection cable 230/115 V.
fan mounting plate, in 482.6 mm (19˝) with Example D version, Model No. 7200.210,
7320.440 or on the frame with 7320.450). see Cat. 32, page 818.
● Suitable for international use, thanks to wide-
range power supply 100 – 240 V AC and socket
to IEC 320. Accessories:
● Pre-configured. 1 U mounting unit, Model No. 7320.440,
● Network-compatible via CMC-TC processing see Cat. 32, page 821.
unit II 7320.100 (all relevant data such as Mounting module, Model No. 7320.450,
temperature etc. are displayed in the web see Cat. 32, page 821.
browser, or alarms are sent in the form of an
SNMP trap).
Note:
For more information on the FCS system,
see Cat. 32, page 813.

Rittal System Climate Control 57


Fan systems

Fan roof, modular, two-piece Material:


Sheet steel, spray finished
for TS, FR(i)
The modular roof plate consists of individual com- Colour:
ponents and can be configured for the ventilation RAL 7035
of the enclosures in various ways. Technical specifications for one fan:
The modules consist of: Rated operating voltage: 230 V
Roof plate, two-piece with cut-out Power consumption: 15/14 W at 50/60 Hz
For fan mounting and cable entry at the rear via a Air throughput (unimpeded air flow):
sliding angular bracket with rubber cable clamp 160/180 m3/h at 50/60 Hz
1 strip. Replacing the existing roof plate. The two- Temperature range: –10°C to +55°C
piece design allows convenient retrofitting of Detailed drawing,
cables at any time. see page 241.
Cover plate
To cover the cut-out, optionally solid or vented Accessories:
Fan systems

options. The top-mounted cover plate may be


raised for extra air throughput using the supplied Fan expansion kit DK 7980.000,
spacers. see page 56.
Thermostat SK 3110.000,
Fan insert see page 178.
For active ventilation: Speed control SK 3120.000,
2 A fully pre-wired fan tray including 2.5 m connec- see page 179.
tion cable, with two fan motors and additional cut-
outs. The air throughput may be increased with a
fan expansion kit.
5
3 4

1 2
Model No. DK
For enclosures Roof plate Roof plate Fan insert
Cover plate
FR(i) TS

Width Depth 1 2 4 5 3 Fans Maximum


mm mm With With pre-wired no. of fans
cut-out cut-out Solid Vented Fan insert
600 600 7856.3661) 7826.366 2102.1801) 2102.400 2102.320 2 2
600 800 7856.3681) 7826.368 2102.1901) 2102.410 2102.490 2 6
600 900 – 7826.369 2102.1901) 2102.410 2102.490 2 6
600 1000 7856.3601) 7826.360 2102.1901) 2102.410 2102.490 2 6
600 1200 7856.3621) 7826.362 2102.1901) 2102.410 2102.490 2 6
800 600 – 7826.486 7885.100 7885.200 7885.000 2 3
800 800 7856.3881) 7826.488 7886.100 7886.200 7886.000 2 8
800 900 – 7826.489 7886.100 7886.200 7886.000 2 8
800 1000 7856.3801) 7826.480 7886.100 7886.200 7886.000 2 8
800 1200 – 7826.382 7886.100 7886.200 7886.000 2 8
1) Delivery
times available on request.
Design panel FR(i) already included with the supply of the standard roof plate.

Fan unit, active For enclosures Number of Possible


Model No.
WxD pre-wired number of
for TE TE
mm fans fans
For active ventilation of the TE 7000. The fan
All
unit is installed in the prepunched cut-out. An dimensions
2 3 7000.670
additional fan may optionally be integrated.
Supply includes:
Fan unit including assembly parts, 2 fans, Note:
1 thermostat and open connection cable. Connection via distributor box or country-specific
connector.
Technical specifications for one fan:
Fan extension kit, 7980.000,
see page 56. Accessories:
Technical specifications of thermostat: Fan expansion kit,
Rated operating voltage: 250 V see page 56.
Temperature range: +5°C to +55°C

Active kit Packs of Model No. DK


for TE 1 set 7000.680
consisting of fan unit including thermostat, com-
plete, wired ready for connection, socket strip
(DK 7000.630) for up to 8 earthing pin plugs,
version D and connection cable (DK 7200.210).

58 Rittal System Climate Control


Fan systems

Door-mounted fan Supply includes:


Wired ready for connection with 2.5 m connection
for server enclosures TS, TE cable, including assembly parts.
Specifically for installing in perforated doors.
The growing packaging density in data Accessories:
communications and network enclosures make
active, direct ventilation of the enclosure indispen- Fan expansion kit,
sable. The door-mounted fan, which is attached to see page 59.
the rear or front door, supports horizontal air rout- Note:
ing via the servers and therefore facilitates faster Only for mounting on the tubular door frame!
heat dissipation from active components.
Door configuration for installation in 2 and 4-door
Technical specifications: ISP racks available on request.
● Standard assembly with two fans.
● Air throughput, unimpeded air flow 600 m3/h.
● By adding two fan extension kits, the air

Fan systems
throughput is increased to 1200 m3/h.
● The direction of air flow is easily reversed by
rotating the fan.
● Several units may be positioned in a cascade
arrangement.
● Simple mounting on the tubular door frame.

59.5
B
5

606
552
H

9
Ø 4.5

230 (350)
27

475 (675)
493 (693)

T
B = Width
T = Depth

Model No. SK 3165.6241) 3165.6481) 3165.6151) 3165.630 3165.8241) 3165.8481) 3165.8151) 3165.830 Page
Rated operating voltage V/Hz 24 (DC) 48 (DC) 115, 50/60 230, 50/60 24 (DC) 48 (DC) 115, 50/60 230, 50/60
Air throughput (unimpeded air flow) 600 m3/h
Power consumption for two fans 40 W 48 W 70 W/64 W 70 W/70 W 40 W 48 W 70 W/64 W 70 W/70 W
Rated current of fan 1.5 A 1.0 A 0.76 A/0.72 A 0.38 A/0.36 A 1.5 A 1.0 A 0.76 A/0.72 A 0.38 A/0.36 A
W 493 693
Dimensions in mm H 606 606
D 64.5 64.5
For doors with width (mm) 600 800
Noise level 55 dB (A)
Temperature range +20°C to +55°C
Colour RAL 7035
Accessories
Temperature indicator 3114.024 – 3114.115 3114.100 3114.024 – 3114.115 3114.100 177
Thermostat 3110.000 178
1) Delivery times on request.
Special voltages available on request. Technical modifications reserved.

Fan expansion kit To fit door-mounted fan Model No. SK


for door-mounted fan SK 3165.624, SK 3165.824 3165.024
To increase the air throughput of the door- SK 3165.648, SK 3165.848 3165.048
mounted fan. SK 3165.615, SK 3165.815 3165.115
SK 3165.630, SK 3165.830 3165.230

Rittal System Climate Control 59


Air/air heat exchangers
Air/air heat exchangers

The requirement for using air/air heat exchangers is aggressive ambient air is unable to ingress the

that the ambient temperature must be below the enclosure interior, thanks to the two separate air

required enclosure internal temperature. Dust and any circuits.

60 Rittal System Climate Control


Safety
High protection category
Thanks to the seamlessly sealed heat
exchanger module, a protection category
of IP 54 to EN 60 529 is achieved.
High load capacity
The motors of the fans are equipped with

Air/air heat exchangers


thermal winding protection.
Top quality: Guaranteed protection for
your electronics.
All devices in the Rittal TopTherm-Plus series
are tested in accordance with the interna-
tionally valid approvals (GS, UL).

Simple maintenance
The heat exchanger unit is very easily
removed and cleaned. The cleverly thought-
out structure enables fast, economical main-
tenance.

Platform strategy/
installation
Identical installation cut-outs
for various output classes.
Easily retrofitted
Thanks to the low weight, simple
assembly cut-outs and problem-
free attachment of the heat
exchangers, a cabinet or
enclosure is easily retro-fitted.

Benefits at a glance Important Tips and tricks


● Specific thermal output from 17.5 W/K to The temperature difference between the Applications see page 202
90 W/K room temperature and enclosure internal
Selection criteria see page 203
● External and internal circuit may be temperature will have a decisive effect on
controlled separately the heat loss that may be dissipated. Assembly see page 204
● Mounting cut-outs and enclosure
Air routing see page 205
dimensions identical to TopTherm
wall-mounted cooling units Electrical connection
● Suitable for external and internal and control see page 206
mounting
● Top design identical to TopTherm wall-
mounted cooling units

Rittal System Climate Control 61


Air/air heat exchangers
Wall-mounted

T
T

H
H
B
B
Air/air heat exchangers

Supply includes: SK 3125.800


Fully wired unit ready for con- Compact wall-mounted air/air
nection. heat exchanger. Ideal for small
enclosures and command
Detailed drawing,
panels.
H

see page 241.


Suitable for external and inter-
Performance diagrams, nal mounting.
available on the Internet.
SK 3129.800
Super-slimline air/air heat
exchangers. Ideal for external
door mounting. B

B = Width
T = Depth

Model No. SK 3125.800 3129.800


Rated operating voltage V/Hz 230, 1~, 50/60
W 200 400
Dimensions in mm H 400 1360
D 146 110
Specific thermal output 12 W/K 62 W/K

Fans 2 per heat exchanger


Max. rated current per fan 0.11 A/0.13 A 0.45 A/0.55 A
Pre-fuse T 2.0 A
Output per fan 25 W/30 W 100 W/130 W
External circuit 265 m3/h / 315 m3/h 860 m3/h / 900 m3/h
Air throughput of fans (unimpeded air flow)
Internal circuit 265 m3/h / 315 m3/h 860 m3/h / 900 m3/h
Temperature range –5°C to +55°C
Type of connection Connection cable
Weight 8 kg 30 kg
Colour RAL 7035
Protection category to EN 60 529 Internal circuit IP 54
Accessories Packs of Page
Thermostat 1 3110.000 178
Temperature display 1 3114.100 177
Speed control 1 3120.000 179
Special voltages available on request. We reserve the right to make technical modifications.

Accessories Page 171 Recooling systems From page 116 Configuration software Page 195

62 Rittal System Climate Control


Air/air heat exchangers
Wall-mounted with controller

550

950
28 40 T2
0 8 0
10
0 T1 50
15 42

Air/air heat exchangers


Supply includes:
Fully wired unit ready for con-

1580
nection.
Approvals,
see page 276.
Detailed drawing,
● With controller and digital see page 244.
temperature display Performance diagrams, 40 5
16
● Floating fault signal contact available on the Internet.
0
21
5 50
in case of overtemperature
T = Depth

230 V 3126.100 3127.100 3128.100 3129.100 3130.100


Model No. SK
115 V 3126.115 3127.115 3128.115 3129.115 3130.115
Rated operating voltage V/Hz 230/115, 1~, 50/60
W 280 400 400 400
H 550 950 950 1580
Dimensions in mm
T1 150 205 225 215
T2 – 155 175 –
Specific thermal output 17.5 W/K 30 W/K 45 W/K 60 W/K 90 W/K

Fans 2 per heat exchanger


230 V 0.11 A/0.13 A 0.28 A/0.34 A 0.3 A/0.4 A 0.38 A/0.4 A 0.67 A/0.88 A
Max. rated current per fan
115 V 0.23 A/0.25 A 0.55 A/0.7 A 0.6 A/0.8 A 0.65 A/0.8 A 1.3 A/1.8 A
Pre-fuse T 2.0 A 4.0 A
Output per fan 23 W/27 W 60 W/75 W 70 W/90 W 85 W/90 W 150 W/200 W
Air throughput of fans External circuit 265 m3/h / 315 m3/h 480 m3/h / 525 m3/h 600 m3/h / 625 m3/h 860 m3/h / 900 m3/h 850 m3/h / 945 m3/h
(unimpeded air flow) Internal circuit 265 m3/h / 315 m3/h 480 m3/h / 525 m3/h 600 m3/h / 625 m3/h 860 m3/h / 900 m3/h 850 m3/h / 945 m3/h
Temperature range –5°C to +55°C
Type of connection Plug-in terminal strip
Weight 10 kg 18 kg 19 kg 21 kg 34 kg
Colour RAL 7035
Protection category to EN 60 529 Internal circuit IP 54
Accessories Packs of Page
Filter mats 3 3286.300 3286.400 189
Metal filters 1 3286.310 3286.410 190
Special voltages available on request. We reserve the right to make technical modifications.

Accessories Page 171 Recooling systems From page 116 Configuration software Page 195

Rittal System Climate Control 63


Air/air heat exchangers
Wall-mounted, railway-compatible version

H
B T1
T1
Air/air heat exchangers

External Partial Internal B = Width


mounting internal mounting T = Depth
mounting1)

Rittal air/air heat exchangers in a Railway-compatible design of Benefits, technical details: Detailed drawing,
railway-compatible version are the units includes construction ● External and internal fans may see page 242/243.
used specifically in the mobile to EN 50 155, halogen-free con- be controlled separately
railway engineering sector, e.g. nection cables, screw protec- ● Simple maintenance
for local trains, locomotives and tion, shock and vibration testing
Supply includes:
high-speed trains. Products are to EN 61 373, preparation for
Fully wired unit ready for
available both in 24 V DC and in EN 45 545, and spray-finishing
connection.
110 V DC. in RAL 7035 S to DB TL 918340,
among other things.

Model No. SK 3126.424 3128.424 3129.424 3130.424 3126.410 3128.410 3129.410 3130.410
Rated operating voltage 24 V (DC) 24 V (DC) 24 V (DC) 24 V (DC) 110 V (DC) 110 V (DC) 110 V (DC) 110 V (DC)
B 280 400 400 400 280 400 400 400
Dimensions in mm H 650 950 950 1580 650 950 950 1580
T1 127 140 150 150 127 140 150 150
Specific thermal output 27 W/K 47 W/K 66 W/K 98 W/K 27 W/K 47 W/K 66 W/K 98 W/K

Max. rated current per fan 2.7 A 7.5 A 10.5 A 9.2 A 2.7 A 1.9 A 2.47 A 2.3 A
Output per fan 65 W 180 W 240 W 220 W 65 W 203 W 256 W 230 W
Air throughput of fans External circuit 360 m3/h 560 m3/h 1055 m3/h 1125 m3/h 360 m3/h 560 m3/h 1055 m3/h 1125 m3/h
(unimpeded air flow) Internal circuit 360 m3/h 560 m3/h 1055 m3/h 1125 m3/h 360 m3/h 560 m3/h 1055 m3/h 1125 m3/h
Temperature range –5°C to +55°C
Weight 10 kg 16 kg 18 kg 25 kg 12.5 kg 18.5 kg 20.5 kg 27.5 kg
Colour RAL 7035
Protection category
Internal circuit IP 54
to EN 60 529
Accessories Packs of Page
Adjustable frame 1 3286.260 3286.270 3286.270 3286.280 3286.260 3286.270 3286.270 3286.280 183
Metal filters 1 3286.230 3286.240 3286.240 3286.250 3286.230 3286.240 3286.240 3286.250 190
Delivery times available on request. We reserve the right to make technical modifications.
1) Partial installation is only supported with an adjustable frame (see accessories).

The requirement for using air/air heat


exchangers is that the ambient tem-
perature must be below the required
enclosure internal temperature.
Dust and any aggressive ambient air
is unable to ingress the enclosure,
thanks to the two separate air cir-
cuits.
Contamination of the outer circuit
with coarse dust can be reduced
via the use of optional metal filters.
Attachment options: External mount-
ing, internal mounting, partial inter-
nal mounting via a special mounting
frame.

64 Rittal System Climate Control


Air/air heat exchangers
Roof-mounted
T B

H
B = Width
T = Depth

Air/air heat exchangers


Application: ● This design gives the unit an ● The internal and external Supply includes:
These units are used specifi- extremely low weight (16.8 kg) circuits can be connected Fully wired unit ready for
cally if the doors or side panels combined with a high degree separately; separate routing connection. The fans are
must not be obstructed, or of enclosure rigidity. effectively prevents the connected via two 3-wire
space must be kept clear for ● The built-in radial fans ensure ingress of dust, moisture and connection cables, with wire
escape routes. effective air circulation, even dirt. end ferrules.
where the enclosure is
Technical design:
densely packed. Detailed drawing,
● The heat exchanger module
● All motors are equipped with see page 241.
and the enclosure of the heat
thermal winding protection.
exchanger form a single unit,
● As you would expect, the heat
thereby substantially enlarg-
exchanger membranes are
ing the surface area for heat
conductively connected to
dissipation.
one another and thereby
incorporated into the electri-
cal safety features.

Model No. SK 3248.000


Rated operating voltage V/Hz 230, 1~, 50/60
W 595
Dimensions in mm H 362
D 440
Specific thermal output 66 W/K

Fans 2 per heat exchanger


Max. rated current per fan 0.45 A/0.55 A
Pre-fuse T 4.0 A
Output per fan 75 W
Air throughput of fans External circuit 965 m3/h
(unimpeded air flow) Internal circuit 965 m3/h
Temperature range –5°C to +55°C
Type of connection Connection cable
Weight 16.8 kg
Colour RAL 7035/9005
Protection category to EN 60 529 Internal circuit IP 54
Accessories Packs of Page
Temperature display 1 3114.100 177
Thermostat 1 3110.000 178
Hygrostat 1 3118.000 178
Speed control 1 3120.000 179
Special voltages available on request. We reserve the right to make technical modifications.

Rittal System Climate Control 65


Cooling units

E Modular climate control concept from page 68


   Cooling modules . . . . . . . . . . . . . . . . . . . . . . . . . 1500/2500 W. . . . . . . . 70
 Section doors for installing cooling modules . . . . . . . . . . . . . . . . . . . . . . . 71

E Roof-mounted cooling units from page 72


    Roof-mounted cooling units . . . . . . . . . . . . . . . . . . 500/750 W. . . . . . . . 74
    Roof-mounted cooling units . . . . . . . . . . . . . . . . . . . . . . 1000 W. . . . . . . . 75
   Roof-mounted cooling units . . . . . . . . . . . . . . . . 1100/3000 W. . . . . . . . 76
    Roof-mounted cooling units . . . . . . . . . . . . . . . . 1500/2000 W. . . . . . . . 77
    Roof-mounted cooling units . . . . . . . . . . . . . . . . 3000/4000 W. . . . . . . . 78

Cooling units
    with CO2 as the coolant . . . . . . . . . . . . . . . . . . . . . . . . . 1000 W. . . . . . . . 79

E Wall-mounted cooling units from page 80


  VIP small cooling units . . . . . . . . . . . . . . . . . . . . . . . . . . 225 W. . . . . . . . 82
   Mini, in horizontal format . . . . . . . . . . . . . . . . . . . . . . . . . 300 W. . . . . . . . 83
   Wall-mounted cooling units . . . . . . . . . . . . . . . . . . . 300/500 W. . . . . . . . 84
   Wall-mounted cooling units . . . . . . . . . . . . . . . . . . . . . . . 750 W. . . . . . . . 85
   Cool Efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1000 W. . . . . . . . 86
    Wall-mounted cooling units . . . . . . . . . . . . . . . . . 1000/1500 W. . . . . . . . 87
    Wall-mounted cooling units, slimline . . . . . . . . . . . . . . . 1500 W. . . . . . . . 88
    Wall-mounted cooling units . . . . . . . . . . . . . . . . . 2000/2500 W. . . . . . . . 89
    Wall-mounted cooling units . . . . . . . . . . . . . . . . . . . . . . 4000 W. . . . . . . . 90
     Design NEMA 4x . . . . . . . . . . . . . . . . . . . . . . 500/1000/1500 W. . . . . . . . 91
     Design NEMA 4x . . . . . . . . . . . . . . . . . . . . . . . . . 2000/2500 W. . . . . . . . 92
    for precision machine tools . . . . . . . . . . . . . . . . . 1000/1500 W. . . . . . . . 93
   Explosion-proof cooling units
for zone 22 (dust) . . . . . . . . . . . . . . . . . . . . . . . . . 1000/1500 W. . . . . . . . 94
    with CO2 as the coolant . . . . . . . . . . . . . . . . . . . . . . . . . 1000 W. . . . . . . . 95

E Thermoelectric coolers from page 96


  Thermoelectric coolers . . . . . . . . . . . . . . . . . . . . . . . . . . 100 W. . . . . . . . 97

Stainless steel version Energy-efficient and Coolant CO2


E nano-coated

Standardised installation Suitable for command panels Industry solutions

Integral condensate NEMA 4x


evaporation

Rittal System Climate Control 67


Modular climate control concept
Modular climate control concept

Less is more! We offer almost limitless application The existing sheet steel doors are easily exchanged

possibilities from just six cooling modules and eight for section doors with cooling modules. These can

door modules. Top cooling technology, complete and also be exchanged or upgraded while the system is

ready to use – no need to make mounting cut-outs. operational.

68 Rittal System Climate Control


1 Cooling module, 1500 W useful cooling
output
2 Cooling module, 2500 W useful cooling
output
3 Section doors for installing cooling
modules in 600 mm wide enclosures
4 Section doors for installing cooling
modules in 800 mm wide enclosures
5 Section doors for installing cooling
modules in 1200 mm wide enclosures;
cooling module fitted on the left
6 Section doors for installing cooling
modules in 1200 mm wide enclosures;
cooling module fitted on the right,
including lockable door on the left

Modular climate control concept


Infinite possibilities
Seamless baying and perfect integration.
Cooling of a bayed enclosure suite is easily
achieved, even under awkward room condi-
tions, such as low ceiling heights.

60
0
1800/2000

80
0
1800/2000

12
00
Modularity 3
With the section door and cooling
module, you can create your own
1800/2000

individual climate control solution 4 12


00
in next to no time.
Choose from 48 different options
with varying sizes, cooling outputs 5
1800/2000
1
and voltages.

2 6

Benefits at a glance Important Tips and tricks


● Combination of TS 8 section door and The TS base/plinth is required for opera- Applications see page 207
climate control module tional purposes.
Selection criteria see page 208
● One item number each for the door and
climate control module Assembly see page 209
● 8 section doors x 6 climate control
Air routing see page 210
modules = 48 combination options
● Standard RTT PLUS version with integral Condensate management see page 213
condensate evaporation and RiNano
Electrical connection
coating
and control see page 215
● Intelligent control
− Climate control module with Comfort
controller
− Controller is identical to those used
with TopTherm climate control systems

Rittal System Climate Control 69


Modular climate control concept
Cooling modules, 1500/2500 W useful cooling output

Supply includes: Approvals,


Cooling module prepared for Also required: see page 277.
Modular climate control concept

installation in section door, with Section door, fits TS 8 enclo- Detailed drawing,
RiNano coating and integrated sures, 600, 800, 1200 mm see page 245.
condensation evaporation.
widths and 1800, 2000 mm
heights, see page 71. Performance diagrams,
available on the Internet.
Base/plinth, 100 or 200 mm
high,
see Cat. 32, page 893.

Model No. SK with Comfort controller 3307.700 3307.710 3307.740 3310.700 3310.710 3310.740
400, 3~, 50/ 400, 3~, 50/
Rated operating voltage V/Hz 230, 1~, 50/60 115, 1~, 50/60 230, 1~, 50/60 115, 1~, 50/60
460, 3~, 60 460, 3~, 60
.
Useful cooling output QK L 35 L 35 1500 W/1550 W 1500 W/1550 W 2500 W/2520 W 2500 W/2500 W
to DIN 3168 L 35 L 50 850 W/900 W 930 W/950 W 1620 W/1730 W 1760 W/1800 W

Rated current max. 6.0 A/6.5 A 12.6 A/12.6 A 2.6 A/2.8 A 7.8 A/8.8 A 18.1 A/19.8 A 3.6 A/3.8 A
Start-up current 22.0 A/24.0 A 36.0 A/39.0 A 8.5 A/9.2 A 22.0 A/24.0 A 36.0 A/39.0 A 13.0 A/14.0 A
Pre-fuse gG 16.0 A/16.0 A 16.0 A/16.0 A 6.3 – 10.0 A1) 16.0 A/16.0 A 20.0 A/20.0 A 6.3 – 10.0 A1)
Power consumption Pel L 35 L 35 910 W/1100 W 940 W/1130 W 850 W/910 W 1410 W/1620 W 1460 W/1670 W 1380 W/1580 W
to DIN 3168 L 35 L 50 1100 W/1250 W 1140 W/1280 W 920 W/980 W 1580 W/1950 W 1630 W/2000 W 1620 W/1920 W
.
Refrigeration factor ε = QK/Pel L 35 L 35 1.6 1.6 1.7 1.7 1.8
Refrigerant R134a, 700 g R134a, 900 g
Permissible operating pressure p. max. 28 bar
Temperature and setting range +20°C to +55°C
Protection category External circuit IP 34
to EN 60 529 Internal circuit IP 54
Duty cycle 100 %
Type of connection Plug-in terminal strip
Weight2) 72 kg 72 kg 75 kg 74 kg 74 kg 76 kg
Colour RAL 7035
External circuit 1100 m3/h 1100 m3/h
Air throughput of fans
Internal circuit 520 m3/h 1100 m3/h
Temperature control Comfort controller (factory setting +35°C)
Accessories Packs of Page
Door-operated switch 1 4127.000 176
Filter media 1 See accessories section door 71
SK BUS system for Comfort controller 1 3124.100 180
RiDiag II including cables
1 3159.100 195
for Comfort controller
Interface card for Comfort controller 1 3124.200 179
Special voltages available on request. We reserve the right to make technical modifications.
1) Motor circuit-breaker
2) Includes section door weight

Accessories Page 171 TS 8 enclosures Cat. 32, from Page 142 Configuration software Page 195

70 Rittal System Climate Control


Modular climate control concept
Section doors for installing cooling modules

H
H

H
B B B

B = Width
T = Depth

Colour: Note for 1200 mm wide


RAL 7035 TS 8 enclosures: Also required:

Modular climate control concept


With the device positioned on Cooling module,
Supply includes:
the “right”, one pack consists see page 70.
Section door unit without pre-
of a section door for installing
fitted cooling module, including Base/plinth, 100 or 200 mm
in the right-hand half of the
TS 8 hinges, door opening angle
enclosure plus a special high,
approx. 110°. see Cat. 32, page 893.
lockable door for the left-hand
half. Detailed drawing,
With the device positioned on see page 245.
the “left”, one pack consists of a
section door for installing in the
left-hand half of the enclosure.
The existing lockable door on
the right may be used.

Model No. SK for 1800 mm high TS enclosures 3300.040 3300.060 3300.080 3300.110
Model No. SK for 2000 mm high TS enclosures 3300.050 3300.070 3300.090 3300.120
1200 1200
Dimensions Width
600 800 (unit positioned (unit positioned
to fit TS enclosures mm
on the left) on the right)
Accessories Packs of
Filter media 1 3284.210 3284.210 3284.210 3284.210
All SK 3307.700/.710/.740 or 3310.700/.710/.740 cooling module models, see page 70, can be integrated in the section doors mentioned above.

Accessories Page 171 TS 8 enclosures Cat. 32, from Page 142 Configuration software Page 195

Rittal System Climate Control 71


Roof-mounted cooling units
Roof-mounted cooling units

Cooling units keep the enclosure internal temperature Rittal TopTherm-Plus roof-mounted cooling units:

at a constant level, with the air routing being tailored to Top design and top performance with a host of

individual requirements. Two separate circuits prevent assembly benefits and sophisticated air routing.

the ingress of dust into the enclosure. Superb performance plus cost-cutting

design.

72 Rittal System Climate Control


Optimum flow conditions
Targeted air routing inside the enclosure
The internal air circulation is targeted and
effective: The heated air is extracted cen-
trally. Air exhaust occurs in the four corners,
depending on requirements. Cold air is
routed in a controlled manner into the lower
enclosure chamber via the optional ducting
system. The result is highly effective cooling
and the avoidance of air short-circuits. The
targeted air circulation inside the enclosure
via ducts also prevents the creation of hot-
spots.

Roof-mounted cooling units


Versatility and Integrated into TopTherm-
flexibility of roof Plus cooling units
mounting Electrical condensate evaporation
Cut your costs Condensate arising inside the enclosure
All three-phase cooling units are or on the evaporator coil of the cooling unit
suitable for a voltage range of 400/ is effectively evaporated. The evaporator
460 V and a frequency range of 50/ device inside the cooling units has a very
60 Hz without rewiring. No need for high evaporation output (several litres per
expensive additional transformers. day). This is achieved thanks to the princi-
ple of direct evaporation.
Flexible performance
Just 3 mounting cut-outs for 6 dif- RiNano coating
ferent output categories provide The standard nano-coating on the heat
investment security and facilitate exchanger membranes ensure a longer,
easy adaptation of the cooling out- constant cooling output and renders the use
put to the ambient conditions and of filter media superfluous in many areas.
the installed heat loss.
Rittal platform strategy
TopTherm air/water heat exchang-
ers and roof-mounted fans are also
compatible with the mounting cut-
outs.

Benefits at a glance Important Tips and tricks


● Highly efficient in both performance and Avoid overloading the roof plate by using Applications see page 207
energy consumption stays (with TS 8 system accessories,
Selection criteria see page 208
● Wide output range from 500 to 4000 W Catalogue 32, page 998)
● Control and monitoring with Basic or Assembly see page 209
Comfort controllers
Air routing see page 210
● Three-phase cooling units support
multiple voltages as standard Condensate management see page 213
● Uniform, performance-related, system-
Electrical connection
wide mounting cut-outs
and control see page 215
● Targeted, individual air routing
● Electric condensate evaporation and
RiNano coating

Rittal System Climate Control 73


Roof-mounted cooling units
Useful cooling output 500/750 W
59
Property rights:
7 German registered design
no. 402 02 324
German registered design

417
no. 402 02 325

0
38

47
5 0
26

Supply includes: Approvals,


Nano-coated condenser and Accessories: see page 277.
Roof-mounted cooling units

integral electronic condensate Roof plate for TS 8 with Detailed drawing,


evaporation. mounting cut-out, see page 246.
Fully wired ready for connection,
see page 181.
including drilling template and Performance diagrams,
assembly parts. available on the Internet.

Model No. SK with Basic controller, RAL 7035 3382.100 3382.110 3359.100 3359.110 3359.140
Model No. SK with Comfort controller, RAL 7035 3382.500 3382.510 3359.500 3359.510 3359.540
Model No. SK with Basic controller, stainless steel1) 3382.200 3382.210 3359.200 3359.210 3359.240
Model No. SK with Comfort controller, stainless steel1) 3382.600 3382.610 3359.600 3359.610 3359.640
Rated operating voltage V/Hz 230, 1~, 50/60 115, 1~, 50/60 230, 1~, 50/60 115, 1~, 50/60 400, 2~, 50/60
Dimensions in mm WHD 597 x 417 x 380
.
Useful cooling output QK L 35 L 35 500 W/510 W 750 W/810 W
to DIN 3168 L 35 L 50 270 W/370 W 545 W/590 W

Rated current max. 3.3 A/3.5 A 6.7 A/7.2 A 3.6 A/4.5 A 7.2 A/9.0 A 2.1 A/2.6 A
Start-up current 9.2 A/10.2 A 18.4 A/18.4 A 10.0 A/10.7 A 20.0 A/21.4 A 5.8 A/6.2 A
Pre-fuse T 10.0 A 10.0 A 10.0 A 16.0 A 6.3 A – 10.0 A2)
Power consumption Pel L 35 L 35 500 W/550 W 510 W/560 W 550 W/660 W 560 W/675 W
to DIN 3168 L 35 L 50 550 W/590 W 560 W/610 W 630 W/740 W 640 W/750 W
.
Refrigeration factor ε = QK/Pel L 35 L 35 1.0 1.4
Refrigerant R134a, 250 g R134a, 300 g
Permissible operating pressure p. max. 25 bar
Temperature and setting range +20°C to +55°C
Protection category External circuit IP 34
to EN 60 529 Internal circuit IP 54
Duty cycle 100 %
Type of connection Plug-in terminal strip
Weight 30 kg 35 kg 32 kg 37 kg
Air throughput of fans External circuit 910 m3/h
(unimpeded air flow) Internal circuit 440 m3/h
Temperature control Basic or Comfort controller (factory setting +35°C)
Accessories Packs of Page
Filter mats 3 3286.500 189
Metal filters 1 3286.510 190
Quick-change frame 1 3286.700 182
Door-operated switch 1 4127.000 176
SK BUS system for Comfort controller 1 3124.100 180
RiDiag II including cables for Comfort controller 1 3159.100 195
Interface card for Comfort controller 1 3124.200 179
Air-ducting system 1 3286.870 174
Cover stoppers for interior air outlet 2 3286.780 175
Condensate hose 1 3301.612 192
1) Delivery
times available on request. 2) Transformer protection switch.
Special voltages available on request. We reserve the right to make technical modifications.

Accessories Page 171 Configuration software Page 195

74 Rittal System Climate Control


Roof-mounted cooling units
Useful cooling output 1000 W
59
Property rights:
7 German registered design
no. 402 02 324
German registered design

417
no. 402 02 325

5
47

49 0
0 39

Supply includes: Approvals,


Nano-coated condenser and Accessories: see page 277.

Roof-mounted cooling units


integral electronic condensate Roof plate for TS 8 with Detailed drawing,
evaporation. mounting cut-out, see page 246.
Fully wired ready for connection,
see page 181.
including drilling template and Performance diagrams,
assembly parts. available on the Internet.

Model No. SK with Basic controller, RAL 7035 3383.100 3383.110 3383.140
Model No. SK with Comfort controller, RAL 7035 3383.500 3383.510 3383.540
Model No. SK with Basic controller, stainless steel1) 3383.200 3383.210 3383.240
Model No. SK with Comfort controller, stainless steel1) 3383.600 3383.610 3383.640
Rated operating voltage V/Hz 230, 1~, 50/60 115, 1~, 50/60 400, 2~, 50/60
Dimensions in mm WHD 597 x 417 x 475
.
Useful cooling output QK L 35 L 35 1000 W/1080 W
to DIN 3168 L 35 L 50 760 W/820 W

Rated current max. 4.9 A/5.1 A 9.5 A/10.0 A 2.8 A/2.8 A


Start-up current 15.5 A/15.5 A 25.3 A/24.3 A 8.0 A/8.8 A
Pre-fuse T 10.0 A 16.0 A 6.3 A – 10.0 A2)
Power consumption Pel L 35 L 35 690 W/790 W 720 W/800 W
to DIN 3168 L 35 L 50 800 W/890 W 810 W/900 W
.
Refrigeration factor ε = QK/Pel L 35 L 35 1.4
Refrigerant R134a, 500 g
Permissible operating pressure p. max. 25 bar
Temperature and setting range +20°C to +55°C
Protection category External circuit IP 34
to EN 60 529 Internal circuit IP 54
Duty cycle 100 %
Type of connection Plug-in terminal strip
Weight 40 kg 46 kg 46 kg
External circuit 1760 m3/h
Air throughput of fans
Internal circuit 440 m3/h
Temperature control Basic or Comfort controller (factory setting +35°C)
Accessories Packs of Page
Filter mats 3 3286.500 189
Metal filters 1 3286.510 190
Quick-change frame 1 3286.800 182
Door-operated switch 1 4127.000 176
SK BUS system for Comfort controller 1 3124.100 180
RiDiag II including cables for Comfort controller 1 3159.100 195
Interface card for Comfort controller 1 3124.200 179
Air-ducting system 1 3286.870 174
Cover stoppers for interior air outlet 2 3286.880 175
Condensate hose 1 3301.612 192
1) Delivery
times available on request. 2) Transformer protection switch.
Special voltages available on request. We reserve the right to make technical modifications.

Accessories Page 171 Configuration software Page 195

Rittal System Climate Control 75


Roof-mounted cooling units
Useful cooling output 1100/3000 W
59 59
7 7

417

417
5
47 5
89

49 0
0 39

2
39
2 69

Especially for office Property rights: Approvals,


applications. Low noise level (Not with SK 3301.800) see page 278.
Roof-mounted cooling units

(considerably quieter than German registered design


Detailed drawing,
cooling units for industrial no. 402 02 324
see page 246.
applications). German registered design
no. 402 02 325 Performance diagrams,
Supply includes:
available on the Internet.
Nano-coated condenser and
integral electronic condensate Accessories:
evaporation. Fully wired ready
Roof plate for TS 8 with
for connection, including drilling mounting cut-out,
template and assembly parts. see page 181.

Model No. SK with Comfort controller 3273.500 3273.5151) 3301.800


Rated operating voltage V/Hz 230, 1~, 50/60 115, 1~, 50/60 230, 1~, 50
Dimensions in mm WHD 597 x 417 x 475 597 x 417 x 895
.
Useful cooling output QK L 35 L 35 1100 W/1200 W L 35 L 25 3000 W
to DIN 3168 L 35 L 50 850 W/870 W L 45 L 35 3200 W

Rated current max. 5.2 A/5.4 A 11.0 A/11.5 A 9.2 A


Start-up current 15.5 A/16.5 A 32.0 A/35.0 A 36.0 A
Pre-fuse T gG 10.0 A 20.0 A Power circuit-breaker 16.0 A
Power consumption Pel L 35 L 35 890 W/910 W 920 W/940 W L 35 L 25 1820 W
to DIN 3168 L 35 L 50 960 W/1100 W 990 W/1140 W L 45 L 35 2325 W
.
Refrigeration factor ε = QK/Pel L 35 L 35 1.2 1.6
Refrigerant R134a, 700 g R134a, 1200 g
Permissible operating pressure p. max. 25 bar
Temperature and setting range +20°C to +55°C
Protection category External circuit IP 34
to EN 60 529 Internal circuit IP 542)
Duty cycle 100 %
Type of connection Plug-in terminal strip
Weight 42 kg 47 kg 72 kg
Colour RAL 7035
External circuit 1760 m3/h 1850 m3/h
Air throughput of fans
Internal circuit 440 m3/h 1450 m3/h
Temperature control Comfort controller (factory setting +35°C)
Accessories Packs of Page
Filter mats 3 3286.500 3286.600 189
Metal filters 1 3286.510 3286.610 190
Door-operated switch 1 4127.000 176
SK BUS system for Comfort controller 1 3124.100 180
RiDiag II including cables for Comfort controller 1 3159.100 195
Interface card for Comfort controller 1 3124.200 179
Air-ducting system 1 3286.870 3286.970 174
Cover stoppers for interior air outlet 2 3286.880 3286.980 175
Condensate hose 1 3301.612 192
1) Delivery times on request. 2) In order to avoid increased condensation, we recommend enclosures with a protection category of at least IP 54.
Special voltages available on request. We reserve the right to make technical modifications.

Accessories Page 171 Configuration software Page 195

76 Rittal System Climate Control


Roof-mounted cooling units
Useful cooling output 1500/2000 W
59
Property rights:
7 German registered design
no. 402 02 324
German registered design

417
no. 402 02 325

5
47

49 0
0 39

Supply includes: Approvals,


Nano-coated condenser and Accessories: see page 277.

Roof-mounted cooling units


integral electronic condensate Roof plate for TS 8 with Detailed drawing,
evaporation. Fully wired ready mounting cut-out, see page 246.
for connection, including drilling
see page 181.
template and assembly parts. Performance diagrams,
available on the Internet.

Model No. SK with Basic controller, RAL 7035 3384.100 3384.110 3384.140 3385.100 3385.110 3385.140
Model No. SK with Comfort controller, RAL 7035 3384.500 3384.510 3384.540 3385.500 3385.510 3385.540
Model No. SK with Basic controller,
3384.200 3384.210 3384.240 3385.200 3385.210 3385.240
stainless steel1)
Model No. SK with Comfort controller,
3384.600 3384.610 3384.640 3385.600 3385.610 3385.640
stainless steel1)
Rated operating voltage V/Hz 230, 1~, 50/60 115, 1~, 50/60 400, 2~, 50/60 230, 1~, 50/60 115, 1~, 50/60 400, 2~, 50/60
Dimensions in mm WHD 597 x 417 x 475 597 x 417 x 475
.
Useful cooling output QK L 35 L 35 1500 W/1520 W 2000 W/2130 W
to DIN 3168 L 35 L 50 1100 W/1210 W 1570 W/1670 W

Rated current max. 6.3 A/7.4 A 13.7 A/15.3 A 3.8 A/4.4 A 6.3 A/7.2 A 14.2 A/15.4 A 3.7 A/4.2 A
Start-up current 16.6 A/17.1 A 30.7 A/29.1 A 9.8 A/9.6 A 16.8 A/18.4 A 36.0 A/32.0 A 10.0 A/12.0 A
Pre-fuse T 10.0 A 20.0 A 6.3 A – 10.0 A2) 10.0 A 20.0 A 6.3 A – 10.0 A2)
Power consumption Pel L 35 L 35 955 W/1070 W 990 W/1090 W 1140 W/1310 W 1190 W/1390 W
to DIN 3168 L 35 L 50 1090 W/1230 W 1140 W/1290 W 1240 W/1450 W 1300 W/1520 W
.
Refrigeration factor ε = QK/Pel L 35 L 35 1.6 1.5 1.8 1.7
Refrigerant R134a, 500 g R134a, 950 g
Permissible operating pressure p. max. 25 bar
Temperature and setting range +20°C to +55°C
Protection category External circuit IP 34
to EN 60 529 Internal circuit IP 54
Duty cycle 100 %
Type of connection Plug-in terminal strip
Weight 41 kg 47 kg 47 kg 42 kg 48 kg 48 kg
External circuit 1760 m3/h 1820 m3/h
Air throughput of fans
Internal circuit 470 m3/h
Temperature control Basic or Comfort controller (factory setting +35°C)
Accessories Packs of Page
Filter mats 3 3286.500 189
Metal filters 1 3286.510 190
Quick-change frame 1 3286.800 182
Door-operated switch 1 4127.000 176
SK BUS system for Comfort controller 1 3124.100 180
RiDiag II including cables
1 3159.100 195
for Comfort controller
Interface card for Comfort controller 1 3124.200 179
Air-ducting system 1 3286.870 174
Cover stoppers for interior air outlet 2 3286.880 175
Condensate hose 1 3301.612 192
1) Delivery
times available on request. 2) Transformer protection switch.
Special voltages available on request. We reserve the right to make technical modifications.
Accessories Page 171 Configuration software Page 195

Rittal System Climate Control 77


Roof-mounted cooling units
Useful cooling output 3000/4000 W
79
Property rights:
6 German registered design
no. 402 02 324
German registered design

470
no. 402 02 325

0
58

69 2
2 39

Supply includes: Approvals,


Nano-coated condenser and Accessories: see page 277.
Roof-mounted cooling units

integral electronic condensate Roof plate for TS 8 with Detailed drawing,


evaporation. mounting cut-out, see page 246.
Fully wired ready for connection,
see page 181.
including drilling template, Performance diagrams,
eyebolt and assembly parts. available on the Internet.

Model No. SK with Basic controller, RAL 7035 3386.140 3387.140


Model No. SK with Comfort controller, RAL 7035 3386.540 3387.540
Model No. SK with Basic controller, stainless steel1) 3386.240 3387.240
Model No. SK with Comfort controller, stainless steel1) 3386.640 3387.640
Rated operating voltage V/Hz 400, 3~, 50/460, 3~, 60 400, 3~, 50/460, 3~, 60
Dimensions in mm WHD 796 x 470 x 580 796 x 470 x 580
.
Useful cooling output QK L 35 L 35 3000 W/3300 W 4000 W/4200 W
to DIN 3168 L 35 L 50 2200 W/2500 W 3250 W/3490 W

Rated current max. 3.4 A/3.4 A 3.9 A/3.9 A


Start-up current 8.0 A/9.0 A 17.0 A/19.0 A
Pre-fuse T Motor circuit breaker 6.3 A – 10.0 A
Power consumption Pel L 35 L 35 1320 W/1630 W 1760 W/2200 W
to DIN 3168 L 35 L 50 1570 W/1910 W 2010 W/2480 W
.
Refrigeration factor ε = QK/Pel L 35 L 35 2.3
Refrigerant R134a, 1600 g R134a, 1800 g
Permissible operating pressure p. max. 25 bar
Temperature and setting range +20°C to +55°C
External circuit IP 34
Protection category to EN 60 529
Internal circuit IP 54
Duty cycle 100 %
Type of connection Plug-in terminal strip
Weight 70 kg 77 kg
External circuit 3450 m3/h 3870 m3/h
Air throughput of fans
Internal circuit 1280 m3/h 1420 m3/h
Temperature control Basic or Comfort controller (factory setting +35°C)
Accessories Packs of Page
Filter mats 3 3286.600 189
Metal filters 1 3286.610 190
Quick-change frame 1 3286.900 182
Door-operated switch 1 4127.000 176
SK BUS system for Comfort controller 1 3124.100 180
RiDiag II including cables for Comfort controller 1 3159.100 195
Interface card for Comfort controller 1 3124.200 179
Air-ducting system 1 3286.970 174
Cover stoppers for interior air outlet 2 3286.980 175
Condensate hose 1 3301.612 192
1) Delivery
times available on request.
Special voltages available on request. We reserve the right to make technical modifications.

Accessories Page 171 Configuration software Page 195

78 Rittal System Climate Control


Roof-mounted cooling units
with CO2 as the coolant, useful cooling output 1000 W
59
7

417
5
47

49 0
0 39

Environmentally friendly Approvals,


coolant Accessories: see page 278.

Roof-mounted cooling units


This generation of cooling units Roof plate for TS 8 with Detailed drawing,
already uses the alternative CO2 mounting cut-out, see page 246.
as the coolant for generating the
see page 181.
cooling power.
Supply includes:
Nano-coated condenser and
integral electronic condensate
evaporation.
Fully wired ready for connection,
including drilling template and
assembly parts.

Model No. SK with Comfort controller 3383.740


Rated operating voltage V/Hz 230, 50/60
Dimensions in mm WHD 597 x 417 x 475
.
Useful cooling output QK
L 35 L 35 1000 W
to DIN 3168

Temperature and setting range +20°C to +55°C


External circuit IP 34
Protection category to EN 60 529
Internal circuit IP 54
Duty cycle 100 %
Type of connection Plug-in terminal strip
Weight 42 kg
Colour RAL 7035
External circuit 1760 m3/h
Air throughput of fans
Internal circuit 440 m3/h
Temperature control Comfort controller (factory setting +35°C)
Accessories Packs of Page
Filter mats 3 3286.500 189
Metal filters 1 3286.510 190
Door-operated switch 1 4127.000 176
Air-ducting system 1 3286.870 174
Cover stoppers for interior air outlet 2 3286.880 175
Condensate hose 1 3301.612 192
We reserve the right to make technical modifications. Other specifications available upon request.

Accessories Page 171 Configuration software Page 195

Rittal System Climate Control 79


Wall-mounted cooling units
Wall-mounted cooling units

Top design and top performance with a host of air/air heat exchangers allows easy adaptation to the

assembly benefits. The Rittal platform strategy with required cooling output, even retrospectively.

system-wide mounting cut-outs to fit cooling units and

80 Rittal System Climate Control


Integrated into TopTherm-
Plus cooling units
Electrical condensate evaporation
Condensate arising inside the enclosure
or on the evaporator coil of the cooling unit
is effectively evaporated. The evaporator
device inside the cooling units has a very
high evaporation output (several litres per
day). This is achieved thanks to the princi-
ple of direct evaporation.
RiNano coating
The standard nano-surface finish on heat
exchanger membranes ensures a long,
constant cooling output and eliminates the
need for filter media in many areas.

Wall-mounted cooling units


Versatility and
flexibility of wall
mounting
Wall-mounted cooling units –
practical and elegant.
Determination of the mounting cut-
out depends on the mounting vari-
ant – external, internal or partial
internal mounting. This makes opti-
mum use of the space available.
With external mounting, openings
are only required for air inlet and
outlet. The enclosure surface con-
taining the cut-out for partial or full
internal mounting is stabilised by
the divided internal case construc- Platform strategy
tion. Special internal or external Flexible performance
mounting kits are not required. Just 5 mounting cut-outs for 8 different out-
put categories provide investment security
and facilitate easy adaptation of the cooling
output to the ambient conditions and the
installed heat loss.
Rittal platform strategy
TopTherm air/air heat exchangers are also
compatible with the mounting cut-outs.

Benefits at a glance Important Tips and tricks


● Super-efficient performance and energy Air inlet and outlet openings in the internal Applications see page 207
consumption and external circuit must not be obstructed
Selection criteria see page 208
● Wide output range from 225 to 4000 W by electrical installations.
● Controlling and monitoring via Basic or Assembly see page 209
Comfort controller
Air routing see page 210
● Three-phase cooling units support
multiple voltages as standard Condensate management see page 213
● Uniform, output-related, cross-system
Electrical connection
mounting cut-outs, to match TopTherm-
and control see page 215
Plus air/air heat exchangers
● Electrical condensate evaporation and
RiNano coating

Rittal System Climate Control 81


Wall-mounted cooling units
VIP small cooling units, useful cooling output 225 W

5
10 52
6

296
32 32
18 60
3

353.5
60

353.5
28
8
46
5 1
18
3
1 5
10
46 28
5 8

296
The new VIP SK small cooling Supply includes: 1 Distance from installed Approvals,
units were developed especially Fully wired ready for connection equipment at least 60 mm see page 279.
Wall-mounted cooling units

for cooling the VIP 6000 com- and pre-mounted on an


Performance diagrams,
mand panel. In addition, VIP aluminium rear panel to fit
available on the Internet.
small cooling units also offer a VIP 6000 operating housing 7 U.
space-saving, economical solu-
Property rights:
tion for the climate control of
German patent no. 198 17 917
small enclosures where small
heat loads are generated by the
system.

Model No. SK 3201.100 3202.100


Condenser version Left Right
Rated operating voltage V/Hz 230, 50/60
W 526
Dimensions in mm H 353.5
D 105
.
Useful cooling output QK L 35 L 35 225 W/270 W
to DIN 3168 L 35 L 45 160 W/200 W

Rated current max. 1.5 A/1.5 A


Start-up current 1.9 A/2.0 A
Pre-fuse T 4.0 A/4.0 A
Power consumption Pel L 35 L 35 285 W/300 W
to DIN 3168 L 35 L 45 315 W/325 W
.
Refrigeration factor ε = QK/Pel L 35 L 35 0.8/0.9
Refrigerant R134a, 170 g
Permissible operating pressure p. max. 27 bar
Temperature and setting range +20°C to +45°C
Protection category External circuit IP 24
to EN 60 529 Internal circuit IP 54
Duty cycle 100 %
Type of connection Terminal strip
Weight 10.5 kg
Colour Rear panel aluminium, vent grille RAL 7035
External circuit 235 m3/h / 270 m3/h
Air throughput of fans
Internal circuit 160 m3/h / 180 m3/h
Temperature control Electronic control (factory setting +35°C)
Accessories Packs of Page
Temperature indicator 1 3114.100 177
Condensate hose 1 3301.608 192
Special voltages available on request. We reserve the right to make technical modifications.

Accessories Page 171 Configuration software Page 195

82 Rittal System Climate Control


Wall-mounted cooling units
Mini cooling unit in horizontal format, useful cooling output 300 W

340
52
5

15
3 98
55

Mini cooling units in horizontal Supply includes: Approvals,


format, ideal for cooling small Nano-coated condenser. Fully see page 279.

Wall-mounted cooling units


enclosures and operating hous- wired ready for connection,
Detailed drawing,
ings with optimum space utilisa- including drilling template and
see page 247.
tion. assembly parts.
Performance diagrams,
available on the Internet.

Model No. SK 3302.300 3302.310


Rated operating voltage V/Hz 230, 1~, 50/60 115, 1~, 60
W 525
Dimensions in mm H 340
D 153
.
Useful cooling output QK L 35 L 35 300 W/320 W 300 W
to DIN 3168 L 35 L 50 150 W/160 W 150 W

Rated current max. 1.6 A/1.7 A 4.0 A


Start-up current 4.3 A/5.3 A 12.0 A
Pre-fuse T 10.0 A 10.0 A
Power consumption Pel L 35 L 35 285 W/300 W 290 W
to DIN 3168 L 35 L 50 320 W/340 W 340 W
.
Refrigeration factor ε = QK/Pel L 35 L 35 1.1
Refrigerant R134a, 100 g R134a, 95 g
Permissible operating pressure p. max. 25 bar
Temperature and setting range +20°C to +55°C
Protection category External circuit IP 34
to EN 60 529 Internal circuit IP 54
Duty cycle 100 %
Type of connection Plug-in terminal strip
Weight 13 kg
Colour RAL 7035
External circuit 345 m3/h
Air throughput of fans
Internal circuit 310 m3/h
Temperature control Basic controller
Accessories Packs of Page
Temperature indicator 1 3114.100 177
Condensate hose 1 3301.608 192
Filter mats 3 3286.110 189
Metal filters 1 3286.120 190
Special voltages available on request. We reserve the right to make technical modifications.

Accessories Page 171 Configuration software Page 195

Rittal System Climate Control 83


Wall-mounted cooling units
Useful cooling output 300/500 W

550
28
0 00 T2
01
T 11 42

T = Depth

Supply includes: 1 Partial internal mounting Property rights:


Nano-coated condenser. Fully possible with 3303.XXX German registered design
Wall-mounted cooling units

wired ready for connection, only. no. 402 02 324 and


including drilling template and no. 402 02 325
Approvals,
assembly parts. Japanese registered design
see page 280.
no. 1 187 896
Detailed drawing, Indian registered design
see page 247. no. 189 953
US design patent no. D 488,480
Performance diagrams,
IR reg. design no. DM/061 967
available on the Internet.
with validity for FR, IT, ES

Model No. SK with Basic controller, RAL 7035 3302.100 3302.110 3303.100 3303.110
Model No. SK with Comfort controller, RAL 7035 – – 3303.500 3303.510
Model No. SK with Basic controller, stainless steel1) 3302.200 3302.210 3303.200 3303.210
Model No. SK with Comfort controller, stainless steel1) – – 3303.600 3303.610
Rated operating voltage V/Hz 230, 1~, 50/60 115, 1~, 60 230, 1~, 50/60 115, 1~, 60
W 280 280
H 550 550
Dimensions in mm
T 140 210
T2 98 164
.
Useful cooling output QK L 35 L 35 300 W/320 W 300 W 500 W/610 W 500 W
to DIN 3168 L 35 L 50 150 W/170 W 150 W 280 W/350 W 280 W

Rated current max. 1.6 A/1.7 A 3.3 A 2.6 A/2.6 A 5.7 A


Start-up current 3.0 A/3.4 A 8.0 A 5.1 A/6.4 A 11.5 A
Pre-fuse T 10.0 A 10.0 A 10.0 A 10.0 A
Power consumption Pel L 35 L 35 245 W/255 W 290 W 360 W/380 W 470 W
to DIN 3168 L 35 L 50 255 W/275 W 340 W 420 W/390 W 500 W
.
Refrigeration factor ε = QK/Pel L 35 L 35 1.2 1.4
Refrigerant R134a, 100 g R134a, 170 g
Permissible operating pressure p. max. 25 bar 28 bar
Temperature and setting range +20°C to +55°C
Protection category External circuit IP 34
to EN 60 529 Internal circuit IP 54
Duty cycle 100 %
Type of connection Plug-in terminal strip
Weight 13 kg 17 kg
External circuit 310 m3/h 345 m3/h
Air throughput of fans
Internal circuit 345 m3/h 310 m3/h
Temperature control Basic or Comfort controller (factory setting +35°C)
Accessories Packs of Page
Filter mats 3 3286.300 189
Metal filters 1 3286.310 190
Door-operated switch 1 4127.000 176
SK BUS system for Comfort controller 1 – 3124.100 180
RiDiag II including cables for Comfort controller 1 – 3159.100 195
Interface card for Comfort controller 1 – 3124.200 179
Condensate hose 1 3301.608 3301.610 192
1) Delivery
times available on request.
Special voltages available on request. We reserve the right to make technical modifications.

Accessories Page 171 Configuration software Page 195

84 Rittal System Climate Control


Wall-mounted cooling units
Useful cooling output 750 W

550
28 5
0 25 23
51
28
0 15 45

Supply includes: Approvals, Property rights:


Nano-coated condenser. Fully see page 280. German registered design

Wall-mounted cooling units


wired ready for connection, no. 402 02 324 and
Detailed drawing,
including drilling template and no. 402 02 325
see page 247.
assembly parts. Japanese registered design
Performance diagrams, no. 1 187 896
available on the Internet. Indian registered design
no. 189 953
US design patent no. D 488,480
IR reg. design no. DM/061 967
with validity for FR, IT, ES

Model No. SK with Basic controller, RAL 7035 3361.100 3361.110 3361.140
Model No. SK with Comfort controller, RAL 7035 3361.500 3361.510 3361.540
Model No. SK with Basic controller, stainless steel1) 3361.200 3361.210 3361.240
Model No. SK with Comfort controller, stainless steel1) 3361.600 3361.610 3361.640
Rated operating voltage V/Hz 230, 1~, 50/603) 115, 1~, 603) 4002), 2~, 50/603)
W 280
Dimensions in mm H 550
D 280
.
Useful cooling output QK L 35 L 35 750 W/780 W 750 W 750 W/780 W
to DIN 3168 L 35 L 50 510 W/540 W 500 W 510 W/540 W

Rated current max. 2.3 A/2.4 A 5.3 A 1.2 A/1.4 A


Start-up current 5.6 A/5.6 A 12.0 A 3.1 A/3.3 A
Pre-fuse T 10.0 A 10.0 A 6.3 A – 10.0 A4)
Power consumption Pel L 35 L 35 480 W/550 W 570 W 480 W/550 W
to DIN 3168 L 35 L 50 530 W/640 W 670 W 530 W/640 W
.
Refrigeration factor ε = QK/Pel L 35 L 35 1.5
Refrigerant R134a, 280 g R134a, 260 g R134a, 280 g
Permissible operating pressure p. max. 28 bar
Temperature and setting range +20°C to +55°C
Protection category External circuit IP 34
to EN 60 529 Internal circuit IP 54
Duty cycle 100 %
Type of connection Plug-in terminal strip
Weight 22 kg
Air throughput of fans External circuit 480 m3/h
(unimpeded air flow) Internal circuit 600 m3/h
Temperature control Basic or Comfort controller (factory setting +35°C)
Accessories Packs of Page
Filter mats 3 3286.300 189
Metal filters 1 3286.310 190
Door-operated switch 1 4127.000 176
SK BUS system for Comfort controller 1 3124.100 180
RiDiag II including cables for Comfort controller 1 3159.100 195
Interface card for Comfort controller 1 3124.200 179
Condensate hose 1 3301.610 192
1) Delivery times on request. 2) External toroidal core transformer Ø 126 x 65 mm deep for mounting in the enclosure. 3) Tu max. = 52°C/60 Hz.
4) Transformer protection switch.
Special voltages available on request. Technical modifications reserved.

Accessories Page 171 Configuration software Page 195

Rittal System Climate Control 85


Wall-mounted cooling units
Cool Efficiency, useful cooling output 1000 W

950
40 0
0 05 21
0 51 50
26 15

NEW 45 % less tion


p
up to y consum
energ

Supply includes: Approvals,


Nano-coated condenser and see page 280.
Wall-mounted cooling units

integral condensate evapo-


Detailed drawing,
ration. Fully wired ready for
see page 248.
connection, including drilling
template and assembly parts. Performance diagrams,
available on the Internet.

Model No. SK with Basic controller, RAL 7035 3304.700


Model No. SK with Comfort controller, RAL 7035 3304.800
Rated operating voltage V/Hz 230, 1~, 50
W 400
Dimensions in mm H 950
D 260
.
Useful cooling output QK
L35 L35 1000 W
to DIN 3168

Rated current max. 3.0 A


Start-up current 12.0 A
Pre-fuse T 10.0 A
Power consumption Pel L 35 L 35 520 W
to DIN 3168 L 35 L 45 580 W
.
Refrigeration factor ε = QK/Pel L 35 L 35 1.9
Refrigerant R134a, 325 g
Permissible operating pressure p. max. 20 bar
Temperature and setting range +20°C to +45°C
Protection category External circuit IP 34
to EN 60 529 Internal circuit IP 54
Duty cycle 100 %
Type of connection Plug-in terminal strip
Weight 40 kg
External circuit 600 m3/h
Air throughput of fans
Internal circuit 450 m3/h
Temperature control Basic or Comfort controller (factory setting +35°C)
Accessories Packs of Page
Filter mats 3 3286.400 189
Metal filters 1 3286.410 190
Door-operated switch 1 4127.000 176
SK BUS system for Comfort controller 1 3124.100 180
RiDiag II including cables
1 3159.100 195
for Comfort controller
Interface card for Comfort controller 1 3124.200 179
Condensate hose 1 3301.612 192
Delivery times on request.
Special voltages and other output categories available on request. Technical modifications reserved.

Accessories Page 171 Configuration software Page 195

86 Rittal System Climate Control


Wall-mounted cooling units
Useful cooling output 1000/1500 W

950
40 0
0 05 21
0 51 50
26 15

Supply includes: Approvals, Property rights:


Nano-coated condenser and see page 280. German registered design

Wall-mounted cooling units


integral electronic condensate no. 402 02 325
Detailed drawing,
evaporation. Fully wired ready IR reg. design no. DM/062 557
see page 248.
for connection, including drilling with validity for FR, IT, ES
template and assembly parts. Performance diagrams, Indian registered design
available on the Internet. no. 190 269
Japanese registered design
no. 1 187 905

Model No. SK with Basic controller, RAL 7035 3304.100 3304.110 3304.140 3305.100 3305.110 3305.140
Model No. SK with Comfort controller, RAL 7035 3304.500 3304.510 3304.540 3305.500 3305.5101) 3305.540
Model No. SK with Basic controller,
3304.200 3304.210 3304.240 3305.200 3305.210 3305.240
stainless steel1)
Model No. SK with Comfort controller,
3304.600 3304.610 3304.640 3305.600 3305.610 3305.640
stainless steel1)
400, 3~, 50/ 400, 3~, 50/
Rated operating voltage V/Hz 230, 1~, 50/60 115, 1~, 50/60 230, 1~, 50/60 115, 1~, 50/60
460, 3~, 60 460, 3~, 60
W 400 400
Dimensions in mm H 950 950
D 260 260
.
Useful cooling output QK L 35 L 35 1000 W/1060 W 1500 W/1510 W
to DIN 3168 L 35 L 50 790 W/840 W 1230 W/1250 W

Rated current max. 5.4 A/5.0 A 10.6 A/11.1 A 2.8 A/2.9 A 6.0 A/6.5 A 12.1 A/13.6 A 2.6 A/2.9 A
Start-up current 12.0 A/14.0 A 26.0 A/28.0 A 11.5 A/12.7 A 22.0 A/24.0 A 42.0 A/46.0 A 12.2 A/11.3 A
Pre-fuse T 10.0 A 16.0 A 6.3 A – 10.0 A2) 16.0 A 20.0 A 6.3 A – 10.0 A2)
Power consumption Pel L 35 L 35 825 W/775 W 850 W/800 W 700 W/675 W 975 W/1125 W 1000 W/1175 W 925 W/1100 W
to DIN 3168 L 35 L 50 875 W/835 W 900 W/875 W 785 W/800 W 1125 W/1285 W 1165 W/1325 W 1085 W/1275 W
.
Refrigeration factor ε = QK/Pel L 35 L 35 1.2 1.4 1.5 1.6
Refrigerant R134a, 325 g R134a, 500 g R134a, 600 g
Permissible operating pressure p. max. 25 bar
Temperature and setting range +20°C to +55°C
Protection category External circuit IP 34
to EN 60 529 Internal circuit IP 54
Duty cycle 100 %
Type of connection Plug-in terminal strip
Weight 39 kg 44 kg 40 kg 41 kg 46 kg 42 kg
External circuit 900 m3/h
Air throughput of fans
Internal circuit 600 m3/h 800 m3/h
Temperature control Basic or Comfort controller (factory setting +35°C)
Accessories Packs of Page
Filter mats 3 3286.400 189
Metal filters 1 3286.410 190
Door-operated switch 1 4127.000 176
SK BUS system for Comfort controller 1 3124.100 180
RiDiag II including cables
1 3159.100 195
for Comfort controller
Interface card for Comfort controller 1 3124.200 179
Condensate hose 1 3301.612 192
1) Delivery
times available on request. 2) Motor circuit-breaker.
Special voltages available on request. We reserve the right to make technical modifications.

Accessories Page 171 Configuration software Page 195

Rittal System Climate Control 87


Wall-mounted cooling units
Slimline, useful cooling output 1500 W

1590

1590
0 0
43 14 43 14
5
20
5 65 5 5
16 25

● Simple, fast assembly without Supply includes: Approvals,


the need to drill additional Nano-coated condenser and see page 281/282.
Wall-mounted cooling units

holes integral electronic condensate


Detailed drawing,
● Ideal for restricted mounting evaporation. Fully wired ready
see page 249.
locations for connection, including drilling
● Super-slimline design template and assembly parts. Performance diagrams,
● Minimal installation depth and available on the Internet.
build height.

Model No. SK with Basic controller, RAL 7035 3366.100 3377.1001) 3366.110 3377.1101) 3366.140 3377.1401)
Model No. SK with Comfort controller, RAL 7035 3366.500 3377.5001) 3366.510 3377.5101) 3366.540 3377.5401)
Model No. SK with Basic controller,
3366.200 3377.200 3366.210 3377.210 3366.240 3377.240
stainless steel1)
Model No. SK with Comfort controller,
3366.600 3377.600 3366.610 3377.610 3366.640 3377.640
stainless steel1)
Rated operating voltage V/Hz 230, 1~, 50/60 115, 1~, 50/60 400, 3~, 50/460, 3~, 60
W 435 435 435 435 435 435
Dimensions in mm H 1590 1590 1590 1590 1590 1590
D 205 165 205 165 205 165
.
Useful cooling output QK L 35 L 35 1500 W/1500 W 1500 W/1500 W
to DIN 3168 L 35 L 50 1050 W/1100 W 980 W/1080 W

Rated current max. 7.1 A/7.3 A 14.3 A/14.7 A 3.0 A/3.1 A


Start-up current 22.0 A/24.0 A 43.0 A/47.0 A 8.0 A/8.8 A
Pre-fuse T 10.0 A 20.0 A 6.3 A – 10.0 A2)
Power consumption Pel L 35 L 35 1045 W/1175 W 1075 W/1200 W 1090 W/1240 W
to DIN 3168 L 35 L 50 1220 W/1335 W 1265 W/1375 W 1260 W/1430 W
.
Refrigeration factor ε = QK/Pel L 35 L 35 1.4 1.3
Refrigerant R134a, 700 g
Permissible operating pressure p. max. 28 bar
Temperature and setting range +20°C to +55°C
Protection category External circuit IP 34
to EN 60 529 Internal circuit IP 54
Duty cycle 100 %
Type of connection Plug-in terminal strip
Weight 45 kg 50 kg 46 kg
Air throughput of fans External circuit 910 m3/h
(unimpeded air flow) Internal circuit 860 m3/h
Temperature control Basic or Comfort controller (factory setting +35°C)
Accessories Packs of Page
Filter mats 3 3286.400 3253.010 3286.400 3253.010 3286.400 3253.010 189
Metal filters 1 3286.410 3253.220 3286.410 3253.220 3286.410 3253.220 190
Trim frame for external device mounting 1 3377.000 182
Door-operated switch 1 4127.000 176
SK BUS system for Comfort controller 1 3124.100 180
RiDiag II including cables
1 3159.100 195
for Comfort controller
Interface card for Comfort controller 1 3124.200 179
Condensate hose 1 3301.612 192
1) Delivery
times available on request. 2) Motor circuit-breaker.
Special voltages available on request. Technical modifications reserved.

Accessories Page 171 Configuration software Page 195

88 Rittal System Climate Control


Wall-mounted cooling units
Useful cooling output 2000/2500 W

40

1580
5
40 45 24
0 5 01
29 15 50

Supply includes: panel fasteners (TS 8800.071),


Nano-coated condenser and Also required: see Cat. 32, page 918.

Wall-mounted cooling units


integral electronic condensate For installation in the door, we Approvals,
evaporation. Fully wired ready recommend the use of the ride- see page 280.
for connection, including drilling
up roller (TS 4538.000) see
template, eyebolt and assembly Cat. 32, page 967 and 180° Detailed drawing,
parts. hinges (TS 8800.710), see see page 248.
Cat. 32, page 961, and for use Performance diagrams,
in the side panel we recommend available on the Internet.
the use of the TS enclosure

Model No. SK with Basic controller, RAL 7035 3328.100 3328.110 3328.140 3329.100 3329.110 3329.140
Model No. SK with Comfort controller, RAL 7035 3328.500 3328.510 3328.540 3329.500 3329.510 3329.540
Model No. SK with Basic controller,
3328.200 3328.210 3328.240 3329.200 3329.210 3329.240
stainless steel1)
Model No. SK with Comfort controller,
3328.600 3328.610 3328.640 3329.600 3329.610 3329.640
stainless steel1)
400, 3~, 50/ 400, 3~, 50/
Rated operating voltage V/Hz 230, 1~, 50/60 115, 1~, 50/60 230, 1~, 50/60 115, 1~, 50/60
460, 3~, 60 460, 3~, 60
W 400 400
Dimensions in mm H 1580 1580
D 295 295
.
Useful cooling output QK L 35 L 35 2000 W/2350 W 2500 W/2750 W 2500 W/2700 W
to DIN 3168 L 35 L 50 1450 W/1690 W 1600 W/1750 W 1900 W/1950 W

Rated current max. 7.5 A/9.1 A 14.7 A/17.3 A 2.8 A/3.3 A 8.6 A/10.6 A 17.0 A/22.0 A 3.7 A/3.8 A
Start-up current 22.0 A/26.0 A 36.0 A/39.0 A 6.8 A/7.8 A 21.0 A/21.0 A 44.0 A/42.0 A 6.8 A/7.6 A
Pre-fuse T 16.0 A 25.0 A 6.3 A – 10.0 A2) 16.0 A 25.0 A 6.3 A – 10.0 A2)
Power consumption Pel L 35 L 35 1025 W/1200 W 1085 W/1250 W 1050 W/1275 W 1450 W/1675 W 1500 W/1725 W 1425 W/1625 W
to DIN 3168 L 35 L 50 1250 W/1350 W 1300 W/1410 W 1275 W/1525 W 1625 W/2000 W 1675 W/2065 W 1675 W/1975 W
.
Refrigeration factor ε = QK/Pel L 35 L 35 2.0 1.8 1.9 1.7 1.8
Refrigerant R134a, 950 g
Permissible operating pressure p. max. 28 bar
Temperature and setting range +20°C to +55°C
Protection category External circuit IP 34
to EN 60 529 Internal circuit IP 54
Duty cycle 100 %
Type of connection Plug-in terminal strip
Weight 66 kg 73 kg 67 kg 69 kg 76 kg 70 kg
External circuit 640 m3/h 710 m3/h
Air throughput of fans
Internal circuit 550 m3/h 640 m3/h
Temperature control Basic or Comfort controller (factory setting +35°C)
Accessories Packs of Page
Filter mats 3 3286.400 189
Metal filters 1 3286.410 190
Door-operated switch 1 4127.000 176
SK BUS system for Comfort controller 1 3124.100 180
RiDiag II including cables
1 3159.100 195
for Comfort controller
Interface card for Comfort controller 1 3124.200 179
Condensate hose 1 3301.612 192
1) Delivery times available on request. 2) Motor circuit-breaker. Special voltages available on request. Technical modifications reserved.
Accessories Page 171 Configuration software Page 195

Rittal System Climate Control 89


Wall-mounted cooling units
Useful cooling output 4000 W

1580
50 45
0 0 51
34 19

Supply includes: Note: Approvals,


Nano-coated condenser and External mounting and partial Also required: see page 280.
Wall-mounted cooling units

integral electronic condensate internal mounting of the cooling When mounting in the door: Detailed drawing,
evaporation. Fully wired ready unit are available as standard. Ride-up roller (TS 4538.000), see page 248.
for connection, including drilling Partial internal mounting not
see Cat. 32, page 967.
template, eyebolt and assembly possible with: When fitted with 180° hinges Performance diagrams,
parts. – 600 mm wide TS enclosures (TS 8800.710), available on the Internet.
and
see Cat. 32, page 961.
– 1200 mm wide TS enclosures When mounting in the side
in the lockable door. panel: Enclosure panel fasteners
(TS 8800.071),
see Cat. 32, page 918.
Model No. SK with Basic controller, RAL 7035 3332.140
Model No. SK with Comfort controller, RAL 7035 3332.540
Model No. SK with Basic controller, stainless steel1) 3332.240
Model No. SK with Comfort controller, stainless steel1) 3332.640
Rated operating voltage V/Hz 400, 3~, 50/460, 3~, 60
W 500
Dimensions in mm H 1580
D 340
.
Useful cooling output QK L 35 L 35 4000 W/4400 W
to DIN 3168 L 35 L 50 3070 W/3570 W

Rated current max. 4.2 A/4.2 A


Start-up current 9.2 A/11.0 A
Pre-fuse T Motor circuit-breaker 6.3 A – 10.0 A
Power consumption Pel L 35 L 35 1850 W/2250 W
to DIN 3168 L 35 L 50 2120 W/2590 W
.
Refrigeration factor ε = QK/Pel L 35 L 35 2.1
Refrigerant R134a, 3000 g
Permissible operating pressure p. max. 28 bar
Temperature and setting range +20°C to +55°C
Protection category External circuit IP 34
to EN 60 529 Internal circuit IP 54
Duty cycle 100 %
Type of connection Plug-in terminal strip
Weight 91 kg
External circuit 2000 m3/h
Air throughput of fans
Internal circuit 1500 m3/h
Temperature control Basic or Comfort controller (factory setting +35°C)
Accessories Packs of Page
Filter mats 3 3286.400 189
Metal filters 1 3286.410 190
Door-operated switch 1 4127.000 176
SK BUS system for Comfort controller 1 3124.100 180
RiDiag II including cables for Comfort controller 1 3159.100 195
Interface card for Comfort controller 1 3124.200 179
Condensate hose 1 3301.612 192
1) Delivery
times available on request.
Special voltages available on request. Technical modifications reserved.

Accessories Page 171 Configuration software Page 195

90 Rittal System Climate Control


Wall-mounted cooling units
Design NEMA 4x, useful cooling output 500/1000/1500 W

8
29
8
35

620

1020
8
23
8
28
5 29

40
5

Supply includes: Approvals,


Nano-coated condenser and see page 282.

Wall-mounted cooling units


partly integral electrical
Detailed drawing,
condensate evaporation. Fully
see page 249.
wired ready for connection,
including drilling template and Performance diagrams,
assembly parts. available on the Internet.

Model No. SK with Basic controller1) 3303.1043) 3303.1143) 3304.104 3304.114 3304.144 3305.104 3305.114 3305.144
Model No. SK with Comfort controller1) 3303.5043) 3303.5143) 3304.504 3304.514 3304.544 3305.504 3305.514 3305.544
230, 1~, 115, 1~, 230, 1~, 115, 1~, 400, 3~, 50/ 230, 1~, 115, 1~, 400, 3~, 50/
Rated operating voltage V/Hz
50/60 60 50/60 50/60 460, 3~, 60 50/60 50/60 460, 3~, 60
W 285 405 405
Dimensions in mm H 620 1020 1020
D 298 358 358
.
Useful cooling output QK L 35 L 35 500 W/610 W 500 W 1000 W/1060 W 1500 W/1510 W
to DIN 3168 L 35 L 50 280 W/350 W 280 W 790 W/840 W 1230 W/1250 W

Rated current max. 2.6/2.6 A 5.7 A 5.4/5.0 A 10.6/11.1 A 2.8/2.9 A 6.0/6.5 A 12.1/13.6 A 2.6/2.9 A
Start-up current 5.1/6.4 A 11.5 A 12.0/14.0 A 26.0/28.0 A 11.5/12.7 A 22.0/24.0 A 42.0/46.0 A 12.2/11.3 A
6.3 A – 6.3 A –
Pre-fuse T 10.0 A 10.0 A 10.0 A 16.0 A 16.0 A 20.0 A
10.0 A2) 10.0 A2)
Power consumption Pel L 35 L 35 360/380 W 470 W 825/775 W 850/800 W 700/675 W 975/1125 W 1000/1175 W 925/1100 W
to DIN 3168 L 35 L 50 420/390 W 500 W 875/835 W 900/875 W 785/800 W 1125/1285 W 1165/1325 W 1085/1275 W
.
Refrigeration factor ε = QK/Pel L 35 L 35 1.4 1.7 1.8 1.7 1.9
R134a,
Refrigerant R134a, 170 g R134a, 325 g R134a, 600 g
500 g
Permissible operating pressure p. max. 28 bar 25 bar 25 bar
Temperature and setting range +20°C to +55°C
Protection rating NEMA 4x
Duty cycle 100 %
Type of connection Plug-in terminal strip
Weight 25 kg 49 kg 54 kg 50 kg 51 kg 56 kg 52 kg
Material Stainless steel 1.4404 (V4A) (AISI 316L)
Air throughput External circuit 345 m3/h 900 m3/h 900 m3/h
of fans Internal circuit 310 m3/h 600 m3/h 800 m3/h
Temperature control Basic or Comfort controller (factory setting +35°C)
Packs
Accessories Page
of
Door-operated switch 1 4127.000 176
SK BUS system for Comfort controller 1 3124.100 – 3124.100 180
RiDiag II including cables
1 3159.100 195
for Comfort controller
Interface card
1 3124.200 179
for Comfort controller
Condensate hose 1 3301.610 3301.612 192
1) Delivery
times available on request. 2) Motor circuit-breaker. 3) Without integral condensate evaporation.
Special voltages available on request. We reserve the right to make technical modifications.

Accessories Page 171 Configuration software Page 195

Rittal System Climate Control 91


Wall-mounted cooling units
Design NEMA 4x, useful cooling output 2000/2500 W

8
38

1650
8
32

40
5

Supply includes: Approvals,


Nano-coated condenser and see page 282.
Wall-mounted cooling units

integral electronic condensate


Detailed drawing,
evaporation. Fully wired ready
see page 250.
for connection, including drilling
template and assembly parts. Performance diagrams,
available on the Internet.

Model No. SK with Basic controller1) 3328.104 3328.114 3328.144 3329.104 3329.114 3329.144
Model No. SK with Comfort controller1) 3328.504 3328.514 3328.544 3329.504 3329.514 3329.544
400, 3~, 50/ 400, 3~, 50/
Rated operating voltage V/Hz 230, 1~, 50/60 115, 1~, 50/60 230, 1~, 50/60 115, 1~, 50/60
460, 3~, 60 460, 3~, 60
W 405
Dimensions in mm H 1650
D 388
.
Useful cooling output QK L 35 L 35 2000 W/2350 W 2500 W/2750 W 2500 W/2700 W
to DIN 3168 L 35 L 50 1450 W/1690 W 1600 W/1750 W 1900 W/1950 W

Rated current max. 7.5 A/9.1 A 14.7 A/17.3 A 2.8 A/3.3 A 8.6 A/10.6 A 17.0 A/22.0 A 3.7 A/3.8 A
Start-up current 22.0 A/26.0 A 36.0 A/39.0 A 6.8 A/7.8 A 21.0 A/21.0 A 44.0 A/42.0 A 6.8 A/7.6 A
Pre-fuse T 16.0 A 25.0 A 6.3 A – 10.0 A2) 16.0 A 25.0 A 6.3 A – 10.0 A2)
Power consumption Pel L 35 L 35 1025/1200 W 1085/1250 W 1050/1275 W 1450/1675 W 1500/1725 W 1425/1625 W
to DIN 3168 L 35 L 50 1250/1350 W 1300/1410 W 1275/1525 W 1625/2000 W 1675/2065 W 1675/1975 W
.
Refrigeration factor ε = QK/Pel L 35 L 35 1.7 2.3 1.9 2.0
Refrigerant R134a, 900 g
Permissible operating pressure p. max. 28 bar
Temperature and setting range +20°C to +55°C
Protection rating NEMA 4x
Duty cycle 100 %
Type of connection Plug-in terminal strip
Weight 80 kg 87 kg 80 kg 83 kg 90 kg 83 kg
Material Stainless steel 1.4404 (V4A) (AISI 316L)
External circuit 640 m3/h 710 m3/h
Air throughput of fans
Internal circuit 550 m3/h 640 m3/h
Temperature control Basic or Comfort controller (factory setting +35°C)
Accessories Packs of Page
Door-operated switch 1 4127.000 176
SK BUS system for Comfort controller 1 3124.100 180
RiDiag II including cables
1 3159.100 195
for Comfort controller
Interface card for Comfort controller 1 3124.200 179
Condensate hose 1 3301.612 192
1) Delivery
times available on request. 2) Motor circuit-breaker.
Special voltages available on request. We reserve the right to make technical modifications.

Accessories Page 171 Configuration software Page 195

92 Rittal System Climate Control


Wall-mounted cooling units
for precision machine tools, useful cooling output 1000/1500 W

950
40 0
0 05 21
0 51 50
26 15

These new devices meet the Supply includes: Approvals, Property rights:
current requirements of preci- Nano-coated condenser and see page 283. German registered design

Wall-mounted cooling units


sion machine tools. This in- integral electronic condensate no. 402 02 325
Detailed drawing,
cludes high acceleration values evaporation. Fully wired ready IR reg. design no. DM/062 557
see page 248.
and a massive reduction in for connection, including drilling with validity for FR, IT, ES
weight. The associated in- template and assembly parts. Performance diagrams, Indian registered design
creased sensitivity to vibration available on the Internet. no. 190 269
also places greater demands Japanese registered design
on supply equipment such as no. 1 187 905
cooling units.

Model No. SK with Basic controller, RAL 70351) 3304.142 3305.142


Model No. SK with Comfort controller, RAL 70351) 3304.542 3305.542
400, 3~, 50/ 400, 3~, 50/
Rated operating voltage V/Hz
460, 3~, 60 460, 3~, 60
W 400 400
Dimensions in mm H 950 950
D 260 260
.
Useful cooling output QK L 35 L 35 1000 W/1060 W 1500 W/1510 W
to DIN 3168 L 35 L 50 790 W/840 W 1230 W/1250 W

Rated current max. 2.8 A/2.9 A 2.6 A/2.9 A


Start-up current 11.5 A/12.7 A 12.2 A/11.3 A
Pre-fuse T Motor circuit breaker 6.3 A – 10.0 A
Power consumption Pel L 35 L 35 700 W/675 W 925 W/1100 W
to DIN 3168 L 35 L 50 785 W/800 W 1085 W/1275 W
.
Refrigeration factor ε = QK/Pel L 35 L 35 1.4 1.9
Refrigerant R134a, 500 g R134a, 600 g
Permissible operating pressure p. max. 25 bar
Temperature and setting range +20°C to +55°C
Protection category External circuit IP 34
to EN 60 529 Internal circuit IP 54
Duty cycle 100 %
Type of connection Plug-in terminal strip
Weight 40 kg 42 kg
External circuit 900 m3/h
Air throughput of fans
Internal circuit 600 m3/h 800 m3/h
Temperature control Basic or Comfort controller (factory setting +35°C)
Accessories Packs of Page
Filter mats 3 3286.400 189
Metal filters 1 3286.410 190
Door-operated switch 1 4127.000 176
SK BUS system for Comfort controller 1 3124.100 180
RiDiag II including cables
1 3159.100 195
for Comfort controller
Interface card for Comfort controller 1 3124.200 179
Condensate hose 1 3301.612 192
1) Delivery
times available on request.
Special voltages available on request. We reserve the right to make technical modifications.

Accessories Page 171 Configuration software Page 195

Rittal System Climate Control 93


Wall-mounted cooling units
Explosion-proof cooling units for zone 22 (dust), useful cooling output 1000/1500 W

950
40
0
0
26

These cooling units have been Supply includes: Approvals,


especially developed for control- Nano-coated condenser. Fully see page 283.
Wall-mounted cooling units

ling the climate in potentially wired ready for connection,


Detailed drawing,
explosive dust Zone 22 sectors. including drilling template and
see page 248.
assembly parts.
Performance diagrams,
available on the Internet.

Model No. SK with Basic controller, RAL 7035 3304.130 3304.160 3305.130 3305.160
Model No. SK with Comfort controller, RAL 7035 3304.530 3304.560 3305.530 3305.560
Rated operating voltage V/Hz 230, 50/60 400, 3~, 50/460, 3~, 60 230, 50/60 400, 3~, 50/460, 3~, 60
W 400 400
Dimensions in mm H 950 950
D 260 260
.
Useful cooling output QK L 35 L 35 1000 W/1060 W 1500 W/1510 W
to DIN 3168 L 35 L 50 790 W/840 W 1230 W/1250 W

Rated current max. 4.8 A/4.4 A 2.5 A/2.6 A 5.4 A/6.0 A 2.3 A/2.6 A
Start-up current 12.0 A/14.0 A 11.5 A/12.7 A 22.0 A/24.0 A 12.2 A/11.3 A
Pre-fuse T 10.0 A/10.0 A 6.3 A – 10.0 A1) 16.0 A/16.0 A 6.3 A – 10.0 A1)
Power consumption Pel L 35 L 35 700 W/650 W 580 W/550 W 850 W/1000 W 800 W/980 W
to DIN 3168 L 35 L 50 750 W/710 W 660 W/680 W 1000 W/1160 W 960 W/1150 W
.
Refrigeration factor ε = QK/Pel L 35 L 35 1.4 1.7 1.8 1.9
Refrigerant R134a, 325 g R134a, 500 g R134a, 600 g
Permissible operating pressure p. max. 25 bar
Temperature and setting range +20°C to +50°C
Protection category External circuit IP 54
to EN 60 529 Internal circuit IP 54
Duty cycle 100 %
Type of connection Plug-in terminal strip
Weight 39 kg 41 kg
External circuit 900 m3/h
Air throughput of fans
Internal circuit 600 m3/h 800 m3/h
Temperature control Basic or Comfort controller (factory setting +35°C)
Accessories Packs of Page
Filter mats 3 3286.400 189
Door-operated switch 1 4127.000 176
SK BUS system for Comfort controller 1 3124.100 180
RiDiag II including cables for Comfort controller 1 3159.100 195
Interface card for Comfort controller 1 3124.200 179
Condensate hose 1 3301.612 192
Delievery times available on request. We reserve the right to make technical modifications.
1) Motor circuit-breaker

Accessories Page 171 Configuration software Page 195

94 Rittal System Climate Control


Wall-mounted cooling units
with CO2 as the coolant, useful cooling output 1000 W

950
40 0
0 05 21
0 51 50
26 15

Environmentally friendly Approvals,


coolant see page 283.

Wall-mounted cooling units


This generation of cooling units
Detailed drawing,
already uses the alternative CO2
see page 248.
as the coolant for generating the
cooling power.
Supply includes:
Nano-coated condenser and
integral electronic condensate
evaporation. Fully wired ready
for connection, including drilling
template and assembly parts.

Model No. SK with Comfort controller 3304.740


Rated operating voltage V/Hz 230, 50/60
Dimensions in mm WHD 400 x 950 x 260
.
Useful cooling output QK
L 35 L 35 1000 W
to DIN 3168

Temperature and setting range +20°C to +40°C


Protection category External circuit IP 34
to EN 60 529 Internal circuit IP 54
Duty cycle 100 %
Type of connection Plug-in terminal strip
Weight 47 kg
Colour RAL 7035
External circuit 900 m3/h
Air throughput of fans
Internal circuit 600 m3/h
Temperature control Comfort controller (factory setting +35°C)
Accessories Packs of Page
Filter mats 3 3286.400 189
Metal filters 1 3286.410 190
Door-operated switch 1 4127.000 176
Air-ducting system 1 – 174
Cover stoppers for interior air outlet 2 – 175
Condensate hose 1 3301.612 192
We reserve the right to make technical modifications. Other specifications available upon request.

Accessories Page 171 Configuration software Page 195

Rittal System Climate Control 95


Thermoelectric coolers
Thermoelectric coolers

The powerful thermoelectric unit in a light-weight

design is the eco-friendly climate-control solution for

command panels and small enclosures producing

energy savings of more than 60 % compared with


Internal mounting External mounting
conventional industry systems. When installed in the enclosure, Its low weight also allows it to
the unit only protrudes by a few be externally mounted on simple
millimetres, and therefore does aluminium rear panels or blanking
not interrupt either the aesthetic panels.
appearance or freedom of move-
Scalable output
ment on support arm systems.
The modular designs allows
simple scaling of the cooling
output depending on your
requirements.

96 Rittal System Climate Control


Thermoelectric coolers
Useful cooling output 100 W

B = Width
T = Depth

Application: Supply includes: Approvals,


● Ideal for cooling small Thermoelectric cooling unit, see page 284.

Thermoelectric coolers
enclosures and command wired ready for connection, with
Detailed drawing,
panels. multilingual documentation and
see page 250.
● Especially suitable for use on mounting accessories.
support arm systems as well.
● Optimum space utilisation.
● Targeted cooling of hot-spots.
● RJ45 interface for connecting
to the Rittal CMC system

Model No. SK 3201.200 3201.300


W 125
Dimensions in mm H 400
D 155
Rated operating voltage V/Hz 100 – 230 V (AC) 24 V DC
Refrigeration factor/COP L 35 L 35 1.0 1.2
.
Useful cooling output QK
L 35 L 35 100 W 100 W
to DIN 3168
Power pack integrated  –
Colour of cover/unit RAL 7024/Anodised aluminium
Protection rating IP 54
Weight 3.0 kg 2.5 kg
Temperature range 0°C to +55°C 0°C to +55°C
Air throughput, unimpeded air flow 50 m3/h
Type of connection Plug-in spring connection terminal
Pre-fuse gG 2A 10 A
Accessories Packs of Page
Power pack 150 watts for 35 mm top-hat rail 1 – 3201.030 192
Filter mat 1 3201.050 191
Door-operated switch 1 4127.010 176
Digital temperature indicator 1 3114.100/3114.115 3114.024 177
CMC monitoring system See Cat. 32, from page 808.
Condensate hose, ∅ 6 mm 1 St. 3301.606 –
We reserve the right to make technical modifications. Special voltages available on request.

Innovative control
The PID control ensures opti-
mum activation of the Peltier
elements and fans. Speed and
output are energy-efficiently
adjusted to the optimum operat-
ing point thanks to pulse width
modulation.

Accessories Page 171 Configuration software Page 195

Rittal System Climate Control 97


Liquid cooling IE

E Air/water heat exchangers from page 100


   Roof-mounted. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2500 W. . . . . . . 102
   Roof-mounted. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4000 W. . . . . . . 103
   Micro, wall-mounted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 300 W. . . . . . . 104
  Wall-mounted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 600/1250 W. . . . . . . 105
   Wall-mounted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 500/1000 W. . . . . . . 106
   Wall-mounted . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2000/3000 W. . . . . . . 107
   Wall-mounted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5000 W. . . . . . . 108
 Wall-mounted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7000 W. . . . . . . 109

Water-carrying parts Suitable for command panels Wall-mounted


E stainless steel

Standardised installation Roof-mounted

E Direct Cooling Package from page 110


 

Liquid cooling IE
Cold Plate for frequency converters. . . . . . . . . . 2500 – 6000 W. . . . . . . 112
   Cold Plate for frequency converters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
  Cooling Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 400 – 900 W. . . . . . . 114
 Panel Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150/350 W. . . . . . . 115

Stainless steel Suitable for command panels


E

Standardised installation Manufacturer-specific

W Ö E
Recooling systems from page 116
 Mini . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1/1.5 kW. . . . . . . 118
 Mini . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3/4.5 kW. . . . . . . 119
 Mini . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 kW. . . . . . . 120
  Power Fluid Cooler . . . . . . . . . . . . . . . . . . . . . . . . . 7.5 to 59 kW. . . . . . . 121
 In floor-standing enclosure. . . . . . . . . . . . . . . . . . . 2.1 to 36 kW. . . . . . . 123
 Power Fluid Cooler . . . . . . . . . . . . . . . . . . . . . . . . 68 to 502 kW. . . . . . . 125
 In TS 8 Top enclosure system . . . . . . . . . . . . . . . . . 6 to 25 kW. . . . . . . 127
  Mini for wall mounting. . . . . . . . . . . . . . . . . . . . . . . . 1/2.5/4 kW. . . . . . . 129
  In floor-standing enclosure. . . . . . . . . . . . . . . . . . . 2.5 to 26 kW. . . . . . . 130

W Ö E
Immersible recooling systems from page 116
 Immersible recooling systems . . . . . . . . . . . . . . . 2.4 to 5.6 kW. . . . . . . 132
 Immersible recooling systems . . . . . . . . . . . . . . 8.5 to 17.3 kW. . . . . . . 133
 Immersible recooling systems . . . . . . . . . . . . . . . . 21 to 78 kW. . . . . . . 134
 Immersible recooling systems . . . . . . . . . . . . . . . 2.4 to 5.6 kW. . . . . . . 132
 Immersible recooling systems . . . . . . . . . . . . . . 8.5 to 17.3 kW. . . . . . . 133
 Immersible recooling systems . . . . . . . . . . . . . . . . 21 to 78 kW. . . . . . . 134

W Medium to be cooled: E Medium to be cooled: Wall-mounted


Water Emulsion

Ö Medium to be cooled: Roof-mounted Fast delivery range


Oil

Rittal System Climate Control 99


Air/water heat exchangers
Air/water heat exchangers

The air of the enclosure interior may also be cooled to the enclosure does not raise the temperature of the

below the level of the external temperature, if required, ambient air, provided the heat exchanger and cold

by using cooling water from a central recooling water supply system are spatially separated from one

system. The ingress of dust from outside into the another.

cooled enclosure is prevented. The waste heat from

100 Rittal System Climate Control


Climate control
platform strategy
Identical mounting interface for
cooling units and air/water heat
exchangers. In this way, the device
type and cooling output are easily
varied.

Comfort controller
● Switching hysteresis: 2 – 10 K
preset to 5 K
● System alarm, individually configurable for
Variants 2 floating fault signal contacts
● Visualisation of the current enclosure
Roof mounted
internal temperature and all system
Especially for bayed enclosures,
messages on the display
where wall-mounted devices would
● Storage of all system statuses in the log
obstruct the door.
file
Wall mounted ● Optional extension card for integration into
For mounting on the wall or any superordinate remote monitoring systems
sufficiently large vertical surface. e.g. with CMC

Effective in extreme
conditions
Air/water heat exchangers can also be used
at particularly extreme ambient tempera-

Air/water heat exchangers


tures from +1° to +70°C. Even extreme lev-
els of contamination in the ambient air, e.g.
with dust and oil, do not affect functionality.
High heat losses are dissipated in the most
confined spaces without emitting them
directly to the ambient air.
A high operating ratio is achieved, thanks to
the large surface area of the heat exchanger
unit.

Basic controller
● Visualisation of the operating status via
LED display
● Switching hysteresis: 5 K
● Floating fault signal contact in case of
overtemperature
● Setpoint externally adjustable via poten-
tiometer (setting range 20°C – 55°C)

Benefits at a glance Important Tips and tricks


● Useful cooling output from 300 W to Air/water heat exchangers should always Applications see page 217
7000 W be used in conjunction with recooling
Selection criteria see page 218
● Suitable for use even under extreme systems or a cooling water circuit.
conditions and at ambient temperatures Assembly see page 219
of up to +70°C
Air routing see page 220/221
● Also available with all water-carrying
parts made from V4A Condensate management
● System for TS 8 integrated into the side see page 222/223
panel
Electrical connection
● High protection category. Thanks to the
and control see page 224/225
sealed design, a protection category of
IP 55 to EN 60 529 is achieved.

Rittal System Climate Control 101


Air/water heat exchangers
Roof-mounted, useful cooling output 2500 W
5 59
47 7

417
2
1

0 49
39 0

Supply includes: 1 Condensate discharge 1/2˝ Property rights:


Fully wired ready for connection, (flexible) German registered designs
with connector, including drilling 2 Cooling water connection 1/2˝
no. 402 02 324 and
template, sealing mat and no. 402 02 325
(flexible)
assembly parts. US design patent
Approvals, no. US D 492,319S
see page 284. Indian registered design
Also required: no. 189 956
Detailed drawing,
Chinese registered design
Air/water heat exchangers

Cooling water system such as see page 251.


Rittal recooling systems, no. ZL 0330 6415.6
Performance diagrams,
from page 116.
available on the Internet.

Water-carrying parts
Model No. SK Basic controller CuAL 3209.100 3209.110 3209.1401)
Model No. SK Comfort controller CuAL 3209.500 3209.510 3209.5401)
Useful cooling output CuAL L 35 W 10, 400 l/h 2500 W
Model No. SK Basic controller V4A (stainless steel) 3209.1041) 3209.1141) 3209.1441)
Model No. SK Comfort controller V4A (stainless steel) 3209.5041) 3209.5141) 3209.5441)
Useful cooling output V4A L 35 W 10, 400 l/h 1875 W
Rated operating voltage V, Hz 230, 50/60 115, 50/60 400, 2~, 50/60
W 597
Dimensions in mm H 417
D 475

Rated current max. 0.40 A/0.48 A 0.85 A/0.95 A 0.25 A/0.30 A


Pre-fuse T 4.0 A
Cooling medium Water (refer to specifications on the Internet; assembly instructions chapter 13)
Water inlet temperature > +1°C to +30°C
Permissible operating pressure p. max. 1 to 10 bar
Temperature range +1°C to +70°C
Protection category to EN 60 529 IP 552)
Duty cycle 100 %
Type of connection Plug-in terminal strip
Weight 23.5 kg 27.5 kg 27.5 kg
Colour RAL 7035
Air throughput of fans (unimpeded air flow) 1030 m3/h
Temperature control Basic or Comfort controller (factory setting +35°C)
Accessories Packs of Page
Door-operated switch 1 4127.000 176
SK BUS system for Comfort controller 1 3124.100 180
Interface card for Comfort controller 1 3124.200 179
Air ducting system 1 3286.870 174
Cover stoppers for interior air outlet 1 3286.880 175
Condensate hose 1 3301.612 192
Flow regulator valve 1 See accessories 194
1) Delivery times available on request.
2) IP 65 available on request.
Special voltages available on request. We reserve the right to make technical modifications.

Accessories Page 171 Recooling systems Page 116 Configuration software Page 195

102 Rittal System Climate Control


Air/water heat exchangers
Roof-mounted, useful cooling output 4000 W
5 59
47 7

417
2
1

0 49
39 0

Supply includes: 1 Condensate discharge 1/2˝ Property rights:


Fully wired ready for connection, (flexible) German registered designs
with connector, including drilling 2 Cooling water connection 1/2˝
no. 402 02 324 and
template, sealing mat and no. 402 02 325
(flexible)
assembly parts. US design patent
Approvals, no. US D 492,319S
see page 284. Indian registered design
Also required: no. 189 956
Detailed drawing,
Chinese registered design

Air/water heat exchangers


Cooling water system such as see page 251.
Rittal recooling systems, no. ZL 0330 6415.6
Performance diagrams,
from page 116.
available on the Internet.

Water-carrying parts
Model No. SK Basic controller CuAL 3210.100 3210.110 3210.1401)
Model No. SK Comfort controller CuAL 3210.500 3210.510 3210.5401)
Useful cooling output CuAL L 35 W 10, 400 l/h 4000 W
Model No. SK Basic controller V4A (stainless steel) 3210.1041) 3210.1141) 3210.1441)
Model No. SK Comfort controller V4A (stainless steel) 3210.5041) 3210.5141) 3210.5441)
Useful cooling output V4A L 35 W 10, 400 l/h 3000 W
Rated operating voltage V, Hz 230, 50/60 115, 50/60 400, 2~, 50/60
W 597
Dimensions in mm H 417
D 475

Rated current max. 0.44 A/0.5 A 0.9 A/1.0 A 0.25 A/0.3 A


Pre-fuse T 4.0 A
Cooling medium Water (refer to specifications on the Internet; assembly instructions chapter 13)
Water inlet temperature > +1°C to +30°C
Permissible operating pressure p. max. 1 to 10 bar
Temperature range +1°C to +70°C
Protection category to EN 60 529 IP 552)
Duty cycle 100 %
Type of connection Plug-in terminal strip
Weight 25.5 kg 29.5 kg 29.5 kg
Colour RAL 7035
Air throughput of fans (unimpeded air flow) 925 m3/h
Temperature control Basic or Comfort controller (factory setting +35°C)
Accessories Packs of Page
Door-operated switch 1 4127.000 176
SK BUS system for Comfort controller 1 3124.100 180
Interface card for Comfort controller 1 3124.200 179
Air ducting system 1 3286.870 174
Cover stoppers for interior air outlet 1 3286.880 175
Condensate hose 1 3301.612 192
Flow regulator valve 1 See accessories 194
1) Delivery times available on request.
2) IP 65 available on request.
Special voltages available on request. We reserve the right to make technical modifications.

Accessories Page 171 Recooling systems Page 116 Configuration software Page 195

Rittal System Climate Control 103


Air/water heat exchangers
Micro, wall-mounted, useful cooling output 300 W

85 15
0 85 15
0

300

300
1 1
2 2

Especially for selective cooling Supply includes: 1 Condensate discharge 3/8˝ Approvals,
of hot-spots in small enclosures. Fully wired ready for connection, 2 Cooling water connection 3/8˝
see page 284.
including drilling template and
Detailed drawing,
assembly parts.
see page 251.
Performance diagrams,
available on the Internet.
Air/water heat exchangers

Model No. SK 3212.230 3212.1151) 3212.024


Rated operating voltage V, Hz 230, 50/60 115, 50/60 24 V (DC)
W 150
Dimensions in mm H 300
D 85
Useful cooling output L 35 W 10, 200 l/h 300 W

Rated current max. 0.11 A/0.13 A 0.23 A/0.24 A 1.20 A


Pre-fuse T 4.0 A
Cooling medium Water (refer to specifications on the Internet; assembly instructions chapter 12)
Water inlet temperature > +1°C to +30°C
Permissible operating pressure p. max. 1 to 10 bar
Temperature range +1°C to +70°C
Protection category to EN 60 529 IP 552)
Duty cycle 100 %
Type of connection Connection clamp
Weight 3 kg
Colour RAL 7035
Air throughput of fans (unimpeded air flow) 280 m3/h 250 m3/h
Accessories Packs of Page
Temperature indicator 1 3114.100 177
Door-operated switch 1 4127.000 176
Condensate hose 1 3301.612 192
Flow regulator valve 1 See accessories 194
1) Delivery times available on request.
2) IP 65 available on request.
Special voltages available on request. We reserve the right to make technical modifications.

Accessories Page 171 Recooling systems Page 116 Configuration software Page 195

104 Rittal System Climate Control


Air/water heat exchangers
Wall-mounted, useful cooling output 600/1250 W

0 20
10 0
0
10 20
0

500
1
2

950
1
2

Supply includes: 1 Condensate discharge 1/2˝ Approvals,


Fully wired ready for connection, Also required: 2 Cooling water connection 1/2˝
see page 285.
with terminal strip, including Cooling water system such as Detailed drawing,
drilling template, sealing mat Rittal recooling systems, see page 251/252.
and assembly parts.
see page 116 onwards.
Performance diagrams,
available on the Internet.

Air/water heat exchangers


Model No. SK 3214.100 3215.100
Rated operating voltage V, Hz 230, 50/60
W 200 200
Dimensions in mm H 500 950
D 100 100
L 35 W 10, 200 l/h 600 W 1250 W
Useful cooling output
L 35 W 10, 400 l/h 650 W 1300 W

Rated current max. 0.17 A/0.18 A 0.38 A/0.4 A


Pre-fuse T 2.0 A 4.0 A
Cooling medium Water (refer to specifications on the Internet; assembly instructions chapter 12)
Water inlet temperature > +1°C to +30°C
Permissible operating pressure p. max. 1 to 10 bar
Temperature range +1°C to +70°C
Protection category to EN 60 529 IP 551)
Duty cycle 100 %
Type of connection Terminal strip
Weight 7 kg 13 kg
Colour RAL 7035
Air throughput of fans 120 m3/h 200 m3/h
Temperature control Thermostat-controlled magnetic valve
Internal thermostat, with change-over contact, switching load 16 A,
Temperature monitoring
setting range +20°C to +60°C (factory setting +35°C)
Accessories Packs of Page
Temperature indicator 1 3114.100 177
Door-operated switch 1 4127.000 176
Condensate hose 1 3301.612 192
Flow regulator valve 1 See accessories 194
1) IP
65 available on request.
Special voltages available on request. We reserve the right to make technical modifications.

Accessories Page 171 Recooling systems Page 116 Configuration software Page 195

Rittal System Climate Control 105


Air/water heat exchangers
Wall-mounted, useful cooling output 500/1000 W
92 28 14
2 28
0 0

550

550
2 2
1 1

Supply includes: Approvals,


Fully wired ready for connection, Also required: see page 285.
with connector, including drilling Cooling water system such as Detailed drawing,
template, sealing mat and Rittal recooling systems, see page 252.
assembly parts.
from page 116.
Performance diagrams,
available on the Internet.

1 Cooling water connection 1/2˝


Air/water heat exchangers

2 Condensate discharge 1/2˝

Water-carrying parts
Model No. SK Basic controller CuAL 3363.100 3363.1101) 3363.1401) 3364.100 3364.1101) 3364.1401)
Model No. SK Comfort controller CuAL 3363.500 3363.5101) 3363.5401) 3364.500 3364.5101) 3364.5401)
Useful cooling output CuAL L 35 W 10, 400 l/h 500 W 1000 W
Model No. SK Basic controller V4A (stainless steel) 3363.1041) 3363.1141) 3363.1441) 3364.1041) 3364.1141) 3364.1441)
Model No. SK Comfort controller V4A (stainless steel) 3363.5041) 3363.5141) 3363.5441) 3364.5041) 3364.5141) 3364.5441)
Useful cooling output V4A L 35 W 10, 400 l/h 375 W 750 W
230, 1~, 115, 1~, 400, 2~, 230, 1~, 115, 1~, 400, 2~,
Rated operating voltage V, Hz
50/60 50/60 50/60 50/60 50/60 50/60
W 280 280
Dimensions in mm H 550 550
D 92 142

Rated current max. 0.17 A/0.18 A 0.35 A/0.40 A 0.1 A/0.12 A 0.2 A/0.19 A 0.4 A/0.38 A 0.12 A/0.11 A
Pre-fuse T 4.0 A 4.0 A3) 4.0 A 4.0 A3)
Cooling medium Water (refer to specifications on the Internet; assembly instructions chapter 13)
Water inlet temperature +1°C to +30°C
Permissible operating pressure p. max. 1 to 10 bar
Temperature range +1°C to +70°C
Protection category to EN 60 529 IP 552)
Duty cycle 100 %
Type of connection Plug-in terminal strip
Weight 12 kg 15 kg
Colour RAL 7035
Air throughput of fans (unimpeded air flow) 270/320 m3/h
Temperature control Basic or Comfort controller (factory setting +35°C)
Accessories Packs of Page
Door-operated switch 1 4127.000 176
SK BUS system for Comfort controller 1 3124.100 180
Interface card for Comfort controller 1 3124.200 179
Condensate hose 1 3301.612 192
Flow regulator valve 1 See accessories 194
1) Delivery times available on request.
2) IP 65 available on request.
3) 2-pole miniature circuit breaker
Special voltages available on request. We reserve the right to make technical modifications.

Accessories Page 171 Recooling systems Page 116 Configuration software Page 195

106 Rittal System Climate Control


Air/water heat exchangers
Wall-mounted, useful cooling output 2000/3000 W
2
14 40
0

950
2
1

Supply includes: Approvals,


Fully wired ready for connection, Also required: see page 285.
with connector, including drilling Cooling water system such as Detailed drawing,
template, sealing mat and Rittal recooling systems, see page 253.
assembly parts.
from page 116.
Performance diagrams,
available on the Internet.

1 Cooling water connection 1/2˝

Air/water heat exchangers


2 Condensate discharge 1/2˝

1 Water-carrying parts
Model No. SK Basic controller CuAL 3373.100 3373.1101) 3373.1401) 3374.100 3374.1101) 3374.1401)
Model No. SK Comfort controller CuAL 3373.500 3373.5101) 3373.5401) 3374.500 3374.5101) 3374.5401)
Useful cooling output CuAL L 35 W 10, 400 l/h 2000 W 3000 W
Model No. SK Basic controller V4A (stainless steel) 3373.1041) 3373.1141) 3373.1441) 3374.1041) 3374.1141) 3374.1441)
Model No. SK Comfort controller V4A (stainless steel) 3373.5041) 3373.5141) 3373.5441) 3374.5041) 3374.5141) 3374.5441)
Useful cooling output V4A L 35 W 10, 400 l/h 1500 W 2250 W
230, 1~, 115, 1~, 400, 2~, 230, 1~, 115, 1~, 400, 2~,
Rated operating voltage V, Hz
50/60 50/60 50/60 50/60 50/60 50/60
W 400
Dimensions in mm H 950
D 142

Rated current max. 0.38 A/0.43 A 0.75 A/0.85 A 0.22 A/0.25 A 0.57 A/0.78 A 1.15 A/1.55 A 0.35 A/0.45 A
Pre-fuse T 4.0 A 4.0 A3) 4.0 A 4.0 A3)
Cooling medium Water (refer to specifications on the Internet; assembly instructions chapter 13)
Water inlet temperature +1°C to +30°C
Permissible operating pressure p. max. 1 to 10 bar
Temperature range +1°C to +70°C
Protection category to EN 60 529 IP 552)
Duty cycle 100 %
Type of connection Plug-in terminal strip
Weight 20 kg
Colour RAL 7035
Air throughput of fans (unimpeded air flow) 600/625 m3/h 700/730 m3/h
Temperature control Basic or Comfort controller (factory setting +35°C)
Accessories Packs of Page
Door-operated switch 1 4127.000 176
SK BUS system for Comfort controller 1 3124.100 180
Interface card for Comfort controller 1 3124.200 179
Condensate hose 1 3301.612 192
Flow regulator valve 1 See accessories 194
1) Delivery times available on request.
2) IP 65 available on request.
3) 2-pole miniature circuit breaker
Special voltages available on request. We reserve the right to make technical modifications.

Accessories Page 171 Recooling systems Page 116 Configuration software Page 195

Rittal System Climate Control 107


Air/water heat exchangers
Wall-mounted, useful cooling output 5000 W
0
25 45
0

1400
2
1

Supply includes: Approvals,


Fully wired ready for connection, Also required: see page 285.
with connector, including drilling Cooling water system such as Detailed drawing,
template, sealing mat and Rittal recooling systems, see page 253.
assembly parts.
from page 116.
Performance diagrams,
available on the Internet.

1 Cooling water connection 1/2˝


Air/water heat exchangers

2 Condensate discharge 1/2˝

Water-carrying parts
Model No. SK Basic controller CuAL 3375.100 3375.1101) 3375.1401)
Model No. SK Comfort controller CuAL 3375.500 3375.5101) 3375.5401)
Useful cooling output CuAL L 35 W 10, 400 l/h 5000 W
Model No. SK Basic controller V4A (stainless steel) 3375.1041) 3375.1141) 3375.1441)
Model No. SK Comfort controller V4A (stainless steel) 3375.5041) 3375.5141) 3375.5441)
Useful cooling output V4A L 35 W 10, 400 l/h 3750 W
Rated operating voltage V, Hz 230, 1~, 50/60 115, 1~, 50/60 400, 2~, 50/60
W 450
Dimensions in mm H 1400
D 250

Rated current max. 1.0 A/1.35 A 2.0 A/2.7 A 0.6 A/0.8 A


Pre-fuse T 4.0 A 4.0 A3)
Cooling medium Water (refer to specifications on the Internet; assembly instructions chapter 13)
Water inlet temperature +1°C to +30°C
Permissible operating pressure p. max. 1 to 10 bar
Temperature range +1°C to +70°C
Protection category to EN 60 529 IP 552)
Duty cycle 100 %
Type of connection Plug-in terminal strip
Weight 56 kg 59 kg
Colour RAL 7035
Air throughput of fans (unimpeded air flow) 2365/2750 m3/h
Temperature control Basic or Comfort controller (factory setting +35°C)
Accessories Packs of Page
Door-operated switch 1 4127.000 176
SK BUS system for Comfort controller 1 3124.100 180
Interface card for Comfort controller 1 3124.200 179
Condensate hose 1 3301.612 192
Flow regulator valve 1 See accessories 194
1) Delivery times available on request.
2) IP 65 available on request.
3) 2-pole miniature circuit breaker
Special voltages available on request. We reserve the right to make technical modifications.

Accessories Page 171 Recooling systems Page 116 Configuration software Page 195

108 Rittal System Climate Control


Air/water heat exchangers
Wall-mounted, useful cooling output 7000 W

0
30 45
0

1800
2 1

Supply includes: 1 Condensate discharge 1/2˝ Approvals,


Fully wired ready for connection, Also required: 2 Cooling water connection 1/2˝
see page 285.
with terminal strip, including Cooling water system such as Detailed drawing,
drilling template, sealing mat Rittal recooling systems, see page 254.
and assembly parts.
from page 116.
Performance diagrams,
available on the Internet.

Model No. SK 3216.4801)

Air/water heat exchangers


Rated operating voltage V, Hz 400, 3~, 50/60 480, 3~, 60
W 450
Dimensions in mm H 1800
D 300
L 35 W 10, 500 l/h 7000 W
Useful cooling output
L 35 W 20, 500 l/h 4500 W

Rated current max. 1.4 A/1.6 A 1.2 A


Pre-fuse T 4.0 A, 3-pole
Power consumption Pel 450 W/700 W 630 W
Cooling medium Water (refer to specifications on the Internet; assembly instructions chapter 12)
Water inlet temperature +1°C to +30°C
Permissible operating pressure p. max. 1 to 10 bar
Temperature range +1°C to +70°C
Protection category to EN 60 529 IP 552)
Duty cycle 100 %
Type of connection Terminal strip
Weight 79 kg
Colour RAL 7035
Air throughput of fans 2400 m3/h
Temperature control Thermostat-controlled magnetic valve
Accessories Packs of Page
Temperature indicator 1 3114.100 177
Door-operated switch 1 4127.000 176
Condensate hose 1 3301.612 192
Flow regulator valve 1 See accessories 194
1) Delivery times available on request.
2) IP 65 available on request.
Special voltages available on request. We reserve the right to make technical modifications.

Adaptor frame Packs of Model No. SK


For mounting the air/water heat exchanger 1 3216.470
SK 3216.480 on side panels of 500 mm deep
TS enclosures.
Detailed drawing,
Material: see page 254.
Sheet steel
Colour:
RAL 7035

Accessories Page 171 Recooling systems Page 116 Configuration software Page 195

Rittal System Climate Control 109


Direct cooling package
Direct cooling package

Power electronic components can be cooled the high enclosure protection category in any way.

particularly effectively using the liquid cooled DCP Furthermore, liquid cooling is both quiet and

mounting plate. Heat losses are cleverly dissipated 1000 times more efficient than heat dissipation

from the enclosure or housing without compromising via air.

The Rittal DCP Cold Plate has received


type-tested certification from the TÜV yp
inspection authority and is approved for e Te s te
pressures up to 10 bar.

110 Rittal System Climate Control


Assembly
Attachment with retainers
Frequency converters with dimensions
marginally smaller than the T-slot spacing
can be secured with special retainers.
Attachment with tapped holes
Power electronics can be mounted at any
position over the whole surface by drilling
tapped holes up to max. 12 mm in depth.

Assembly
Attachment directly in the T-slot
Direct and fast mounting using sliding nuts
for components with suitable dimensions.

Direct cooling package


Direct earthing or equipotential bonding
points may be provided on the Cold Plate.
Attachment with variable clamping system
Supports fast mechanical installation with-
out the need for drilling, independently of
the original attachment points on the compo-
nent. For use with a wide range of models
and makes.

Assembly
Height and depth-variable mount-
ing positions are offered by the
system punchings of the TS 8
profiles in conjunction with
punched section with mounting
flange 17 x 73 mm (for the outer
mounting level).

Benefits at a glance Important


● High surface quality (Ra = 1.2 μm) to Manufacturer or customer-specific Cold
reduce thermal resistance Plates may be supplied on a project-related
● No vibrations from compressors and fans basis on request.
● Ideal for precision machine tools
● No noise generation
● No top-mounted parts on the enclosure
● Enclosure may be installed in the
machine base and in niches
● The protection category of the enclosure
is preserved
● Mounting surface on both sides may be
used as a contact surface for heat
dissipation
● Space-saving configuration of electronic
components in the enclosure

Rittal System Climate Control 111


DCP – Direct Cooling Package
Cold Plate for frequency converters
T

H
B

B = Width
T = Depth

Without T-slot Version: Approvals,


Liquid-cooled partial mounting Press-fitted copper or stainless Accessories: see page 286.
plate with drilling surface steel tubes, dependent on the Accessories for fluid distribution Detailed drawing,
Whole surface can be used by application, in closed recooling connection, see page 255.
the customer for own tapped systems or existing (open) water
see page 184.
holes (blind holes) to a maxi- circuit. Cooling water connec-
mum drilling depth of 12 mm. tion: G 1/4˝, anti-twist. TS punched section with mount-
ing flange 17 x 73 mm for the
With T-slot Supply includes: external mounting level,
DCP – Direct Cooling Package

Liquid-cooled partial mounting Mounting accessories for system


see Catalogue 32, page 1023.
plate for fastening with a integration into TS.
variable clamping system Recooling systems for closed
Fast mounting of converters with cooling circuits,
system fastening and additional see from page 116.
possibility for tapped holes Further technical
(blind holes) to a maximum
information is available at
drilling depth of 8 mm. www.rittal.com/dcp

Without T-slot
Model No. DCP 8616.610 8616.630 8616.810 8616.830 8616.0102) 8616.0302) 8616.2102) 8616.2302)
Enclosure width mm 600 600 800 800 1000 1000 1200 1200
For installation in
Enclosure depth (side) mm 600 600 800 800 1000 1000 – –
W 499 499 699 699 899 899 1099 1099
Dimensions in mm H 399 399 399 399 399 399 399 399
D 25 25 25 25 25 25 25 25
Output1) 2500 W 2500 W 3000 W 3000 W 5000 W 5000 W 6000 W 6000 W
Material CU VA CU VA CU VA CU VA
Packs of 1 1 1 1 1 1 1 1
.
1) At 25°C medium inlet temperature, DCP surface temperature ≈ 50°C, medium flowrate Q = 200 l/h, surface roughness: 1.2 μm.
2) Delivery times available on request.

With T-slot
Model No. DCP 8616.600 8616.620 8616.800 8616.820 8616.0002) 8616.0202) 8616.2002) 8616.2202)
Enclosure width mm 600 600 800 800 1000 1000 1200 1200
For installation in
Enclosure depth (side) mm 600 600 800 800 1000 1000 – –
W 499 499 699 699 899 899 1099 1099
Dimensions in mm H 399 399 399 399 399 399 399 399
D 20 20 20 20 20 20 20 20
Output1) 2500 W 2500 W 3000 W 3000 W 5000 W 5000 W 6000 W 6000 W
Material CU VA CU VA CU VA CU VA
Packs of 1 1 1 1 1 1 1 1
.
1) At 25°C medium inlet temperature, DCP surface temperature ≈ 50°C, medium flowrate Q = 200 l/h, surface roughness: 1.2 μm.
2) Delivery times available on request.

Recooling systems page 116 Accessories page 184

112 Rittal System Climate Control


DCP – Direct Cooling Package
Cold Plate for frequency converters, manufacturer-specific
T

H
B

B = Width
T = Depth

Siemens SINAMICS Danfoss frequency converters Approvals,


S120 series Booksize VLT Automation Drive FC300 see page 286.
Pre-manufactured tapped holes for enclosure sizes
Detailed drawing,
on a 50 mm pitch pattern for A2 (0.37 – 4 kW/380 – 500 V)
see page 255.
attaching the S120 modules. A3 (5.5 – 7.5 kW/380 – 500 V)
For the design of SINAMICS with a channel spacing of
drive modules in the S120 257 mm may be used.
series, please contact your
local Siemens agent.

DCP – Direct Cooling Package


Version Siemens SINAMICS S120 Booksize Danfoss VLT Automation Drive FC300
Model No. DCP 8616.640 8616.6411) 8616.840 8616.8411) 8616.6501) 8616.6511) 8616.8501) 8616.8511)
Enclosure width mm 600 600 800 800 600 600 800 800
For installation in
Enclosure depth mm 600 600 800 800 600 600 800 800
W 499 499 699 699 499 499 699 699
Dimensions in mm H 449 449 449 449 299 299 299 299
D 20 20 20 20 20 20 20 20
Material CU VA CU VA CU VA CU VA
Packs of 1 1 1 1 1 1 1 1
Special sizes available on request. Surface roughness: 1.2 μm.
Rear: Press-fitted copper or stainless steel tubes, dependent on the application, in closed recooling systems or existing (open) water infrastructure.
Cooling water connection: G 1/4˝, anti-twist.
1) Delivery times available on request.

Recooling systems page 116 Accessories page 184

Rittal System Climate Control 113


DCP – Direct Cooling Package
Cooling Unit

H
B

B = Width
T = Depth

1 2

The Cooling Unit is available in Functional principle: Convincing arguments: Approvals,


two variants. As add-on 1 in The warm air inside the enclo- ● Direct cooling of power see page 286.
conjunction with a Rittal Cold sure is drawn in by a powerful electronics on the Rittal
Further technical
Plate or as a stand-alone unit 2 radial fan and passed through Cold Plate and lowering
information is available at
with press-fitted pipework in the the cooler. of the enclosure internal
www.rittal.com/dcp
cooler. The optional housing for temperature
The unit can be operated either
the cooler ensures even more ● Decentralised cooling of
indirectly, i.e. mounted on a
efficient air routing and thus high-performance power
Rittal Cold Plate, or as a fully
reliable cooling of the air inside electronics
DCP – Direct Cooling Package

autonomous system with its own


the enclosure. ● No change to the existing
cooling water circulation. The
protection category of the
latter supports direct mounting
enclosure
on the mounting plate in the
immediate vicinity of major heat
loss sources.
In this variant, additional copper
or stainless steel tubes are
press-fitted into the cooler.

Version 1 Add-on 2 Stand-alone


Model No. DCP 8616.500 8616.5101) 8616.5502) 8616.5602)
W 252 252 252 252
Dimensions in mm H 572 572 572 572
D 205 205 205 205
Power 400 W 800 W 500 W 900 W
Packs of 1 1 1 1
1) Space required behind the DCP = 110 mm
2) Cooling unit as stand-alone unit with its own fluid connection (2 x G 1/ ˝), anti-twist.
4
Delivery times available on request.

Recooling systems page 116 Accessories page 184

114 Rittal System Climate Control


DCP – Direct Cooling Package
Panel Cooling

H
T

B = Width
T = Depth

This integrated Panel Cooling Functional principle: Convincing arguments: Approvals,


solution was developed by The fan unit with six individual ● High performance with see page 287.
Rittal for optimum, space-saving fans ensures optimum air circu- minimal space requirements
Further technical
cooling of operating housings. lation at the cooler for efficient ● No reduction of the original
winformation is available at
Heat losses of approx. dissipation of the heat losses protection category
www.rittal.com/dcp
150 – 350 W can be dissipated arising in the housing. ● No external add-ons
without the need for external The unit can be connected necessary
add-ons. The high protection either to an existing coolant
Operating housing cooling e.g.
category of the enclosure is circuit or else to an external

DCP – Direct Cooling Package


for the Comfort Panel and for
retained, thanks to the fluid recooling system.
special enclosures such as
connection at the rear of the
stainless steel enclosures for the
panel.
food and consumables industry.
Cooling units may be ordered for
heat losses of up to 350 W on a
project-specific basis.

Model No. DCP 8616.300 8616.310


W 300 400
Dimensions in mm H 250 300
D 50 60
Power 150 W 350 W
Packs of 1 1
Delivery times available on request.

Recooling systems page 116

Rittal System Climate Control 115


Recooling systems IE
Recooling systems IE

Recooling systems ensure centralised, efficient cooling Spatial separation between cooling production and

and supply of the cooling medium (generally water). All process cooling can be achieved with recooling

cooling tasks on a system or machine can be solved systems.

via a single pipeline system.

116 Rittal System Climate Control


Standard RiNano coating
Recooling systems, mini-wall-mounted and
Power Fluid coolers: with RiNano coating as
standard. The heat exchanger membranes
ultra-thin, glass-like seals prevent dirt from
settling on the condenser.

Application diversity of
centralised cooling
technology

Recooling systems IE
Enclosure cooling
In conjunction with air/water heat exchang-
ers, optimum dissipation of high heat loads
is guaranteed, even under extreme ambient
temperatures and air contamination levels.
Cooling of liquid media
The direct and indirect cooling of liquids is
essential for ensuring the required levels of
machine accuracy and speed.
Process cooling
High-quality material processing, such as
laser cutting, necessitates high levels of
temperature precision with simultaneous
cooling of the peripheral technology.

NE W
Fast delivery range up
to 50 kW
● Standardised versions
● Basic version available off-the-shelf
● Shorter delivery times for defined
options

Benefits at a glance Important Tips and tricks


● Cooling output from 1 to 500 kW Cooling output calculated at 32°C ambient Applications see page 226
● A single system for enclosure cooling, temperature and an inlet temperature of
Selection criteria see page 227
process and machine cooling, and the 10°C and 18°C (water) or 20°C (oil)
cooling of liquid media. Assembly see page 228
● Integration into bayed enclosure suites
Notes see page 229
● Individual project management
● Commissioning and servicing
● Comprehensive pipeline calculation
● Global service network

Rittal System Climate Control 117


Recooling systems for water
Mini, cooling output 1/1.5 kW

60
0

400
0
43

Technical design: Supply includes: Approvals,


● Compact, modular structure Recooling system wired ready see page 287.
of the cooling components on for connection, with multilingual
Layout diagram,
a base plate designed as a documentation including func-
see page 258.
collecting tray. tional diagram and wiring plans.
● With RiNano coating. Characteristic curves of pump,
● Pump to convey the medium. see page 258.
● Precise temperature control,
Other options,
based on microprocessor
Recooling systems for water

see page 256.


technology.
● Collective fault signal with
floating contact.
● Application-specific special
equipment available on
request.
● Pressure-sealed system (.600)
or open system with tank
(.610).

Model No. SK 3318.600 3318.610 3319.600 3319.610


Rated operating voltage V/Hz 230, 50/60
W 600
Dimensions in mm H 400
D 430
Cooling output at
Tw = 10°C/Tu = 32°C 0.8 kW/0.9 kW 1.2 kW/1.3 kW
Tw = 18°C/Tu = 32°C 1.0 kW/1.1 kW 1.5 kW/1.7 kW

Power consumption 0.63 kW/0.78 kW 0.85 kW/1.05 kW


Rated current max. 4.2 A 5.4 A
Refrigerant R134a
No. of cooling circuits 1
Environment +15°C to +43°C
Temperature range
Liquid media +10°C to +25°C
Pump capacity See characteristic curve
Tank Pressure-sealed Made from PP plastic Pressure-sealed Made from PP plastic
Tank capacity – 2.5 l – 2.5 l
Water connections 1/
2˝ internal thread
Weight 48 kg 51 kg
Colour RAL 7035
Protection category (electrics) IP 44
Air throughput of fans 900 m3/h
Temperature control Microcontroller control (factory setting +18°C)
Accessories Packs of Page
Metal filters 1 3286.510 190
Special voltages and technical modifications available on request.
We reserve the right to make technical modifications.

Air/water heat exchangers From page 102 Overflow valve Page 194 Cooling medium Page 194

118 Rittal System Climate Control


Recooling systems for water
Mini, cooling output 3/4.5 kW

60
2

25
5
64

676
Technical design: Supply includes: Approvals,
● Compact, modular configura- Recooling system wired ready see page 287.
tion of the cooling compo- for connection, with multilingual
Layout diagram,
nents with integral water tank. documentation including func-
see page 258.
● With RiNano coating. tional diagram and wiring plans.
● Integral tank level display. Characteristic curves of pump,
● Pump to convey the medium. see page 258.
● Precise temperature control,
Other options,
based on microprocessor

Recooling systems for water


see page 256.
technology.
● Collective fault signal with
floating contact.
● Application-specific special
equipment available on
request.

Model No. SK 3320.600 3334.600


Rated operating voltage V/Hz 400, 3~, 50/60/460, 3~, 601)
W 602
Dimensions in mm H 676
D 645
Cooling output at
Tw = 10°C/Tu = 32°C 2.7 kW/3.0 kW 3.9 kW/4.7 kW
Tw = 18°C/Tu = 32°C 3.0 kW/3.4 kW 4.5 kW/5.4 kW

Power consumption 1.72 kW/1.95 kW 2.00 kW/2.51 kW


Rated current max. 3.8 A/4.6 A/3.9 A 4.9 A/5.9 A/5.0 A
Refrigerant R134a
No. of cooling circuits 1
Environment +15°C to +43°C
Temperature range
Liquid media +10°C to +25°C
Pump capacity See characteristic curve
Tank Plastic
Tank capacity 30 l
Water connections 1/
2˝ internal thread
Weight (empty) 88 kg 94 kg
Colour RAL 7035
Protection category (electrics) IP 44
Air throughput of fans 1785 m3/h
Temperature control Microcontroller control (factory setting +18°C)
Accessories Packs of Page
Metal filters 1 3286.520 190
1) Supports multiple voltages without rewiring.
Special voltages and technical modifications available on request.
We reserve the right to make technical modifications.

Air/water heat exchangers From page 102 Overflow valve Page 194 Cooling medium Page 194

Rittal System Climate Control 119


Recooling systems for water
Mini, cooling output 6 kW

60
2

25
5
64

1050
Technical design: Supply includes: Approvals,
● Compact, modular configura- Recooling system wired ready see page 288.
tion of the cooling compo- for connection, with multilingual
Layout diagram,
nents with integral water tank. documentation including func-
see page 258.
● With RiNano coating. tional diagram and wiring plans.
● Integral tank level display. Characteristic curves of pump,
● Pump to convey the medium. see page 258.
● Precise cooling control based
Other options,
on microprocessor technol-
Recooling systems for water

see page 256.


ogy.
● Collective fault signal with
floating contact.
● Application-specific special
equipment available on
request.

Model No. SK 3334.660


Rated operating voltage V/Hz 400, 3~, 50/60/460, 3~, 601)
W 602
Dimensions in mm H 1050
D 645
Cooling output at
Tw = 10°C/Tu = 32°C 4.8 kW/5.2 kW/5.2 kW
Tw = 18°C/Tu = 32°C 6.0 kW/6.6 kW/6.6 kW

Power consumption 4.3 kW/5.1 kW/5.1 kW


Rated current max. 8 A/9.7 A/8 A
Refrigerant R134a
No. of cooling circuits 1
Environment +15°C to +43°C
Temperature range
Liquid media +10°C to +25°C
Pump capacity See characteristic curve
Tank Made from PP plastic
Tank capacity 30 l
Water connections 3/
4˝ internal thread
Weight 125 kg
Colour RAL 7035
Protection category (electrics) IP 44
Air throughput of fans 2200/2500 m3/h
Temperature control Microcontroller control (factory setting +18°C)
Accessories Packs of Page
Metal filters 1 3286.520 190
1) Supports multiple voltages without rewiring.
Special voltages and technical modifications available on request.
We reserve the right to make technical modifications.

Air/water heat exchangers From page 102 Overflow valve Page 194 Cooling medium Page 194 Twin castors Catalogue 32, page 907

120 Rittal System Climate Control


Recooling systems for water
Power Fluid Cooler, cooling output 7.5 kW

H
B
T

B = Width
T = Depth

Fast ry range
delive

Technical design: Options: Approvals,


● Enclosure in a modern indus- 1. Flow monitor see page 288.
trial design. 2. Flow monitor
Layout diagram,
● Compact, modular layout of + pump (4 bar stainless steel)
see page 258.
the refrigeration components. 3. Automatic bypass valve
● With RiNano coating. 4. Automatic bypass valve Characteristic curves of pump,
● Collective fault signal with + pump (4 bar stainless steel) see page 258.
floating contact. 5. Hot gas bypass
● Space-saving, compact 6. Flow monitor

Recooling systems for water


design. + pump (4 bar stainless steel)
+ hot gas bypass
Supply includes:
Recooling system wired ready
for connection, with multilingual
documentation including func-
tional diagram and wiring plans.

Model No. SK 3234.090


Rated operating voltage V/Hz 400, 3~, 50
W 595
Dimensions in mm H 1305
D 800
Cooling output at
Tw = 10°C/Tu = 32°C 5.2 kW
Tw = 18°C/Tu = 32°C 7.5 kW

Power consumption 3.8 kW


Rated current max. 7A
Refrigerant R134a
No. of cooling circuits 1
Environment +15°C to +43°C
Temperature range
Liquid media +10°C to +25°C
Pump capacity See characteristic curve
Tank Plastic
Tank capacity 57 l
Water connections 1˝ internal thread
Weight (empty) 147 kg
Colour RAL 7035
Protection category (electrics) IP 44
Air throughput of fans 3140 m3/h
Temperature control Microcontroller control (factory setting +18°C)
Accessories Packs of
Metal filters 1 on request
We reserve the right to make technical modifications.

Air/water heat exchangers From page 102 Overflow valve Page 194 Cooling medium Page 194

Rittal System Climate Control 121


Recooling systems for water
Power Fluid Cooler, cooling output 10 to 59 kW

H
B T

B = Width
T = Depth
Fast ry range
delive

Technical design: Options for Options for Approvals,


● Enclosure in a modern indus- SK 3234.100/.110/.120/.130/ SK 3234.160/.170/.180/.190 see page 288.
trial design. .140/.150 1. Automatic bypass valve
Layout diagram,
● Compact, modular layout of 1. Flow monitor + pump (4 bar stainless steel)
see page 258.
the refrigeration components. 2. Flow monitor 2. Pressure-sealed tank
● With RiNano coating. + pump (4 bar stainless steel) + pump (4 bar stainless steel) Characteristic curves of pump,
● Collective fault signal with 3. Automatic bypass valve + automatic bypass valve see page 258.
floating contact. 4. Automatic bypass valve 3. Pressure-sealed tank
● Space-saving, compact + pump (4 bar stainless steel)
Recooling systems for water

Supply includes:
design. 5. Hot gas bypass
Recooling system wired ready
6. Flow monitor
for connection, with multilingual
+ pump (4 bar stainless steel)
documentation including func-
+ hot gas bypass
tional diagram and wiring plans.

Model No. SK 3234.100 3234.110 3234.120 3234.130 3234.140 3234.150 3234.160 3234.170 3234.180 3234.190
Rated operating voltage V, Hz 400, 3~, 50
W 655 755 855 1040
Dimensions in mm H 1280 1280 1500 1700
D 1160 1360 1560 2000
Cooling output at
Tw = 10°C/Tu = 32°C 7 kW 10 kW 11 kW 13 kW 15 kW 18 kW 23 kW 25 kW 33 kW 41 kW
Tw = 18°C/Tu = 32°C 10 kW 14 kW 16 kW 19 kW 21 kW 25 kW 32 kW 36 kW 47 kW 59 kW

Power consumption 3.8 kW 4.8 kW 5.3 kW 6.4 kW 7.1 kW 8.1 kW 15.9 kW 17.6 kW 15.0 kW 21.0 kW
Rated current max. 10.6 A 13.1 A 14.1 A 16.2 A 18.2 A 19.7 A 24.4 A 26.9 A 28.0 A 36.0 A
Refrigerant R407C
No. of cooling circuits 1
Environment +15°C to +43°C
Temperature range
Liquid media +10°C to +25°C
Pump capacity See characteristic curve
Tank Plastic Stainless steel
Tank capacity 60 l 100 l 150 l 220 l
Water connections 1˝ internal thread 11/4˝ internal thread 11/2˝ internal thread
Weight (empty) 215 kg 225 kg 235 kg 240 kg 250 kg 260 kg 280 kg 300 kg 460 kg 490 kg
Colour RAL 7035
Protection category (electrics) IP 54
Air throughput of fans 6280 m3/h 10880 m3/h 18000 m3/h 32000 m3/h
Temperature control Microcontroller control (factory setting +18°C)
Accessories Packs of
Metal filters 1 on request
We reserve the right to make technical modifications.

Air/water heat exchangers From page 102 Overflow valve Page 194 Cooling medium Page 194

122 Rittal System Climate Control


Recooling systems for water
In floor-standing enclosure, cooling output 2.1 to 7.7 kW

H
B T

B = Width
T = Depth

Technical design: Supply includes: Approvals,


● Robust industrial standard in Recooling system wired ready Accessories: see page 288.
3 enclosure sizes. for connection, with multilingual Metal filter mats, castors and Layout diagram,
● Identical basic enclosure documentation including func- bypass valve available on see page 260.
for oil and water recooling tional diagram and wiring plans.
request.
systems. Characteristic curves of pump,
Note:
● Spare space for the integra- see page 260.
The illustration shows units with
tion of special equipment
customer-specific options. Options,
● Variable air routing is possi-

Recooling systems for water


see page 256.
ble via the l/h or r/h side panel
● Floating contact for collective
fault signal.
● Level monitor/float-actuated
switch.
● Multi-coil vaporiser in the tank.

Model No. SK 3336.100 3336.200 3336.300 3336.500 3336.600 3336.650


Rated operating voltage V/Hz 400, 3~, 50
W 470 485 595
Dimensions in mm H 725 965 1180
D 540 650 800
Cooling output at
Tw = 10°C/Tu = 32°C 1.7 kW 2.1 kW 2.3 kW 3.6 kW 4.8 kW 5.2 kW
Tw = 18°C/Tu = 32°C 2.1 kW 2.6 kW 3.4 kW 5.0 kW 6.2 kW 7.7 kW

Power consumption 1.5 kW 1.7 kW 2.3 kW 2.9 kW 3.7 kW 3.9 kW


Rated current max. 3.4 A 3.0 A 4.2 A 5.5 A 6.2 A 7.3 A
Refrigerant R134a
No. of cooling circuits 1
Environment +15°C to +43°C
Temperature range
Liquid media +10°C to +25°C
Pump capacity See characteristic curve
Tank Made from stainless steel 1.4301 (AISI 304)
Tank capacity 17 l 33 l 57 l
Water connections 3/
4˝ internal thread 1˝ internal thread
Weight 75 kg 97 kg 99 kg 141 kg 143 kg 147 kg
Colour RAL 7035
Protection category (electrics) IP 54
Air throughput of fans 700 m3/h 1250 m3/h 1785 m3/h 3140 m3/h
Temperature control Electronic control with digital display (factory setting +18°C)
Delivery times available on request.
Special voltages, other frequencies, and technical modifications available on request.
We reserve the right to make technical modifications.

Air/water heat exchangers From page 102 Overflow valve Page 194 Cooling medium Page 194

Rittal System Climate Control 123


Recooling systems for water
In floor-standing enclosure, cooling output 10 to 36 kW

H
T
B

B = Width
T = Depth

Technical design: Supply includes: Approvals,


● Robust industrial housing in Recooling system wired ready Accessories: see page 288.
2 enclosure sizes. for connection, with multilingual Metal filter mats, castors, Layout diagram,
● Identical basic enclosure documentation including func- eyebolts and bypass valve see page 260.
for oil and water recooling tional diagram and wiring plans.
available on request.
systems. Characteristic curves of pump,
Note:
● Integration of application- see page 260.
The illustration shows units with
specific special equipment
customer-specific options. Options,
on request.
Recooling systems for water

see page 256.


● Variable air routing is possi-
ble via the l/h or r/h side
panel.
● Optimum accessibility for
servicing purposes by remov-
ing the side panel.
● Floating contact for collective
fault signal.
● Flow monitor.

Model No. SK 3336.700 3336.710 3336.720 3336.730 3336.740 3336.750 3339.100 3339.200
Rated operating voltage V, Hz 400, 3~, 50/460, 3~, 60
W 615 715 815
Dimensions in mm H 1178 1178 1400
D 1160 1360 1560
Cooling output at
Tw = 10°C/Tu = 32°C 8.3/10.4 kW 11.9/15.5 13.5/16.6 15.0/18.1 17.0/20.7 20.6/26.4 26.2/31.4 29.6/35.5
Tw = 18°C/Tu = 32°C 10.0/12.6 kW 14.4/18.7 16.3/20.1 18.5/22.4 20.9/25.4 25.2/32.3 32.0/38.4 36.2/43.5

Power consumption 3.8 kW 4.8 kW 5.3 kW 6.4 kW 7.1 kW 13.1 kW 18.3 kW 18.6 kW
Rated current max. 10.6 A 13.1 A 14.1 A 16.2 A 18.2 A 23.7 A 29.2 A 30.7 A
Refrigerant R407C
No. of cooling circuits 1
Environment +15°C to +43°C1)
Temperature range
Liquid media +10°C to +25°C
Pump capacity See characteristic curve
Tank Made from stainless steel 1.4301 (AISI 304)
Tank capacity 60 l 100 l 150 l
Water connections 1˝ internal thread 11/4˝ internal thread
Weight 215 kg 225 kg 235 kg 240 kg 250 kg 260 kg 260 kg 300 kg
Colour RAL 7035
Protection category (electrics) IP 54 IP 54
Air throughput of fans 6280 m3/h 10880 m3/h 16000 m3/h
Temperature control Electronic control with digital display (factory setting +18°C)
1) SK3336.720 and SK 3336.750 +15°C to +40°C.
Delivery times available on request.
Special voltages and technical modifications available on request.
We reserve the right to make technical modifications.

Air/water heat exchangers From page 102 Overflow valve Page 194 Cooling medium Page 194

124 Rittal System Climate Control


Recooling systems for water
Power Fluid Cooler, cooling output 68 to 209 kW

H
T

B = Width
T = Depth

Technical design: Supply includes: Approvals,


● Compact design with control Recooling system wired ready see page 289.
components in the front and for connection, with multilingual
Layout diagram,
air intake via both side pan- documentation including func-
see page 258.
els, air outlet upwards. tional diagram and wiring plans.
● Open system. Characteristic curves of pump,
● Digital thermostat for tempera- see page 258.
ture control with setpoint and
actual value display.

Recooling systems for water


● Flow monitor.
Options:
1. Automatic bypass valve
+ pump (4 bar stainless steel)
2. Pressure-sealed tank
+ pump (4 bar stainless steel)
+ automatic bypass valve
3. Pressure-sealed tank

Model No. SK 3234.200 3234.210 3234.220 3234.230 3234.240 3234.250 3234.260 3234.270 3234.280
Rated operating voltage V, Hz 400, 3~, 50
W 1100 1100 1100 1100 1100 1100 1100 1100 1100
Dimensions in mm H 1606 1606 1606 1606 1875 1875 1875 1875 1875
D 2450 2450 2450 2950 2950 2950 2950 2950 3950
Cooling output at
Tw = 10°C/Tu = 32°C 48 kW 55 kW 63 kW 71 kW 87 kW 95 kW 111 kW 123 kW 146 kW
Tw = 18°C/Tu = 32°C 68 kW 79 kW 90 kW 101 kW 124 kW 135 kW 158 kW 175 kW 209 kW

Power consumption 20.5 kW 24.0 kW 27.0 kW 28.0 kW 38.5 kW 41.2 kW 50.0 kW 55.8 kW 66.0 kW
Rated current max. 40.0 A 46.0 A 50.0 A 77.0 A 66.5 A 71.9 A 88.4 A 99.7 A 112.3 A
Refrigerant R410A
No. of cooling circuits 2
Environment –20°C to +43°C
Temperature range
Liquid media +10°C to +25°C
Pump capacity See characteristic curve
Tank Made from stainless steel 1.4301 (AISI 304)
Tank capacity 300 l 500 l
Water connections 21/2˝ internal thread
Weight (empty) 790 kg 820 kg 835 kg 920 kg 1115 kg 1140 kg 1215 kg 1305 kg 1485 kg
Colour RAL 9002
Protection category (electrics) IP 54
Air throughput of fans 13720 m3/h 20450 m3/h 27300 m3/h 35500 m3/h 60900 m3/h
Temperature control Microcontroller control
We reserve the right to make technical modifications.

Air/water heat exchangers From page 102 Cooling medium Page 194

Rittal System Climate Control 125


Recooling systems for water
Power Fluid Cooler, cooling output 271 to 502 kW

H
T

B = Width
T = Depth

Technical design: Supply includes: Approvals,


● Compact design with control Recooling system wired ready see page 289.
components in the front and for connection, with multilingual
Layout diagram,
air intake via both side pan- documentation including func-
see page 258.
els, air outlet upwards. tional diagram and wiring plans.
● Pressure-sealed system. Characteristic curves of pump,
● Digital thermostat for tempera- see page 258.
ture control with setpoint and
actual value display.
Recooling systems for water

● Flow monitor.
Options:
Automatic bypass valve
+ pump (4 bar stainless steel)

Model No. SK 3234.290 3234.300 3234.310 3234.320 3234.330 3234.340


Rated operating voltage V, Hz 400, 3~, 50
W 2200 2200
Dimensions in mm H 2450 2450
D 3400 4250
Cooling output at
Tw = 10°C/Tu = 32°C 190 kW 214 kW 237 kW 284 kW 316 kW 351 kW
Tw = 18°C/Tu = 32°C 271 kW 305 kW 339 kW 406 kW 452 kW 502 kW

Power consumption 80 kW 88 kW 96 kW 120 kW 132 kW 144 kW


Rated current max. 200 A 219 A 237 A 300 A 328 A 355 A
Refrigerant R410A
No. of cooling circuits 2
Environment –20°C to +43°C
Temperature range
Liquid media +10°C to +25°C
Pump capacity See characteristic curve
Tank Steel
Tank capacity 700 l
Water connections 3˝ internal thread 4˝ internal thread
Weight (empty) 2650 kg 2740 kg 2780 kg 3400 kg 3500 kg 3600 kg
Colour RAL 9002
Protection category (electrics) IP 54
Air throughput of fans 83000 m3/h 78000 m3/h 76000 m3/h 112000 m3/h 111500 m3/h 111000 m3/h
Temperature control Microcontroller control
We reserve the right to make technical modifications.

Air/water heat exchangers From page 102 Cooling medium Page 194

126 Rittal System Climate Control


Recooling systems for water
In TS 8 Top enclosure system, cooling output 6/7.5 W

H
100
B
T

B = Width
T = Depth

Technical design: Supply includes: Approvals,


● Compact structure with con- Recooling system wired ready Accessories: see page 289.
trol components in the front for connection, with multilingual Metal filter mat and bypass Detailed drawing,
and air intake via the rear. documentation including func- valve available on request. see page 263.
● Suitable for bayed siting. tional diagram and wiring plans.
● Special fittings and options Layout diagram,
Note:
available on request. see page 263.
The illustration shows units with
● Float-actuated switch as pro-
customer-specific options. Characteristic curves of pump,
tection against running dry.

Recooling systems for water


see page 263.
● Floating collective fault signal.
● Equipped with Grundfos Options,
pumps and Siemens compo- see page 256.
nents.
● Service accessibility from all
sides.

Model No. SK 3335.060 3335.075


Rated operating voltage V/Hz 400, 3~, 50
W 600
Dimensions in mm H 2150
D 600
Base/plinth height mm 100
Cooling output at
Tw = 10°C/Tu = 32°C 4.8 kW 6.0 kW
Tw = 18°C/Tu = 32°C 6.0 kW 7.5 kW

Power consumption 2.4 kW 2.5 kW


Rated current max. 8.0 A 8.5 A
Refrigerant R407C
No. of cooling circuits 1
Environment +10°C to +43°C
Temperature range
Liquid media +10°C to +30°C
Pump capacity See characteristic curve
Tank Made from PP plastic
Tank capacity 105 l
Water connections 3/
4˝ external thread
Weight 180 kg 190 kg
Colour RAL 7035
Protection category (electrics) IP 54
Air throughput of fans 4000 m3/h
Electronic control with digital display, setting range +10°C to +30°C
Temperature control
(factory setting +18°C)
Delivery times available on request.
Special voltages, other frequencies and refrigerants, and technical modifications available on request.
We reserve the right to make technical modifications.

Air/water heat exchangers From page 102 TS 8 lock systems Cat. 32, from page 947 TS 8 baying system Cat. 32, from page 138
Overflow valve page 194 Cooling medium page 194

Rittal System Climate Control 127


Recooling systems for water
In TS 8 Top enclosure system, cooling output 10/25 W

H
100

100
B
T
B

B = Width
T = Depth

Technical design: Supply includes: Approvals,


● Compact design with control Recooling system wired ready Accessories: see page 289.
components in the front and for connection, with multilingual Metal filter mat and bypass Layout diagram,
air intake via the rear. documentation including func- valve available on request. see page 263.
● Suitable for bayed siting. tional diagram and wiring plans.
● Special fittings and options Characteristic curves of pump,
Note:
available on request. see page 263.
The illustration shows units with
● Float-actuated switch as pro-
customer-specific options. Options,
tection against running dry.
Recooling systems for water

see page 256.


● Floating collective fault signal.
● Magnetic valve in the cooling
circuit.
● Equipped with Grundfos
pumps and Siemens compo-
nents.
● Service accessibility from all
sides.

Model No. SK 3335.100 3335.120 3335.150 3335.200 3335.250


Rated operating voltage V/Hz 400, 3~, 50
W 800 1200
Dimensions in mm H 2150 2150
D 600 600
Base/plinth height mm 100
Cooling output at
Tw = 10°C/Tu = 32°C 8.0 kW 10.0 kW 11.5 kW 17.0 kW 22.0 kW
Tw = 18°C/Tu = 32°C 10.0 kW 12.0 kW 15.0 kW 20.0 kW 25.0 kW

Power consumption 4.0 kW 4.8 kW 5.8 kW 8.0 kW 9.0 kW


Rated current max. 12.0 A 14.0 A 17.0 A 20.0 A 22.0 A
Refrigerant R407C
No. of cooling circuits 1
Environment +15°C to +43°C
Temperature range
Liquid media +10°C to +25°C
Pump capacity See characteristic curve
Tank Made from PP plastic
Tank capacity 120 l 240 l
Water connections 3/
4˝ external thread 1˝ external thread
Weight 250 kg 270 kg 380 kg 530 kg 560 kg
Colour RAL 7035
Protection category (electrics) IP 54
Air throughput of fans 6000 m3/h 8000 m3/h
Temperature control Electronic control with digital display (factory setting +18°C)
Delivery times available on request.
Special voltages, other frequencies, and technical modifications available on request.
We reserve the right to make technical modifications.

Air/water heat exchangers From page 102 TS 8 lock systems Cat. 32, from page 947 TS 8 baying system Cat. 32, from page 138
Overflow valve page 194 Cooling medium page 194

128 Rittal System Climate Control


Recooling systems for water
Mini, for wall mounting, cooling output 1/2.5/4 kW

H
H
B B
T T

B = Width
T = Depth

Technical design: Supply includes: Approvals,


● Compact, modular configura- Recooling system wired ready see page 289.
tion of the cooling compo- for connection, with multilingual
Layout diagram,
nents with integral water tank. documentation including func-
see page 264.
● With RiNano coating tional diagram and wiring plans.
● Application-specific special Characteristic curves of pump,
equipment available on see page 264.
request.
Other options,
● Open system with tank.

Recooling systems for water


see page 256.

Model No. SK 3360.100 3360.250 3360.470


Rated operating voltage V/Hz 400, 3~, 50/60/460, 3~, 601)
W 400 400 500
Dimensions in mm H 950 1580 1580
D 310 290 390
Cooling output at
Tw = 10°C/Tu = 32°C 0.8 W/0.9 kW 2.1 kW/2.3 kW 3.3 kW/3.7 kW
Tw = 18°C/Tu = 32°C 1.0 kW/1.1 kW 2.5 kW/2.8 kW 4.0 kW/4.5 kW

Power consumption 0.7 kW/0.76 kW 1.55 kW/2.0 kW 1.85 kW/2.74 kW


Rated current max. 2.7 A/3.0 A 3.7 A/3.8 A 4.6 A/5.2 A
Refrigerant R134a
No. of cooling circuits 1
Environment +15°C to +43°C
Temperature range
Liquid media +10°C to +25°C
Pump capacity See characteristic curve
Tank Plastic
Tank capacity 5l 10 l 15 l
Water connections Quick-release coupling (counterpart included in accessory bag) 3/ ˝ internal thread
4

Weight 47 kg 78 kg 103 kg
Colour RAL 7035
Protection category (electrics) IP 44
Air throughput of fans 500 m3/h 710 m3/h 2000 m3/h
Temperature control Microcontroller control (factory setting +18°C)
Packs
Accessories Page
of
Filter mat 1 3286.400 189
Metal filter mat 1 3286.410 190
1) Supports multiple voltages without rewiring.
Special voltages and technical modifications available on request.
We reserve the right to make technical modifications.

Air/water heat exchangers From page 102 Overflow valve Page 194 Cooling medium Page 194

Rittal System Climate Control 129


Recooling systems for oil
In floor-standing enclosure, cooling output 2.5 to 8 kW

H
B T

B = Width
T = Depth

Technical design: Supply includes: Approvals,


● Robust industrial standard in Recooling system wired ready Accessories: see page 290.
2 enclosure sizes. for connection, with multilingual Metal filter mats and castors Layout diagram,
● Identical basic enclosure documentation including func- available on request. see page 265.
for oil and water recooling tional diagram and wiring plans.
systems. Options,
Note:
● Variable air routing is possi- see page 256.
The illustration shows units with
ble via the l/h or r/h side panel
customer-specific options.
● High-capacity gear pump.
Recooling systems for oil

● Floating contact for collective


fault signal.
● Integration of application-spe-
cific special equipment on
request.

Model No. SK 3337.200 3337.300 3337.500 3337.600 3337.650


Rated operating voltage V/Hz 400, 3~, 50
W 485 595
Dimensions in mm H 965 1180
D 650 800
Cooling output with oil ISO VG 32
Toil = 20°C 2.5 kW 3.4 kW 5.2 kW 6.7 kW 8.0 kW
Tu = 32°C

Power consumption 1.4 kW 1.9 kW 3.0 kW 3.9 kW 4.9 kW


Rated current max. 3.1 A 3.5 A 5.0 A 7.0 A 7.8 A
Refrigerant R134a
No. of cooling circuits 1
Environment +15°C to +43°C
Temperature range
Liquid media +15°C to +25°C
Pump capacity at 10 bar 10 l /min 24 l /min
Optional tank Made from stainless steel 1.4301 (AISI 304)
Optional tank capacity 33 l 57 l
Connections 3/
4˝ internal thread 1˝ internal thread
Weight 103 kg 105 kg 148 kg 150 kg 154 kg
Colour RAL 7035
Protection category (electrics) IP 54
Air throughput of fans 1250 m3/h 1785 m3/h 3140 m3/h
Temperature control Electronic control with digital display (factory setting +20°C)
Delivery times available on request.
Special voltages, other frequencies, and technical modifications available on request.
We reserve the right to make technical modifications.

^go
Layout diagram Page 265

130 Rittal System Climate Control


Recooling systems for oil
In floor-standing enclosure, cooling output 11 to 26 kW

H
T
B

B = Width
T = Depth

Technical design: Supply includes: Approvals,


● Robust industrial housing in Recooling system wired ready Accessories: see page 290.
2 enclosure sizes. for connection, with multilingual Metal filter mats and castors Layout diagram,
● Identical basic enclosure documentation including func- available on request. see page 265.
for oil and water recooling tional diagram and wiring plans.
systems. Options,
Note:
● Variable air routing is possi- see page 256.
The illustration shows units with
ble via the l/h or r/h side
customer-specific options.
panel.

Recooling systems for oil


● Optimum accessibility for
servicing purposes by remov-
ing the side panel.
● High-capacity gear pump.
● Floating contact for collective
fault signal.
● Integration of application-
specific special equipment on
request.

Model No. SK 3337.700 3337.710 3337.720 3337.730 3337.740 3337.750


Rated operating voltage V/Hz 400, 3~, 50/460, 3~, 60
W 615 715
Dimensions in mm H 1178 1178
D 1160 1360
Cooling output with oil ISO VG 32
Toil = 20°C 11 kW 15.5 kW 17.2 kW 19.0 kW 22.0 kW 26.0 kW
Tu = 32°C

Power consumption 5.3 kW 6.4 kW 7.1 kW 8.7 kW 9.6 kW 10.5 kW


Rated current max. 12.0 A 15.0 A 16.0 A 19.0 A 21.0 A 22.0 A
Refrigerant R407C
No. of cooling circuits 1
Environment +15°C to +43°C1)
Temperature range
Liquid media +15°C to +25°C
Pump capacity at 10 bar 45 l /min 68 l /min
Optional tank Made from stainless steel 1.4301 (AISI 304)
Optional tank capacity 60 l 100 l
Connections 1˝ internal thread
Weight 222 kg 232 kg 242 kg 248 kg 258 kg 268 kg
Colour RAL 7035
Protection category (electrics) IP 54
Air throughput of fans 6280 m3/h 10880 m3/h
Temperature control Electronic control with digital display (factory setting +20°C)
1) SK3337.720 and SK 3337.750 +15°C to +40°C.
Delivery times available on request.
Special voltages, other refrigerants, and technical modifications available on request.
We reserve the right to make technical modifications.

Layout diagram Page 265

Rittal System Climate Control 131


Immersible recooling systems for oil/emulsion
Cooling output 2.4 to 5.6 kW
T1 B1

H1
H2
B2
T2

B = Width
T = Depth

Application: Technical design: Supply includes: Approvals,


Ideal for cooling contaminated ● For the cooling of oil/emulsion. Immersible recooling system see page 290.
cooling lubricants, such as drill- ● Robust industrial standard. wired ready for connection,
Layout diagram,
ing, cutting and grinding oils in ● Flat evaporator coil insensi- metal filter, eyebolts, with
see page 265.
machine tools. The units are tive to dirt. multilingual documentation,
placed on top of the oil or emul- ● Bi-frequency components including functional diagram Options,
sion tank and immersed in the (50/60 Hz). and wiring plans. see page 257.
fluid.
Immersible recooling systems for oil/emulsion

Model No. SK for oil 3338.020 3338.040 3338.060 3338.080


Model No. SK for emulsion 3338.500 3338.520 3338.540 3338.560
Rated operating voltage V, Hz 400, 3~, 50/460, 3~, 60
Cooling output at
Toil/EM = 20°C/Tu = 32°C 2.4 kW/2.7 kW 3.2 kW/3.6 kW 4.6 kW/5.2 kW 5.6 kW/6.3 kW
B1 785
Dimensions in mm H1 1650
T1 785
B2 719
Dimensions of immersible part, mm
T2 719
Immersion depth mm H2 550
Minimum media level with oil/emulsion mm 203/178 278/203

Oil 1.6 kW/1.9 kW 1.8 kW/2.2 kW 2.4 kW/3.0 kW 2.6 kW/3.3 kW


Power consumption
Emulsion 1.8 kW/2.1 kW 2.0 kW/2.5 kW 2.6 kW/3.2 kW 2.8 kW/3.6 kW
Oil 3.5 A/3.7 A 3.8 A/4.0 A 5.5 A/5.9 A 5.6 A/5.8 A
Rated current max.
Emulsion 3.8 A/4.0 A 4.1 A/4.3 A 5.9 A/6.3 A 6.0 A/6.3 A
Refrigerant R134a
Number of cooling circuits 1
Environment +15°C to +42°C
Temperature range
Liquid media +10°C to +25°C
Weight 133/130 kg 143/140 kg 158/155 kg 173/170 kg
Colour RAL 7035
Protection category (electrics) IP 54
Air throughput of fans 1500/1560 m3/h 2200/2350 m3/h
Electronic controller with digital display; +10°C to +25°C adjustment range
Temperature control
(factory setting +20°C)
Delivery times available on request.
Special voltages available on request. Technical modifications reserved.

Layout diagram Page 265

132 Rittal System Climate Control


Immersible recooling systems for oil/emulsion
Cooling output 8.5 to 17.3 kW
T1 B1

H1
H2
B2
T2

B = Width
T = Depth

Application: Technical design: Supply includes: Approvals,


Ideal for cooling contaminated ● For the cooling of oil/emulsion. Immersible recooling system see page 290.
cooling lubricants, such as drill- ● Robust industrial standard. wired ready for connection,
Layout diagram,
ing, cutting and grinding oils in ● Flat evaporator coil insensi- metal filter, eyebolts, with
see page 265.
machine tools. The units are tive to dirt. multilingual documentation,
placed on top of the oil or emul- ● Bi-frequency components including functional diagram Options,
sion tank and immersed in the (50/60 Hz). and wiring plans. see page 257.
fluid.

Immersible recooling systems for oil/emulsion


Model No. SK for oil 3338.100 3338.120 3338.140 3338.160 3338.180 3338.200
Model No. SK for emulsion 3338.580 3338.600 3338.620 3338.640 3338.660 3338.680
Rated operating voltage V, Hz 400, 3~, 50/460, 3~, 60
Cooling output at 8.5 kW/ 10.5 kW/ 12.0 kW/ 13.6 kW/ 15.3 kW/ 17.3 kW/
Toil/EM = 20°C/Tu = 32°C 9.5 kW 11.8 kW 13.4 kW 15.2 kW 17.1 kW 19.4 kW
B1 785
Dimensions in mm H1 1650
T1 785
B2 719
Dimensions of immersible part, mm
T2 719
Immersion depth mm H2 550
Minimum media level with oil/emulsion mm 328/278 378/278 428/328

Oil 4.6 kW/5.5 kW 5.0 kW/6.0 kW 5.6 kW/6.6 kW 6.1 kW/7.3 kW 6.7 kW/8.1 kW 7.5 kW/9.0 kW
Power consumption
Emulsion 4.8 kW/5.7 kW 5.3 kW/6.3 kW 5.8 kW/6.8 kW 6.3 kW/7.6 kW 6.6 kW/8.5 kW 7.7 kW/9.3 kW
Oil 8.4 A/8.6 A 9.2 A/9.3 A 10.1 A/10.5 A 11.1 A/11.5 A 12.1 A/12.4 A 13.3 A/13.7 A
Rated current max.
Emulsion 8.5 A/9.0 A 9.6 A/9.9 A 10.6 A/11.2 A 11.5 A/12.0 A 12.5 A/13.2 A 13.7 A/14.1 A
Refrigerant R407C
Number of cooling circuits 1
Environment +15°C to +42°C
Temperature range
Liquid media +10°C to +25°C
Weight 183 kg 203 kg 228 kg 248 kg 253 kg 263 kg
Colour RAL 7035
Protection category (electrics) IP 54
Air throughput of fans 7200/7480 m3/h 7900/8480 m3/h
Temperature control Electronic control with digital display (factory setting +20°C)
Delivery times available on request.
Special voltages available on request. Technical modifications reserved.

Layout diagram Page 265

Rittal System Climate Control 133


Immersible recooling systems for oil/emulsion
Cooling output 21 to 78 kW
B1

T1

H1
H2
T2
B2

B = Width
T = Depth

Application: Technical design: Supply includes: Approvals,


Ideal for cooling contaminated ● For the cooling of oil/emulsion. Immersible recooling system see page 290/291.
cooling lubricants, such as drill- ● Robust industrial standard in wired ready for connection,
Layout diagram,
ing, cutting and grinding oils in 2 enclosure sizes. metal filter, eyebolts, with
see page 265.
machine tools. The units are ● Flat evaporator coil insensi- multilingual documentation,
placed on top of the oil or emul- tive to dirt. including functional diagram Options,
sion tank and immersed in the ● Bi-frequency components and wiring plans. see page 257.
fluid. (50/60 Hz).
Immersible recooling systems for oil/emulsion

Model No. SK for oil 3338.220 3338.240 3338.260 3338.280 3338.300 3338.320 3338.340 3338.360
Model No. SK for emulsion 3338.700 3338.720 3338.740 3338.760 3338.780 3338.800 3338.820 3338.840
Rated operating voltage V, Hz 400, 3~, 50/460, 3~, 60
Cooling output at 21.0 kW/ 31.0 kW/ 35.0 kW/ 46.0 kW/ 49.0 kW/ 61.0 kW/ 73.0 kW/ 78.0 kW/
Toil/EM = 20°C/Tu = 32°C 23.0 kW 35.0 kW 39.0 kW 50.0 kW 54.0 kW 69.0 kW 81.0 kW 87.0 kW
B1 785 1830
Dimensions in mm H1 1650 1650
T1 1830 1830
B2 719 1764
Dimensions of immersible part, mm
T2 1764 1764
Immersion depth mm H2 550
Minimum media level with oil/emulsion mm 378/278 428/328 378/278 428/278 428/328 428/378

9.7 kW/ 13.0 kW/ 14.6 kW/ 18.8 kW/ 20.0 kW/ 23.6 kW/ 27.3 kW/ 29.0 kW/
Oil
9.9 kW 16.2 kW 18.2 kW 22.6 kW 24.1 kW 28.5 kW 32.9 kW 34.9 kW
Power consumption
10.1 kW/ 13.4 kW/ 14.0 kW/ 19.5 kW/ 20.8 kW/ 24.4 kW/ 28.0 kW/ 29.8 kW/
Emulsion
12.6 kW 16.7 kW 18.7 kW 23.5 kW 25.0 kW 29.5 kW 33.9 kW 35.9 kW
17.3 A/ 21.6 A/ 24.3 A/ 35.5 A/ 35.4 A/ 42.7 A/ 50.0 A/ 53.0 A/
Oil
17.8 A 23.0 A 25.5 A 35.2 A 35.8 A 42.9 A 50.0 A 53.0 A
Rated current max.
17.9 A/ 22.2 A/ 24.9 A/ 36.7 A/ 36.6 A/ 43.9 A/ 50.2 A/ 54.2 A/
Emulsion
18.4 A 23.6 A 26.1 A 36.5 A 37.0 A 44.1 A 51.1 A 54.2 A
Refrigerant R407C
Number of cooling circuits 1
Environment +15°C to +45°C
Temperature range
Liquid media +10°C to +25°C
Weight 305 kg 380 kg 425 kg 435 kg 455 kg
Colour RAL 7035
Protection category (electrics) IP 54
Air throughput of fans 15000/15600 m3/h 30000/31200 m3/h
Temperature control Electronic control with digital display (factory setting +20°C)
Delivery times available on request.
Special voltages available on request. Technical modifications reserved.

Layout diagram Page 265

134 Rittal System Climate Control


Liquid cooling IT

CRAC systems from page 136


      CRAC systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 – 118 kW. . . . . . . 138

Water-cooled With heater With humidifier

Refrigerant-cooled Without heater With heater and humidifier

Aisle containment page 136


Aisle containment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139

– + Liquid Cooling Package from page 136


    LCP Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . up to 20 kW. . . . . . . 141
  LCP Plus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . up to 40 kW. . . . . . . 142
  LCP Extend. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 kW. . . . . . . 143
    LCP Smart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . up to 20 kW. . . . . . . 144
  LCP Inline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . up to 30 kW. . . . . . . 145

Liquid cooling IT
– + Scalable output Suitable for retrofitting Mid density

Standardised installation Low density High density

W Ö E
Chillers for IT cooling from page 146
 Chillers for IT cooling . . . . . . . . . . . . . . . . . . . . . . 15 to 123 kW. . . . . . . 148
 Chillers for IT cooling . . . . . . . . . . . . . . . . . . . . . 145 to 462 kW. . . . . . . 149

W Medium to be cooled: Ö Medium to be cooled: E Medium to be cooled:


Water Oil Emulsion

E Water/water heat exchangers from page 150


 Water/water heat exchangers . . . . . . . . . . . . . . . 25 to 250 kW. . . . . . . 153

Water-carrying parts
E stainless steel (optional)

Piping systems page


 Piping systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154

User-specific

Rittal System Climate Control 135


CRAC systems,
Liquid Cooling Package
CRAC systems, Liquid Cooling Package

Modular climate control concepts – tailored to your dissipated from the network enclosures and server

specific requirements! Rittal solves the problem of racks via air/water heat exchangers.

climate control for high heat losses per rack with liquid Additionally, this system allows data centres to be

cooling components. Extremely high heat loads are extended in a temperature-neutral way.

136 Rittal System Climate Control


CRAC systems
Perfect solutions for cooling via a LCP Smart/LCP Plus
raised floor. Integral, scalable, and These units provide reliable climate control
energy-efficient. and precise server loads up to 30 kW.

LCP Inline
The LCP Inline is designed for siting within a
bayed enclosure suite. The hot air is drawn
in from the room or hot aisle at the rear of the
device and expelled at the front into the cold
aisle after cooling. The LCP Inline achieves
maximum performance and efficiency in
conjunction with Rittal aisle containment.
With this product, a raised floor is not
necessary.

CRAC systems, Liquid Cooling Package

Benefits at a glance LCP Extend:


● Complete unit with 12 kW useful cooling
Important
CRAC systems: output ● All enclosures are bayable with the corre-
● An alternative to water and refrigerant ● Independent unit; ideal for retrofitting to sponding TS 8 racks.
● Energy-efficient EC fan system racks while operational ● To ensure proper use of LCP compo-
● Relieves the pressure on the room air- nents, the racks being cooled should be
LCP Plus:
sealed against the ingress of ambient air
● Complete unit with 30 kW useful cooling conditioning system
wherever possible.
output LCP Inline: For suitable accessories see page 187.
● Touchscreen ● Complete unit with 30 kW useful cooling
● Basic CMC as standard output
LCP Smart: ● No raised-floor climate control is required Tips and tricks
● Complete unit with 20 kW useful cooling in the cold aisle Applications see page 140
output All LCPs come with networking capability
● Basic CMC as standard Selection criteria see page 227
as standard, thanks to the Basic CMC with
● Optional touchscreen integral graphic user interface. Assembly see page 228

Rittal System Climate Control 137


CRAC systems
Useful cooling output 18 – 118 kW
T
B

H
B = Width
T = Depth

Application and mode of Benefits: Equipment:


operation: ● The unit is available in a User-friendly, high-quality con-
The CRAC system draws warm broad output range, and for a troller with an extensive range
waste air from the top of your variety of cooling media. of functions and connectivity.
data centre, cools it using either ● The unit supports optimum Space-saving, readily accessi-
water or refrigerant in a closed integration of both hardware ble, high-efficiency fan.
heat exchanger, and blows the and software. Flow and energy-optimised
cooled, filtered supply air into ● Optimum energy and space special heat exchanger with
the raised floor with overpres- efficiency thanks to intelligent a generous safety factor.
sure. design features, such as the
Colour:
slanted heat exchanger and
RAL 7035
base-integrated fan.
● Frame based on the popular
TS 8 system.
CRAC systems

Model No. SK Without heater 3301.620 3301.660 3301.830 3301.870 3300.510 3300.560 3300.710 3300.760
Model No. SK With heater 3301.630 3301.670 3301.840 3301.880 3300.520 3300.570 3300.720 3300.770
Model No. SK With humidifier 3301.640 3301.680 3301.850 3301.890 3300.530 3300.580 3300.730 3300.780
With heater
Model No. SK 3301.650 3301.690 3301.860 3301.990 3300.540 3300.590 3300.740 3300.790
and humidifier
Useful cooling output1) 23 kW 39 kW 78 kW 118 kW 18 kW 30 kW 43 kW 54 kW
Operating voltage V/Hz 400/50 400/50 400/50 400/50 400/50 400/50 400/50 400/50
W 1100 1100 1800 2600 1100 1100 1400 1800
Dimensions in mm H 1950 1950 1950 1950 1950 1950 1950 1950
D 650 850 850 850 850 850 850 850

Cooling medium Water2) Refrigerant R407C2)


Volumetric airflow at an external pressure loss
6000 m3/h 11000 m3/h 22000 m3/h 33000 m3/h 6000 m3/h 8500 m3/h 12500 m3/h 16000 m3/h
of 20 Pa
No. of fans 1 1 2 3 1 1 1 2
Power consumption of fans 0.6 kW 1.5 kW 3.0 kW 4.6 kW 0.6 kW 0.9 kW 1.8 kW 1.7 kW
Start-up current of fans 1.8 A 4.6 A 9.2 A 13.8 A 1.8 A 4.6 A 4.6 A 9.2 A
Max. speed 1150 rpm 1200 rpm 1200 rpm 1200 rpm 1150 rpm 1200 rpm 1200 rpm 1200 rpm
No. of compressors – 1 2 3 3
Power consumption of compressors – 5 kW 8.8 kW 13.1 kW 15 kW
Start-up current of compressors – 13.1 A 25.6 A 38.4 A 39.3 A
Type of connection Terminal strip –
Weight 300 kg 360 kg 550 kg 770 kg 455 kg 505 kg 585 kg 935 kg
Noise output 75 dB (A) 79 dB (A) 82 dB (A) 84 dB (A) 74 dB (A) 74 dB (A) 81 dB (A) 76 dB (A)
Filter quality to DIN EN 779 G4 G4
1) Outputfigures less heat from the fans.
CW: 26°C/45 % air inlet and 10°C/15°C water temperatures DX: 26°C/45 % air inlet and 50°C condensation temperature
2) Other
media available on request.
Other options available on request. We reserve the right to make technical modifications.

Recooling systems From page 146

138 Rittal System Climate Control


Aisle containment

12
00 00
0/8
60

2000
Application and mode of Benefits: Equipment: Note:
operation: ● Increased energy efficiency Slimline door element with view- Other size variants and
Rittal aisle containment is a and performance capability ing window. individually modified systems
combination of door and roof of climate control. Stable roof components in a available on request.
components which facilitate ● Superior output density is composite metal with a high
consistent separation of the hot facilitated, thanks to guaran- level of light permeability.
and cold air in the data centre. teed cold air supply. Where required, safety glass
Such separation is elementary ● Easily installed and retrofit- may also be used.
when it comes to saving energy ted, as it is fully compatible
and increasing the efficiency of with the TS 8 enclosure
the available climate control system.
technology. It is the cold air that ● An inexpensive way to boost
determines whether your equip- the performance of your exist-
ment is at its best in the enclo- ing plant, lengthening the
sures. investment cycle until a
With this in mind, Rittal has replacement needs to be pur-

Aisle containment
deliberately chosen to focus on chased.
this aspect, and to route cold air
selectively to the equipment.

Model No. SK roof element 3300.170 3300.180 –


Model No. SK door element – – 3300.160

Width of element (identical to enclosure width), mm 600 800 –


Width of cold aisle mm 1200 1200 1200
Height of cold aisle mm – – 2000

LCP Extend From page 143

Rittal System Climate Control 139


Liquid Cooling Package
Applications
Efficient climate control concepts – tailored to your specific
Possible Water/water heat
interfaces for exchanger
requirements!
● Emergency
water supply Rittal solves the problem of climate control for high heat
IT chiller
losses per rack with liquid cooling components. Extremely

high heat loads are dissipated from the enclosures, IT and


● Free
cooling
server racks via air/water heat exchangers. Additionally,

data centres may be extended in a temperature-neutral

● Heat manner, and cold aisles efficiently supplied with cold air.
recovery
Control
Distribution

LCP Standard LCP Smart

Bayable with TS 8 server racks Maximum efficiency with


As the height and depth are EC fan technology
identical, it may be bayed either The latest yardstick in the mid-
Liquid Cooling Package

in the middle of an enclosure range performance category.


suite or at the end. Highly efficient and compact.

LCP Plus LCP Inline

Useful cooling output up to Targeted cooling of selected


40 kW aisles
Useful cooling outputs of 30 kW With a useful cooling output of
(rack height 2000 mm) or 40 kW up to 30 kW, aisles can be effi-
(rack height 2400 mm) are ciently cooled in conjunction
achieved with 6 or 8 high-per- with aisle containment.
formance fans, which may be
exchanged without the need for
tools.

LCP Extend

Installation while operational


Air/water heat exchanger
(12 kW) to support climate
control of the room.

140 Rittal System Climate Control


Liquid Cooling Package
LCP Standard, useful cooling output up to 20 kW
B
T

H
B = Width
T = Depth

Application and mode of Benefits: ● LCPs are easy to handle Approvals,


operation: ● The separation of cooling and (max. 2 m) and may be trans- see page 293.
Air/water heat exchanger, rack prevents water from pen- ported in lifts and through
bayable with server racks etrating the server rack. doors.
based on TS 8 (H x D 2000 x ● Increased assembly- and ● The low weight means a mini-
1000/1200 mm). service-friendliness mal area load.
The useful cooling output of
max. 20 kW can be achieved
by installing additional modules.

Model No. SK 3301.2301) 3301.420


Description LCP Standard
Rated operating voltage V/Hz 230, 50/60
W 300 300

Liquid Cooling Package


Dimensions in mm H 2000 2000
D 1000 1200
Usable U 42
Useful cooling output Up to 20 kW

Rated current 3.8 A/4.4 A


Pre-fuse 10 A/10 A
Cooling medium Water (for specifications see Internet)
Water inlet temperature +6°C to +20°C
Permissible operating pressure p. max. 5 bar
Protection category to EN 60 529 IP 30
Duty cycle 100 %
Electrical connection Connection cable
Water connection 3/ ˝ external thread
4

Weight max. 160 kg


Colour RAL 7035
Air throughput of fans 3000 m3/h
4-way fan control
Temperature control
Electro-magnetic valve
Accessories Packs of Page
Add-on cover for height compensation with 2200 mm high racks 1 3301.221 3301.421 188
Special voltages and sizes available on request. We reserve the right to make technical modifications.
1) Also available with 115 V, Model No. 3301.210.

Cooling module
The cooling module allows the
useful cooling output of the
LCP Standard to be increased
in 6.6 kW increments.
Model No. see page 186.

Accessories Page 186 IT chillers From page 146 Server racks Cat. 32, from page 774

Rittal System Climate Control 141


Liquid Cooling Package
LCP Plus, useful cooling output up to 40 kW
B
T

H
B = Width
T = Depth

Application and mode of Benefits: ● LCPs are easy to handle and Approvals,
operation: ● The separation of cooling and may be transported in lifts and see page 293.
Air/water heat exchanger, rack prevents water from pen- through doors.
bayable with server racks etrating the server rack. ● The low weight means a mini-
based on TS 8 (H x D 2000 x ● Increased assembly- and mal area load.
1200 mm). service-friendliness
Complete unit with 40 kW useful
cooling output.

Model No. SK 3301.4801) on request


Description LCP Plus LCP Plus
230, 1~, 50/60 230, 1~, 50/60
Rated operating voltage V/Hz
Liquid Cooling Package

400, 3~, 50/60 400, 3~, 50/60


W 300 300
Dimensions in mm H 2000 2400
D 1200 1200
Usable U 42 51
Useful cooling output Up to 30 kW Up to 40 kW

Rated current 9.3 A/10.4 A


Pre-fuse 16 A/16 A
Water
Cooling medium
(for specifications see Internet)
Water inlet temperature +6°C to +20°C
Permissible operating pressure p. max. 5 bar
Protection category to EN 60 529 IP 30
Duty cycle 100 % Technical specifications
available on request.
Electrical connection Connection cable
Water connection 1˝ external thread
Weight 230 kg
Colour RAL 7035
Air throughput of fans 5000 m3/h
4-way fan control
Temperature control
Two-way control valve
Accessories Packs of Page
Add-on cover for height compensation with 2200 mm high racks 1 3301.421 188
Special voltages and sizes available on request. We reserve the right to make technical modifications.
1) Delivery times available on request.

Accessories Page 186 IT chillers From page 146 Server racks Cat. 32, from page 774

142 Rittal System Climate Control


Liquid Cooling Package
LCP Extend, useful cooling output 12 kW
T
B

H
B = Width
T = Depth

Application and mode of Benefits: Approvals,


operation: ● Mounted on the rear of see page 294.
Air/water heat exchanger for the server rack; eases the
retrofitting to racks while opera- pressure on the room air-
tional. conditioning system.
● Water connection either at
The stand-alone unit replaces
the bottom or top.
the rear door (for other brands
on request).

Model No. SK 3301.4901)


Description LCP Extend
230, 1~, 50/60
Rated operating voltage V/Hz

Liquid Cooling Package


400, 3~, 50/60
W 520
Dimensions in mm H 1910
D 160
Usable U 42
Useful cooling output 12 kW

Rated current 2.4 A/3.0 A


Pre-fuse 6 A/6 A
Cooling medium Water (for specifications see Internet)
Water inlet temperature +15°C
Permissible operating pressure p. max. 5 bar
Protection category to EN 60 529 IP 20
Duty cycle 100 %
Electrical connection Connection cable
Water connection 3/ ˝ external thread
4

Weight 130 kg
Colour RAL 7035
Air throughput of fans 3000 m3/h
Temperature control Fan control
Special voltages and sizes available on request. We reserve the right to make technical modifications.
1) Delivery times available on request.

Accessories Page 186 IT chillers From page 146 Server racks Cat. 32, from page 774

Rittal System Climate Control 143


Liquid Cooling Package
LCP Smart, useful cooling output up to 20 kW
B
T

H
B = Width
T = Depth

Application and mode of Maximum efficiency is achieved, Benefits: ● Extended functionality of the
operation: thanks to the use of EC fans. ● High energy efficiency. monitoring and control tech-
The LCP Smart draws in the air The heat exchanger of the LCP ● Bayable with server/network nology/software.
at the sides of the server enclo- Smart supports the longest enclosures based on TS 8 ● Optimum adaptability thanks
sure rear, cools it using high- possible usage of free cooling. (H 2000, D 1000). to dynamic, continuous con-
performance compact registers, ● Fans may be individually trol of the cold water volume
and blasts the cooled air back exchanged with the system flow.
into the front part of the server operational, self-contacting. ● Control of the inlet air temper-
enclosure at the sides. ● Basic CMC as standard. ature and the temperature dif-
● Touchscreen display may be ference for the best possible
retrofitted. supply to your server systems.
● Shorter servicing times.
Liquid Cooling Package

Model No. SK 3301.460


Number of preassembled cooling modules 1
200 – 230, 1~, 50/60
Rated operating voltage V/Hz
400, 3~, 50/60
W 300
Dimensions in mm H 2000
D 1000
Usable U 42
Useful cooling output Up to 20 kW

Pre-fuse 10 A
Power consumption Pel max. 600 W
Cooling medium Water
Permissible operating pressure p. max. 5 bar
Duty cycle 100 %
Electrical connection Connection cable
Water connection 1˝ external thread
Weight 230 kg
Colour RAL 7035
Temperature control Via integral controller
Max. air throughput 3000 m3/h

Touchscreen
display
for LCP Smart,
Model No. see page 186.

Accessories Page 186 IT chillers From page 146 Server racks Cat. 32, from page 774

144 Rittal System Climate Control


Liquid Cooling Package
LCP Inline, useful cooling output up to 30 kW
B
T1

H
B = Width
T = Depth

Application and mode of Equipment: Benefits:


operation: High-performance heat ● Combines the slimline design
The LCP Inline is designed for exchanger with very even of the LCP with the function of
siting within a bayed enclosure temperature distribution. room air-conditioning.
suite. The hot air is extracted Integrated condensate ● Climate control technology,
from the room or warm aisle at management. specially designed for IT envi-
the rear of the unit, cooled, then Controller with networking capa- ronments with comprehensive
expelled forwards into the cold bility, compatible with all com- monitoring functions.
aisle, where it is available to your mon communication standards ● Frame based on the popular
IT equipment. (SNMP, BACnet etc.). TS 8 system.
The LCP Inline achieves maxi-
mum performance and effi-
ciency in conjunction with Rittal
cold aisle containment. With this
product, a raised floor is not
necessary.

Liquid Cooling Package


Model No. SK 3301.470
230, 1~, 50/60
Rated operating voltage V/Hz
400, 3~, 50/60
B 300
Dimensions in mm H 2000
T1 1200
Usable U 42
Useful cooling output Up to 30 kW

Rated current 9.3 A/10.4 A


Pre-fuse 16 A/16 A
Cooling medium Water1)
Permissible operating pressure p. max. 5 bar
Duty cycle 100 %
Electrical connection Connection cable
Water connection 1˝ external thread
Weight 230 kg
Colour RAL 7035
Temperature control Via integral controller
Max. air throughput 4600/4300 m3/h
1) Water quality according to unit specifications.

Front cover
The optional front cover reduces the air outlet
speed, thereby minimising draught effects.
Model No. see page 186.

Accessories Page 186 IT chillers From page 146 Server racks Cat. 32, from page 774 Aisle containment Page 139

Rittal System Climate Control 145


Chillers for IT cooling
Chillers for IT cooling

IT chillers in conjunction with free cooling, for example, Safety-relevant options such as redundant pumps,

ensure efficient cooling and supply of the cooling emergency cooling or buffer stores are the distinguish-

medium. Specially designed for supplying critical IT ing features of these atmospherically sealed systems.

applications cooled via LCP, air/water heat exchangers

or CRAC systems.

146 Rittal System Climate Control


Piping system
The Rittal piping system provides the link
between the equipment and the refrigera-
tion system.

Safety Energy-saving free cooling


Chillers are particularly well-suited chillers
for cooling IT applications, such as Cold ambient air is used for cooling. If the
LCP or air/water heat exchangers. ambient temperature is too high, the chiller
Redundant pumps and optional will cut in. Free cooling systems are particu-
special equipment for emergency larly energy-saving. The operating costs
cooling or thermal recovery are the may be cut by up to 80 %. The service life
distinguishing features of these of components is extended, and operational
systems. reliability is increased. The waste heat pro-
duced may be effectively used for heating
and hot water supply in facility management.

Chillers for IT cooling


gs
y savin
g
Enerp to 80 %
of u

Benefits at a glance Tips and tricks


Cooling output from 15 to 462 kW Applications see page 226
● A system for cooling server racks and
Selection criteria see page 227
IT applications
● Compact structure with control Assembly see page 228
components in the front and air intake
Notes see page 229
via both sides
● Individual project management
● Commissioning and servicing
● Comprehensive pipeline calculation
● Global service network

Rittal System Climate Control 147


Chillers for IT cooling
Cooling output 15 to 123 kW

H
T

B = Width
T = Depth

Application: Technical design: Options: Layout diagram,


Especially for cooling IT applica- ● Compact design with control ● Free cooling may be inte- see page 266.
tions, such as LCP or air/water components in the front and grated from 61 kW.
heat exchangers. Safety-rele- air intake via both side pan- Please follow the instructions!
vant features such as redundant els, air outlet upwards. ● Buffer store for separate siting
speed-controlled pumps, com- ● Pressure-sealed system. ● Emergency cooling with
pressors or buffer stores are the ● Digital thermostat for tempera- mains water infeed
distinguishing features of these ture control with setpoint and ● Special voltages
atmospherically sealed systems. actual value display.
Note:
● Monitoring interface with Rittal
The illustration shows a unit with
CMC-TC supported.
customer-specific options.
● Integral automatic bypass
Technical deviations in terms of
valve.
cooling output, dimensions or
● Flow monitor.
weight are possible for unit
Supply includes: types with free cooling.
Chiller wired ready for
Chillers for IT cooling

connection, with multilingual


documentation including
functional diagram and wiring
plans.

Model No. SK 3232.700 3232.710 3232.720 3232.730 3232.740 3232.750 3232.760 3232.770 3232.780 3232.790
Rated operating voltage V/Hz 400, 3~, 50
W 815 815 815 1000 1100 1100 1100 1100 1100 1100
Dimensions in mm H 1400 1400 1400 2180 1606 1606 1606 1606 1875 1875
D 1560 1560 1560 2000 2450 2450 2450 2950 2950 2950
Cooling output
15 kW 24 kW 36 kW 48 kW 61 kW 72 kW 82 kW 92 kW 113 kW 123 kW
at Tw = 15°C/Tu = 35°C

Power consumption 6900 W 9700 W 14600 W 21000 W 21400 W 24400 W 27500 W 31100 W 38900 W 42600 W
Rated current max. 23.0 A 25.0 A 37.0 A 46.5 A 71.2 A 74.2 A 77.2 A 83.2 A 106.1 A 112.1 A
Refrigerant R407C
Pmax. cooling circuit 28 bar
Environment –20°C to +43°C
Temperature range
Liquid media +5°C to +15°C
Pump capacity 60 l/min. 120 l/min. 240 l/min. 500 l/min.
Pump pressure 2.5 bar
Number of cooling circuits 1 2
Tank with 10 mm condensate insulation Steel
Tank capacity 48 l 100 l 300 l 500 l
Water connections 1˝ 1 1/4˝ 2˝ 2 1/2˝
Operating weight 375 kg 390 kg 480 kg 710 kg 810 kg 849 kg 864 kg 949 kg 1150 kg 1175 kg
Colour RAL 7035 RAL 9002
Protection category (electrics) IP 54
Air throughput
m3/h 10880 14000 18000 13720 20450 27300 35000
of fans
Temperature control Electronic control with digital display (factory setting +15°C)
Delivery times available on request. We reserve the right to make technical modifications.
Cooling output makes allowance for 35 % glycol.

Accessories Page 181

148 Rittal System Climate Control


Chillers for IT cooling
Cooling output 145 to 462 kW

H
T

B = Width
T = Depth

Application: Technical design: Options: Layout diagram,


Especially for cooling IT applica- ● Compact design with control ● Free cooling may be inte- see page 266.
tions, such as LCP or air/water components in the front and grated from 61 kW.
heat exchangers. Safety-rele- air intake via both side pan- Please follow the instructions!
vant features such as redundant els, air outlet upwards. ● Buffer store for separate siting
speed-controlled pumps, com- ● Pressure-sealed system. ● Emergency cooling with
pressors or buffer stores are the ● Digital thermostat for tempera- mains water infeed
distinguishing features of these ture control with setpoint and ● Special voltages
atmospherically sealed systems. actual value display.
Note:
● Monitoring interface with Rittal
The illustration shows a
CMC-TC supported.
customised unit design up to
● Integral automatic bypass
180 kW.
valve.
Technical deviations in terms of
● Flow monitor.
cooling output, dimensions or
Supply includes: weight are possible for unit
Chiller wired ready for types with free cooling.

Chillers for IT cooling


connection, with multilingual
documentation including
functional diagram and wiring
plans.

Model No. SK 3232.800 3232.810 3232.820 3232.830 3232.840 3232.850 3232.860 3232.870 3232.880
Rated operating voltage V/Hz 400, 3~, 50
W 1100 1100 1100 2200 2200 2200 2200 2200 2200
Dimensions mm H 1875 1875 1875 2450 2450 2450 2450 2450 2450
D 2950 2950 3950 3400 3400 3400 4250 4250 4250
Cooling output
145 kW 161 kW 193 kW 248 kW 280 kW 312 kW 372 kW 415 kW 462 kW
at Tw = 15°C/Tu = 35°C

Power consumption 50900 W 57600 W 63700 W 89100 W 97300 W 105400 W 138000 W 148200 W 158400 W
Rated current max. 141 A 146 A 153 A 208 A 227 A 245 A 311 A 339 A 366 A
Refrigerant R407C
Pmax. cooling circuit 28 bar
Environment –20°C to +43°C
Temperature range
Liquid media +5°C to +15°C
Pump capacity 500 l/min. 810 l/min. 1200 l/min.
Pump pressure 2.5 bar
Number of cooling circuits 2
Tank with 10 mm condensate insulation Steel
Tank capacity 500 l 700 l 1000 l
Water connections 2 1/2˝ 3˝ 4˝
Operating weight 1250 kg 1340 kg 1520 kg 2702 kg 2795 kg 2831 kg 3460 kg 3567 kg 3667 kg
Colour RAL 9002
Protection category (electrics) IP 54
Air throughput
m3/h 35500 60900 86000 76000 111000
of fans
Temperature control Electronic control with digital display (factory setting +15°C)
Delivery times available on request. We reserve the right to make technical modifications.
Cooling output makes allowance for 35 % glycol.

Accessories Page 181

Rittal System Climate Control 149


Water/water heat exchangers
Water/water heat exchangers

Water/water heat exchangers allow existing water such as water circuits with cooling tower, process or

circuits within the company to be used, even if they well water, or aggressive or contaminated water.

are not suitable for direct enclosure climate control,

150 Rittal System Climate Control


Redundancy
Double pump, speed-controlled, with alter-
nating 24 h operation.

Interrogate operating Stainless steel pipework


statuses For added safety (optional).
and make settings via the Web
(TCP/IP).

Water/water heat exchangers

Benefits at a glance Important


● Redundancy thanks to double pump unit The pipework may also be supplied in
fitted with linear speed control stainless steel (1.4401).
● Linear controlled 3-way valve (4 – 20 mA)
● Floating contact for collective fault signal
● Flow rate display and monitoring
● Digital controller
● Water connection in base
● Integrated into a TS 8 enclosure
● Compact construction mounted in a
tubular frame

Rittal System Climate Control 151


Water/water heat exchangers
Layout diagram

9
8

10

5 6

4
Water/water heat exchangers

All climate control solutions


from a single source:
1 Rittal aisle containment
2 CRAC systems
3 LCP Standard/Plus/Smart
4 + 8 Water/water
heat exchangers
5 IT chiller
6 Double pump unit
7 Heat recovery
9 Buffer store
10 Emergency water supply

152 Rittal System Climate Control


Water/water heat exchangers
Cooling output 25 to 250 kW

H
B

B = Width
T = Depth

Application: Technical design: Supply includes:


Water/water heat exchangers ● Compact construction Water/water heat exchanger Accessories:
are primarily used to hydrauli- mounted in a tubular frame wired ready for connection, with ● Buffer store 1000 – 3000 l
cally and physically separate a ● Integrated in a TS 8 enclosure multilingual documentation ● Standard pump with
definable primary water circuit ● Digital controller including functional diagram
automatic bypass
(dirt, pressure fluctuations) from ● Floating contact for collective and wiring plans. ● Emergency water infeed
a defined secondary water cir- fault signal ● Secondary flow monitor
Note:
cuit. ● Flow rate display and
The illustration shows units with ● Ethernet, BACnet and
monitoring SNMP link
customer-specific options.
● Water connection in base ● Magnetic filter
● Double pump unit fitted with
● Pipework in stainless steel
linear speed controller 1.4401 (AISI 316)
● Linear controlled 3-way valve ● Tubular frame,
(4 – 20 mA)
without TS 8 enclosure
Layout diagram,

Water/water heat exchangers


see page 267.

Model No. SK 3232.900 3232.910 3232.920 3232.930 3232.940 3232.950 3232.960


Rated operating voltage V/Hz 400, 3~, 50
W 1200 1200 1200 1600 1600 2000 2000
Dimensions
H 1900 1900 1900 1900 1900 1900 1900
incl. base/plinth in mm
D 800 800 800 800 800 800 800
Cooling output at
Twp = 6°C/Tws = 15°C 25 kW 50 kW 75 kW 100 kW 150 kW 200 kW 250 kW

Power consumption 3.54 kW 5.7 kW 5.7 kW 10.4 kW 10.4 kW 13.6 kW 13.6 kW


Rated current max. 3.5 A 5.9 A 5.9 A 10.2 A 10.2 A 10.8 A 10.8 A
Environment +5°C to +45°C
Temperature range Tp primary side +6°C to +30°C
Ts secondary side +6°C to +30°C
Pump capacity (l/min.) primary/secondary 62 125 187 250 375 500 625
primary 1.5 – 6.0
Pump pressure (bar) secondary
2.5
(equipment)
Water connections primary/secondary RP 1˝ RP 1 1/4˝ RP 1 1/2˝ RP 2˝ RP 2˝ RP 2 1/2˝ RP 2 1/2˝
Weight 400 kg 450 kg 450 kg 700 kg 700 kg 900 kg 900 kg
Colour RAL 7035
Protection category (electrics) IP 54
Temperature control Electronic controller with digital display; +5°C to +50°C adjustment range
Delivery times available on request.
Special voltages, other frequencies, and technical modifications available on request.

Air/water heat exchangers From page 102 TS 8 lock systems Cat. 32, from page 947 TS 8 baying system Cat. 32, from page 138
Overflow valve Page 194 Cooling medium Page 194

Rittal System Climate Control 153


Piping systems in the data centre

Efficient cooling solutions rely on an excellent infra- efficient operation of all cooling components. This also

structure. The Rittal piping system provides the link includes safety-relevant options such as redundant

between the equipment and the refrigeration system. pumps, emergency cooling or buffer stores.

An optimum design and targeted media supply ensure


Piping systems in the data centre

Speed-controlled pumps are used to convey The standard hydraulic layout includes the use Use of compact distributors to distrib-
the coolant. of a hydraulic separating filter. ute the cooling medium among differ-
The pumped volume may be varied by using Different volumes of water on the producer side ent pieces of equipment.
state-of-the-art EC motors. and equipment side for process cooling do not
Your practical benefit:
adversely affect the function of the cooling sys-
Your practical benefit: Redundancies in the supply lines to
tems.
Lower energy consumption thanks to “cold the equipment may be designed as
water on demand”. Your practical benefit: required. For example, a layout can
Only the volume of water that is actually Less energy consumption thanks to the use of be designed to facilitate the auto-
needed for cooling is moved through the free-cooling heat exchangers including redun- matic shut off of sub-sections in the
system. dancy. event of pipe leaks.
Chiller pumps may be switched on and off as
required.

154 Rittal System Climate Control


Piping systems in the data centre

● Pipeline systems are part of a turnkey solution for the targeted ● Maximum energy efficiency thanks to the use of polypropylene
cooling of IT operating environments piping with exceptionally low pipe friction losses
● Media network for the connection of coolers (IT chillers) and ● Systems are suitable for the use of cold water and water/antifreeze
cooling equipment (liquid cooling package and CRAC systems) mixtures (glycol)
● Free scalability of chiller and equipment output via the hydraulic ● Media pumping redundancy by fitting every chiller with its own
separation of the producer and equipment sides primary pump and via the use of redundant main pumps on the
● Use of a hydraulic separating filter with dual function as a buffer equipment side
store

1 2

Piping systems in the data centre


4

5 6

The innovative polypropylene piping is 1 Direct cooling systems 5 Dirt collector station
distinguished by minimal pipe friction (e.g. LCP) with maintenance bypass
resistance. 2 CRAC systems 6 Main pump (redundant)
Your practical benefit: 3 IT chiller 7 Compact distributor
Less energy consumption for conveying
with lockable outlets
the cooling medium, thanks to lower flow 4 Buffer store
resistance.
The material is corrosion-resistant and may
be machined without residues.

Rittal System Climate Control 155


156
Outdoor climate control

Cooling units
for CS modular enclosures from page 158
    for roof-mounted type 1 . . . . . . . . . . . . . . . . . . . . . . . . . . 900 W. . . . . . . 160
   for door-mounted type 2. . . . . . . . . . . . . . . . . . . . . . . . . . 900 W. . . . . . . 160
   for wall-mounted type 3 . . . . . . . . . . . . . . . . . 900/1400/2500 W. . . . . . . 160
    for universal installation type 4 . . . . . . . . . . . . . . . . . . . . 1500 W. . . . . . . 160

Heat exchangers
for CS modular enclosures from page 158
   for roof-mounted type 1 . . . . . . . . . . . . . . . . . . . . . . . . . 30 W/K. . . . . . . 161
    for roof-mounted type 2 . . . . . . . . . . . . . . . . . . . . . . . . . 60 W/K. . . . . . . 161
   for wall-mounted type 3 . . . . . . . . . . . . . . . . . . . . . . . . . 60 W/K. . . . . . . 161
   for door-mounted type 4. . . . . . . . . . . . . . . . . . . . . . .40/60 W/K. . . . . . . 162
   for door-mounted type 5. . . . . . . . . . . . . . . . . . . . . .85/120 W/K. . . . . . . 162

Outdoor climate control


Climate control units for Toptec CR from page 158
   Heat exchangers . . . . . . . . . . . . . . . . . . . . . . . . . . .85/105 W/K. . . . . . . 163
    Cooling units . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1000/1600 W. . . . . . . 163

Ex-proof climate control systems page


Ex overpressure enclosure with integral enclosure cooling unit . . . . . . . 164

Integral heater Aluminium Wall-mounted

Protection category IP 55 Roof-mounted

Rittal System Climate Control 157


Outdoor climate control
Outdoor climate control

Rittal Communication Systems offer everything you exchangers, fans and heaters especially designed for

need to protect your electronic equipment, from outdoor use ensure constant interior temperatures. A

weather-tested enclosure solutions, to a variety of protection category of IP 55 is retained for the system

climate control components, through to complete as a whole when using Outdoor heat exchangers and

security management systems. Cooling units, heat cooling units.

158 Rittal System Climate Control


Flexibility
Climate control modules in varying
output categories may be posi-
tioned on the door, rear panel, side
panel or roof of the modular enclo-
sure.
Suitable for use within the tem- Heat exchanger/cooling unit
perature range –33°C to +55°C With three mounting positions for internal
(cooling units) and +65°C (heat mounting, partial internal mounting or exter-
exchangers). Many units feature nal mounting plus a choice between cooling
an integral heater. via the front or rear door of the Toptec CR.

Standardised installation
The full 25 mm double wall takes care of
heat exchange and minimises the influence
of sunlight, featuring an active climate con-
trol concept with fixed cut-out sizes and a
mounting frame for depth-variable position-
ing of the climate control unit. Depending on
the local conditions at the installation site,
either a heat exchanger or a cooling unit
may be used.

Outdoor climate control

Benefits at a glance Important


● The IP 55 protection category of the ● CS Outdoor cooling units and CS Out-
enclosures is retained. door heat exchangers are manufactured
● Hermetically separate air circuits – to order.
Pollutant-laden ambient air is unable ● CS Outdoor cooling units and CS Out-
to penetrate the enclosure door heat exchangers are supplied as
● Backup-compatible 48 V DC air/air heat fully integrated units on the CS Outdoor
exchangers enclosure. Mounting on other Rittal
● Integral heater in many units enclosures is only possible by arrange-
ment.

Rittal System Climate Control 159


CS Outdoor climate control
Cooling units for CS modular enclosures

Type 1 for roof mounting Type 2 for door mounting Type 3 for wall mounting Type 4 for universal
With microcontroller and With microcontroller and With microcontroller and installation
400 watt heater as standard. 400 watt heater as standard. 400 watt heater as standard. With microcontroller and
Alternative mounting on the rear 800 watt heater as standard.
Mounting frame:
or side panels is also possible.
Required for CS 9764.012. Installation options:
The picture shows the cooling
● in the door or rear panel
unit with designer cover (not
● in the side panel
included in the supply).

Model No. CS 9762.012 9768.100 9761.012 9761.032 9761.042 9768.150 Page


Type 1 Type 2 Type 3 Type 4
Internal mounting
Roof-mounted Door-mounted Wall-mounted Universal
Rated operating voltage AC 230 V, 50/60 Hz
W 535 430 515 695 776 400
Unit dimensions (mm) H 390 1070 1170 1132 1100 1050
D 400 210 151.5 151.5 250 310
Minimum enclosure W x H/D x H – 600 x 1200 600 x 1200 800 x 1200 800 x 1200 600 x 1200
dimensions (mm)
CS Outdoor climate control

WxD 600 x 500 – – – – –


Useful cooling output L35 L35 900 W 900 W 900 W 1400 W 2500 W 1500 W
EN 814 L35 L50 750 W 650 W 750 W 1050 W 2000 W 1250 W
Heater 400 W 400 W 400 W 400 W 400 W 800 W

Rated current max. 4.0 A 4.0 A 3.5 A 5.5 A 10.0 A 5.8 A


Start-up current max. 10.7 A 11.6 A 10.8 A 15.5 A 32.0 A 19.0 A
L35 L35 460 W 470 W 450 W 900 W 1450 W 940 W
Power consumption
L35 L50 520 W 530 W 520 W 1000 W 1650 W 1045 W
Coolant R134a
p. max. 26 bar 28 bar 24 bar 24 bar 28 bar 28 bar
Temperature range –33°C to +55°C
Air throughput of fans Internal circuit fan 570 m3/h 580 m3/h 880 m3/h 850 m3/h 1450 m3/h 850 m3/h
– unimpeded air flow External circuit fan 570 m3/h 430 m3/h 880 m3/h 880 m3/h 1450 m3/h 680 m3/h
Temperature control Microcontroller1)
Type of connection Plug panel
Weight 29 kg 31 kg 45 kg 48 kg 52 kg 40 kg
Protection category to EN 60 529/IEC 529 IP 55 (internal circuit to external circuit)
Material (enclosure) Aluminium Sheet steel Aluminium
Surface finish Spray finished in RAL 7035
CE Declaration of Conformity      
Accessories
Cable connection kit 9765.105 9765.105 9765.105 9765.105 9765.105 9765.105 180
Mounting frame 9765.051 – – – – – –
1) With
temperature-controlled activation of the components (internal/external circuit, heater).
Setpoints are preset. Modifications can only be made by arrangement.
Delivery times available on request.
Cooling units for modular enclosures are manufactured to order. The units are assembled and supplied connected to the modular enclosure.
Adaptations to other enclosure platforms are available on request.

CS modular enclosures Cat. 32, page 874 Test adaptor Page 180 Heaters Page 169

160 Rittal System Climate Control


CS Outdoor climate control
Heat exchangers for CS modular enclosures
Property rights for Type 1
and 2:
German patent no. 196 09 796

Type 1 for roof mounting Type 2 for roof mounting Type 3 for wall mounting
Without microcontroller, With microcontroller and heater With microcontroller and heater
without heater. as standard. as standard. For external mount-
ing on side or rear panels.
Mounting frame:
The picture shows the heat
Required for CS 9764.012.
exchanger with designer cover
(not included in the supply).

Model No. CS 9764.040 9764.012 9763.012 Page


Type 1 Type 2 Type 3
Internal mounting
Roof-mounted Roof-mounted Wall-mounted
DC (fan/
48 V
Rated operating voltage microcontroller)
AC (heater) – 230 V, 50/60 Hz
W 470 535 515
Unit dimensions (mm) H 158 390 1170
D 380 400 151.5

CS Outdoor climate control


Minimum enclosure W x H/D x H – – 600 x 1200
dimensions (mm) WxD 600 x 500 600 x 500 –
Specific thermal output 30 W/K 60 W/K 60 W/K
Heater – 400 W 400 W

DC (fan/
Rated current 1.3 A 3.1 A 3.2 A
microcontroller)
max.
AC (heater) – 1.9 A 1.9 A
Temperature range –33°C to +65°C
Air throughput of fans internal/
345 m3/h 830 m3/h 830 m3/h
– unimpeded air flow external circuit fan
Temperature control without1) Microcontroller2)
Type of connection Plug panel
Weight 7 kg 17 kg 31 kg
Protection category to EN 60 529/IEC 529 IP 55 (internal circuit to external circuit)
Material (enclosure) Aluminium Sheet steel
Surface finish Spray finished in RAL 7035
CE Declaration of Conformity   
UL/CUL –  
Accessories
Cable connection kit 9765.110 9765.110 9765.110 180
Thermostat 3110.000 – – 178
Mounting frame – 9765.051 – –
1) Customers may fit their own temperature control (SK 3110.000).
2) With temperature-controlled activation of the components (internal/external circuit, heater).
Setpoints are preset. Modifications can only be made by arrangement.
Delivery times available on request.
Heat exchangers for modular enclosures are manufactured to order. The units are assembled and supplied connected to the modular enclosure.
Adaptations to other enclosure platforms are available on request.

CS modular enclosures Cat. 32, page 874 Test adaptor Page 180 Heaters Page 169

Rittal System Climate Control 161


CS Outdoor climate control
Heat exchangers for CS modular enclosures

Type 4 for door mounting Type 5 for door mounting


With microcontroller and With microcontroller and heater
400 watt heater as standard. as standard.

Model No. CS 9768.032 9768.012 9768.042 9768.062 Page


Type 4 Type 5
Internal mounting
Door-mounted Door-mounted
DC (fan/
48 V
Rated operating voltage microcontroller)
AC (heater) 230 V, 50/60 Hz –
W 480 510 445 575
Unit dimensions (mm) H 1005 1005 1050 1050
D 110 150 150 195
CS Outdoor climate control

Minimum enclosure dimensions W 600 650 650 800


(mm) H 1200 1200 1300 1300
Specific thermal output 40 W/K 60 W/K 85 W/K 120 W/K
Heater 400 W –

DC (fan/
Rated current 2.0 A 3.2 A 6.4 A 7.9 A
microcontroller)
max.
AC (heater) 1.9 A –
Temperature range –33°C to +65°C
Air throughput of fans internal/
515 m3/h 530 m3/h 1020 m3/h
– unimpeded air flow external circuit fan
Temperature control Microcontroller1)
Sub-D connector
Type of connection Plug panel
13W32)
Weight 13 kg 15 kg 28 kg 32 kg
Protection category to EN 60 529/IEC 529 IP 55 (internal circuit to external circuit)
Material (enclosure) Aluminium
Surface finish Spray finished in RAL 7035
CE Declaration of Conformity    
UL/CUL    
Accessories
Cable connection kit 9765.110 9765.110 9765.115 – 180
1) Withtemperature-controlled activation of the components (internal/external circuit, heater).
Setpoints are preset. Modifications can only be made by arrangement.
2) Special connection cable included in the supply.

Delivery times available on request.


Heat exchangers for modular enclosures are manufactured to order. The units are assembled and supplied connected to the modular enclosure.
Adaptations to other enclosure platforms are available on request.

CS modular enclosures Cat. 32, page 874 Test adaptor Page 180 Heaters Page 169

162 Rittal System Climate Control


CS Outdoor climate control
Climate control units for Toptec CR
B2

T1

H2
H1
B1

B = Width
T = Depth

1 2

1 Heat exchanger/ 2 Heat exchanger/


cooling unit cooling unit,
With three mounting built into the Toptec CR.
positions for internal
mounting, partial internal
mounting or external
mounting plus a choice
between cooling via front or
rear door.

Heat exchangers Cooling units Page


Model No. CS 9776.100 9776.150 9776.500 9776.550
Internal mounting Universal Universal
DC 48 V –
Rated operating voltage
AC – 230 V, 50/60 Hz
B1 500 500 500 500
Unit dimensions (mm) H1 1000 1000 1000 1000
T1 150 200 150 260
Minimum enclosure dimensions (mm) W x H 800 x 1200 800 x 1200

CS Outdoor climate control


Specific thermal output 85 W/K 105 W/K – –
Useful cooling output L35 L35 1000 W/1180 W 1600 W/1750 W
– –
EN 814 L35 L50 650 W/700 W 1200 W/1250 W
Heater – – 400 W

Rated current DC 4.2 A 4.5 A – –


max. AC – 5.0 A/5.0 A 6.0 A/6.8 A
Start-up current max. – 24.0 A/22.0 A 34.0 A/32.0 A
L35 L35 640 W/760 W 960 W/1170 W
Power consumption –
L35 L50 780 W/920 W 1125 W/1310 W
Coolant – R134a
p. max. – 28 bar 28 bar
Temperature range –33°C to +65°C –33°C to +55°C
Air throughput of fans internal/external 600/625 m3/h 880/950 m3/h
530 m3/h 1130 m3/h
– unimpeded air flow circuit fan 600/625 m3/h 1000/1090 m3/h
Temperature control Microcontroller1) Microcontroller2)
Type of connection Plug panel Female multi-point connector 9-pole
Weight 22 kg 30 kg 35 kg 45 kg
Protection category to EN 60 529/IEC 529 IP 55 (internal circuit to external circuit)
Material (enclosure) Aluminium
Surface finish Spray finished in RAL 7035
CE Declaration of Conformity    
Accessories
Cable connection kit 9765.115 – – – 180
1) With temperature-controlled activation of the components (internal/external circuit, heater).
Setpoints are preset. Modifications can only be made by arrangement.
2) Settings may be amended directly on the unit display.

Toptec CR Cat. 32, page 877 Heaters Page 169

Rittal System Climate Control 163


Ex-proof climate control systems
Ex overpressure enclosure with integral enclosure cooling unit for zone II (gas)
Ex-proof climate control systems for zone II (gas) provide sion over long distances, from the camera systems to the
protection for high-tech monitoring systems in the oil and control room. To this end, amplifier units, known as concen-
gas extraction industry. trators, are needed, and are installed half-way between
These days, high-tech monitoring systems have become a the camera system and the control room. The technical
permanent feature in almost every sector. Whether in indus- challenge faced by climate control technology in these
trial zones or public areas, a sophisticated camera system applications is the potentially explosive zone II (gas) occur-
makes everything more transparent and manageable. In this ring in selected areas of the oil and gas extracting industry.
specialist field, it is necessary to ensure signal tranasmis-
Ex-proof climate control systems

The compressed air connection including The design challenge with this type of climate Further information available on
control unit integrated into the enclosure control technology is to arrange the external air request.
ensures a constant overpressure (2 mbar). circuit with all the components of the cooling
This produces an ex-free zone in the enclosure circuit in such a way that effective cooling out-
interior. put is provided, while at the same time meet-
ing the ex-proof requirements for zone II (gas).

164 Rittal System Climate Control


Ex-proof climate control systems
Ex overpressure enclosure with integral enclosure cooling unit for zone II (gas)
These concentrator units must be kept at a certain internal sive zone II. A compact cooling output of up to 4 kW is
temperature in order to ensure optimum performance ensured by a unit designed specifically for potentially
capabilities and transmissions from the camera systems. explosive areas.
Rittal has taken up the challenge and designed enclosure
and climate control components for use in potentially explo-

Ex-proof climate control systems

The sealed cover and intelligent Special fans designed for potentially explosive Control of the cooling unit with the popular
filter design in the extraction zone areas are used here. Comfort controller ensures an efficient supply
of the external circuit provides of useful cooling output. Visualisation of the
effective protection against exter- operating states and the current enclosure
nal ambient influences such as internal temperature are easily read via the
coarse dust or even sand. display positioned centrally in the enclosure.

Rittal System Climate Control 165


Enclosure heaters

Enclosure heaters from page 168


   Enclosure heaters . . . . . . . . . . . . . . . . . . . . . . . . . . 10 – 150 W. . . . . . . 169
   Enclosure heaters . . . . . . . . . . . . . . . . . . . . . . . . . 250 – 800 W. . . . . . . 169

Indoor with fan

Outdoor without fan

Enclosure heaters

Benefits at a glance Important Tips and tricks


● Useful cooling output from 10 to ● For the correct temperature and to avoid Applications see page 234
800 watts condensation, use a thermostat and/or
Assembly see page 234
● Self-regulating PTC technology hygrostat,
● Quick-assembly system see page 178 Electrical connection see page 234
● Heaters should always be installed in an
upright position. Leave a distance of
50 mm at the top and bottom to allow
convection
● The thermal output is increased with fans
● Heat is distributed evenly in large
enclosures by using several low-output
heaters

Rittal System Climate Control 167


Enclosure heaters
Enclosure heaters

Condensation poses a particular risk for control

electronics, especially with outdoor siting, but also

indoors. A range of output categories ensures that the

correct thermal output is always available. In this way,


Fast assembly Fully wired unit ready for
the total required thermal output can be distributed Achieved using snap fastening on connection
35 mm support rails to EN 50 022 or Clamp-type terminal connection
via screw fastening directly onto the for simple, effective wiring.
with complete accuracy within an enclosure. mounting plate.

168 Rittal System Climate Control


Enclosure heaters
Continuous thermal output 10 – 800 W

B = Width
T = Depth

Supply includes: ● In larger enclosures, even Approvals,


Ready-to-install unit with clamp- heat distribution is best see page 297.
type terminal connection achieved by installing several
Detailed drawing,
low-output heaters.
Note: see page 267.
● The installation of heaters is
● Thermostat SK 3110.000
generally advisable, even
(see accessories) is recom-
when using heat exchangers
mended for precise tempera-
and cooling units, in order to
ture control in the enclosure.
prevent condensation.
● In order to prevent condensa-
tion on assemblies, hygrostat
SK 3118.000 (see accesso-
ries) is recommended to
regulate heating.

Enclosure heaters without fan


Model No. SK 3105.110 3106.120 3115.130 3116.140 3107.150 3107.160 3102.170
W 81 81 102 102 102 140 140
Dimensions in mm H 123 164 155 225 260 205 250
D 49 49 60 60 81 60 81
Rated operating voltage V, Hz 110 – 240 V AC
Continuous thermal output at Tu = 10°C 10 W 20 W 30 W 50 W 75 W 100 W 150 W
Pre-fuse T 2A 4A
Accessories Packs of Page
Thermostat 1 3110.000 178
Hygrostat 1 3118.000 178

Enclosure heaters
Temperature indicator 1 3114.100 177
Special voltages available on request. We reserve the right to make technical modifications.

Enclosure heaters with fan


Model No. SK 110 V 3105.210 3105.220 3105.230
Model No. SK 230 V 3105.180 3105.190 3105.200
W 142 142 142
Dimensions in mm H 170 170 170
D 101 101 101
Rated operating voltage V, Hz 110 or 240 V AC
Continuous thermal output at Tu = 10°C 250 W1) 400 W1) 800 W1)
Pre-fuse gG for 110 V 4A 6A 10 A
Pre-fuse gG for 230 V 4A 6A 6A
Accessories Packs of Page
Thermostat 1 3110.000 178
Hygrostat 1 3118.000 178
Temperature indicator 1 3114.100 177
1) Outputwith fan.
Special voltages available on request. We reserve the right to make technical modifications.

Accessories Page 171 Configuration software Page 195

Rittal System Climate Control 169


System accessories

Features from page 172

Air routing from page 174


Air duct system ...............................................................................174 Stoppers ......................................................................................... 175
90° deflector ..................................................................................174 Air diverter ...................................................................................... 176
Shallow air duct system ..................................................................175 Door-operated switch ..................................................................... 176
Shallow duct extension ..................................................................175

Control/regulation from page 177


Digital enclosure internal temperature display and thermostat .....177 Mounting adaptor for speed control ............................................... 179
Enclosure internal thermostat .........................................................178 Interface card ................................................................................. 179
Hygrostat.........................................................................................178 SK BUS system ............................................................................... 180
Bottom-mounted adaptor................................................................178 Cable connection kit ....................................................................... 180
Speed control..................................................................................179 Test adaptor ................................................................................... 180

Mounting accessories from page 181


Roof plates TS.................................................................................181 Quick-change frame ....................................................................... 182
Roof plates DK-TS...........................................................................181 Adjustable frame............................................................................. 183
Vent attachment TS.........................................................................182 Adaptor frame ................................................................................. 183
Trim frame .......................................................................................182 Integrated louvres ........................................................................... 183

Cold Plate from page 184


System attachment .........................................................................184 Quick-action vent valve .................................................................. 184

System accessories
Fluid distributor ...............................................................................184 Elbow coupling ............................................................................... 185
Direct fluid connection ....................................................................184 Double-nipple coupling ................................................................. 185
Flexible hose ...................................................................................184 Temperature sensor TF25............................................................... 185

Liquid Cooling Package from page 186


Cooling module...............................................................................186 Accessories for rack sealing .......................................................... 187
Touchscreen display.......................................................................186 Vent valve ....................................................................................... 188
Front cover ......................................................................................186 Connection hose ............................................................................. 188
Vertical shielding ............................................................................186 Quick-release fastener ................................................................... 188
Horizontal shielding ........................................................................187 Add-on cover .................................................................................. 188
Covers.............................................................................................187

Filter technology from page 189


Filter mats for centrifugal fans ........................................................189 Louvred grille for lint screen ........................................................... 191
Filter mats for cooling units ............................................................189 Spare filter mats .............................................................................. 191
Metal filter........................................................................................190 Fine filter mats for fan-and-filter units ............................................. 191
Lint screen ......................................................................................191

General from page 192


Wide-range power pack 24 V (DC) for thermoelectric cooler ........192 Front outlet grille, 2 U, for centrifugal fans...................................... 193
Electric condensate evaporator......................................................192 Filter holder ..................................................................................... 194
Condensate collecting bottle ..........................................................192 Overflow valve ................................................................................ 194
Condensate hose............................................................................192 Flow regulator valve ........................................................................ 194
Outlet filters .....................................................................................193 Cooling medium for recooling systems .......................................... 194
Hose-proof hoods ...........................................................................193

Software service from page 195


Therm Software...............................................................................195 RiDiag II .......................................................................................... 195
EPLAN Cabinet ...............................................................................195

Rittal System Climate Control 171


System accessories
System accessories

Finding the perfect climate control solution is now even Be it targeted air routing or precise control of the

easier, with matching system accessories. Superbly equipment, Rittal has the perfect solution for

coordinated components tailor the climate control everything.

components perfectly to your specific requirements.

172 Rittal System Climate Control


Interface board
for TopTherm cooling systems with
Comfort controller
The interface card is an extension for
TopTherm cooling systems with Comfort
controller. In this way it is possible, e.g. to
monitor a master/slave combination of up
to 10 cooling systems. Control is via stand-
ardised interfaces: RS232 (DB9) or RS485,
one PLC interface (DB9). RS422 (RJ 45 jack)
is the connection to the Rittal CMC-TC. In
this way, remote monitoring via TCP-IP,
graphical interfaces for operation, evalua-
tion and control, documentation, and con-
nection to additional sensors for access
control and monitoring are possible.

OPC
Air duct system Roof plates
for TopTherm roof-mounted SNMP For fast mounting of:
cooling systems ● TopTherm roof-mounted cooling units
Cold air can be routed directly to ● TopTherm air/water heat exchangers
specific areas of the enclosure ● TopTherm roof-mounted fans
using the air duct system. The risk ● Vent attachment TS
of “short circuits” in the air circula- The cut-outs are pre-integrated into the roof
tion due to self-ventilated installed plate.
devices is therefore eliminated.
TCP/IP

PC

System accessories

Recooling

Benefits at a glance Important


● Complete system solutions Details of direct matching accessories and
● Simple assembly (where applicable) Model Numbers may be
● Fast ordering found in the relevant product ordering
table.

Rittal System Climate Control 173


System accessories
Air routing

Air duct system Accessories:


for TopTherm roof-mounted cooling units
and air/water heat exchangers Deflector 90°,
It is possible to route the cold air directly to see page 174.
specific areas of the enclosure using the air Stopper,
duct system. The risk of “short circuits” in the see page 175.
air circulation due to self-ventilated installed
devices is therefore eliminated.
The length of the shallow duct is 1500 mm, Also required:
and it may be cut to any required length. TS support strips for securing the shallow duct in
Material: a vertical direction,
Flame-resistant plastic to DIN 4102/B1 see Cat. 32, page 997.
Supply includes:
Shallow duct, compensating hose.
Model No. SK
For Packs of
Air duct system
SK 3209. . . ./SK 3210. . . ./SK 3273. . . ./SK 3359. . . ./SK 3382. . . ./
1 3286.870
SK 3383. . . ./SK 3384. . . ./SK 3385. . . .
SK 3386. . . ./SK 3387. . . . 1 3286.970

Note:
Do not direct cold air straight at active compo-
nents. When using the ducting system, the
performance of the cooling unit may be reduced,
depending on the application in question.
System accessories

Deflector, 90° Packs of Model No. SK


for air duct system 1 3286.990
For targeted air deflection at the end of the
shallow channel.
Material:
Flame-resistant plastic to DIN 4102/B1

174 Rittal System Climate Control


System accessories
Air routing

Shallow air duct system Accessories:


for TopTherm roof-mounted cooling units
and air/water heat exchangers, to fit TS 8 Deflector 90°,
enclosures from a width of 800 mm. see page 174.
It is possible to route the cold air directly to Stopper,
specific areas of the enclosure using the air see page 175.
duct system. The risk of “short circuits” in the
air circulation due to self-ventilated installed
devices is therefore eliminated. Also required:
The length of the shallow duct is 1500 mm, Shallow duct extension SK 3286.860 to compen-
and it may be cut to any required length. sate for the enclosure width and height.
Material: TS support strips for securing the shallow duct in
Flame-resistant plastic to DIN 4102/B1 a vertical direction,
see Cat. 32, page 997.
Supply includes:
Shallow duct, adaptor, compensating piece, Note:
deflector 90°. Do not direct cold air straight at active compo-
nents. When using the ducting system, the
performance of the cooling unit may be reduced,
depending on the application in question.

Model No. SK
For Packs of
Shallow air duct system
SK 3209. . . ./SK 3210. . . ./SK 3273. . . ./SK 3359. . . ./SK 3382. . . ./
1 3286.850
SK 3383. . . ./SK 3384. . . ./SK 3385. . . .

System accessories
Note:
Observe max. no. of
stoppers per unit.
Max. 2 x
Max. 1 x

SK 3359. . . . /SK 3382. . . . SK 3209. . . . /SK 3210. . . .


SK 3386. . . . /SK 3387. . . . SK 3383. . . . /SK 3384. . . .
SK 3385. . . .

Shallow duct extension Packs of Model No. SK


Extension kit for shallow air duct system 1 3286.860
SK 3286.850 for width, depth or height
length extensions in TS 8 enclosures.
Material:
Flame-resistant plastic to DIN 4102/B1
Supply includes:
1500 mm shallow duct, connection piece.

Stoppers Material:
Polyurethane foam
for TopTherm roof-mounted cooling units
To cover unneeded cold air outlets in TopTherm
roof-mounted cooling units.
Max. no. of
For Packs of Model No. SK
stoppers per unit
SK 3359. . . ./SK 3382. . . . 1 2 3286.780
SK 3209. . . ./SK 3210. . . ./SK 3273. . . ./SK 3383. . . ./
2 2 3286.880
SK 3384. . . ./SK 3385. . . .
SK 3386. . . ./SK 3387. . . . 1 2 3286.980

Rittal System Climate Control 175


System accessories
Air routing

Air diverter For Model No. SK


For use in climate controlled enclosures, climate SK 8607. . . ./SK 8687. . . .
3213.300
control doors, climate control side panels and SK 3306. . . ./SK 3331. . . .
TopTherm wall-mounted cooling units. SK 3304. . . ./SK 3305. . . . 3213.310
For targeted air routing of the cold air in a down- SK 3328. . . ./SK 3329. . . . 3213.320
ward direction. SK 3332. . . . 3213.3301)
Particularly well-suited for densely-packed elec-
trical components in the lower section of the
enclosure.
Material:
Sheet steel External air
circuit

Internal air
circuit

65 1)

1) 115 mm for SK 3213.330

Door-operated switch Packs of Model No. SZ


Without connection cable 1 4127.000
System accessories

For activation/deactivation of enclosure lights, for


deactivation of cooling units and air/water heat
exchangers whilst the door is open (to prevent
condensation) or for monitoring the door.
No drilling required for installation.
Supply includes:
Door-operated switch including mounting
accessories

176 Rittal System Climate Control


System accessories
Control/regulation

Digital enclosure internal Rated operating voltage Model No. SK


temperature display and 230 V (AC) 3114.100
115 V (AC) 3114.1151)
thermostat
24 V (DC) 3114.0241)
For installing on the enclosure door or wall and
1) Delivery
times available on request.
in a cooling unit or heat exchanger.
Special requirements available on request.
Technical specifications:
● Small dimensions.
● Depth: 100 mm.
● The 3-digit 7-segment display is 13 mm high
and clearly legible.
● Can be switched from °C/°F.
● The display can be used in a temperature
range from +5°C to +70°C.
● Includes 1500 mm long NTC sensor.
● Two relay outputs as change-over contact and
normally open contact (maximum contact load
230 V, 6 A).
● Freely selectable switching difference.
● The freely adjustable setpoint values can be
adjusted via the membrane keyboard at the
front.
Setting range: +5°C to +55°C.
● Display and switching accuracy +/– 2 K.
● Mounting cut-out 68 x 33 mm.
● The minimum and maximum recorded tempera-
tures are stored until it is next reset.

Digital enclosure internal Colour Model No. DK

temperature display and RAL 7035 7109.035

System accessories
thermostat
Integrated into a patch panel 1 U.
Including cable attachment for connection cable
and label holder.
Rated operating voltage:
230 V (AC)
Special voltages available on request.
Technical specifications:
● Small dimensions.
● Depth: 100 mm.
● The 3-digit 7-segment display is 13 mm high
and clearly legible.
● Can be switched from °C/°F.
● The display can be used in a temperature
range from +5°C to +70°C.
● Includes 1500 mm long NTC sensor.
● Two relay outputs as change-over contact and
normally open contact (maximum contact load
230 V, 6 A).
● Freely selectable switching difference.
● The freely adjustable setpoint values can be
adjusted via the membrane keyboard at the
front.
Setting range: +5°C to +55°C.
● Display and switching accuracy +/– 2 K.
● Mounting cut-out 68 x 33 mm.
● The minimum and maximum recorded tempera-
tures are stored until it is next reset.
Supply includes:
Patch panel, temperature display and thermostat,
identification strip.

Rittal System Climate Control 177


System accessories
Control/regulation

Enclosure internal thermostat Rated operating voltage Model No. SK


Especially suitable for controlling fan-and-filter 230/115/60/48/24 V (AC)
3110.000
units, heaters and heat exchangers, this thermo- 60/48/24 V (DC)
stat can also be used as a signal generator for
monitoring the enclosure internal temperature.
Technical specifications:
● Bi-metal sensor as a temperature-sensitive
element with thermal feedback.
● Contact population: Single-pole change-over
contact as a quick-break contact. ● A broad voltage spectrum i.e. just one model
● Permissible contact load: covers 24 to 230 V.
Cat. 5 – 3 (heating) ● Time-saving connection technique using a
AC 10 (4)1) A, terminal strip with a screw connection from the
DC = 30 W outside.
cat 5 – 4 (cooling) ● Flexible mounting on a vertical or horizontal
AC 5 (4)1) A, 35 mm support rail to EN 50 022, and snap
DC = 30 W fastening in the TS/ES enclosure section using
(1)) = inductive load at cos ϕ = 0.6 the supplied adaptor.
● Setting range: +5°C to +60°C
● Weight: approx. 105 g
● Dimensions: 71 x 71 x 33.5 mm
● Switching difference: approx. 1 K ± 0.8 K.

Hygrostat Rated operating voltage Model No. SK


The hygrostat switches on the heater and/or fan 24 – 230 V (AC/DC) 3118.000
when a preset relative humidity in the enclosure is
exceeded.
In this way, the relative humidity is raised above ● A broad voltage spectrum i.e. just one model
the dew point, and condensation on assemblies covers 24 to 230 V.
or electronic components is avoided. ● Time-saving connection technique using a
terminal strip with a screw connection from the
System accessories

Technical specifications: outside.


● Contact population: Single-pole change-over ● Flexible mounting on a vertical or horizontal
contact as a quick-break contact. 35 mm support rail to EN 50 022, and snap
● Permissible contact load: fastening in the TS/ES enclosure section using
AC ~ 5 (0.2)1) A the supplied adaptor.
DC = max. 20 W
(1)) = inductive load at cos ϕ = 0.6
● Setting range: 50 – 100 % relative humidity
● Weight: approx. 100 g
● Dimensions: 71 x 71 x 33.5 mm
● Switching difference: approx. 4 %

Bottom-mounted adaptor Packs of Model No. SK


for enclosure internal thermostat SK 3110.000 1 3110.200
and hygrostat SK 3118.000
Bottom-mounted adaptor with mounting option for
screwed cable glands, for targeted cable infeed
from appropriate equipment such as SK fan-and-
filter units and enclosure heaters. In conjunction
with screwed cable glands, it is also suitable for
use as strain relief.

178 Rittal System Climate Control


System accessories
Control/regulation

Speed control Rated operating voltage Model No. SK


Temperature-dependent speed control for Rittal 230 V (AC) 3120.000
fan-and-filter units and air/air heat exchangers 115 V (AC) 3120.1151)
with a rated operating voltage of 230 V AC, for 1) Delivery times available on request.
noise reduction and to save energy in part-load
operation.
Technical specifications:
● For mounting on a 35 mm support rail
DIN EN 50 022 Supply includes:
● Dimensions (W x H x D): Speed control, built into a PK enclosure 9512.100,
180 x 94 x 57 mm NTC sensor, length 1.80 m.
● Rated operating voltage:
230 V (AC)/115 V (AC)
● Setting range: +20°C to +55°C
● Phase cross-over with microcontroller
● Maximum fan output 250 W or 1.2 A
at 230 V (AC)
● Maximum fan output 100 W or 1.2 A
at 115 V (AC)

Mounting adaptor Packs of Model No. DK


for speed control 1 set 7526.964
The mounting adaptor enables direct attachment
of the speed control SK 3120.000/.115 to the
vertical frame sections of network enclosures. Supply includes:
Mounting adaptor including assembly parts.
Material:
Sheet steel, zinc-plated, passivated

System accessories
Interface card Packs of Model No. SK
for TopTherm cooling units with Comfort 1 3124.200
controller
The interface card is an extension for TopTherm
cooling units with Comfort controller. In this way it Supply includes:
is possible, e.g. to monitor a master/slave com- Interface card integrated into a plastic box
bination of up to 10 cooling units in conjunction W x H x D (mm): 136 x 44 (1 U) x 129.
with a Rittal CMC-TC. Control is achieved via Serial SUB-D cable 1.5 m.
standardised interfaces: RS-232 (DB9) or RS-485, Note:
one PLC interface (DB9). RS-422 (RJ 45 jack) is Networking and monitoring plan may be found on
the connection to the Rittal CMC-TC. Remote the relevant product page on the Internet, under
monitoring via TCP-IP, graphical interfaces for “Download”.
operation, evaluation and control, documentation
and connection of additional sensors for access
control is therefore possible. The extension card is
built into a 1 U plastic housing.
A voltage supply of 24 V DC is needed. This may
be supplied from the CMC-TC via a wide-range
power pack DK 7320.425 (100 to 240 V AC,
50/60 Hz) or externally via a Kycon connector.

Rittal System Climate Control 179


System accessories
Control/regulation

SK BUS system For Model No. SK


The SK bus system facilitates communications TopTherm 3124.100
between several enclosure cooling units, Rittal Climate controlled
3124.000
35C
TopTherm .500/.510/.540, production date 05/02 enclosures
or later, via a master/slave construction such as
25C
that required e.g. in complex bayed enclosure
20C
systems for optimum operating conditions. Supply includes:
30C 40C 3 m shielded interface cable, including operating
20C Technical specifications: manual on programming the cooling units.
The master/slave construction facilitates common
activation and deactivation via door limit switches, Note:
35C
parallel activation and deactivation via a tempera- nB = n K – 1
ture setpoint, and common collective fault signals nB: Number of order units (SK bus system)
and temperature logging, thereby eliminating the nK: Number of cooling units to be linked.
need for intricate wiring. Networking and monitoring plan may be found on
the relevant product page on the Internet, under
“Download”.

Property rights:
German patent no. 196 15 469

Cable connection kit Packs of Model No. CS


for CS Outdoor cooling units 1 set 9765.105
For simple connection of CS cooling units.
All cables preassembled with the corresponding
connectors.
Length of cables approx. 2500 mm.
Supply includes:
1 set = 3 cables for AC,
door-operated switch and
alarm connection.
Note:
System accessories

Not required for CS 9776.500 and CS 9776.550.

Cable connection kit Design Model No. CS


for CS Outdoor heat exchangers 3 cables for AC/DC and
9765.110
For simple connection of CS heat exchangers. alarm connection
All cables preassembled with the corresponding 2 cables for AC/DC and
9765.115
connectors. alarm connection
Length of cables approx. 2500 mm.
Note:
Not required for CS 9776.150.

Test adaptor Packs of Model No. CS


for CS Outdoor climate control equipment 1 set 9765.050
The 9-pole sub-D interface allows testing of
CS climate control equipment. Alternatively
supports automatic or manual test procedures.
Supply includes:
1 set = Test adaptor
including 2 m connection cable.
Note:
Not suitable for CS 9776.XXX.

180 Rittal System Climate Control


System accessories
Mounting accessories

Roof plates TS For enclosures To fit the Model No.


W x D mm mounting of TS
For mounting:
● TopTherm roof-mounted cooling units 600 x 600 SK 3359. . . . 8801.3001)
SK 3382. . . .
● TopTherm air/water heat exchangers SK 3149.4 . .
800 x 600 8801.320
● TopTherm roof-mounted fans SK 3149.8 . .
● Vent attachment TS
600 x 600 SK 3273.5. . 8801.3101)
The cut-outs in the roof plate are arranged in such SK 3383. . . .
a way that the TopTherm roof-mounted cooling 800 x 600 8801.330
SK 3384. . . .
units are positioned centrally on the enclosure. 1200 x 600 SK 3385. . . . 8801.350
SK 3209. . . .
Material: 800 x 800 SK 3210. . . . 8801.920
Sheet steel TS 8801.380
Supply includes: 800 x 600 SK 3386. . . . 8801.3402)
= SK 3387. . . .
T3 Assembly parts. 1200 x 600 8801.360
13

B2 T2 1) When mounting the cooling units, there may be a


Colour:
B1 collision with the eyebolts of the enclosure; for this
= RAL 7035 reason, roof fastening screws are supplied loose with
T1
the roof plates.
2) Attachment is from the inside using metal brackets and

B = Width retaining clamps.


T = Depth

B1 B2 T1 T2 T3
For mounting Model No. TS
mm mm mm mm mm
SK 3382. . . ./SK 3359. . . . 567.5 475 567.5 260 129.3 8801.300
SK 3149.4 . ./SK 3149.8 . . 767.5 475 567.5 260 129.3 8801.320
567.5 490 567.5 390 61.3 8801.310
SK 3209. . . ./SK 3383. . . ./SK 3210. . . ./ 767.5 490 567.5 390 61.3 8801.330
SK 3384. . . ./SK 3273. . . ./SK 3385. . . .
TS 8801.380 1167.5 490 567.5 390 61.3 8801.350
767.5 490 767.5 390 161.3 8801.920
767.5 692 567.5 392 57.8 8801.340
SK 3386. . . ./SK 3387. . . .
1167.5 692 567.5 392 57.8 8801.360

System accessories
Roof plates DK-TS For enclosures
To fit the Model No.
WxD
For mounting: mounting of TS
mm
● TopTherm roof-mounted cooling units
600 x 900 SK 3209. . . . 8801.410
● TopTherm air/water heat exchangers SK 3210. . . .
● TopTherm roof-mounted fans 600 x 1000 SK 3273.5 . . 8801.420
● Vent attachment TS SK 3383. . . .
800 x 900 8801.430
The cut-outs in the roof plate are arranged in such SK 3384. . . .
a way that the TopTherm roof-mounted cooling SK 3385. . . .
800 x 1000 8801.440
units are positioned centrally on the enclosure. TS 8801.380

Material:
Sheet steel
Colour:
=
T3
RAL 7035
13

B2 T2
B1 B1 B2 T1 T2 T3
= For mounting Model No. TS
T1 mm mm mm mm mm
SK 3209. . . . 567.5 490 867.5 390 211.3 8801.410
SK 3210. . . .
B = Width SK 3273.5 . . 767.5 490 967.5 390 261.3 8801.420
T = Depth SK 3383. . . . 567.5 490 867.5 390 211.3 8801.430
SK 3384. . . .
SK 3385. . . .
767.5 490 967.5 390 261.3 8801.440
TS 8801.380

Rittal System Climate Control 181


System accessories
Mounting accessories

Vent attachment TS For roof plates


Model No. TS
with cut-out
For passive ventilation with labyrinthine air flow
routing, to match the roofs for TopTherm roof- 490 x 390 mm 8801.380
mounted cooling units.
Colour:
RAL 7035
Protection category:
IP 43
Supply includes:
Assembly parts.
37.5

59 5
5 49

Trim frame For cooling unit Model No. SK


for slimline cooling units SK 3366. . . .
3377.000
Slimline cooling units can be internally or exter- SK 3377. . . .
nally mounted on an enclosure door or wall. The
trim frame presents a closed front for the cooling
unit.
Material:
Sheet steel
Colour:
140

RAL 7035
System accessories

Quick-change frame For Model No.


TopTherm cooling unit SK
for TopTherm roof-mounted cooling units
The quick-change frame is more than just an alter- SK 3359. . . ./SK 3382. . . . 3286.700
nate frame. Together with the seal, the lower part SK 3209. . . ./SK 3210. . . .
of the frame is screw-fastened to the enclosure, SK 3383. . . .
3286.800
making it possible to attach or remove the plug-in SK 3384. . . .
SK 3385. . . .
cooling unit to/from the top part of the quick-
change frame. In case of servicing, this means SK 3386. . . .
3286.900
SK 3387. . . .
minimal assembly times and hence minimal down-
time. What is more, the quick-change frame offers
effective protection against the ingress of oil into Property rights:
the enclosure in oily atmospheres, thanks to its German patent no. 41 10 323
integral drainage trough. French patent no. 2 675 317
Material: UK patent no. 2 254 735
Sheet steel
Colour:
RAL 7035
Supply includes:
Quick-change frame, seal,
quick-release fasteners.

182 Rittal System Climate Control


System accessories
Mounting accessories

Adjustable frame For heat exchangers Model No. SK


for air/air heat exchangers, SK 3126.4. . 3286.260
railway-compatible version SK 3128.4. ./SK 3129.4. . 3286.270
The adjustable frame allows variable partial instal- SK 3130.4. . 3286.280
lation of air/air heat exchangers on enclosures, to
facilitate optimum space utilisation.
Material:
Sheet steel
Colour:
RAL 7035

Adaptor frame For cooling units


Cat. 32, Packs Model No.
300 W
for wall-mounted cooling units page of TP
Model No. SK
To compensate for the rear tilt of the TP consoles. 3302.3X0 642 1 6730.600
Material: Delivery times available on request.
Sheet steel
Surface finish:
Powder coated in textured RAL 7035
Supply includes:
Assembly parts.

167 Mounting cut-out


1
481
77.5 200 200 77.5

System accessories
84
277

20
3

329
201

2
84

245
Ø7

1 Top edge of console


2 Adaptor frame
3 Cooling units SK 3302.3X0

Integrated louvres W (B) H D (T) Packs


Model No. SK
mm mm mm of
For ventilation by convection; easily retro-fitted
using 4 screws. 160 110 8 4 2541.235
210 100 8 4 2542.235
Material:
Sheet steel 330 110 8 4 2543.235
To order in textured RAL 7032 please add extension .200
Colour: to the Model No., and for a primed version please add
RAL 7035 extension .300. Delivery times available on request.

Detailed drawing,
see page 268.
T
H

Rittal System Climate Control 183


System accessories
Cold Plate

System attachment For the attachment of frequency Packs Model No.


converters of DCP
for frequency converters
For mounting frequency converters on the Cold with all-round clamping surface 1 8616.700
Plate. with side clamping surfaces 1 8616.710
Supply includes: with clamping surfaces top and
1 8616.720
bottom
Wire clamp system, T-slot blocks.

Fluid distribution manifold Packs of Model No. DCP


in stainless steel 1 set 8616.750
For the connection of up to 4 Cold Plate units.
Supply includes:
2 fluid distributors (inlet and return), Accessories:
screw plugs G1/4˝, G3/8˝,
connector sleeves G1/2˝, Flex hose, see page 184,
seals. quick-action vent valve, see page 184,
temperature sensor, see page 185.

Direct fluid connection Packs of Model No. DCP


For connection of the Cold Plate through the rear 1 set 8616.751
or side panel of the enclosure.
Supply includes:
2 connector sleeves G1/2˝, Accessories:
2 Mini stop valves G1/2˝,
2 reducers G1/2˝ – G1/4˝, Flex hose, see page 184,
System accessories

seals. double-nipple coupling, see page 185.

Flexible hose Packs of


Length
Model No. DCP
mm
For connection of the Cold Plate to a fluid distribu-
tion manifold or direct fluid connection. 1 set 500 8616.760
1 set 1000 8616.761
Supply includes:
2 flexible hoses G1/4˝ with stainless steel braid,
seals.
Accessories:
Elbow coupling, see page 185

Quick-action vent valve Packs of Model No. DCP


To vent the complete Direct Cooling Package 1 8616.762
system.
Easily mounted on the fluid distributor.
Supply includes:
Quick-action vent valve G3/8˝,
seal.

184 Rittal System Climate Control


System accessories
Cold Plate

Elbow coupling Packs of Model No. DCP


For horizontal or vertical connection of the Cold 1 set 8616.763
Plate.
Supply includes:
4 L-shaped 90° fittings G1/4˝,
seals.

Double-nipple coupling Packs of Model No. DCP


For connection of the flexible hose to the fluid 1 set 8616.764
distribution manifold.
Supply includes:
4 double-nipple fittings G1/4˝,
seals.

System accessories
Temperature sensor TF25 Packs of Model No. DCP
For monitoring the inlet and return temperatures 1 8616.765
in the fluid distributor.
Supply includes: Other versions available on request.
Temperature sensor TF25 (NTC, 10 kΩ),
stainless steel cable gland G1/4˝,
seal.

Rittal System Climate Control 185


System accessories
Liquid Cooling Package

Cooling module For LCP Cooling output Model No. SK


for LCP Standard and Smart Standard 6.6 kW 3301.250
With the cooling module, the useful cooling output Smart 7.0 kW 3301.290
may be gradually increased. There is 1 module
fitted as standard.

Touchscreen display Packs of Model No. SK


for LCP Smart 1 3301.790
The display offers the opportunity of directly
monitoring key functions of the LCP Smart,
and implementing settings.

Front cover Packs of Model No. SK


System accessories

The optional front cover, together with the built-in 1 3301.980


filter fleece, ensures even air outlet at the sides as
well, and reduces the air outlet speed, thus mini-
mising draught effects.

Vertical shielding For sealing


For
enclosure width Model No. SK
To block the airflow on the left and right of the between
mm
482.6 mm (19˝) level, for enclosure height
Side panel and 600 3301.380
2000 mm. 482.6 mm (19˝)
level 800 3301.390
Material:
Cellular PU foam, LCP and 600 3301.370
flame-inhibiting to UL 94 (HF1) 482.6 mm (19˝)
level 800 3301.320
Length: 1900 mm, self-adhesive on one side.
Packs of 1

186 Rittal System Climate Control


System accessories
Liquid Cooling Package

Horizontal shielding For


enclosure width Packs of Model No. SK
Allows horizontal shielding of the airflow with a mm
partially configured 482.6 mm (19˝) rack.
600 1 3301.330
Material: 800 1 3301.340
Sheet steel, spray finished in RAL 7035

Covers Packs of Model No. SK


for LCP Standard 2 3301.310
For sealing any air inlet and outlet openings that
are not required.
Material:
Sheet steel, spray finished in RAL 7035

System accessories
Accessories for rack sealing
for LCP Standard and LCP Plus
To prevent the ingress of ambient air.

Description Dimensions mm Packs of Model No. Cat. 32, page


Side panel, screw fastened HxD 2000 x 1000 2 8100.235 917
600 x 2000 1 8610.600 934
Glazed door WxH
800 x 2000 1 8610.800 934
600 x 2000 1 7824.205 936
Sheet steel door, solid WxH
800 x 2000 1 7824.207 936
600 x 1000 1 7826.6051) 972
Divided roof plate for cable entry WxD
800 x 1000 1 7826.8051) 972
1) Retrospective installation is not possible.

Rittal System Climate Control 187


System accessories
Liquid Cooling Package

Vent valve Packs of Model No. SK


For effective cooling of individual LCP modules 1 3301.400
(SK 3301.250). With quick-release system for
simple installation in the water inlet of the LCP,
including stop valve.

Connection hose For LCP Thread Model No. SK


SK 3301.230/.420 3/
1 m long, flexible connection hose, may be 4˝ 3301.350
shortened, including union nuts on both sides SK 3301.480 1˝ 3301.351
for connecting the LCP to existing pipework. Packs of 2
System accessories

Quick-release fastener Packs of Model No. SK


The shut-off quick-release fasteners on both sides 1 connector
3301.360
facilitate easy connection and disconnection of 1 coupling
the LCP to the existing pipe work (3/4˝ external
thread) and connection hose SK 3301.350.

Add-on cover For LCP Model No. SK


For height compensation with 2200 mm high SK 3301.210
3301.221
racks in conjunction with the LCP (H = 2000 mm). SK 3301.230
SK 3301.420
Material: 3301.421
SK 3301.480
Sheet steel, spray finished in RAL 7035
Delivery times available on request.

188 Rittal System Climate Control


System accessories
Filter technology

Filter mats for tangential fans Material:


Chemical fibre
Made of chopped-fibre mat with a progressive
structure. Temperature-resistant to 100°C, self-
extinguishing category F1 to DIN 53 438.
Dust-laden air side: Open structure.
Clean air side: Closed structure.
Reliable filtering of virtually all types of dust from a
particle size of 10 μm.
For tangential fans/front outlet grilles 2 U W x H x D mm Packs of Model No. SK
SK 3144.000/SK 3145.000/SK 3176.000 425 x 85 x 8 5 3177.000

Filter mats for cooling units Material:


Open-celled polyurethane foamed plastic with
Rittal cooling units are low-maintenance and are excellent physical and mechanical properties.
supplied without filter mats. Filter mats may be Temperature-resistant from –40°C to +80°C.
used for extreme conditions. Thickness: 10 mm.
For TopTherm cooling units W x H x D mm Packs of Model No. SK
SK 3302.300/SK 3302.310 190 x 95 x 10 3 3286.110
SK 3302. . . ./SK 3303. . . ./SK 3361. . . . 265 x 200 x 10 3 3286.300
SK 3304. . . ./SK 3305. . . ./SK 3328. . . ./SK 3329. . . ./
344 x 268 x 10 3 3286.400
SK 3332. . . ./SK 3366. . . .
SK 3273. . . ./SK 3382. . . ./SK 3383. . . ./SK 3384. . . ./
530 x 255 x 10 3 3286.500
SK 3385. . . ./SK 3359. . . .
SK 3386. . . ./SK 3387. . . . 720 x 300 x 10 3 3286.600
SK 3377. . . . 205 x 210 x 10 3 3253.010

System accessories
For discontinued cooling units W x H x D mm Packs of Model No. SK
SK 3296. . . ./SK 3272.100/SK 3290. . . ./SK 3280.100/
539 x 332 x 10 3 3286.100
SK 3299. . . ./SK 3261. . . .
SK 3265.100/SK 3266.100 270 x 332 x 10 3 3267.100
SK 3256. . . . 395 x 300 x 10 3 3254.000
SK 3293. . . ./SK 3281.100/SK 3298. . . ./SK 3279.100/
SK 3260. . . ./SK 3269. . . ./SK 3262.100/SK 3393. . . ./ 334 x 313 x 10 3 3294.100
SK 3381.100/SK 3391. . . .
SK 3255. . . ./SK 3395. . . . 350 x 245 x 10 3 3253.000
SK 3394. . . . 315 x 200 x 10 3 3285.000
SK 3292.134/SK 3278.134 325 x 250 x 10 3 3286.000

Rittal System Climate Control 189


System accessories
Filter technology

Metal filter Material:


Aluminium
Particularly when cooling units are used in dusty Thickness: 10 mm
and damp environments, it is advisable to use
washable metal filters.
If air or steam condenses on the metal surfaces,
any particles that may be present will adhere to
the metal and are easily washed out with water or
grease-dissolving detergents.
For TopTherm cooling units W x H x D mm Packs of Model No. SK
SK 3302.300/SK 3302.310 190 x 95 x 10 1 3286.120
SK 3302.100/SK 3302.110/SK 3303. . . ./SK 3361. . . . 265 x 200 x 10 1 3286.310
SK 3304. . . ./SK 3305. . . ./SK 3328. . . ./SK 3329. . . ./
344 x 288 x 10 1 3286.410
SK 3332. . . ./SK 3366. . . .
SK 3273. . . ./SK 3382. . . ./SK 3383. . . ./SK 3384. . . ./
530 x 255 x 10 1 3286.510
SK 3385. . . ./SK 3359. . . .
SK 3386. . . ./SK 3387. . . . 720 x 300 x 10 1 3286.610
SK 3377. . . . 225 x 200 x 10 1 3253.220

For discontinued cooling units W x H x D mm Packs of Model No. SK


SK 3296. . . ./SK 3272.100/SK 3290. . . ./SK 3280.100 520 x 290 x 10 1 3286.210
SK 3299. . . ./SK 3261. . . . 520 x 315 x 10 1 3286.200
SK 3265.100/SK 3266.100 265 x 320 x 10 1 3267.200
SK 3256. . . . 315 x 365 x 10 1 3254.200
SK 3293. . . ./SK 3281.100/SK 3298. . . ./SK 3279.100/
SK 3260. . . ./SK 3269. . . ./SK 3262.100/SK 3393. . . ./ 300 x 328 x 10 1 3294.200
SK 3381.100/SK 3391. . . .
SK 3255. . . ./SK 3395. . . . 348 x 210 x 10 1 3253.200
SK 3394. . . . 375 x 415 x 10 1 3285.200

For TopTherm climate control door/section door W x H x D mm Packs of Model No. SK


SK 3300.040/SK 3300.050/SK 3300.060/SK 3300.070/
425 x 78 x 10 1 3284.210
SK 3300.080/SK 3300.090/SK 3300.110/SK 3300.120

For discontinued climate control doors W x H x D mm Packs of Model No. SK


SK 3306. . . ./SK 3307. . . ./SK 3309. . . ./SK 3310. . . . 424 x 100 x 10 1 3284.200
System accessories

SK 3308. . . . 624 x 100 x 10 1 3288.200

For discontinued climate control side panel W x H x D mm Packs of Model No. SK


SK 3331. . . . 380 x 150 x 10 1 3289.200

For heat exchangers W x H x D mm Packs of Model No. SK


SK 3126.4XX 130 x 130 x 10 1 3286.230
SK 3128.4XX/SK 3129.4XX 208 x 208 x 10 1 3286.240
SK 3130.4XX 225 x 225 x 10 1 3286.250

For Mini recooling systems W x H x D mm Packs of Model No. SK


SK 3318.600/SK 3318.610/SK 3319.600/SK 3319.610 530 x 255 x 10 1 3286.510
SK 3320.600/SK 3334.600 500 x 558 x 8 1 3286.520
SK 3360. . . . 344 x 268 x 10 1 3286.410

190 Rittal System Climate Control


System accessories
Filter technology

Lint screen For


Packs
Model No. SK
of
Especially for the use of cooling units and air/air
heat exchangers where there is a high proportion SK 3304. . . ./SK 3305. . . ./
SK 3328. . . ./SK 3329. . . ./
of lint in the ambient air. SK 3332. . . ./SK 3360. . . ./
1 3329.904
Material: SK 3126. . . ./SK 3127. . . ./
Stainless steel mesh SK 3128. . . ./SK 3129. . . ./
SK 3130. . . .
Delivery times available on request.

Louvred grille For


Packs
Model No. SK
of
for lint screen SK 3329.904 1 3329.903
Material: Delivery times available on request.
ABS

Spare filter mats Material:


Chemical fibre
Made of chopped-fibre mat with a progressive
structure.
Temperature-resistant to 100°C, self-extinguish-
ing category F1 to DIN 53 438.
Dust-laden air side: Open structure.
Clean air side: Closed structure.
Reliable filtering of virtually all types of dust from a
particle size of 10 μm.
For thermoelectric coolers W x H x D mm Packs of Model No. SK
SK 3201.200/SK 3201.300 106 x 90 x 8 5 3201.050

System accessories
For fan-and-filter units/outlet filters W x H x D mm Packs of Model No. SK
SK 3321. . . . 89 x 89 x 10 5 3321.700
SK 3322. . . . 120 x 120 x 12 5 3322.700
SK 3323. . . . 173 x 173 x 17 5 3171.100
SK 3324. . . ./SK 3325. . . . 221 x 221 x 17 5 3172.100
SK 3326. . . . 289 x 289 x 17 5 3173.100
SK 3327. . . . 286 x 286 x 10 5 3327.700

For filter holders W x H x D mm Packs of Model No. SK


SK 3175.000 338 x 242 x 20 3 3174.000

Fine filter mats Material:


Chemical fibre
for fan-and-filter units
Made of chopped-fibre mat with a progressive
structure. Temperature-resistant to 100°C, self-
extinguishing category F1 to DIN 53 438.
Dust-laden air side: Open structure.
Clean air side: Closed structure.
Reliable filtering of virtually all types of dust from a
particle size of 10 μm.

For fan-and-filter units/outlet filters W x H x D mm Packs of Model No. SK


SK 3323. . . . 173 x 173 x 12 5 3181.100
SK 3324. . . ./SK 3325. . . . 221 x 221 x 12 5 3182.100
SK 3326. . . ./SK 3327. . . . 289 x 289 x 12 5 3183.100

Rittal System Climate Control 191


System accessories
General

Wide-range power pack Power pack 24 V (DC)


Model No. SK
for SK 3201.300
24 V (DC) 150 W for snap-mounting
for thermoelectric cooler 3201.030
onto top-hat rail 35 mm
To supply voltage to the thermoelectric cooler with
primary 96 – 264 V (AC) voltage supply input.
Power packs for other outputs available on
request.

Electric condensate evaporator Model No. SK


For external mounting on enclosures. Rated operating for for
voltage SK 3302/ 400 mm wide
For use with all enclosure cooling units and
SK 3303 cooling units
air/water heat exchangers.
Evaporation performance: 230 V, 50/60 Hz 3301.5601) 3301.5702)
1) 2.4 l/d 115 V, 50/60 Hz 3301.5801) 3301.5902)
2) 4.2 l/d

Colour: Detailed drawing,


RAL 7035 see page 268.
Supply includes:
Electric condensate evaporator,
ready to connect.

1 Condensate collecting bottle Packs of Model No. SK


System accessories

2 For mounting on the enclosure. 1 3301.600


For use with all enclosure cooling units and
3 air/water heat exchangers.
Safety overflow at the side. Supply includes:
Condensate collecting bottle, bottle holder
239

Capacity approximately 0.75 l.


including assembly parts.
1 Condensate discharge tube
66

2 Membrane grommet
Ø 73
3 Max. 70 mm

Condensate hose Material


Model No.
For devices thickness
For removing and forwarding condensate. SK
Ø
For connecting to enclosure cooling units.
SK 3302. . . ./SK 3201. . . . 8 x 1.5 mm 3301.608
Material: SK 3303. . . ./SK 3361. . . . 10 x 1.5 mm 3301.610
PVC, transparent
SK 3273. . . ./SK 3304. . . ./
Supply includes: SK 3305. . . ./SK 3328. . . ./
10 m hose. SK 3329. . . ./SK 3332. . . ./
SK 3359. . . ./SK 3366. . . ./
12 x 2 mm 3301.612
SK 3377. . . ./SK 3382. . . ./
SK 3383. . . ./SK 3384. . . ./
SK 3385. . . ./SK 3386. . . ./
SK 3387. . . .

192 Rittal System Climate Control


System accessories
General

Outlet filters Dimensions


Model No. SK
in mm
For ventilation by convection, an outlet filter can
be installed in the upper and lower sections of the 116.5 x 22 3321.207
enclosure. 148.5 x 24.5 3322.207
Material: 204 x 30 3323.207
ABS, 255 x 30 3325.207
material resistance to UL 94-V0. 323 x 30 3326.207
Colour: For RAL 7032, use order extension .200.
RAL 7035
Supply includes: Note:
Outlet filter including filter mat. EMC version,
see page 48.

Accessories:
Spare filter mats,
see page 191.
Fine filter mats,
see page 191.

Hose-proof hoods For


Dimensions Model No.
in mm SK
for fan-and-filter units/outlet filters
When the hose-proof hood is mounted above the SK 3321. . . . 150 x 260 x 40 3321.8001)
fan-and-filter unit and outlet filter in conjunction SK 3322. . . . 176 x 270 x 55 3322.800
with a fine filter mat, a protection category of IP 56 SK 3323. . . . 233 x 410 x 55 3323.800
to EN 60 529 is achieved. SK 3324. . . .
282 x 500 x 85 3324.800
Material: SK 3325. . . .

System accessories
Stainless steel SK 3326. . . .
350 x 560 x 110 3326.800
SK 3327. . . .
Protection category: 1) Delivery times available on request.
In conjunction with the fan-and-filter units/outlet
filters, NEMA 3R + 12 is met.

Front outlet grille 2 U Packs of Model No. SK


for tangential fans 1 3176.000
This front outlet grille is required if a 482.6 mm
(19˝) cross-flow blower (SK 3144.000/
SK 3145.000) is used in the lower section of
the electronic enclosure and the hot air is to Accessories:
be expelled to the outside from the upper Filter mat,
section of the enclosure. see page 189.
The design of the grille matches that of the
intake grille in the cross-flow blower.
These grilles can also be used as simple inflow
and outflow grilles with natural convection.

Rittal System Climate Control 193


System accessories
General

Filter holder W x H x D mm Model No. SK


for roof ventilation 340 x 244 x 15 3175.000
The use of a filter mat is required in order to
increase the protection category of the roof
vent (SK 3148.007).
Protection category IP 44 to EN 60 529 is Accessories:
achieved. Spare filter mat,
Material: see page 191.
Sheet steel
Supply includes:
Filter holder including filter mat.

Overflow valve Version Packs of Model No. SK


1/ ˝ bypass valve 1 3301.900
Pressostat for use in the water cycle between 2
the recooling system and the air/water heat 3/ ˝
4 bypass valve 1 3301.910
exchanger. It prevents an increase in pump pres- 1˝ bypass valve 1 3301.920
sure in the recooling system against the closed
magnetic valve of the air/water heat exchanger
outside of the cooling cycle.
Material:
Brass
Setting range:
2 – 12 bar
Presetting:
3 bar
System accessories

Flow regulator valve Version Packs of Model No. SK


3/
x 1/2˝
For use with air/water heat exchangers, espe- 4˝
1 3301.930
cially if more than one heat exchanger (n > 1) is for volumetric flow control
3/ 3/
used in the water cooling circuit. The correctly set 4˝ x 4˝
1 3301.940
valve then ensures the same quantity of cooling for volumetric flow control
medium for all equipment. The valve is used for
hydraulic balancing.
Material:
Brass
Setting range:
3 – 12 l/min

Cooling medium Rifrost


Antifreeze/
Container Model No. SK
water mixture
for recooling systems 10 l 3301.950
Ready mix
Outdoor 1:2 25 l 3301.955
Apart from the recooling systems for oil and emul-
sion, all other recooling systems are only suitable 200 l 3301.9571)
for the cooling of water or a water/glycol mixture. 10 l 3301.960
As well as protecting against frost, this cooling Standard 1:4 25 l 3301.965
medium also serves to inhibit bacterial growth and 200 l 3301.9671)
provide optimum corrosion protection. 1) Delivery times available on request.
Supply includes:
10 l canister, 25 l canister or 200 l barrel.

194 Rittal System Climate Control


System accessories
Software service

Therm Software Supply includes


Rittal Therm is a calculation program CD-ROM
for enclosure climate control. Languages: Available in 13 languages
All electrical and electronic components have a Model No. SK 3121.000
certain power loss which is dissipated to the envi-
ronment in the form of heat. Because an increas-
ing number of components are now being housed
in ever smaller spaces, the heat produced can
soon reach levels which are harmful to electronic Note:
components and may severely curtail their useful Your free 30-day trial version may
lives. be downloaded at www.rittal.com
The Therm software package takes care of the
complex calculation of climate control require-
ments. A user-friendly interface guides the opera-
tor to the most suitable, correctly dimensioned
climate control component.
All evaluations are closely based on the require-
ments of IEC/TR 60 890 AMD 1/02.95 and
DIN 3168 for enclosure cooling units.

EPLAN Cabinet Automatic generation of bills of materials and


order lists are, of course, included, as are high-
Boost your productivity at every stage, from quality, dimensioned drawings for plant documen-
electrical planning, to enclosure population, tation.
through to production
Supplementary modules such as routing or NC
The electrical planning and mechanical installa- generate drilling plans and programs, optimised
tion of an enclosure are combined into an inte- wiring paths and lists, as well as information for
grated workflow with EPLAN Cabinet. drilling and milling machines. The simple plan-
Equipment and component data is transferred ning and detailed documentation of EPLAN
from the wiring schematic in EPLAN Electric P8 Cabinet support an optimum workflow, from
or earlier versions of EPLAN into the layout plan. the wiring schematic through to the populated

System accessories
Rittal enclosures are integrated as original 3D enclosure.
models via component libraries (Rittal RiCAD-3D). EPLAN Cabinet is available from:
Cable trunking, support rails, terminals and www.eplan.com
devices may be positioned in the 3D representa-
tion of the enclosure at a click of the mouse. Colli-
sion controls ensure compliance with distances
and blocked surfaces, and help to avoid design
errors.

RiDiag II Supply includes


RiDiag II is a tool for diagnosing the operating CD-ROM
behaviour of Comfort controller-regulated cooling Language: German/English/Italian/French
units. By connecting a PC, it is possible to retrieve Connection cable
error messages, temperatures and capacity utili-
Model No. SK 3159.100
sation levels of the cooling units which are stored
in the Comfort controller. The system includes
integrated temperature measurement from four
sensors in the cooling unit, and also features
graphical representation of the temperature
development over time.

Rittal System Climate Control 195


196
Tips and tricks

Cooling with ambient air from page 198


Fan-and-filter units Air/air heat exchangers
Applications/selection criteria ........................................................198 Applications .................................................................................... 202
Assembly ........................................................................................200 Selection criteria ............................................................................. 203
Rack-mounted fans/tangential fans – Applications .......................201 Assembly ........................................................................................ 204
Air routing ....................................................................................... 205
Electrical connection and control .................................................. 206

Cooling units from page 207


Applications ....................................................................................207 Condensation management ........................................................... 213
Selection criteria .............................................................................208 Electrical connection and control .................................................. 215
Assembly ........................................................................................209 Thermoelectric cooler – Mounting options ..................................... 216
Air routing........................................................................................210

Liquid cooling IE from page 217


Air/water heat exchangers Recooling systems/chillers
Applications ....................................................................................217 Applications .................................................................................... 226
Selection criteria .............................................................................218 Selection criteria ............................................................................ 227
Assembly ........................................................................................219 Assembly ........................................................................................ 228
Air routing........................................................................................220 Notes............................................................................................... 229
Condensation management............................................................222
Electrical connection and control ..................................................224

Liquid cooling IT from page 230


Aisle containment Liquid Cooling Package
Benefits ...........................................................................................230 Plus, Smart, Extend......................................................................... 233
Usage..............................................................................................231

Tips and tricks


Application examples ....................................................................232

Enclosure heaters from page 234


Applications/assembly/electrical connection ................................234

Monitoring from page 235


Master/slave mode..........................................................................235 CMC-TC enclosure monitoring system ........................................... 237
Interface card..................................................................................235

Rittal System Climate Control 197


Cooling with ambient air
Fan-and-filter units – Applications/selection critiera
Fan-and-filter units utilise the ambient air for direct Ambient conditions
cooling of the enclosure interior.

This requires cool, reasonably clean ambient air.

Cool

Application diversity and design


In most cases, it makes sense to install
the axial fan with the air directed from
outside into the enclosure so that over-
pressure is created inside the enclos-
ure, as per the delivered state. This helps
to avoid the ingress of unfiltered ambient
air.
Advantage: Aesthetics and function
The extremely low build height is typical
of the Rittal fan-and-filter unit design.
The super-slimline vent grille guarantees
optimum air throughput with low noise
generation. Fan-and-filter units are ideal for dissipating heat loads cost-
effectively. The prerequisite is that the ambient air must
be relatively clean with a temperature below the desired
enclosure internal temperature. A temperature difference
of 10 K is ideal.
Cooling with ambient air

Air direction
Direction of airflow “blowing into the 0° 3
18
enclosure”. Standard arrangement of
fan and outlet filter. In this case, a mini- 2
mal overpressure is generated inside
2
the enclosure. The incoming air is
routed completely via the filter mat.

Direction of airflow “extracting from


the enclosure”. Configuration after
changing the airflow direction of the 1
fan-and-filter motor. In such cases,
unfiltered “bad air” may be drawn in
via leaks in the enclosure.
1
2

1 Fan-and-filter
unit 1 Dismantling
2 Outlet filter 2 Direction of airflow in the supplied state/standard
3 Direction of airflow after rotating the fan motor

198 Rittal System Climate Control


Cooling with ambient air
Fan-and-filter units – Applications/selection critiera

Practical example of a fan-and-filter unit


Fan-and-filter units are used in virtually all segments of indus- 5
try: from the smallest enclosures, to command panels and 5
consoles, through to large and bayed enclosure systems.
They are the easiest method of protecting against overheat-
ing and hot-spots.
The basic prerequisite for their use is that the ambient tem-
perature must be significantly lower than the enclosure inter-
nal temperature.
A wide range of control units such as thermostat, hygrostat
and speed control for noise minimisation extend the applica-
tion range to other areas, such as the office sector and labo-
ratories.
4
EMC fans meet the requirements for increased RF shielding.
Particularly when using fan-and-filter units in conjunction with
PC enclosures or monitor panels, DC variants are used which 2
provide effective protection from interference.

1 3

1 Small enclosure
2 Command panel
3 Console
4 Bayed enclosure/large enclosures
5 PC enclosure

Cooling with ambient air


Sealed and shielded
Also available with EMC Hosed water protection
shielding Particularly for applications
All fan-and-filter units and in the food industry, the
outlet filters are alternatively hose-proof hood prevents
available with EMC shield- the ingress of damp. The
ing. The required conduc- protection category IP 55 is
tive connection is achieved achieved in conjunction with
via a metallic coating on the additional fine filter mats.
fan-and-filter unit housing
Important
and a special sealing frame.
● The prescribed heat loss
Protection functions and the maximum antici-
The membranes of the fan pated ambient tempera-
grille in the form of a rain ture define the required
canopy provide exceptional volumetric flow.
protection against the ● Always use the fan-and-
ingress of splashed water filter units and outlet filters
and dust. together.
Protection category IP 54
is achieved as standard. Calculation formulae,
see page 34
or refer to the Internet at
www.rittal.com

Rittal System Climate Control 199


Cooling with ambient air
Fan-and-filter units – Assembly

Benefits of Rittal fan-and-filter units and


outlet filters
● All-round foamed-in seal as standard to achieve a protec-
tion category of IP 54
● Additional mounting catches for fast, screwless assembly,
to ensure secure attachment to the enclosure
● A new unlatching system for removal of the louvred grille
Super-simple assembly without screws.
Benefits:
● Air throughput from 20 to 700 m3/h
● Super-fast assembly
● Air flow direction may be reversed from blowing (default
setting) to extracting
● All fans also available with EMC shielding

Louvred grill lock system 1 IP 55 with standard mat (A)


● Can only be opened with tools plus additional micro-filter mat (B)
● Achieves a protection category of IP 55 with types Not applicable to SK 3321.... and
SK 3323 . . . . to SK 3327. . . . SK 3322....
3

4 6
5

2 (A) y
(B)
Cooling with ambient air

200 Rittal System Climate Control


Cooling with ambient air
Rack-mounted fans/tangential fans – Applications

Rack-mounted fan
● Air throughput 320/480 m3/h, 1 U. 1
● Direct ventilation of the subracks prevents hot-spots and
heat accumulation.
● The fan units (24 V DC, 115 – 230 V AC) are also available
with integral speed control and fault evaluation.
1 Mounting directly on the 482.6 mm (19˝) level
2

Rack-mounted Vario fan with guide frame


● The rack-mounted fan slides like a drawer. 3
● Connectors on the rear ensure immediate contact.
2 Installation directly in the subrack
3 Installation via two mounting brackets on the 482.6 mm (19˝)
mounting level

Tangential fan
● 320 m3/h air throughput, 2 U.
● The high air throughput means that Rittal tangential fans
are capable of dissipating large heat losses from the
enclosure.
● The ambient air is drawn in via the front grille and con-
veyed upwards.
● The minimal noise generation of 52 dB creates a pleasant
working environment.

Cooling with ambient air

Rittal System Climate Control 201


Cooling with ambient air
Air/air heat exchangers – Applications
Air/air heat exchangers use the external temperature Ambient conditions
for cooling. By separating the internal and external air

circuits, the ingress of dust into the enclosure is

prevented.

Cool Dust

Outstanding performance and design


The requirement for use of air/air heat exchangers is that the
ambient temperature must be below the desired enclosure
internal temperature.
Dust and aggressive ambient air are unable to enter the
enclosure interior, thanks to the two separate air circuits.
In all situations where the ambient air is sufficient for cooling,
air/air heat exchangers offer effective, energy-saving solu-
tions. The high specific thermal output is attributable to the
special construction and functional design of the heat
exchangers:
● A large heat exchanger area with compact dimensions
● Exceptionally conductive materials and connections
● Fans that may be controlled separately
● Optimum flow conditions
Cooling with ambient air

Practical example of an air/air heat


exchanger
In the paper and wood-processing industries, for example,
particular requirements are placed on climate control compo-
nents. They ensure good internal ventilation and heat dissi- 1
pation from the enclosure. At the same time, they also pre-
vent the ingress of super-fine dusts.
Air/air heat exchangers are ideal for this purpose, since they
effectively dissipate the heat from the enclosure with their two
hermetically separate air circuits based on the reverse cur- 2
rent or counter-current principle, and prevent the ingress of
ambient air into the enclosure.

1 Wood-processing industry
2 Air/air heat exchangers (wall-mounted)

202 Rittal System Climate Control


Cooling with ambient air
Air/air heat exchangers – Selection criteria

Cool ambient air


Air/air heat exchangers utilise the ambient air to cool the air
in the enclosure interior. Based on the counterflow principle,
the completely separate airflows are routed through the heat
exchanger module by powerful fans.
● Ambient conditions: The ambient temperature Tu must be
lower than the permissible enclosure interior temperature.
A temperature difference of 10 K is ideal.
● Also ideal for use in dusty ambient conditions.

Flow and siting conditions 1 2


Internal/external mounting
Air/air heat exchangers may optionally be mounted on the
outside or inside of the enclosure. The slimline design facili-
tates external mounting on the door, rear panel and side

Cooling with ambient air


panels.
By diverting the waste air upwards, this prevents the crea-
tion of disruptive air flows in front of the enclosures.
The fans in the internal and external circuit may be activated
separately via an intelligent controller and thus adapted
ideally to the ambient conditions.
1 External mounting
2 Internal mounting

Rittal System Climate Control 203


Cooling with ambient air
Air/air heat exchangers – Assembly

Sealing of the enclosure


The enclosure must be sealed on all sides (IP 54). Particular
attention should be paid to the sealing of the area around the
cable entry openings and above all, the floor section of the
enclosure.
Additionally, the door seal must be in perfect condition.
The sealing material included with the heat exchangers must
be applied in accordance with the installation instructions.
Take care not to bend the side panel or enclosure door.

External circuit
Flow and siting conditions
Air/air heat exchangers in the external circuit should have a
distance of at least 200 mm from a wall and from one another
(air inlet and outlet openings).
If this distance cannot be met, air baffle plates should be
used.
Siting options
Wall-mounted heat exchangers may be mounted on the rear
Cooling with ambient air

panel, side panels or door of the enclosure.

Distance from the wall


at least 200 mm

204 Rittal System Climate Control


Cooling with ambient air
Air/air heat exchangers – Air routing

Free air circulation 200

It is important to ensure “even” air circulation inside the


enclosure. Air inlet and outlet openings in the internal circuit
must on no account be obstructed by electrical installations.
This would prevent air from circulating inside the enclosure.
Under such conditions, the capacity of the device would not
be adequately utilised. A clearance of > 200 mm must be
guaranteed.
Note:
Wall-mounted cooling units should never be fitted directly
behind the mounting plate. Active power components are
located on the front of the mounting plates. The heat
exchanger would then operate in its own air short-circuit.
If it is impossible to install the device any other way, appropri-
ate air baffle plates should be used, and air inlet and outlet
openings should be provided in the mounting plate.

Cooling with ambient air


Internal circuit – Wall-mounted units
Attention should be paid to components and electronic com-
ponents equipped with their own ventilation systems, such as
blowers and axial fans. If their air flow is directed against the
chilled air flow of the heat exchanger, this could cause an air
short-circuit and adequate climate control would no longer
be guaranteed.
Note:
Never direct the chilled air flow at active components.

Rittal System Climate Control 205


Cooling with ambient air
Air/air heat exchanger – Electrical connection and control

Simple control with digital temperature


display
● Specific thermal output from 17.5 to 90 W/K
● With controller and digital temperature display
● Floating fault signal contact in case of overtemperature
● System analysis via display

Supply connection
● The mains connection parameters (voltage and frequency)
specified on the rating plate must be observed.
● The pre-fuse specified on the rating plate must be used.

Rated voltage 230 V, 50/60 Hz


Rated current 0.6 A/0.8 A
Rated consumption 140 W/180 W
Pre-fuse T 2A
Specific cooling output 45 W/K
Cooling with ambient air

Cabling
1 Signal data cable 3 2 1
1
2 Control cable
3 Motor cable 2

The power cable, power supply unit cable, signal cable and
data cable must be laid separately; cable lengths should be 3
kept as short as possible. Avoid coupled sections.

206 Rittal System Climate Control


Cooling units
Applications
Cooling units keep the enclosure internal temperature Ambient conditions
at a constant level, even to below room temperature.

The air routing meets individual requirements. Two

separate circuits prevent the ingress of dust into the

enclosure.

Heat Dust

● Climate controlled enclosures


● Roof-mounted cooling units
● Wall-mounted cooling units
● Thermoelectric cooler

Integral cooling system/climate controlled


enclosures
The combination of enclosure and cooling components
achieves particularly effective cooling. Assembly time is
eliminated. The investment costs for the complete unit offer
exceptional value for money.

Cooling units
Roof-mounted cooling units
Requirement-oriented routing of cooling air in the internal
circuit is possible, with up to four cold air outlet openings
and the optional use of ducts. In the external circuit, the
heated air is expelled to the rear, left and right, and option-
ally upwards. This means that the enclosure may be sited in
a bayed suite or close to the wall.

Wall-mounted cooling units


Depending on the space and design requirements, internal
mounting, partial internal mounting and external mounting
are all possible. Thanks to large distances between the air
intake and outlet openings, effective cold air throughput of
the enclosure is achieved.

Rittal System Climate Control 207


Cooling units
Selection criteria

Enclosure climate control poses escalating demands on inte- ● What is the heat loss from electronic components inside
gration and adaptation to the local conditions and the exist- the enclosure?
ing process control and monitoring system. Rittal offers the ● Is there a requirement regarding the protection category
right solution to suit every requirement. to EN 60 529/IEC 529?
● What type of ambient pollution, such as dust, oil and
When selecting the appropriate cooling unit for your chemicals, are the cooling units exposed to?
enclosure, please observe the following points: ● For bayed enclosure suites, the output irradiated from
● What is the installation type to IEC 890? neighbouring units may also need to be taken into
(see page 34, calculation bases) account.
● What ambient conditions are anticipated (max. ambient ● Good ventilation should be ensured at the site of installa-
temperature and humidity)? tion (for example, the heat dissipated by the cooling unit
● What is the required maximum internal temperature of the may cause a significant rise in the temperature of small
enclosure (Ti)? rooms).
● Particularly with poor ambient conditions, such as dirt or
small, unvented rooms, air/water heat exchangers should
be used.

Important
Proper use of enclosure cooling units 6. The temperature range specified on the rating plate must be
observed when operating the cooling unit, both indoors and
In order to ensure the proper use of enclosure cooling units, the outdoors.
following points should be observed:
7. The enclosure must be sealed on all sides (IP 54).
1. The unit must only be installed and opened by authorised,
expertly trained personnel. 8. The air inlet and outlet openings in the internal circuit of the
cooling unit must not be obstructed.
2. Choose a location for the cooling unit which ensures excellent
ventilation. The site must be free from excessive contamination 9. The cold air flow should not be directed straight at electronic
and moisture. For example, the atmosphere must not contain components, to prevent the formation of condensation.
any conductive dusts or corrosive media. 10. The unit must only be installed horizontally, in accordance with
3. The mains connection data (connection voltage and frequency) the prescribed installation position. The maximum permissible
specified on the rating plate must be observed. In the case of deviation from the horizontal is 2°.
400 V, 2~ cooling units, we recommend the use of transformer 11. After disconnecting from the supply voltage, the cooling circuit
circuit-breakers, and for three-phase units, the use of motor of the cooling unit must not be switched back on for at least
circuit-breakers is advisable. 5 minutes.
4. The prescribed electrical protection devices must be con- 12. The customer must not make any modifications to the cooling
nected upstream of the unit. No additional temperature control unit.
must be connected upstream of the device at the supply end.
Cooling units

The pre-fuse specified on the rating plate should be provided 13. The heat loss of the components installed in the enclosure must
as line protection. Observe the locally valid regulations when not exceed the specific useful cooling output of the cooling unit.
installing. 14. The installation instructions contained in the cooling unit manual
5. Where a door contact switch is used, a shielded cable should must be observed in full.
be used in environments with increased levels of electro-
magnetic interference.

208 Rittal System Climate Control


Cooling units
Assembly

Sealing of the enclosure


The enclosure must be sealed on all sides (IP 54). Particular
attention should be paid to the sealing of the area around the
cable entry openings and above all, the floor section of the
enclosure.
Additionally, the door seal must be in perfect condition.
The sealing material included with the cooling units must be
applied in accordance with the installation instructions.
Take care not to bend the side panel or enclosure door.

Installation on enclosures
The cooling unit must be correctly installed.
The roof plate of the enclosure must not be allowed to give
under the weight of the cooling unit.
If necessary, additional stays should be used. Do not
obstruct the air inlets and outlets of the internal circuit.
Note:
For TopTherm-Plus roof-mounted units, TS 8 roof plates pre-
pared with mounting cut-outs and reinforcement strips for all
standard enclosure sizes are available as an accessory (see
page 181).
When installing after the unit has been assembled, the twin-
threaded bolts supplied loose should be screwed into the
core holes in the plastic base on the underside of the device,
with a maximum torque of 3 Nm.

Cooling units

Rittal System Climate Control 209


Cooling units
Air routing

External circuit
Flow and siting conditions
In the outer circuit, enclosure cooling units should be spaced
> 200 mm from the wall and/or from each other (air inlet and
outlet openings). In order to ensure adequate air circulation,
at least one air outlet opening must be kept free.
If this clearance cannot be maintained, air baffle plates will
need to be used.
The external circuit supports all siting variants.
Thanks to their compact dimensions and external air routing
design, roof-mounted cooling units may even be installed in
low-height rooms and with bayed enclosure suites.
Air intake is always from the front. The air is expelled at the
sides and rear. An outlet to the top is also possible as an
option. In other words, regardless of which siting mode is
chosen, one air outlet must always be kept free. Distance from the wall
at least 200 mm
Siting options
There are no restrictions here. Only the air intake and exhaust
area in front of the cooling unit must be kept free.
Wall-mounted cooling units may be mounted on the rear
panel, side panels or door of the enclosure.

Internal circuit – Wall-mounted units


Flow conditions
Attention should be paid to components/electronic compo-
nents equipped with their own ventilation systems, such as
blowers and axial fans. If their air flow is directed against the
chilled air flow of the cooling unit, this could cause an air
short-circuit. In the worst case, the internal safety valves of
the cooling unit would discontinue cooling operation.
Note:
Never direct the chilled air flow at active components.
Accessories:
Air diverter, see page 176.
Cooling units

210 Rittal System Climate Control


Cooling units
Air routing

Free air circulation 200

It is important to ensure “even” air circulation inside the


enclosure. Air inlet and outlet openings in the internal circuit
must on no account be obstructed by electrical installations.
This would prevent air from circulating inside the enclosure.
Under such conditions, the cooling capacity of the device
would not be adequately utilised. A clearance of > 200 mm
must be guaranteed.
Note:
Wall-mounted cooling units should never be fitted directly
behind the mounting plate. Active power components are
located on the front of the mounting plates. The cooling unit
would then be left to operate in its own air short-circuit.
If it is impossible to install the device any other way, appropri-
ate air baffle plates should be used, and air inlet and outlet
openings should be provided in the mounting plate.
Accessories:
Air diverter, see page 176.

Air diverter systems


for wall-mounted units
See page 176.
For use in climate control side panels and TopTherm-Plus
wall-mounted cooling units. For targeted air routing of the
cold air in a downward direction. Particularly well-suited for
densely-packed electrical components in the lower section

Cooling units
of the enclosure.

Internal circuit – Roof-mounted units


Flow conditions
When using roof-mounted units, particular attention should
be paid to the air flow from the blowers of built-in electronic
components (such as frequency converters and other drive
units).

Rittal System Climate Control 211


Cooling units
Air routing

Air duct system


for TopTherm-Plus roof-mounted cooling units
It is possible to route the cold air directly to specific areas
of the enclosure using the air duct system. The risk of “short
circuits” in the air circulation due to self-ventilated installed
devices is therefore eliminated.
Note:
● Never direct the cold air flow straight at active compo-
nents.
● Route the air duct system directly downwards with no
bends.
● Cold air must be able to escape unobstructed at the end of
the duct. 1
● Additional deflections will reduce the useful cooling output.
● When using the ducting system, the performance of the
cooling unit may be reduced, depending on the respec-
tive application.
● The air duct system should not be extended.
CAUTION Risk of icing! Accessories:
1 Air duct system for roof-mounted units,
see page 174.

Stoppers
for TopTherm-Plus roof-mounted cooling units
For sealing any cold air outlets that are not required.
Note:
At least two outlet openings must always remain open!
Please note that if two or three openings are closed, the cool-
ing output may be reduced by 20 % and 30 % respectively!
SK 3286.880 for units
SK 3383.xxx SK 3273.xxx
SK 3384.xxx SK 3209.xxx
SK 3385.xxx SK 3210.xxx
Cooling units

max. 2x

SK 3286.780 for units


SK 3382.xxx
SK 3359.xxx

SK 3286.980 for units


SK 3386.xxx
SK 3387.xxx

max. 1x

212 Rittal System Climate Control


Cooling units
Condensation management

Condensate routing (roof-mounted units) 1 2


Any condensation which forms on the evaporator coil (with
high humidity and low enclosure interior temperatures) is
routed to the right and/or downwards out of the device via a y
drain in the evaporator tray. For this purpose, a piece of hose
should be connected to one of the two condensate nozzles
(1 or 2). The drain which is not required should be tightly
sealed. The condensate must be able to run off freely.
If the condensate is to be drained off over a greater
distance, then care must be taken to ensure that the hose
is free from kinks and checked for correct drainage. Units
with a Comfort controller are additionally equipped with a
condensate alarm.

1 Condensate discharge rear


2 Condensate discharge right

Note:
Condensate discharge (wall-mounted units) y
For wall-mounted units, a hose should be connected to the
condensate nozzle on the bottom of the unit.

2
1

The condensate drain pipe should be laid with a gradient,


taking care to ensure there are no kinks in the pipe!

Condensate discharge Condensate hose For unit(s)


If the condensate discharge is extended, its cross-section SK 3301.608 (8 x 1.5) SK 3302.xxx

Cooling units
must not be reduced. SK 3301.610 (10 x 1.5) SK 3303.xxx/SK 3361.xxx
SK 3304.xxx/SK 3305.xxx
SK 3301.612 (12 x 2) SK 3328.xxx/SK 3329.xxx
SK 3332.xxx/SK 3382.xxx
SK 3359.xxx/SK 3383.xxx
SK 3384.xxx/SK 3385.xxx
SK 3386.xxx/SK 3387.xxx
SK 3366.xxx/SK 3377.xxx
SK 3209.xxx/SK 3210.xxx
Accessories: SK 3273.xxx
PVC condensate hose

Rittal System Climate Control 213


Cooling units
Condensation management

Condensate evaporation, electrical


integrated into TopTherm-Plus cooling units
Condensate arising inside the enclosure or on the evapora-
tor coil of the cooling unit is effectively evaporated. The evap- Rittal ation
orator device inside the cooling units has a very high evapo- innov
ration output (several litres per day). This is achieved thanks
to the principle of direct evaporation. Important note: The
enclosure must be sealed on all sides.
Energy-efficient: Activation of the evaporator device is via a
separate heater cartridge. “Condensate evaporation” based
on the hot gas bypass principle is too ineffective, due to
inadequate evaporation temperatures.
Advantage:
● Safe use: No condensate drips onto the factory floor
(no puddles/no risks of slipping/accidents).
● No need to empty the condensate collecting receptacles.
● No time-consuming laying of condensate hoses required.

The internal and external units are active “direct evaporator


coils”, which actively evaporate the condensate incurred.
Advantage:
● No collecting vessel required
● No long hosepipes
Note:
For roof and wall-mounted units, either external evaporator
units or integral condensate evaporators may be used.
TopTherm-Plus cooling units are available with integrated
electronic condensate evaporation and external evaporator
units for retro-fitting.
Cooling units

Filter mats
In dusty environments, we recommend the use of filter mats
to make it easier to clean the cooling unit.
The filter should be changed at regular intervals, depending
on the level of contamination.
If the air is oil-contaminated, it is better to use metal filter
mats which may be cleaned with appropriate detergents and
reused.

214 Rittal System Climate Control


Cooling units
Electrical connection and control

Supply connection
● Supply connection data (voltage and frequency) must be
observed in accordance with the rating plate.
● The pre-fuse specified on the rating plate must be used.

Voltage range 400 V/460 V


Frequency range 50 Hz/60 Hz

400 V/50 Hz 3~ 400 V/60 Hz 3~


Rated current 2.5 A 3.0 A
Start-up current 6.5 A 7.5 A
Motor circuit-breaker 10 A 10 A
L 35 L 35 930 W 1150 W
Rated consumption
L 35 L 50 1150 W 1400 W
L 35 L 35 2000 W 2350 W
Useful cooling output
L 35 L 50 1450 W 1690 W
Coolant/filled weight R 134a, 950 g (34 oz), Fluid Group 2

Use of door-operated switches


One floating door-operated contact should be used for each
unit; under no circumstances must several cooling units be
operated via one door-operated switch.
In environments with increased electromagnetic inter-
ference, a shielded cable should be used.
Alternatively, the door contact may be switched e.g. via
an additional relay in the vicinity of the cooling unit.

Note:
The cables should be laid separately from the mains cables;
short cable distances should be observed.

Cooling units

Cabling
1 Signal data cable 3 2 1
1
2 Control cable
3 Motor cable 2

The power cable, power supply unit cable, signal cable and
data cable must be laid separately; cable lengths should be 3
kept as short as possible. Avoid coupled sections.

Rittal System Climate Control 215


Cooling units
Electrical connection and control/Thermoelectric Cooler – Mounting options

Intelligent control
The two controller variants for operational reliability offer a Comfort controller:
comprehensive range of functions. Essential control elec- ● Master/slave function for up to 10 units, i.e. the unit which
tronics are well protected and cooled in the inner circuit. reaches the setpoint first reports this to the “master”, which
Both variants have the following properties: switches all the other “slaves” on and off. The unit in which
● Three voltage options: 115 V, 230 V, 400/460 V 3 ˜ the door limit switch function is activated reports this to the
● Integral start-up delay and door limit switch function “master”, which deactivates all the “slaves”.
● Icing protection function ● Switching hysteresis: 2 – 10 K; preset to 5 K
● Monitoring of all motors ● System alarm, individually configurable for 2 floating fault
● Phase monitoring for three-phase units signal contacts
● Visualisation of the current enclosure internal temperature
and all system messages on the display
Basic controller: ● Storage of all system statuses in the log file
● Visualisation of the operating status via LED display:
● Optional extension card (SK 3124.200) with RS232,
− Voltage applied, functions OK
RS485, RS422 and PLC interface for integration into
− Door open
superordinate remote control systems, e.g. with CMC,
− Overtemperature
is also possible
− High-pressure monitor has switched
● Switching hysteresis: 5 K
● Floating fault signal contact in case of overtemperature
● Setpoint adjustable from outside via potentiometer (setting
range 20 – 55°C)

Thermoelectric Cooler – Mounting


Installation
When installed in the enclosure, the unit only protrudes by a
few millimetres, and therefore does not interrupt either the
aesthetic appearance or freedom of movement on support
arm systems.
External mounting
Cooling units

Its low weight also allows it to be externally mounted on sim-


ple aluminium rear panels or blanking panels.
Support arm systems
Thanks to its low-vibration operation and minimal weight, the
thermoelectric cooler from Rittal is the ideal partner on sup-
port arm systems.

Thermoelectric Cooler – Scalability


Scalable output
The modular design allows simple scaling of the cooling
output depending on your requirements, both horizontally
and vertically.

216 Rittal System Climate Control


Liquid cooling IE
Air/water heat exchangers – Applications
Air/water heat exchangers effectively dissipate high Ambient conditions
heat losses. Thanks to the spatial separation of the

heat exchanger and recooling system, the room is not

burdened with waste heat.

Heat Dust

Ideal at any installation site


High ambient temperatures and extreme levels of conta-
mination are ideal conditions for the use of air/water heat
exchangers. If direct dissipation of heat loss to the ambient
air is undesirable or ineffective due to the confined space,
the air/water heat exchanger may likewise offer an ideal
solution. Very effective cooling solutions for individual
enclosures or bayed enclosure suites may be achieved
by separating the exchanger from the recooling system.

Liquid cooling IE
Practical example of an air/water heat
exchanger 2
1
In all areas with extreme ambient conditions, enclosure and
climate control components are subject to special require-
ments. This applies, for example, to metal foundries, engine
factories and the chemical and metal-working industries.
In such situations, low-maintenance air/water heat exchang-
ers are used as efficient all-rounders. Either fed from existing 2
cooling water networks or from separate recooling systems, 3
these products contribute to an ideal climate inside the
enclosure. The cooling water absorbs the heat inside the
heat exchanger and conveys it to the corresponding cooling
system. In this way, even small rooms are not subject to addi-
tional waste heat from the enclosure, and the electronics 1 Extreme industrial environments
inside the enclosure are effectively protected. 2 Air/water heat exchangers (roof-mounted, wall-mounted)
3 Recooling system

Rittal System Climate Control 217


Liquid cooling IE
Air/water heat exchangers – Selection criteria

Application example: Parallel connection of 4 air/water heat exchangers


Example: Parallel connection of air/water heat exchangers Overflow valves and bypass control should be integrated into
with cold water supply via a recooling system. the recooling system and the customer’s own pipeline system
respectively.
1 Recooling system
2 2 2 2 2 Air/water heat exchangers
3 Overflow valve
SK 3301.900/.910/.920
(Bypass function with closed
magnetic valve of the air/water
heat exchanger)
1 4 4 4 4
5 4 Flow regulator valve
SK 3301.930/.940
(to regulate the volume flow in
3 air/water heat exchangers)
5 Non-return valve (optional)
6 6 Magnetic valve (optional)

Roof or wall mounting


Two design variants for mounting on the enclosure roof or the
side panel or door are available in the output range from 300
to 7000 watts. Available in two control variants (Basic and
Comfort control), and also optionally with all water-carrying
parts made from V4A (1.4571).
Liquid cooling IE

High temperature range


● Application areas with temperatures up to +70°C and
extreme dust contamination, e.g. in foundries, are ideal
for the use of this technology. 2
1
● Spatial separation of the heat exchanger and cold water
supply is easily achieved.

1 Recooling system
2 Air/water heat exchanger, roof-mounted 3
3 Air/water heat exchanger, wall-mounted 3
4 Additional cooling water circuit for machine cooling
4

Cooling medium quality requirements


For cooling media that cannot be precisely defined, or even General water quality requirements are outlined on page 37
seawater, air/water heat exchangers with all water carrying “Hydrological data”.
parts of stainless steel 1.4571 (V4A) are available.

218 Rittal System Climate Control


Liquid cooling IE
Air/water heat exchangers – Assembly

Application benefits
Compact and lightweight
Air/water heat exchangers have a low weight and a compar-
atively low volume in relation to the heat loss dissipated. As a
result, they are easily mounted on vertical enclosure sur-
faces or on the roof.
Virtually maintenance-free
Because the ingress of ambient air into the heat exchanger is
prevented, dirt is unable to penetrate. Control of the air and
water circuit is electronically monitored.

Sealing of the enclosure


The enclosure must be sealed on all sides (IP 54). Particular
attention should be paid to the sealing of the area around the
cable entry openings and above all, the floor section of the
enclosure.
Additionally, the door seal must be in perfect condition.
The sealing material included with the heat exchangers must
be applied in accordance with the installation instructions.
Take care not to bend the side panel or enclosure door.

Liquid cooling IE
Installation on enclosures
The heat exchanger must be correctly installed.
The roof plate of the enclosure must not be allowed to give
under the weight of the heat exchanger.
If necessary, additional stays should be used. Do not
obstruct the air inlets and outlets of the internal circuit.
Note:
For TopTherm-Plus roof-mounted units, TS 8 roof plates pre-
pared with mounting cut-outs and reinforcement strips for all
standard enclosure sizes are available as an accessory (see
page 181).
When installing after the unit has been assembled, the twin-
threaded bolts supplied loose should be screwed into the
core holes in the plastic base on the underside of the device,
with a maximum torque of 3 Nm.

Rittal System Climate Control 219


Liquid cooling IE
Air/water heat exchangers – Air routing

Free air circulation 200

It is important to ensure “even” air circulation inside the


enclosure. Air inlet and outlet openings in the internal circuit
must on no account be obstructed by electrical installations.
This would prevent air from circulating inside the enclosure.
Under such conditions, the cooling capacity of the device
would not be adequately utilised. A clearance of > 200 mm
must be guaranteed.
Note:
Wall-mounted cooling units should never be fitted directly
behind the mounting plate. Active power components are
located on the front of the mounting plates. The heat
exchanger would then operate in its own air short-circuit.
If it is impossible to install the device any other way, appropri-
ate air baffle plates should be used, and air inlet and outlet
openings should be provided in the mounting plate.

Internal circuit – Roof-mounted units


Flow conditions
When using roof-mounted units, particular attention should
be paid to the air flow from the blowers of built-in electronic
components such as frequency converters and other drive
Liquid cooling IE

units.

220 Rittal System Climate Control


Liquid cooling IE
Air/water heat exchangers – Air routing

Air duct system


for TopTherm-Plus roof-mounted air/water heat
exchangers
It is possible to route the cold air directly to specific areas of
the enclosure using the air duct system. The risk of “short
circuits” in the air circulation due to self-ventilated installed
devices is therefore eliminated.
Note:
● Never direct the cold air flow straight at active compo-
nents.
● Route the air duct system directly downwards with no
bends.
● Cold air must be able to escape unobstructed at the end of 1
the duct.
● Additional deflections will reduce the useful cooling output.
● When using the ducting system, the performance of the
heat exchanger may be reduced, depending on the
respective application.
● The air duct system should not be extended.
Accessories:
1 Air duct system for roof-mounted units, see page 174.

Stoppers
for TopTherm-Plus roof-mounted air/water heat
exchangers
For sealing any cold air outlets that are not required.
Note:
At least two outlet openings must always remain open!
Please note that if two or three openings are closed, the cool-
ing output may be reduced by 20 % and 30 % respectively!
SK 3286.880 for units max. 2x
SK 3209.xxx
SK 3210.xxx

Liquid cooling IE
Internal circuit – Wall-mounted units
Flow conditions
Attention should be paid to components/electronic compo-
nents equipped with their own ventilation systems, such as
blowers and axial fans. If their air flow is directed against the
chilled air flow of the heat exchanger, this could cause an air
short-circuit and prevent adequate climate control. In a worst
case scenario, the heat exchanger will suffer an air short-
circuit.
Note:
Never direct the chilled air flow at active components.

Rittal System Climate Control 221


Liquid cooling IE
Air/water heat exchangers – Condensation management

Condensate routing (roof-mounted units) 1 2


Any condensation which forms on the heat exchanger (with
high humidity and low enclosure interior temperatures) is
routed to the right and/or downwards out of the device via a y
drain in the tray. For this purpose, a piece of hose should be
connected to one of the two condensate nozzles (1 or 2).
The drain which is not required should be tightly sealed.
The condensate must be able to run off freely. If the con-
densate is to be drained off over a greater distance, then
care must be taken to ensure that the hose is free from
kinks, laid with a gradient and checked for correct drain-
age. Units with a Comfort controller are additionally equipped
with a condensate alarm.

1 Condensate discharge rear


2 Condensate discharge right

2
1

Flexible cooling water connection and


condensate drain pipe
Liquid cooling IE

Roof-mounted units:
In its delivered state, hose nozzles for connecting the cool-
ing water and condensate hoses are located on the right-
hand side of the unit. There is a second connection point for
cooling water and condensate at the rear of the unit, which
is sealed with sealing caps. If the connections at the rear 2
are used, the sealing cap and hose nozzle should be un- 1
screwed, cleaned and resealed using standard commer-
cially available sealant (Teflon tape or hemp with sealing
paste). Next, screw in the three sealing caps on the right and
the three hose nozzles at the rear of the unit with the follow-
ing torques: 1 Condensate discharge (flexible)

● 15 Nm for hose nozzles for the supply and return flow 2 Cooling water connection (flexible)
● 15 Nm for sealing caps for the inlet and return
● 2 Nm for condensate discharge
● 2 Nm for sealing caps for condensate discharge

Note:
Any condensate arising is discharged via the 1/2˝ tube con-
nector and a discharge hose, which should be laid with a
gradient ensuring that there are no kinks. In order to avoid
increased condensation, the cooling water temperature
should be adapted to match the required cooling output. Any
condensate occurring may be disposed of using an external
electronic condensate evaporator.

222 Rittal System Climate Control


Liquid cooling IE
Air/water heat exchangers – Condensation management

Note:
Condensate discharge (wall-mounted units)
For wall-mounted units, a hose should be connected to the condensate nozzle on the bottom of the unit.

The condensate drain pipe should be laid with a gradient, taking care to ensure there are no kinks in the pipe!

Condensate discharge Condensate hose For unit(s)


If the condensate discharge is extended, its cross-section SK 3301.612 (12 x 2) SK 3209.xxx/SK 3210.xxx
SK 3364.xxx/SK 3373.xxx
must not be reduced. SK 3374.xxx/SK 3375.xxx
Accessories:
PVC condensate hose

Liquid cooling IE

Rittal System Climate Control 223


Liquid cooling IE
Air/water heat exchangers – Electrical connection and control

Supply connection
● Supply connection data (voltage and frequency) must be
observed in accordance with the rating plate.
● The pre-fuse specified on the rating plate must be used.

Rated voltage 230 V 50 Hz/60 Hz


Rated current 0.4/0.48 A
Pre-fuse T 4A
Power consumption 95/110 W
Useful cooling output 400 l/h L 35 W 10 2500 W
Water
Cooling medium
(see specifications)

Use of door-operated switches


One floating door-operated contact should be used for each
unit; under no circumstances must several air/water heat
exchangers be operated via one door-operated switch.
In environments with increased electromagnetic interfer-
ence, a shielded cable should be used.
Alternatively, the door contact may be switched e.g. via an
additional relay in the vicinity of the air/water heat exchanger.

Note:
The cables should be laid separately from the mains cables;
short cable distances should be observed.
Liquid cooling IE

Cabling
1 Signal data cable 3 2 1
1
2 Control cable
3 Motor cable 2

The power cable, power supply unit cable, signal cable and
data cable must be laid separately; cable lengths should be 3
kept as short as possible. Avoid coupled sections.

224 Rittal System Climate Control


Liquid cooling IE
Air/water heat exchangers – Electrical connection and control

Intelligent control
The two controller variants for operational reliability offer a
comprehensive range of functions. Essential control elec-
tronics are well protected and cooled in the inner circuit.
Both variants have the following properties:
● Three voltage options: 115 V, 230 V, 400/2 ˜
● Integral start-up delay and door limit switch function
● Leak detection
● Monitoring of all motors

Basic controller:
● Visualisation of the operating status via LED display:
− Voltage applied, functions OK
− Door open
− Overtemperature
● Switching hysteresis: 5 K
● Floating fault signal contact in case of overtemperature
● Setpoint adjustable from outside via potentiometer (setting
range 20 – 55°C)

Comfort controller:
● Master/slave function for up to 10 units, i.e. the unit which
reaches the setpoint first reports this to the “master”, which
switches all the other “slaves” on and off. The unit in which
the door limit switch function is activated reports this to the
“master”, which deactivates all the “slaves”.
● Switching hysteresis: 2 – 10 K; preset to 5 K
● System alarm, individually configurable for 2 floating fault
signal contacts
● Visualisation of the current enclosure internal temperature
and all system messages on the display
● Storage of all system statuses in the log file
● Optional extension card (SK 3124.200) with RS232,

Liquid cooling IE
RS485, RS422 and PLC interface for integration into
superordinate remote control systems, e.g. with CMC,
is also possible

Rittal System Climate Control 225


Liquid cooling IE
Recooling systems/chillers – Applications
Recooling systems ensure centralised, efficient cool- Ambient conditions
ing and supply of the cooling medium (generally

water), and are used with particularly high heat loads.

They may serve several pieces of equipment simulta-

neously, and are particularly effective in terms of cool-

ing output. Heat Dust

Application diversity of centralised cooling technology


Enclosure cooling Cooling of liquid media
In conjunction with air/water Direct and indirect cooling of
heat exchangers, optimum liquids are the prerequisite
dissipation of high heat for ensuring the required
loads is guaranteed, even machine precision and
under extreme ambient speed.
temperatures and air con-
tamination levels.
Liquid cooling IE

Process cooling Rack cooling IT


High-quality material Rittal offers solutions for
processing, such as laser base load cooling and
cutting, necessitates high ambient air-neutral, high-
levels of temperature preci- performance cooling for
sion with simultaneous all IT sectors.
cooling of the peripheral
technology.

226 Rittal System Climate Control


Liquid cooling IE
Recooling systems/chillers – Selection criteria

Generally speaking, recooling systems are divided into open If a recooling system is required to serve several pieces of
and closed systems. equipment having different requirements in terms of inlet
temperature and flow rate of the cooling medium, e.g. com-
In the pressure-sealed configuration, the water circuit is
bined enclosure and process cooling, multi-circuit systems
equipped with a pressure relief valve and automatic exhaust.
are used. In such cases, the different circuits may be tai-
There is no need to top up the water.
lored to the respective equipment.
Recooling systems designed as an open system have a tank
If there is already a central cooling water supply available at
made of PP/PE plastic or stainless steel 1.4301 with lid built
the installation site, e.g. in the case of plant water in the auto-
into the recooling system. This is easily filled.
motive industry, recooling systems may optionally be fitted
with a water-cooled condenser. One of the major benefits of
this solution lies in the fact that the factory temperature is not
additionally raised by waste process heat.

Liquid cooling IE
Mini-recooling systems Recooling systems
● Cooling output from 1 to integrated into the TS 8 Top
6 kW enclosure system
● Space-saving, compact ● Cooling output from 6 to
design 60 kW
● Attractive design ● Compact design
● Wall-mounted units: Inte- ● Option of integration into
gration into the machine existing TS 8 enclosure
and enclosure housing combinations
without using additional
floor space

Recooling systems in a Recooling systems in an


floor-standing enclosure industrial enclosure
for water and oil ● Cooling output up to
● Cooling output from 2.1 to 502 kW
26 kW ● High cooling output with
● Stand-alone enclosure optimised space require-
● Minimal base area ments
● The functionally equipped ● Removable enclosure pan-
design facilitates the cool- els offer easier accessibil-
ing of oil and water ity in case of servicing
● There are a range of
options available

Liquid cooling IE
Immersible recooling Power Fluid Cooler
systems ● Fast delivery range
● Wherever it is necessary to ● Standardised version
cool dirt-contaminated available ex works
media (metal swarf or ● New design in the output
aggressive sludge) category 8 to 59 kW
● High-end flat condenser ● Defined options
made of stainless steel
● Sealed cooling circuit

Liquid cooling IT
Data centre
with recooling systems
● Recooling systems ensure ● Spatial separation
central cooling and supply between refrigeration and
of the cooling medium cooling for temperature-
for liquid cooling sys- neutral expansion of the
tems data centre.

Rittal System Climate Control 227


Liquid cooling IE
Recooling systems/chillers – Assembly

Unity with enclosures


For example, recooling systems may be connected directly
2
to a bayed enclosure suite, providing effective, centralised
cooling for all enclosures and housings on a machine or 2
system.
Recooling systems in the TS 8 Top enclosure system are eas-
ily integrated into existing enclosure combinations. For appli-
cations in confined conditions, the Mini-recooling systems for 1
wall and roof mounting are ideal, with their space-saving,
compact design.

1 Recooling system
2 Air/water heat exchanger, roof-mounted

Spatially separated
High heat loads can even be dissipated in confined and
awkward spaces, thanks to the spatial separation of the
recooling system from the enclosures and machine. In all
2
cases, as well as enclosure cooling, cooling water may also
be produced for process and machine cooling or for cooling 1
liquid media.
Recooling systems in floor-standing and industrial enclo-
sures, with their robust design, are the ideal stand-alone
solution, and provide optimum accessibility for servicing 3
purposes.
3
1 Recooling system
2 Air/water heat exchanger, roof-mounted 4
3 Air/water heat exchanger, wall-mounted
4 Other components, e.g. machine cooling
Liquid cooling IE

Outdoor siting
To avoid putting additional pressure on the factory air with
the waste heat incurred during the process, the recooling
system may be supplied with the option of outdoor siting
(for ambient temperatures down to –20°C).
In such cases, a rain canopy should be provided to protect
the recooling system from extreme weather. The water circuit
must be filled with 34 % anti-freeze agent Antifrogen N (or
equivalent) to 66 % water in relation to the total water vol-
ume, or with Rifrost 1 : 2.
IT chillers do not require a rain canopy.

228 Rittal System Climate Control


Liquid cooling IE
Recooling systems/chillers – Notes

Assembly and commissioning


When siting the recooling system, the following points
In the case of air-cooled recooling systems, the following mini-
mum distances from the wall and ceiling should be observed: should be observed:
● Connection of an inlet and outlet duct requires the manu-
facturer's prior consent.
2
− Performance loss (air-cooled recooling system)
● Never site the recooling system in the vicinity of a heater.
− Performance loss
● The recooling system may only be sited on flat, solid
surfaces. The maximum permissible deviation from the
1 Re- vertical is 2°.
cooling ● Connect the equipment to the recooling system using
system
insulated pipe or hose connections.
● If the equipment is positioned higher than the recooling
system, install a non-return valve upstream in the inlet
and a magnetic valve in the return.
− To avoid overflowing the tank.
● With recooling systems that are intended for covered out-
door siting, the minimum external temperature is given in
1 Wall: At least 1x condenser height the technical specifications.
2 Ceiling: At least 3x the condenser height ● In the case of recooling systems (for water) at tempera-
tures below zero, a water/glycol mixture should be added
in the prescribed ratio.
● If it is possible to shut off the equipment cycle, a bypass
must be provided in order to protect the pump.
● Under no circumstances must the circulation pump be
allowed to run dry
– Damage to the pump.

Distance from equipment


Site the recooling system close to the equipment in order to
avoid long distances, which could lead to performance
losses. When selecting the installation site, care should be
taken to ensure easy access at all times; this will make main-
tenance of the system easier.
You should also ensure adequate ventilation of the room
where the recooling system is sited. If there is inadequate
ventilation, the temperature of the room will increase as a
result of waste heat, leading to impaired performance of the
recooling system.

Liquid cooling IE

Cooling media
Apart from the recooling systems for oil and emulsion, all
other recooling systems are only suitable for the cooling of
water or a water/glycol mixture. When filling the systems for
the first time, water from the existing supply line is generally
suitable, although care should be taken to ensure a consist-
ent water quality.
However, as satisfactory results are only rarely achieved with-
out water treatment, additives should always be added to the
cooling water, irrespective of the installation site. As well as
protecting against frost, these also serve to impair bacterial
growth and achieve optimum corrosion protection.
Pre-mixed additive is available from Rittal in the mix ratios
● 1 : 2 for outdoor siting
● 1 : 4 for standard applications, available in 10 l, 25 l and
200 l containers.
See page 194.

Rittal System Climate Control 229


Liquid cooling IT
Aisle containment – Benefits
Instead of flooding the room with cold air, this Rittal concept
routes the cold air generated directly to the equipment via
the cold aisle.
The servers are supplied with chilled air distributed evenly
across the entire rack height. Due to the cold aisle being
contained there is no chance of the hot exhaust air mixing
with the cold inlet air, leading to enhanced system efficiency.
The outstanding energy efficiency of the Rittal cold aisle
concept has a simple and plausible explanation:
1. Cold and hot air cannot mix, hot air does not flow into the
cold aisle.
2. The system can be operated with a much higher waste air
temperature.
3. Standard air circulation cooling units are operated at an
optimum thermal efficiency level.

Standard market concepts Rittal aisle containment


Liquid cooling IT

Hot air extraction using Cold aisle variant Hot aisle variant
a duct system ● Use of standard, inexpensive CRAC sys- ● Standard CRAC systems cannot be
● Complex and costly duct system. tems. Positioning outside the server area. used here.
● Larger surface area and height require- ● Even with low room heights, the raised ● Inline climate control systems are
ments. floor height for cooling air supply can be needed to cool the air.
● Limitation of the raised floor height. maximised without flow losses. ● The waste air produced can be selec-
● As a result, there is no uniform cooling ● Undisturbed and uniform air flow distribu- tively controlled.
air supply to the room area. tion of cooling air in the cold aisle guaran- ● Efficiently raises the waste air tempera-
● Cable management is made more tees high efficiency. tures without impairing the environment.
difficult. ● Favourable working conditions in the cold
● Limited rack positioning flexibility due to aisle due to low temperature, flow and
the air duct connection. noise load conditions.
● Hardware racks not connected to the
enclosure do not impair the cooling
efficiency of the cold aisle.

230 Rittal System Climate Control


Liquid cooling IT
Aisle containment – Usage

Liquid cooling IT

Representation of the air flows in the 4 The heat-laden waste air is discharged
cold aisle variant to the surroundings and rises to the
ceiling.
1 Supply of cooled air via the raised floor.
The recirculation cooling units can be 5 A cushion of hot air forms below the
installed in an air conditioning strip or ceiling. The hot air cushion cannot
an external technical building. force its way into the cold aisle thanks
to isolation.
2 Air supply to the cold aisle via air outlet
grilles in the floor void. The feed air 6 Unimpeded suction of the exhaust air
quantity is calculated and regulated out of the air space. The separation
based on the cold load to be removed. enables high exhaust air temperatures,
therefore the overall equipment effi-
3 A cold air pool forms in the sealed cold ciency of the cooling units is maximised.
aisle according to the fresh air princi-
ple. The hardware components draw 7 The temperature neutrality of server
the required cooling air quantity from racks fitted with LCP climate compo-
this source. nents allows them to be positioned in
the room for expansion or extension
purposes.
8 Optimised use of the server room area
by use of sliding doors to further isolate
the cold aisle.
Rittal System Climate Control 231
Liquid cooling IT
Aisle containment – Application examples

Rittal cold aisle containment with


CRAC systems (cold aisle variant)

By using cold aisle containment, climate control of the room (in


conjunction with the CRAC system) may be optimised in terms of
energy efficiency and cooling output.
● High energy efficiency
● Increased cooling output per server enclosure
● Easily retro-fitted to existing systems
● Protection of your existing infrastructure

1
1 Aisle containment 4 IT chiller
(cold aisle variant) 5 Temperature-neutral expan- 4
2 CRAC systems sion, e.g. with LCP Smart 2
3 Water/water heat exchanger 3

Aisle containment with


LCP Inline (cold aisle variant)

In conjunction with the new LCP Inline, the cold aisle variant is a
further option for the efficient dissipation of high heat loads from
Liquid cooling IT

server enclosures.
● A raised floor is not required for climate control
● To accommodate higher heat loads per server enclosure
● Redundancies easily achieved
● Direct supply of cold air to your server and network components

2
1

1 Aisle containment 4 IT chiller


(cold aisle variant) 5 Temperature-neutral expan-
2 LCP Inline sion, e.g. with LCP Extend 4
3 Water/water heat exchanger
3

232 Rittal System Climate Control


Liquid cooling IT
Liquid Cooling Package Plus, Smart, Extend

Basic solutions

CRAC systems
with aisle containment

LCP Extend

LCP Inline
with aisle containment

LCP Standard/Smart
Product

LCP Plus

Cooling
Low Density Mid Density High Density requirements
The entry-level option The tailor-made The most powerful
for professional solutions for discerning solutions for high-end
IT climate control data centres data centres

LCP Plus
Functional principle:
Air/water heat exchanger, bayable with server racks based on TS 8
(H x D 2000 x 1200 mm). Complete unit with 30 kW useful cooling
output.
The separation of cooling and rack prevents water from penetrating
the server rack, and makes it very easy to assemble and service.
LCPs are easy to handle (max. 2 m) and may be transported in lifts
and through doors. The low weight means a minimal area load.

LCP Smart
Functional principle:
The LCP Smart draws in air at the rear of the server enclosure, cools
it, and blasts the cooled air back into the front part of the server
enclosure.
Differences compared with the LCP Standard:
● Fans may be individually exchanged with the system operational.
● Basic CMC as standard.

Liquid cooling IT
● Touchscreen display may be retrofitted.
● Shorter service times.
● Extended functionality of the monitoring and control technology/
software.
Optimum adaptability thanks to dynamic, continuous control of the
cold water volume flow.

LCP Extend
Functional principle:
Air/water heat exchanger for retrofitting to racks while operational.
The stand-alone unit replaces the rear door (for other brands on
request).
Mounted on the rear of the server enclosure and eases the pressure
on the room air-conditioning system.
Technical specifications:
● Up to 12 kW useful cooling output
Max. air volume 3000 m3/h.

Rittal System Climate Control 233


Enclosure heaters
Applications/assembly/electrical connection

Installation position
Heaters should always be installed in
an upright position.
Leave a distance of 50 mm at the top
and bottom to allow convection.
In order to increase efficiency,
where possible, heaters should always
be fitted in the lower part of the
enclosure.

Flow circuit effective ineffective


Installation position

Installation option for enclosure heaters


The device is attached vertically, i.e. with the connection
cable pointing downwards. The connection cable should be
tightly secured. In order to create the required convection, a
distance of at least 50 mm from components must be main-
tained above and below the device. The thermal safety clear-
ance from neighbouring components is at least 35 mm. Pro-
vided these distances are observed, an ambient temperature
of 65°C will not be exceeded.
Enclosure heaters are used to prevent the formation of con-
densation inside the enclosure and maintain a constant
minimum operating temperature (e.g. when the system is
switched off overnight). They achieve thermal outputs of
10 to 800 watts.
Enclosure heaters

Electrical connection According to IEC 6100-4-5, a fuse is to be provided by


Due to the particular characteristics of the PTC thermal ele- the customer for pulse loads in excess of 1000 V. The
ment, the startup current is approx. 1.8 A for around 0.5 sec. surface temperature of the aluminium section is regu-
A slow pre-fuse (gL) is therefore essential. lated automatically. A separate thermostat (SK 3110.000)
should be connected to control the room temperature. To
control the air humidity inside the enclosure, a hygrostat
(SK 3118.000) may be connected upstream.

234 Rittal System Climate Control


Monitoring

All the relevant parameters for the function and cooling

output of the climate control components are available

on the control desk for monitoring and control

purposes.

Master/slave operation
In open bayed enclosure systems which are not separate 7
6
from one another, cooling units and air/water heat exchang- 4
ers with Comfort control should always be used. These may
be placed in master/slave mode via bus cable SK 3124.100:
● Simultaneous activation and deactivation of the devices
● Parallel fault and door limit switch function
● Even temperature distribution across all sections of the 1
enclosure 3

1 Control cabinets 5 Door limit switch


2
2 Wall-mounted unit 6 Connection terminals 1 and
3 Roof-mounted unit
2 of the cooling unit
7 Master/slave unit 5
4 Comfort controller

Monitoring

Interface card Further information may be found in our assembly and oper-
The new interface board (SK 3124.200) is an extension for ating instructions, at
TopTherm-Plus cooling units and air/water heat exchangers www.rittal.com –> Products –> Product search
with Comfort controller; see page 179. In this way it is possi- –> SK 3124.200.
ble, e.g. to monitor a master/slave combination of up to Warnings and alarms from the interface board
10 cooling units. Control is achieved via standardised inter- ● Interior temperaure too ● Sensor failure, ambient
faces RS232 (DB9) or RS485, a PLC interface. RS422 (RJ 45 high temperature
jack) is the connection to the Rittal CMC-TC. Remote moni- ● Icing ● Sensor failure, icing
toring via TCP-IP, graphical interfaces for operation, evalua- ● High-pressure sensor sensor
tion and control, documentation, and connection to addi- ● Leakage ● Sensor failure, conden-
tional sensors for access control facilitates monitoring. ● Condenser/fan defect sate level
The extension card is built into a 1 U plastic housing. A volt- ● Evaporator coil/fan defect ● Sensor failure, internal
age supply of 24 V (DC) is required. This can be supplied ● Compressor defect temperature
from the CMC-TC via long-range power pack or externally ● Sensor failure, condenser ● Phase missing or incorrect
via a Kycon connector. temperature ● EEPROM defect

Rittal System Climate Control 235


Monitoring

Application example: 1
Master/slave operation and interface board
1 Control point/server room
2 Recooling system
2
3 Machining centre
4 Welding robot
4
3

2 4

Connection example: Master/slave Description:


operation The address of the master depends on the number of
attached slave units (09 = master with 9 slave units). The
with bus cable and interface board address of a slave device always begins with a 1. The sec-
1 Serial interface board, ond number represents the actual address. Up to a maxi-
Model No.: SK 3124.200 mum of 9 slave units may be operated with one master unit,
2 Serial interface cable whereby any unit may be a master. The maximum overall
length of all connected units is 50 m. Single-phase and
3 Master/slave BUS cable,
3-phase units may be connected.
Model No.: SK 3124.100
RTT = Rittal TopTherm-Plus cooling unit/
Air/water heat exchanger
X1 = Supply connection/door limit switch/alarms
X2 = Master/slave connection SUB-D 9-pole
X3 = Serial interface SUB-D 9-pole
St. = SUB-D connector 9-pole
Bu. = SUB-D jack 9-pole

CMC 1
2
Monitoring

RTT Adr.: 09 RTT Adr.: 11 RTT Adr.: 12 RTT Adr.: 19


Master Slave Slave Slave

X1 X1 X1 X1

X2 X3 X2 X3 X2 X3 X2 X3

St. X2 X3 St. St. X2 St. X2 St. X2

X2 X2 X2 X2 X2
Bu. St. Bu. St. Bu.
3

236 Rittal System Climate Control


Monitoring

Notes on connecting cooling units and air/water heat exchangers in the master/slave
combination
Only one unit may be configured as master; the address ID 3. Make the required changes to the master
must match the number of slave units. All slave units must 4. Make the connection between the RTT I/O unit
have different addresses, and the addresses must be in and the PU
ascending order without any gaps in between. – Message on the PU “Unit found”
If changes are made to the configuration of the master, 5. Wait 60 s then confirm
please proceed as follows: – RTT I/O unit is correctly displayed with all its slaves
1. Disconnect any existing connections in the Web
between the RTT I/O unit and the PU Configuration settings on the cooling unit master
– Timeout on the PU regarding the number of slaves must only be made if
2. Confirmation on the PU there is no supply voltage at the RTT I/O unit, neither
– Unit has been removed from the PU nor externally.

Enclosure Processing Unit II


monitoring system Programming cable
CMC-TC Connection cable
Power pack
The RTT I/O unit may be for sensor units
connected to the CMC-TC
system (Ethernet, TCPIP,
SNMP, HTTP). Connection cable
for power pack
Note:
For detailed information,
see Cat. 32, page 806.
Up to 4 sensor units

Monitoring

Rittal System Climate Control 237


Technical Details

Cooling with ambient air from page 240


Fan systems ....................................................................................240
Air/air heat exchangers...................................................................241

Cooling units from page 245


Modular climate control concept ....................................................245 Wall-mounted cooling units ............................................................ 247
Roof-mounted cooling units ............................................................246 Thermoelectric coolers ................................................................... 250

Liquid cooling IE from page 251


Air/water heat exchangers ..............................................................251
Cold Plate........................................................................................255
Recooling systems .........................................................................256

Liquid cooling IT from page 266


Chillers for IT cooling ......................................................................266
Water/water heat exchangers ........................................................267

Enclosure heaters from page 267


Enclosure heaters ..........................................................................267

Technical details

System accessories from page 268


Electric condensate evaporator......................................................268
Integrated louvres ...........................................................................268

Rittal System Climate Control 239


Technical details
Fan systems

Rack-mounted fans
for 482.6 mm (19˝), air throughput 320/480 m3/h Page 52

Rack-mounted fan Vario rack-mounted fan Vario rack-mounted fan


mounted between a pair of 482.6 mm mounted in subracks 84 HP mounted between a pair of 482.6 mm (19˝)
(19˝) mounting angles mounting angles

Centrifugal fans
Air throughput 320 m3/h Page 53
17
76.2
88

60
163
465.1

75
482.6 (19″)

380

Front grille

Roof-mounted fans
Air throughput 360 m3/h Page 54
Mounting cut-out

Without fan With fan 420 360


50

44
15

265
280
340

□ 260 x 340
Ø
8
250
345
Technical details

RTT roof-mounted fan and vent attachment


Air throughput (unimpeded air flow) 400/800 m3/h Page 54
Mounting cut-out

550 370 475 + 1


101
125

260 + 1

500 290
20

240 Rittal System Climate Control


Technical details
Fan systems/Air/air heat exchangers

Fan roof, modular, two-piece for TS/FR(i)


Air throughput per fan (unimpeded air flow) 160/180 mm3/h at 50/60 Hz Page 58

B1
For enclosures Cover plate Roof dimensions
B2 Model No.
Width Depth C D

3
Solid Vented B1 B2 T1 TS
mm mm
133

223.5
600 600 2102.180 2102.400 567.5 435 567.5 400 224 7826.366
36.5 600 800 2102.190 2102.410 567.5 435 767.5 400 424 7826.368
600 900 2102.190 2102.410 567.5 435 867.5 400 424 7826.369
600 1000 2102.190 2102.410 567.5 435 967.5 400 424 7826.360
T1

800 600 7885.100 7885.200 767.5 635 567.5 600 224 7826.486
D

800 800 7886.100 7886.200 767.5 635 767.5 600 424 7826.488
800 900 7886.100 7886.200 767.5 635 867.5 600 424 7826.489
800 1000 7886.100 7886.200 767.5 635 967.5 600 424 7826.480

B = Width
T = Depth

Air/air heat exchangers


Wall-mounted Page 62
SK 3129.800 External Mounting cut-out
mounting for external mounting
110
400 280

25
35
Mounting cut-out
Rear Side view for external and 350

295

380
internal mounting
200 147 164

x)
(8
75

13
Ø
36
1360

1360
130

210

(655)
159

340
135.5

1
378
400

1 110
0
Ø3

275
325

30.5
32.5 280

25
400

1 Optional cable gland

Technical details

Air/air heat exchangers


Roof-mounted Page 65

Rear Side view Mounting cut-out


for external and internal mounting

440 595 600


480
420
362

Ø 23 (2x)

1 2
440
400
360

320

Ø 7(4x)

62 301 45
50

Rittal System Climate Control 241


Technical details
Air/air heat exchangers

Air/air heat exchangers


Wall-mounted, railway-compatible version, specific thermal output 27 – 98 W/K Page 64
Mounting cut-out SK 3126.4xx
External mounting Installation with adjustable frame
127

280 282
244 60 = =

23
(66.5)
22.5

22.5

=
650
600

611

653
699
520
x)
(8
8
Ø
=

x)
(4
Ø7

255
328

Internal mounting
254 Adjustment options
107 8
7.5 1

60
57

37.5
17.5
215

60
60

M6
84.5
104.5

50
127
109.5

27.5
89.5

1.5 M6
650

624

254
30

7.5
42.5
22.5

21.5 105
362.5

74
118
75.5 105

1 Microcellular rubber seal EPDM, black 12 mm,


Ø 8 (8 x) as solid all-round rubber seal
254

Mounting cut-out SK 3128.4xx


External mounting Installation with adjustable frame
400 140
27.5 250 70 250
23
36.5

180
180

280
327

250

x)
Ø 40 (2
255
920
950

(8 x)
953
750
999

Ø 9.5
Technical details

385
345

250
327

160 20
30

50
402
448

Internal mounting
370
Adjustment options 1
7.5
10
30

70
27.5
47.5

Ø 250
365

8
(7 M6
x)
M6
50

160
92.5
112.5
70

27.5
140
112.5
92.5

M6
190.5
920

30
7.5
47.5
27.5

175
619

127
39.5
1 Microcellular rubber seal EPDM, black 12 mm,
175

198

as solid all-round rubber seal


28
39.5

242 Rittal System Climate Control


Technical details
Air/air heat exchangers

Air/air heat exchangers


Wall-mounted, railway-compatible version, specific thermal output 27 – 98 W/K Page 64
Mounting cut-out SK 3129.4xx
External mounting Installation with adjustable frame
400 150
250

23
25 250 70
25

210

280

210
327

250
Ø
9.5
)

255
x
(2

953
750
999
(8

920
950

40

x)
Ø

385
345

250
327

145 35
35

50 402
448
Internal mounting
370 1
Adjustment options 7.5

70
10
30

27.5
47.5

250
365

M6
M6

50
92.5
112.5
70

27.5
160

150
122.5
102.5

M6
30

7.5
190.5
920

57.5
37.5

180
619

127
1 Microcellular rubber seal EPDM, black 12 mm,
37 as solid all-round rubber seal
215
180
37

19.5

Mounting cut-out SK 3130.4xx


External mounting Installation with adjustable frame
400 150
280 70 402
65

200

210
210
395

380

280
x)
x)
1 (8
0 (1
Ø1
Ø4

260
1530

1480
1628
1580

1582
875

320
260
260

280

Technical details
340

275

200

250

Internal mounting 448


400
370
1
Adjustment options 7.5
x)

70
(6

27.5
47.5

250
11
Ø

M6
92.5
112.5

M6
70

50

320
27.5
150
122.5
102.5

M6
113

30
7.5
57.5
47.5

367
1558
1580

1 Microcellular rubber seal EPDM, black 12 mm,


as solid all-round rubber seal
924.5
965

x)
(2

97.5
8
Ø

205
205
215

200
67.5
62.5

370

Rittal System Climate Control 243


Technical details
Air/air heat exchangers

TopTherm air/air heat exchangers


Wall-mounted with controller, specific thermal output 17.5 W/K Page 63

External Internal Mounting cut-out Mounting cut-out


mounting mounting for external mounting for internal mounting

108 280
280 254
150 42
280 251 200

25
Ø 15 (2x)
550

550
518
492
550
501

524
266

Ø 8 (4x)

(230) 18 x 45°

Wall-mounted with controller, specific thermal output 30 – 60 W/K Page 63

External Internal Mounting cut-out Mounting cut-out


mounting mounting for external mounting for internal mounting
50
400
155 (175)
400 370
205 (225) 250 R6 (4x) 25
400
36.5

25 x 45°
235

280

345

Ø 9.5 (8x)
255
950

950

920
920
950

380
385
350

350
Ø 9.5 (4x)
15
25

Dimensions in brackets for 45 W/K and 60 W/K

Wall-mounted with controller, specific thermal output 90 W/K Page 63

External Internal Mounting cut-out Mounting cut-out


mounting mounting for external mounting for internal mounting
165
Technical details

400
400 370
400 215 50 280 324
22
35

Ø 12 (2x)
295

350
380

Ø 13 (8x)
1580
1580

1558

1580
1538
1554

376
875
260

320
Ø 13 (4x)
340

275

R6 (2x)

324
25

244 Rittal System Climate Control


Technical details
Modular climate control concept

Cooling modules
Useful cooling output 1500/2500 W Page 70

500 1500 W 2500 W


145
820

85 135
85 115
1561

1608
140

461 461

135
115
115/135

Section doors
Page 71

For enclosures 1200 mm


For enclosures Device position
600 mm wide 800 mm wide Left Right

592 792 592 592

Technical details
1777.5/1977.5

1777.5/1977.5
1777.5/1977.5
1777.5/1977.5
94

94
94
94

Rittal System Climate Control 245


Technical details
Roof-mounted cooling units

Roof-mounted cooling units Mounting cut-out


Useful cooling output 500/750 W Page 74
597
475 597 379

260
326
379

417

417
1
1 Condensate discharge 1/2˝, flexible

Ø 80 170
1

30
365 326

Useful cooling output 1000 W Page 75 Mounting cut-out


Useful cooling output 1100 W Page 76
597
Useful cooling output 1500/2000 W 490 597 475
Page 77 417
420
390

417
475

1 Condensate discharge 1/2˝, flexible


Ø 100 280

27
1
380 420

Useful cooling output 3000 W Page 76 Mounting cut-out


901
692 597 901
511.5
511.5
597
392

37

Ø 150 488.5
404
Technical details

Useful cooling output 3000/4000 W Page 78 Mounting cut-out

796
692 796 580
470
392
520
580

1 1

1 Condensate discharge 1/2˝,


flexible Ø 150 Ø 150
38.5

538 238

246 Rittal System Climate Control


Technical details
Wall-mounted cooling units

Wall-mounted cooling units


Mini in horizontal format, useful cooling output 300 W Page 83

External Internal Mounting cut-out Mounting cut-out


mounting mounting for external mounting for internal mounting
153
98
55
525

5.5
7.5
6

)
(4x

20
7.5
281
340
340

340
314
325
Ø

20
471 27 20
525 499 5.5
510 7.5
525

Useful cooling output 300 W Page 84

External Internal Mounting cut-out Mounting cut-out


mounting mounting for external for internal mounting
mounting
98 280
140 42 280 254
280 251 200

25
Ø 15 (2x)

550
518
492
550

524
550
501

266

Ø 8 (4x)

(230) 18 x 45°

Useful cooling output 500 W Page 84


Useful cooling output 750 W Page 85
External Partial Internal Mounting cut-out Mounting cut-out Mounting cut-out
Technical details

mounting internal mounting for external mounting for partial internal for internal
mounting mounting mounting
T3 T5 280
T1 T2 T4 280 280 254
262 254
15.5

280 200
20

25

Ø 19 (2x)
266
550
480

550
497
523

550
492
550

518
532

524

524

266 266

Ø 8 (4x) Ø 8 (4x) Ø 8 (4x)

(230) 18 x 45 (230) 18 x 45°

T1 T2 T3 T4 T5
500 W 210 100 110 164 42
750 W 280 125 155 235 42

Rittal System Climate Control 247


Technical details
Wall-mounted cooling units

Wall-mounted cooling units


Useful cooling output 1000/1500 W Page 87

External Partial Internal Mounting cut-out Mounting cut-out Mounting cut-out


mounting internal mounting for external mounting Partial internal for internal mounting
mounting mounting
105 155 400 400 400
50

36.5
400 210 250 370 370
260
330 R6 (4x) 25

235

280
345

2
25 x 45

25 x 45
Ø 9.5 (8x)

255
950
950

950

920
920
950
920

920
380 380

385
350
350

Ø 9.5 (4x) Ø 9.5 (4x)

25

15
Useful cooling output 2000/2500 W Page 89

External Partial Internal Mounting cut-out Mounting cut-out


mounting internal mounting1) for external mounting for partial internal mounting,
mounting internal mounting
145 245 400
400 370
400 295 150 50 280 320

20
35

R9.5 (2x)
310

350
380
550
1580

1558

1580
1540
1554
1580

Ø 13 (10x) 376
325
260

320
Ø 13 (4x)
340

275

R9.5 (2x)

320
25

1) For installation in 600 mm wide doors, move the mounting cut-out


from the centre of the door to the hinged side by at least 10 mm.

Useful cooling output 4000 W Page 90


Technical details

External Partial internal Mounting cut-out Mounting cut-out


mounting mounting for external mounting for partial internal mounting

500 340 500 500


145 195
380 362
25
45
330

380

440
1580

500

1550

1580
1530
1580

Ø 13 (10x) 474
375
164

440

Ø 13 (4x)
360

275
25

248 Rittal System Climate Control


Technical details
Wall-mounted cooling units

Wall-mounted cooling units


Useful cooling output 1500 W Page 88
(SK 3366.XXX and SK 3377.XXX)
External Internal Mounting cut-out Mounting cut-out
mounting mounting for external mounting for internal mounting
354
435 400

45
340

78.5

55
240
353
326

360
1500
1590

1510
354

360
354

49

260
353
Ø8
155
(10x)

165.5
45

382 354
85.5
140
12

205

Design NEMA 4x, useful cooling output 500 W Page 91

External mounting Mounting cut-out


for external mounting

298 285
185 262
19
12

259
173.5
190
172
620

620

220
70
170

143.5

Ø 8 (8x)

285 238
76

Design NEMA 4x, useful cooling output 1000/1500 W Page 91

External mounting Mounting cut-out


for external mounting
Technical details

358 405
38.5

245 250
250

280

345
255

Ø 9.5 (8x)
1020
1020

350
385
350

83
93

405 298

Rittal System Climate Control 249


Technical details
Wall-mounted cooling units/Thermoelectric cooler

Wall-mounted cooling units


Design NEMA 4x, useful cooling output 2000/2500 W Page 92

External mounting Mounting cut-out


for external mounting

388 405
275 280

37
310
350

380
550
1650
1650

Ø 13 (10x)

325
260

320

275
408

93

328
405

Thermoelectric cooler
Page 97

External Internal Mounting cut-out Mounting cut-out


mounting mounting for external mounting for internal mounting

155 100 55 1 1
125 100
6.5
Ø
Technical details

25
25

15 15
400

377

400

377
366
400

386
400

15 40
25
25

Ø
12
18

6.5
Ø
25

(12.5) 100 (12.5) 85


11.5

11.5

10

11
7

(8.5) 108 (8.5) 108


125 125
100

1 Outer contour of climate control unit


55

250 Rittal System Climate Control


Technical details
Air/water heat exchangers

Air/water heat exchangers


Roof-mounted, useful cooling output 2500 W Page 102
Roof-mounted, useful cooling output 4000 W Page 103

597
490 597 475

417
475

390
420

1 Condensate discharge 1/2˝


2 Cooling water connection 1/2˝
Ø 100 (4x)
27

280
380 1 2
420

Micro, wall-mounted, useful cooling output 300 W Page 104

Mounting holes Mounting cut-out 1 Cooling water connection


for internal mounting for external mounting 2 Condensate discharge

150
125
150
102
85 102
Ø7
(4x) 300
276
232
300
276
300

41

Ø7
1 2 (4x)
18
60
55
150

Wall-mounted, useful cooling output 600 W Page 105

Mounting holes Mounting cut-out 1 Condensate discharge 1/2˝


for internal mounting for external mounting
Technical details

2 Cooling water connection 1/2˝

200
200 160
100 200 150 150
30
50

Ø7
170

160
420

420
500

500
500

Ø7 34
4x
130
145

2 1 133
18
150
75 80

Rittal System Climate Control 251


Technical details
Air/water heat exchangers

Air/water heat exchangers


Wall-mounted, useful cooling output 1250 W Page 105
Mounting holes Mounting cut-out 1 Condensate discharge 1/2˝
for internal mounting for external mounting 2 Cooling water connection 1/2˝
200 175
100 200 140 140

24
11

315
475
164

920
920

950
950

170 15
x)
(4
7

80
Ø

126
2 1

96
18

19
Ø 7 (6x)
75

Wall-mounted, useful cooling output 500 W/1000 W Page 106 Mounting cut-out Mounting cut-out
for external mounting for internal mounting

90 90 140 140 250 250


280 280

49 14
External mounting

External mounting
Internal mounting

Internal mounting

91 14
520

520
550

550
506
550

550

15
1 1
15
22

256 280
280
1 50
140
90

1 Ø 6.5 (4 x for internal and external mounting)


70

29
15

2 1
21

50

1 Condensate discharge 1/2˝


2 Water connections 1/2˝
Technical details

252 Rittal System Climate Control


Technical details
Air/water heat exchangers

Air/water heat exchangers


Wall mounting, useful cooling output 2000 W/3000 W Page 107 Mounting cut-out Mounting cut-out
for external mounting for internal mounting
400 400
400 140 140 250 250

36.5

15

15

49 49
External mounting

Internal mounting
91 26

235

280
345

255
950

920
950

920
950
385
250
350

5
9.

9.
Ø

Ø
15

15
25
400

50
2
140
20

1
50

1 Condensate discharge 1/2˝


2 Water connections 1/2˝

Wall mounting, useful cooling output 5000 W Page 108 Mounting cut-out Mounting cut-out
for external mounting for internal mounting
450
410 450

x)
450 250 250

(4
350 350

0
335

9.
15

15

Ø
External mounting

49
Internal mounting

91 26

49
455
470

x)
(8
0
7.
Ø
1400

1400
1365
1400
455
681.5

Technical details
455

433.5

420
165

450

80
40
2
250
100

1 Condensate discharge 1/2˝


2 Water connections 1/2˝

Rittal System Climate Control 253


Technical details
Air/water heat exchangers

Air/water heat exchangers Adaptor frame


Wall-mounted, useful cooling output 7000 W Page 109 Page 109

450
451 417
433.5 380
350 40
300 450 350

30
15
1
433.5

442.5

442.5
392

400
530
417
442.5

442.5
1800

1655.1
Ø 8 (10x)

1740
1800
442.5

442.5
80 417
442.5

230

100

442.5
400
1 2
145

1 Bolts
M6 x 20
350 Ø 8 (10x)

1 Condensate discharge 1/2˝


2 Cooling water connection 1/2˝
Technical details

254 Rittal System Climate Control


Technical details
Cold Plate

Cold Plate
Page 112

SK 8616.610, SK 8616.630 SK 8616.810, SK 8616.830

94.5 62 62 62 62 62 94.5 70.5 62 62 62 62 62 62 62 62 62 70.5

37
37

31
243
325
325

399
399

272
272

1
1

31
55
50

55
37
37

18 18
475 675
25 25
499 699

SK 8616.600, SK 8616.620 SK 8616.800, SK 8616.820

94.5 62 62 62 62 62 94.5 70.5 62 62 62 62 62 62 62 62 62 70.5


10.5

10.5
31
243
325

325
399

399
378

378
272

1
1
31
50
25

51

55
57

55
37

37

21 18 18
10.5

10.5
675
475 21 20
699
499

1 Cooling water connection 1/4˝

Technical details

Rittal System Climate Control 255


Technical details
Recooling systems

Options for recooling systems

Upstream pipework, free from non-ferrous metals


Designed as a once-through cooler without tank

Hot gas bypass control in the cooling circuit

Fault signal with individual messages

Additional medium connections


Ambient temperature control

Tank (stainless steel 1.4301)


Heater in the tank (1000 W)

Water-cooled condenser
Pressure-sealed system

More powerful pump(s)


Open system with tank

Automatic tank filling

Filter mat monitoring


Special spray finish
Water filter/oil filter

Refrigerant R134a
Harting connector
Automatic bypass
Water level switch

Double pump unit


Special voltages
Manual bypass

Metal filter mat


Outdoor siting
Flow monitor

Base tray
Castors
Recooling systems Mini and Mini for wall mounting
SK 3318.600  – – – ▫ – –  – ▫ ▫ – – ▫ – – ▫ – ▫ ▫ ▫ ▫  –  – – –
SK 3318.610 –  – – ▫ – –  – ▫ ▫ – – ▫ – – ▫ – ▫ ▫ ▫ ▫  –  – – –
SK 3319.600  – – – ▫ – –  – ▫ ▫ – – ▫ – – ▫ – ▫ ▫ ▫ ▫  –  – – –
SK 3319.610 –  – – ▫ – –  – ▫ ▫ – – ▫ – – ▫ – ▫ ▫ ▫ ▫  –  – – –
SK 3320.600 –  – ▫ ▫ – –  – ▫ ▫ – – ▫ ▫ ▫ ▫ – ▫ – ▫ ▫  –  – – –
SK 3334.600 –  – ▫ ▫ – –  – ▫ ▫ – – ▫ ▫ ▫ ▫ – ▫ – ▫ ▫  –  – – –
SK 3334.660 –  – ▫ ▫ – –  – ▫ ▫ – – ▫ ▫ ▫ ▫ – ▫ – ▫ ▫  –  – – –
SK 3360.100 –  – – ▫ – ▫  – ▫ ▫ – – ▫ – ▫ ▫ – ▫ – ▫ –  –  – – –
SK 3360.250 –  – – ▫ – ▫  – ▫ ▫ – – ▫ – ▫ ▫ – ▫ – ▫ –  –  – – –
SK 3360.470 –  – ▫ ▫ – ▫  – ▫ ▫ – – ▫ – ▫ ▫ – ▫ – ▫ –  –  – – –
Recooling systems in floor-standing enclosure and industrial enclosure
SK 3336.100 –  ▫ ▫ ▫ ▫  ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫  – – –  ▫
SK 3336.200 –  ▫ ▫ ▫ ▫  ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫  – – –  ▫
SK 3336.300 –  ▫ ▫ ▫ ▫  ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫  – – –  ▫
SK 3336.500 –  ▫ ▫ ▫ ▫  ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫  – – –  ▫
SK 3336.600 –  ▫ ▫ ▫ ▫  ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫  – – –  ▫
SK 3336.650 –  ▫ ▫ ▫ ▫  ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ – ▫ ▫  – – –  ▫
SK 3336.700 –  ▫ ▫ ▫ ▫ ▫  ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ – – – –  ▫
SK 3336.710 –  ▫ ▫ ▫ ▫ ▫  ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ – – – –  ▫
SK 3336.720 –  ▫ ▫ ▫ ▫ ▫  ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ – – – –  ▫
SK 3336.730 –  ▫ ▫ ▫ ▫ ▫  ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ – – – –  ▫
SK 3336.740 –  ▫ ▫ ▫ ▫ ▫  ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ – – – –  ▫
SK 3336.750 –  ▫ ▫ ▫ ▫ ▫  ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ – – – –  ▫
SK 3339.100 –  ▫ ▫ ▫ ▫ ▫  ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ – – – –  ▫
SK 3339.200 –  ▫ ▫ ▫ ▫ ▫  ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ – – – –  ▫
Recooling systems in a floor standing enclosure for oil
SK 3337.200 – ▫  ▫ ▫ ▫ – ▫ ▫ – – – ▫ ▫  – ▫ ▫ ▫ ▫ ▫ ▫  – – – ▫ ▫
SK 3337.300 – ▫  ▫ ▫ ▫ – ▫ ▫ – – – ▫ ▫  – ▫ ▫ ▫ ▫ ▫ ▫  – – – ▫ ▫
SK 3337.500 – ▫  ▫ ▫ ▫ – ▫ ▫ – – – ▫ ▫  – ▫ ▫ ▫ ▫ ▫ ▫  – – – ▫ ▫
Technical details

SK 3337.600 – ▫  ▫ ▫ ▫ – ▫ ▫ – – – ▫ ▫  – ▫ ▫ ▫ ▫ ▫ ▫  – – – ▫ ▫
SK 3337.650 – ▫  ▫ ▫ ▫ – ▫ ▫ – – – ▫ ▫  – ▫ ▫ ▫ – ▫ ▫  – – – ▫ ▫
SK 3337.700 – ▫  ▫ ▫ ▫ – ▫ ▫ – – – ▫ ▫  – ▫ ▫ ▫ ▫ ▫ ▫ – – – – ▫ ▫
SK 3337.710 – ▫  ▫ ▫ ▫ – ▫ ▫ – – – ▫ ▫  – ▫ ▫ ▫ ▫ ▫ ▫ – – – – ▫ ▫
SK 3337.720 – ▫  ▫ ▫ ▫ – ▫ ▫ – – – ▫ ▫  – ▫ ▫ ▫ ▫ ▫ ▫ – – – – ▫ ▫
SK 3337.730 – ▫  ▫ ▫ ▫ – ▫ ▫ – – – ▫ ▫  – ▫ ▫ ▫ ▫ ▫ ▫ – – – – ▫ ▫
SK 3337.740 – ▫  ▫ ▫ ▫ – ▫ ▫ – – – ▫ ▫  – ▫ ▫ ▫ ▫ ▫ ▫ – – – – ▫ ▫
SK 3337.750 – ▫  ▫ ▫ ▫ – ▫ ▫ – – – ▫ ▫  – ▫ ▫ ▫ ▫ ▫ ▫ – – – – ▫ ▫
Recooling systems in the TS 8 Top enclosure system
SK 3335.060 –  – ▫ ▫ ▫  ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3335.075 –  – ▫ ▫ ▫  ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3335.100 –  – ▫ ▫ ▫  ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3335.120 –  – ▫ ▫ ▫  ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3335.150 –  – ▫ ▫ ▫  ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3335.200 –  – ▫ ▫ ▫  ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3335.250 –  – ▫ ▫ ▫  ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
 Standard ▫ Optional

256 Rittal System Climate Control


Technical details
Recooling systems

Options for recooling systems

Hot gas bypass control in the cooling circuit

Ambient temperature control

Fault signal “Filter mat dirty”

Immersion depth 1000 mm


Immersion depth 650 mm

Immersion depth 750 mm

Immersion depth 850 mm


Water-cooled condenser

Control voltage 24 V DC

Liquid injection valve


Special spray finish
Harting connector

Special voltages
Radial fan

Immersible recooling systems


SK 3338.020 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3338.040 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3338.060 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3338.080 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3338.100 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3338.120 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3338.140 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3338.160 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3338.180 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3338.200 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3338.220 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3338.240 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3338.260 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3338.280 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3338.300 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3338.320 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3338.340 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3338.360 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3338.500 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3338.520 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3338.540 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3338.560 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3338.580 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3338.600 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3338.620 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3338.640 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3338.660 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3338.680 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3338.700 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3338.720 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
Technical details

SK 3338.740
SK 3338.760 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3338.780 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3338.800 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3338.820 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
SK 3338.840 ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
▫ Optional

Rittal System Climate Control 257


Technical details
Recooling systems

Recooling systems for water


Mini, cooling output 1/1.5 W Page 118
Key to the Characteristic curves of pump
diagram opposite: Layout diagram Model No. SK
1 Compressor 3318.600/3318.610/
5 Condenser 5 3319.600/3319.610
10 Condenser fan
50 Hz
15 Evaporator coil 70 P
35
10 25
20 Expansion valve 30
25 Filter dryer 1 25
35 Filling 20 20
45 Vent valve 15 H
15
50 Temperature sensor 10
55 Pump 45 5
60 Flow monitor 0
60 S 0.5 2 4 6 8
61 Overpressure valve .
35 Q
65 Pressure relief valve/ 55
alternatively tank
70 High-pressure switch 60 Hz
65 61 T 50
35
30

25

20
Note: H
15
With an externally lockable cooling cycle, a
bypass (overpressure valve) should be provided 10

in the external water pipes. 5

0
5 6 7 8 9
.
Q
H. = Delivery head H [m]
Q = Delivery flow Q [l/min]

Mini, cooling output 3/4.5 kW Page 119


Mini, cooling output 6 kW Page 120
Key to the Characteristic curves of pump
diagram opposite: Layout diagram Model No. SK
1 Compressor 3320.600/3334.600/3334.660
5 Condenser 5
10 Condenser fan 50 Hz
40
15 Evaporator coil
70 P
20 Expansion valve 10 25 30
25 Filter dryer
30 Tank 1 H 20
35 Filling 20
10
40 Tank drain
Technical details

15
46 Water level switch, optional 46 0
50 Temperature sensor 0 20 40 60 80
.
50 Q
55 Pump
60 Flow monitor 35

70 High-pressure switch
60 Hz
50
30
40 40
60 S

30
H
55 20

10

0
0 20 40 60 80
.
Q
Note:
H. = Delivery head H [m]
With an externally lockable cooling cycle, a Q = Delivery flow Q [l/min]
bypass (overpressure valve) should be provided
in the external water pipes.

258 Rittal System Climate Control


Technical details
Recooling systems

Recooling systems for water


Power Fluid Cooler, cooling output 7.5 kW Page 121
Power Fluid Cooler, cooling output 10 to 59 kW Page 122
Key to the Characteristic curves of pump
diagram opposite: Layout diagram Model No. SK 3234.090
1 Compressor
5 Condenser 10 50 Hz
40
10 Condenser fan
15 Evaporator coil 30
20 Expansion valve 5 70
23
21 Inspection glass 80 H 20
22 Magnetic valve 1
25 10
23 Liquid collector 71
21
25 Filter dryer 0
30 Tank 0 20 40 60 80
.
22 20 35 Q
31 Manometer 15 31
60 30 55
48
35 Filling 81
40 Tank drain 40

48 Level indicator
55 Pump Note:
60 Flow monitor (optional) With an externally lockable cooling cycle, a
70 High-pressure switch bypass (overpressure valve) should be provided
in the external water pipes.
71 Low-pressure switch
80 Thermostat
81 Anti-frost thermostat

Model No. SK Model No. SK Model No. SK Model No. SK


3234.100/.110/.120 3234.130/.140/.150 3234.160/.170 3234.180/.190

50 Hz 50 Hz 50 Hz 50 Hz
24 36 26 36
22 34
24 34
32
20 32
30 22
18 28 30
H
16
H 26 H 20 H
28
24 18
14 26
22
12 16 24
20
10 18 14 22
20 35 50 65 80 20 40 60 80 100 35 50 80 95 120 140 160 80 90 110 130 160 180 210 250
. . . .
Q Q Q Q

H. = Delivery head H [m]


Q = Delivery flow Q [l/min]

Technical details

Rittal System Climate Control 259


Technical details
Recooling systems

Recooling systems for water


In floor-standing enclosure, cooling output 2.1 to 7.7 kW Page 123
Key to the Characteristic curve of pump
diagram opposite: Layout diagram Model No. SK
1 Compressor 3336.100/3336.200/3336.300/
5 Condenser 5 3336.500/3336.600/3336.650
10 Condenser fan
P 70
16 Multi-coil vaporiser 50 Hz
35
19 Capillary tube/expansion valve1)
10
25 Filter dryer 80
25 30
30 Tank 1
31 Manometer H 25
35 Filling
35 20
40 Tank drain
19 46
46 Level monitor/float-actuated switch
0
48 Level indicator 48 20 30 40 50 60
16 30 55 .
55 Pump 31 Q
40
70 High-pressure switch1) H. = Delivery head H [m]
Q = Delivery flow Q [l/min]
80 Thermostat
1) from SK 3336.500
Note:
With an externally lockable cooling cycle, a
bypass (overpressure valve) should be provided
in the external water pipes.

In floor-standing enclosure, cooling output 10 to 36 kW Page 124


Key to the Characteristic curves of pump
diagram opposite: Layout diagram Model No. SK
1 Compressor 3336.700/3336.710/3336.720
5 Condenser 10
10 Condenser fan 50 Hz
40
15 Evaporator coil
20 Expansion valve 5 70 35
23
21 Inspection glass 80
Magnetic valve 1
22 H 30
25
23 Liquid collector 71
21 25
25 Filter dryer
30 Tank 20
Technical details

22 20 35 20 35 50 65 80
31 Manometer 15 31
30 55 .
60 48 Q
35 Filling
40 Tank drain 40

48 Level indicator
55 Pump Note: Model No. SK
60 Flow monitor With an externally lockable cooling cycle, a 3336.730/3336.740/3336.750
70 High-pressure switch bypass (overpressure valve) should be provided
in the external water pipes. 50 Hz
71 Low-pressure switch 38
80 Thermostat 36

34

H 32
30

28

26
20 40 60 80
.
Q

H. = Delivery head H [m]


Q = Delivery flow Q [l/min]

260 Rittal System Climate Control


Technical details
Recooling systems

Recooling systems for water


Power Fluid Cooler, cooling output 68 to 209 kW Page 125
Key to the
diagram opposite: Layout diagram
1 Compressor with oil sump heater
2 Duo pressure monitor LP/HP 3 3
3 Condenser with fan
6 Expansion valve
7 Inspection glass 2 2
8 Magnetic valve
9 9
9 Filter dryer
10 Evaporator coil
12 Flow monitor 7 7
1 8 1 8
13 Thermostat 6 6
14 Draining
17 Manometer
18 Pump
19 Return IN
13
20 Inlet OUT
21 Tank 19
35 Filling 10
35 50
48 Level indicator
50 Temperature sensor
12 18 17
48

21
20

14

Note:
With an externally lockable cooling cycle, a
bypass (overpressure valve) should be provided
in the external water pipes.

Characteristic curves of pump


Model No. SK Model No. SK Model No. SK
3234.200/.210/.220/.230 3234.240/.250/.260/.270 3234.280

50 Hz 50 Hz 50 Hz
38 32 44
36 30 42
34 28 40
32 38
30 26 36
28 24 34
H 26 H 22 H 32
24 20 30
22 18 28
20 26
18 16 24
16 14 22
Technical details

14 12 20
100 150 200 250 300 400 250 300 400 500 600 700 800 250 300 400 500 600 700 800
. . .
Q Q Q
H. = Delivery head H [m]
Q = Delivery flow Q [l/min]

Rittal System Climate Control 261


Technical details
Recooling systems

Recooling systems for water


Power Fluid Cooler, cooling output 271 to 502 kW Page 126
Key to the
diagram opposite: Layout diagram
1 Compressor with oil sump heater
3 3
2 Duo pressure monitor LP/HP
3 Condenser with fan
6 Expansion valve
2 2
7 Inspection glass
8 Magnetic valve 9 9
9 Filter dryer
10 Evaporator coil
7 7
11 Safety assembly 1 8 1 8
12 Flow monitor 6 6

13 Thermostat
14 Draining/filling
15 Pressure relief valve
17 Manometer 13

18 Pump
19 Return IN 19
10
20 Inlet OUT
21 Tank
15

12 11 17

FC 18

21 20

14

Note:
With an externally lockable cooling cycle, a
bypass (overpressure valve) should be provided
in the external water pipes.

Characteristic curves of pump


Model No. SK Model No. SK
3234.290/.300/.310 3234.320/.330/.340

50 Hz 50 Hz
52 52
50 50
48 48
46 46
44 44
42 42
H 40 H 40
38 38
36 36
34 34
32 32
30 30
Technical details

28 28
250 300 400 500 600 700 800 500 600 700 800 1000 1200 1400
. .
Q Q

H. = Delivery head H [m]


Q = Delivery flow Q [l/min]

262 Rittal System Climate Control


Technical details
Recooling systems

Recooling systems for water


In TS 8 Top enclosure system, cooling output 6/7.5 kW Page 127
Key to the Characteristic curve of pump
diagram opposite: Layout diagram Model No. SK
1 Compressor 3335.060/3335.075
5 Condenser 10
10 Condenser fan 50 Hz
5 28
16 Multi-coil vaporiser
23
20 Expansion valve 24
21 Inspection glass
23 Liquid collector 25 H
20

25 Filter dryer
70 16
30 Tank
20
31 Manometer 1
12
21 20 30 40 50 60
33 Fixed pump bypass .
Q
35 Filling
H. = Delivery head H [m]
40 Tank drain Q = Delivery flow Q [l/min]
35 31
16
47 Level switch 47 33
55 Pump
80
70 High-pressure switch
80 Thermostat 40
30 55

In TS 8 Top enclosure system, cooling output 10 to 25 kW Page 128


Key to the Characteristic curves of pump
diagram opposite: Layout diagram Model No. SK
1 Compressor 3335.100/3335.120/3335.150
5 Condenser 10
10 Condenser fan 50 Hz
5 44
16 Multi-coil vaporiser
23 40
20 Expansion valve
36
21 Inspection glass
32
23 Liquid collector 25 H
28
25 Filter dryer
70 24
30 Tank 20
20
31 Manometer 1
16
21 10 20 30 40 50
33 Fixed pump bypass .
Q
35 Filling
40 Tank drain 31
16 35
47 Level switch 47 33
55 Pump Model No. SK
80 3335.200/3335.250
70 High-pressure switch
Technical details

80 Thermostat 40
30 55 50 Hz
50

44

38
H
32

26

20
30 60 90 120 150
.
Q
H. = Delivery head H [m]
Q = Delivery flow Q [l/min]

Rittal System Climate Control 263


Technical details
Recooling systems

Recooling systems for water


Mini, for wall mounting, cooling output 1/2.5/4 kW Page 129
Key to the Characteristic curves of pump
diagram opposite: Layout diagram Model No. SK
1 Compressor 3360.100/3360.250/3360.470
5 Condenser 5
10 Condenser fan
15 Evaporator coil 70 P 50 Hz
10 25 30
20 Expansion valve
25 Filter dryer 1
20 20
30 Tank
15
35 Filling 46 H
40 Tank drain 50 10
46 Water level switch, optional 35
50 Temperature sensor 0
55 Pump 30 0 10 20 30 40
40 .
60 S Q
60 Flow monitor
70 High-pressure switch 55
60 Hz
40

30

Note:
With an externally lockable cooling cycle, a H 20
bypass (overpressure valve) should be provided
in the external water pipes. 10

0
0 10 20 30 40
.
Q

H. = Delivery head H [m]


Q = Delivery flow Q [l/min]
Technical details

264 Rittal System Climate Control


Technical details
Recooling systems

Recooling systems for oil


In floor-standing enclosure, cooling output 2.5 to 8 kW Page 130
Key to the
diagram opposite: Layout diagram
1 Compressor 32 Automatic bypass valve
5 Condenser 56 Oil pump 5
10 Condenser fan 57 Motor for oil pump
P 70
15 Evaporator coil 70 High-pressure switch1)
19 Capillary tube/expansion valve1) 80 Thermostat 10
80
25 Filter dryer 81 Anti-frost thermostat 25 1
31 Manometer
1) from SK 3337.500 81
19 31 56

15 32
57

In floor-standing enclosure, cooling output 11 to 26 kW Page 131


Key to the
diagram opposite: Layout diagram
1 Compressor 31 Manometer
5
5 Condenser 32 Automatic bypass valve
10 Condenser fan 56 Oil pump 70
15 Evaporator coil 57 Motor for oil pump 23 10
80
20 Expansion valve 70 High-pressure switch
1
21 Inspection glass 71 Low-pressure switch
25
22 Magnetic valve 80 Thermostat 81 71
21
23 Liquid collector 81 Anti-frost thermostat 31
56
25 Filter dryer
22 20 15 32
57 M

Immersible recooling systems for oil/emulsion


2.4 – 78 kW cooling output Page 132 – 134 Technical details

Key to the
diagram opposite: Layout diagram
1 Compressor 25 Filter dryer
5 Condenser 30 Tank, to be supplied by the 5
25 70
10 Condenser fan customer
80
21 10
15 Evaporator coil
50 Temperature sensor
Expansion valve
70 High-pressure switch 23
20 1
21 Inspection glass
71 Low-pressure switch
71
22 Magnetic valve
80 Thermostat
Liquid collector
82 Stirrer
23 22 20 82 50
30

15

Rittal System Climate Control 265


Technical details
Recooling systems for IT cooling

Recooling systems for IT cooling


15 – 123 kW cooling output Page 148
Key to the
diagram opposite: Layout diagram
1 Compressor with oil sump heater 3

2 Duo pressure monitor LP/HP


22
3 Condenser with fan
4 Non-return valve 2
5 Pressure sensor
9
6 Expansion valve
7 Inspection glass 1

8 Magnetic valve 7
8
9 Filter dryer 6
10 Evaporator coil
11 Safety assembly 13
12 Flow monitor Controller
13 Thermostat
14 Draining/filling 19
15 Pressure relief valve
10
16 Bypass valve
5
17 Manometer FU 16
15
18 Pump PA
4
12 11 17
19 Return IN
FC PI
20 Inlet OUT
20
21 Tank 21
18
22 Refrigerant collector 4
14 5

PA

FU

Cooling output 145 to 462 kW Page 149


Key to the
diagram opposite: Layout diagram
1 Compressor with oil sump heater 3 3
2 Duo pressure monitor LP/HP
3 Condenser with fan
4 Non-return valve 2 2
5 Pressure sensor
9 9
6 Expansion valve
7 Inspection glass
8 Magnetic valve
Technical details

7 7
1 8 1 8
9 Filter dryer
6 6
10 Evaporator coil
11 Safety assembly
12 Flow monitor
13
13 Thermostat 5
FU Controller
14 Draining/filling
4 PA 19
15 Pressure relief valve
16 Bypass valve 10
17 Manometer
18 Pump 18 16
15 4 5
19 Return IN
12 11 17
20 Inlet OUT PA

21 Tank FC PI
FU 20
21

14

266 Rittal System Climate Control


Technical details
Water/water heat exchangers/enclosure heaters

Water/water heat exchangers


Page 153

Layout diagram

20
2 4 21
2 1
Option B 5
Option C
28 9
16
8
22 25

Option A
10 10
10 10 18
2 1 4

3 Option E

10
23
13
10 10

10 2
11 10 10
1
12
7 10 3
24 10
10
M 6 + 19
7 10 10 10
1 2

10 15 10 11 + 18 9
Key to the 2
diagram opposite:
1 Temperature sensor 15 Automatic bypass valve Option D

2 Pressure transmitter 16 Emergency water supply heat 17


3 Differential pressure monitoring exchanger
4 Flow gauge 17 Water tank 26

5 Extension tank 18 Magnetic filter


7 14 10
6 Speed controlled pump 19 Standard pump
27
7 Non-return valve 20 Customer
8 Safety valve 21 Rittal
9 Automatic bleed system 22 Emergency water supply on
10 Shut-off valve 23 Primary on (onsite)
11 Water filter 24 Primary off
12 3-way valve 25 Secondary on (LCP)
13 Plate-type heat exchanger 26 Secondary off
14 Pressure reduction valve 27 Filling
28 Emergency water supply off

Enclosure heaters Without fan


Continuous thermal output 10 – 800 W Page 169 Model No. SK W (B) mm H mm D (T) mm
Technical details

3105.110 81 123 49
Without fan With fan 3106.120 81 173 49
3115.130 102 155 60
B
B 3116.140 102 225 60
3107.150 102 260 60
3107.160 140 205 80
3102.170 140 250 80

With fan
H

Model No. SK W (B) mm H mm D (T) mm


H

3105.210 142 170 101


3105.220 142 170 101
3105.230 142 170 101
3105.180 142 170 101
T
T

3105.190 142 170 101


3105.200 142 170 101

Rittal System Climate Control 267


Technical details
System accessories

Electronic condensate evaporator


Page 192
SK 3301.560/.580 SK 3301.570/.590
258 378
Ø

Ø
6

6
132.5

132.5
125

125
42

42
280 400

1 1
Ø
60

258 378
50

6
25
6
Ø
25

75 2 45

2 3 3

1 Condensate hose 1 Condensate hose SK 3301.612


SK 3301.608 for SK 3302.XXX 2 Suggestion for position of cable entry
SK 3301.610 for SK 3303.XXX
3 Hose
2 Suggestion for position of cable entry
Length as required
3 Hose
Length as required

Integrated louvres
Page 183

SK 2541.235 SK 2542.235 SK 2543.235


Technical details

A A A
140 190 310

4.5 4.5 4.5


10

100
10

110

40
80

10

110
50
90

90

50

150 1.5
100 1.5 270 1.5
210 8
160 8 330 8
B
B B

268 Rittal System Climate Control


Notes

Notes

Rittal System Climate Control 269


Overview of products and
approvals
Cooling with ambient air from page 272
Fan-and-filter units ..........................................................................272 Tangential fans ............................................................................... 274
EMC fan-and-filter units ..................................................................273 RTT roof-mounted fan and vent attachment for TS......................... 274
Rack-mounted fans ........................................................................273 Roof-mounted fans ......................................................................... 275
Vario rack-mounted fans .................................................................274 Air/air heat exchangers................................................................... 276

Cooling units from page 277


Cooling modules .............................................................................277 Wall-mounted cooling units ........................................................... 279
Section doors ..................................................................................277 Thermoelectric coolers ................................................................... 284
Roof-mounted cooling units ............................................................278

Liquid cooling IE from page 284


Air/water heat exchangers, roof-mounted .....................................284 Recooling systems for water .......................................................... 287
Air/water heat exchangers, wall-mounted .....................................284 Recooling systems for oil ................................................................ 290
Direct Cooling Package .................................................................286 Immersible recooling systems for oil .............................................. 290
Immersible recooling systems for emulsion ................................... 291

Liquid cooling IT from page 292


CRAC systems ................................................................................292 Chillers for IT cooling ...................................................................... 295
Aisle containment............................................................................293 Water/water heat exchangers ......................................................... 295
Liquid Cooling Package..................................................................293

Outdoor climate control from page 296


Cooling units for CS modular enclosures .......................................296 Climate control units for Toptec CR ................................................ 297 Overview of products and approvals
Heat exchangers for CS modular enclosures.................................296

Enclosure heaters from page 297


Enclosure heaters ..........................................................................297

Rittal System Climate Control 271


Overview of products and approvals

System climate control creates the correct Enhanced operational reliability and a longer
ambient conditions for every application, service life for electronics
particularly for sensitive electronics. ● Cooling with ambient air
A broad selection of cooling units, recooling ● Cooling units
systems, heat exchangers, fan-and-filter units ● Liquid cooling IE
and enclosure heaters protects against adverse ● Liquid cooling IT
physical and thermal influences. ● Outdoor climate control
This is supplemented by a versatile range of ● Enclosure heaters
accessory components.
With a full advisory service and its PC software Detailed information
may be found on pages 41 – 169
package Rittal Therm, Rittal will help you to select and on our website at www.rittal.com
the correct climate control unit to optimally suit
your requirements. The latest status of approvals
may be found on our website at: www.rittal.com

Fan-and-filter units
Air throughput Voltage Model No. SK Approvals
Page
unimpeded air flow V, Hz RAL 7035 UL CUL DIN GS CSA
230, 50/60 3321.107   44
20/25 m3/h
115, 50/60 3321.117   44
24 (DC) 3321.027   44
20 m3/h
48 (DC) 3321.0471)   44
230, 50/60 3322.107    44
55/66 m3/h
115, 50/60 3322.117    44
24 (DC) 3322.027    44
55 m3/h
48 (DC) 3322.0471)   44
230, 50/60 3323.107    45
105/120 m3/h
115, 50/60 3323.117    45
24 (DC) 3323.027    45
105 m3/h
48 (DC) 3323.0471)   45
230, 50/60 3324.107    45
180/160 m3/h
115, 50/60 3324.117    45
24 (DC) 3324.027    45
180 m3/h
48 (DC) 3324.0471)   45
230, 50/60 3325.107    46
230/265 m3/h
115, 50/60 3325.117    46
24 (DC) 3325.027    46
230 m3/h
48 (DC) 3325.0471)   46
  
Overview of products and approvals

230, 50/60 3326.107 47


550/600 m3/h
115, 50/60 3326.117    47
230, 50/60 3327.107   47
700/720 m3/h 115, 50/60 3327.117   47
400/460, 3~, 50/60 3327.147   47
1) Delivery times available on request.

272 Rittal System Climate Control


Overview of products and approvals

Fan-and-filter units – EMC


Air throughput Voltage Model No. SK Approvals
Page
unimpeded air flow V, Hz RAL 7035 UL CUL DIN GS CSA
230, 50/60 3321.607   48
20/25 m3/h
115, 50/60 3321.6171)   48
230, 50/60 3322.607   48
55/66 m3/h
115, 50/60 3322.6171)   48
230, 50/60 3323.607    48
105/120 m3/h
115, 50/60 3323.6171)    48
230, 50/60 3324.607    49
180/160 m3/h
115, 50/60 3324.6171)    49
230, 50/60 3325.607    49
230/265 m3/h
115, 50/60 3325.617    49
230, 50/60 3326.607   49
550/600 m3/h
115, 50/60 3326.6171)   49
230, 50/60 3327.607   49
700/720 m3/h
115, 50/60 3327.6171)   49
1) Delivery times available on request.

Rack-mounted fans
Air Distance Approvals
throughput No. of between Voltage Model No.
Page
unimpeded fans axes V, Hz SK UL CUL DIN GS VDE
air flow mm
250 m3/h 3 85 36 (DC) – 72 (DC) 9769.0021) 52
2 85 24 (DC) 3340.0241)    52
320 m3/h 2 85 115 (AC), 50/60 3340.1151)    52
2 85 230 (AC), 50/60 3340.230    52
3 85 24 (DC) 3341.0241)    52
3 105 24 (DC) 3342.024    52
3 85 115 (AC), 50/60 3341.115    52
3 105 115 (AC), 50/60 3342.1151)    52
480 m3/h 3 85 230 (AC), 50/60 3341.230    52
3 105 230 (AC), 50/60 3342.230    52
24 (DC)
3 105 115 – 230 (AC), 3342.500    52
50/60

Overview of products and approvals


1) Delivery times available on request.

Rittal System Climate Control 273


Overview of products and approvals

Vario rack-mounted fan


Air Distance Approvals
throughput No. of between Voltage Model No.
Page
unimpeded fans axes V, Hz SK UL CUL DIN GS VDE
air flow mm
2 85 24 (DC) 3350.0241) 䡲 䡲 䡲 52
320 m3/h 2 85 115 (AC), 50/60 3350.1151) 䡲 䡲 䡲 52
2 85 230 (AC), 50/60 3350.2301) 䡲 䡲 䡲 52
3 85 24 (DC) 3351.0241) 䡲 䡲 䡲 52
3 105 24 (DC) 3352.0241) 䡲 䡲 䡲 52
3 85 115 (AC), 50/60 3351.1151) 䡲 䡲 䡲 52
3 105 115 (AC), 50/60 3352.1151) 䡲 䡲 䡲 52
480 m3/h 3 85 230 (AC), 50/60 3351.230 䡲 䡲 䡲 52
3 105 230 (AC), 50/60 3352.230 䡲 䡲 䡲 52
24 (DC)
3 105 115 – 230 (AC), 3352.500 䡲 䡲 䡲 52
50/60
1) Delivery times available on request.

Tangential fans
Air throughput Dimensions Approvals
Voltage
unimpeded WxHxD Model No. SK Page
V, Hz UL CUL DIN GS
air flow mm
115, 50/60 3145.000 53
320 m3/h 482.6 x 87.2 x 158
230, 50/60 3144.000 53
Overview of products and approvals

RTT roof-mounted fan and vent attachment


for TS
Required Approvals
Air throughput
Voltage mounting cut-out Model No.
unimpeded Page
V, Hz WxD SK UL CUL DIN GS CSA
air flow
mm
115, 50/60 475 x 260 3149.410 54
230, 50/60 475 x 260 3149.420 54
400 m3/h
400, 3~, 50/60
475 x 260 3149.440 54
460, 3~, 60
115, 50/60 475 x 260 3149.810 54
230, 50/60 475 x 260 3149.820 54
800 m3/h
400, 3~, 50/60
475 x 260 3149.840 54
460, 3~, 60
Without motor 490 x 390 8801.380 54

274 Rittal System Climate Control


Overview of products and approvals

Roof-mounted fans
Air throughput Required Approvals
Voltage
unimpeded mounting cut-out Model No. SK Page
V, Hz UL CUL DIN GS CSA
air flow W x D mm
230, 50/60 345 x 265 3149.007 54
360 m3/h
115, 50/60 345 x 265 3169.007 54
Without fan motor 345 x 265 3148.007 54

For TS/FR(i) for the office sector


Air Design Approvals
Dimensions
throughput Voltage with without Model No.
WxHxD Page
unimpeded V, Hz roof roof SK UL CUL DIN GS CSA
mm
air flow plate plate
115, 50/60  800 x 240 x 800 3164.610 55
1500 m3/h
230, 50/60  800 x 240 x 800 3164.620 55
115, 50/60  800 x 240 x 900 3164.810 55
1500 m3/h
230, 50/60  800 x 240 x 900 3164.820 55
115, 50/60  511 x 227 x 511 3164.115 55
1500 m3/h
230, 50/60  511 x 227 x 511 3164.230 55

Overview of products and approvals

Rittal System Climate Control 275


Overview of products and approvals

TopTherm air/air heat exchangers


Wall-mounted, with controller
Dimensions Approvals
Specific thermal Voltage
WxHxD Model No. SK Page
output V, Hz UL CUL DIN GS
mm
17.5 W/K 280 x 550 x 150 230, 50/60 3126.100   63
17.5 W/K 280 x 550 x 150 115, 50/60 3126.115   63
30.0 W/K 400 x 950 x 205 230, 50/60 3127.100   63
30.0 W/K 400 x 950 x 205 115, 50/60 3127.115   63
45.0 W/K 400 x 950 x 225 230, 50/60 3128.100   63
45.0 W/K 400 x 950 x 225 115, 50/60 3128.115   63
60.0 W/K 400 x 950 x 225 230, 50/60 3129.100   63
60.0 W/K 400 x 950 x 225 115, 50/60 3129.115   63
90.0 W/K 400 x 1580 x 215 230, 50/60 3130.100   63
90.0 W/K 400 x 1580 x 215 115, 50/60 3130.115   63

Air/air heat exchangers


Wall-mounted
Dimensions Approvals
Specific thermal Voltage
WxHxD Model No. SK Page
output V, Hz UL CUL DIN GS
mm
12.0 W/K 200 x 400 x 146 230, 50/60 3125.800 62
62.0 W/K 400 x 1360 x 110 230, 50/60 3129.800 62

Wall-mounted, railway-compatible version


Dimensions Approvals
Specific thermal Voltage
WxHxD Model No. SK Page
output V, Hz UL CUL DIN GS
mm
27.0 W/K 280 x 650 x 127 24 V (DC) 3126.424 64
27.0 W/K 280 x 650 x 127 110 V (DC) 3126.410 64
47.0 W/K 400 x 950 x 140 24 V (DC) 3128.424 64
47.0 W/K 400 x 950 x 140 110 V (DC) 3128.410 64
66.0 W/K 400 x 950 x 150 24 V (DC) 3129.424 64
66.0 W/K 400 x 950 x 150 110 V (DC) 3129.410 64
98.0 W/K 400 x 1580 x 150 24 V (DC) 3130.424 64
98.0 W/K 400 x 1580 x 150 110 V (DC) 3130.410 64

Roof-mounted
Dimensions Approvals
Specific thermal Voltage
WxHxD Model No. SK Page
output V, Hz UL CUL DIN GS
mm
66.0 W/K 595 x 362 x 440 230, 50/60 3248.000 65
Overview of products and approvals

276 Rittal System Climate Control


Overview of products and approvals

Cooling modules
Voltage Approvals
Useful cooling output Model No. SK Page
V, Hz UL CUL DIN GS
230, 1~, 50/60 3307.700 70
1500 W 115, 1~, 50/60 3307.710 70
400/460, 3~, 50/60 3307.740 70
230, 1~, 50/60 3310.700 70
2500 W 115, 1~, 50/60 3310.710 70
400/460, 3~, 50/60 3310.740 70

Section doors
for installing cooling modules
For enclosure dimensions Approvals
Model No. SK Page
W x H mm UL CUL DIN GS
600 x 1800 3300.040 71
600 x 2000 3300.050 71
800 x 1800 3300.060 71
800 x 2000 3300.070 71
12001) x 1800 3300.080 71
12001) x 2000 3300.090 71
12002) x 1800 3300.110 71
12002) x 2000 3300.120 71
1) Unit positioned on the left 2) Unit positioned on the right

TopTherm roof-mounted cooling units


Useful Dimensions Model No. SK Approvals
Voltage
cooling WxHxD with Basic with Comfort Page
V, Hz UL CUL DIN GS CSA
output mm controller controller
230, 50/60 3382.100 3382.500     74
500 W 597 x 417 x 380
115, 50/60 3382.110 3382.510     74
230, 50/60 3359.100 3359.500   74
750 W 597 x 417 x 380 115, 50/60 3359.110 3359.510   74
400, 2~, 50/60 3359.140 3359.540   74
230, 50/60 3383.100 3383.500     75
1000 W 597 x 417 x 475 115, 50/60 3383.110 3383.510     75
Overview of products and approvals
400, 2~, 50/60 3383.140 3383.540     75
230, 50/60 3384.100 3384.500     77
1500 W 597 x 417 x 475 115, 50/60 3384.110 3384.510     77
400, 2~, 50/60 3384.140 3384.540     77
230, 50/60 3385.100 3385.500     77
2000 W 597 x 417 x 475 115, 50/60 3385.110 3385.510     77
400, 2~, 50/60 3385.140 3385.540     77
400, 3~, 50
3000 W 796 x 470 x 580 3386.140 3386.540     78
460, 3~, 60
400, 3~, 50
4000 W 796 x 470 x 580 3387.140 3387.540     78
460, 3~, 60
Roof-mounted cooling units in stainless steel version, see page 278.
Delivery times available on request.

Rittal System Climate Control 277


Overview of products and approvals

TopTherm roof-mounted cooling units


for the office sector
Dimensions Approvals
Useful cooling Voltage
WxHxD Model No. SK Page
output V, Hz UL CUL DIN GS
mm
115, 50/60 3273.5151) 76
1100 W 597 x 417 x 475
230, 50/60 3273.500 76
3000 W 597 x 417 x 895 230, 50/60 3301.800 76
1) Delivery times available on request.

Stainless steel
Useful Dimensions Model No. SK Approvals
Voltage
cooling WxHxD with Basic with Comfort Page
V, Hz UL CUL DIN GS CSA
output mm controller controller
597 x 415 230, 50/60 3382.200 3382.600  74
500 W
x 380 115, 50/60 3382.210 3382.610  74
230, 50/60 3359.200 3359.600   74
597 x 415
750 W 115, 50/60 3359.210 3359.610   74
x 380
400, 2~, 50/60 3359.240 3359.640   74
230, 50/60 3383.200 3383.600    75
597 x 417
1000 W 115, 50/60 3383.210 3383.610    75
x 475
400, 2~, 50/60 3383.240 3383.640    75
230, 50/60 3384.200 3384.600    77
597 x 417
1500 W 115, 50/60 3384.210 3384.610    77
x 475
400, 2~, 50/60 3384.240 3384.640    77
230, 50/60 3385.200 3385.600    77
597 x 417
2000 W 115, 50/60 3385.210 3385.610    77
x 475
400, 2~, 50/60 3385.240 3385.640    77
796 x 470 400, 3~, 50
3000 W 3386.240 3386.640    78
x 580 460, 3~, 60
796 x 470 400, 3~, 50
4000 W 3387.240 3387.640    78
x 580 460, 3~, 60
Delivery times available on request.
Overview of products and approvals

With CO2 as the coolant


Dimensions Model No. SK Approvals
Useful cooling Voltage
WxHxD Page
output V, Hz with Basic controller UL CUL DIN GS
mm
1000 W 597 x 417 x 475 230, 50/60 3383.740 79
Delivery times available on request.

278 Rittal System Climate Control


Overview of products and approvals

Wall-mounted cooling units


VIP small cooling units
Useful Dimensions Approvals
Voltage Condenser
cooling WxHxD Model No. SK Page
V, Hz version UL CUL DIN GS
output mm
526 x 353.5 Left 3201.100   82
225 W 230, 50/60
x 105 Right 3202.100   82

TopTherm wall-mounted cooling units


Mini cooling unit, in horizontal format
Useful Dimensions Approvals
Voltage
cooling WxHxD Model No. SK Page
V, Hz UL CUL DIN GS CSA
output mm
230, 50/60 3302.300    83
300 W 525 x 340 x 153
115, 60 3302.310   83

Overview of products and approvals

Rittal System Climate Control 279


Overview of products and approvals

TopTherm wall-mounted cooling units


Useful Dimensions Model No. SK Approvals
Voltage
cooling WxHxD with Basic with Comfort Page
V, Hz UL CUL DIN GS CSA
output mm controller controller
280 x 550 230, 50/60 3302.100 –     84
300 W
x 140 115, 60 3302.110 –     84
280 x 550 230, 50/60 3303.100 3303.500     84
500 W
x 210 115, 60 3303.110 3303.510     84
230, 50/60 3361.100 3361.500    85
280 x 550
750 W 115, 60 3361.110 3361.510    85
x 280
400, 2~, 50/60 3361.140 3361.540    85
230, 50/60 3304.100 3304.500     87
400 x 950 115, 50/60 3304.110 3304.510     87
1000 W
x 260 400, 3~, 50
3304.140 3304.540     87
460, 3~, 60
230, 50/60 3305.100 3305.500     87
400 x 950 115, 50/60 3305.110 3305.510     87
1500 W
x 260 400, 3~, 50
3305.140 3305.540     87
460, 3~, 60
230, 50/60 3328.100 3328.500     89
400 x 1580 115, 50/60 3328.110 3328.510     89
2000 W
x 295 400, 3~, 50
3328.140 3328.540     89
460, 3~, 60
230, 50/60 3329.100 3329.500     89
400 x 1580 115, 50/60 3329.110 3329.510     89
2500 W
x 295 400, 3~, 50
3329.140 3329.540     89
460, 3~, 60
500 x 1580 400, 3~, 50
4000 W 3332.140 3332.540     90
x 340 460, 3~, 60
TopTherm wall-mounted cooling units in stainless steel version, see page 281.

Cool Efficiency, up to 45% less energy consumption


Useful Dimensions Model No. SK Approvals
Voltage
cooling WxHxD with Basic with Comfort Page
V, Hz UL CUL DIN GS CSA
output mm controller controller
400 x 950 3304.700 – 86
1000 W 230, 1~, 50
x 260 – 3304.800 86
Overview of products and approvals

280 Rittal System Climate Control


Overview of products and approvals

TopTherm wall-mounted cooling units


Stainless steel
Useful Dimensions Model No. SK Approvals
Voltage
cooling WxHxD with Basic with Comfort Page
V, Hz UL CUL DIN GS CSA
output mm controller controller
280 x 550 230, 50/60 3302.200 –    84
300 W
x 140 115, 60 3302.210 –    84
280 x 550 230, 50/60 3303.200 3303.600    84
500 W
x 210 115, 60 3303.210 3303.610    84
230, 50/60 3361.200 3361.600    85
280 x 550
750 W 115, 60 3361.210 3361.610    85
x 280
400, 2~, 50/60 3361.240 3361.640    85
230, 50/60 3304.200 3304.600    87
400 x 950 115, 50/60 3304.210 3304.610    87
1000 W
x 260 400, 3~, 50
3304.240 3304.640    87
460, 3~, 60
230, 50/60 3305.200 3305.600    87
400 x 950 115, 50/60 3305.210 3305.610    87
1500 W
x 260 400, 3~, 50
3305.240 3305.640    87
460, 3~, 60
230, 50/60 3328.200 3328.600    89
400 x 1580 115, 50/60 3328.210 3328.610    89
2000 W
x 290 400, 3~, 50
3328.240 3328.640    89
460, 3~, 60
230, 50/60 3329.200 3329.600    89
400 x 1580 115, 50/60 3329.210 3329.610    89
2500 W
x 295 400, 3~, 50
3329.240 3329.640    89
460, 3~, 60
500 x 1580 400, 3~, 50
4000 W 3332.240 3332.640    90
x 340 460, 3~, 60
Delivery times available on request.

Slimline
Useful Dimensions Model No. SK Approvals
Voltage
cooling WxHxD with Basic with Comfort Page
V, Hz UL CUL DIN GS CSA
output mm controller controller
230, 50/60 3377.1001) 3377.5001)    88
115, 50/60 3377.1101) 3377.5101)    88
1500 W 435 x 1590 x 165
400/460, 3~,
3377.1401) 3377.5401)  88
50/60
230, 50/60 3366.100 3366.500    88
115, 50/60 3366.110 3366.510    88
1500 W 450 x 1590 x 205
400/460, 3~,

Overview of products and approvals
3366.140 3366.540 88
50/60
1) Delivery times available on request.

Rittal System Climate Control 281


Overview of products and approvals

TopTherm wall-mounted cooling units


Slimline, stainless steel
Useful Dimensions Model No. SK Approvals
Voltage
cooling WxHxD with Basic with Comfort Page
V, Hz UL CUL DIN GS CSA
output mm controller controller
230, 50/60 3377.200 3377.600    88
115, 50/60 3377.210 3377.610    88
1500 W 450 x 1590 x 165
400/460, 3~,
3377.240 3377.640  88
50/60
230, 50/60 3366.200 3366.600    88
115, 50/60 3366.210 3366.610    88
1500 W 450 x 1590 x 205
400/460, 3~,
3366.240 3366.640  88
50/60
Delivery times available on request.

Nema 4x design
Useful Dimensions Model No. SK Approvals
Voltage
cooling WxHxD with Basic with Comfort Page
V, Hz UL CUL DIN GS CSA
output mm controller controller
230, 50/60 3303.104 3303.504    91
500 W 285 x 620 x 298
115, 50/60 3303.114 3303.514    91
230, 50/60 3304.104 3304.504    91
115, 50/60 3304.114 3304.514    91
1000 W 405 x 1020 x 358
400, 3~, 50
3304.144 3304.544    91
460, 3~, 60
230, 50/60 3305.104 3305.504    91
115, 50/60 3305.114 3305.514    91
1500 W 405 x 1020 x 358
400, 3~, 50
3305.144 3305.544    91
460, 3~, 60
230, 50/60 3328.104 3328.504    92
115, 50/60 3328.114 3328.514    92
2000 W 405 x 1650 x 388
400, 3~, 50
3328.144 3328.544    92
460, 3~, 60
230, 50/60 3329.104 3329.504    92
  
Overview of products and approvals

115, 50/60 3329.114 3329.514 92


2500 W 405 x 1650 x 388
400, 3~, 50
3329.144 3329.544    92
460, 3~, 60
Delivery times available on request.

282 Rittal System Climate Control


Overview of products and approvals

TopTherm wall-mounted cooling units


for machine tools
Useful Dimensions Model No. SK Approvals
Voltage
cooling WxHxD with Basic with Comfort Page
V, Hz UL CUL DIN GS
output mm controller controller
400 x 950 400, 3~, 50
1000 W 3304.142 3304.542 93
x 260 460, 3~, 60
400 x 950 400, 3~, 50
1500 W 3305.142 3305.542 93
x 260 460, 3~, 60
Delivery times available on request.

Zone 22 (dust) explosion-proof cooling units


Useful Dimensions Model No. SK Approvals
Voltage
cooling WxHxD with Basic with Comfort Page
V, Hz UL CUL DIN GS
output mm controller controller
400 x 950 230, 50/60 3304.130 3304.530 94
1000 W
x 260 400, 3~, 50/60 3304.160 3304.560 94
400 x 950 230, 50/60 3305.130 3305.530 94
1500 W
x 260 400, 3~, 50/60 3305.160 3305.560 94
Delivery times available on request.

Overview of products and approvals


With CO2 as the coolant
Useful Dimensions Model No. SK Approvals
Voltage
cooling WxHxD Page
V, Hz with Basic controller UL CUL DIN GS
output mm
1000 W 460 x 950 x 260 230, 50/60 3304.740 95
Delivery times available on request.

Rittal System Climate Control 283


Overview of products and approvals

Thermoelectric coolers
Useful Dimensions Approvals
Voltage
cooling WxHxD Model No. SK Page
V, Hz UL CUL DIN GS CSA
output mm
90 – 264 V (AC) 3201.200 97
100 W 125 x 400 x 155
24 V (DC) 3201.300 97

TopTherm air/water heat exchangers


Roof mounting with Basic/Comfort controller
Useful Dimensions Model No. SK Approvals
Voltage
cooling WxHxD with Basic with Comfort Page
V, Hz UL CUL DIN GS
output mm controller controller
230, 50/60 3209.1041) 3209.5041) 102
1875 W2) 597 x 415 x 475 115, 50/60 3209.1141) 3209.5141) 102
400, 2~, 50/60 3209.1441) 3209.5441) 102
230, 50/60 3209.100 3209.500   102
2500 W3) 597 x 415 x 475 115, 50/60 3209.110 3209.510   102
400, 2~, 50/60 3209.1401) 3209.5401)   102
230, 50/60 3210.1041) 3210.5041) 103
3000 W2) 597 x 415 x 475 115, 50/60 3210.1141) 3210.5141) 103
400, 2~, 50/60 3210.1441) 3210.5441) 103
230, 50/60 3210.100 3210.500   103
4000 W3) 597 x 415 x 475 115, 50/60 3210.110 3210.510   103
400, 2~, 50/60 3210.1401) 3210.5401)   103
1) Delivery times available on request.
2) All water-carrying parts made from stainless steel V4A (1.4571)
3) All water-carrying parts made from CuAl
Overview of products and approvals

Air/water heat exchangers


Micro, for wall mounting
Useful Dimensions Approvals
Voltage
cooling WxHxD Model No. SK Page
V, Hz UL CUL DIN GS
output mm
230, 50/60 3212.230 104
300 W 150 x 300 x 85 115, 50/60 3212.1151) 104
24 V (DC) 3212.024 104
1) Delivery times available on request.

284 Rittal System Climate Control


Overview of products and approvals

Air/water heat exchangers


Wall mounting with thermostat-controlled magnetic valve
Useful Dimensions Model No. SK Approvals
Voltage
cooling WxHxD Page
V, Hz Wall mounting UL CUL DIN GS
output mm
600 W 200 x 500 x 100 230, 50/60 3214.100   105
1250 W 200 x 950 x 100 230, 50/60 3215.100 105
400, 3~, 50/60
7000 W 450 x 1800 x 300 3216.4801) 109
480, 3~, 60
1) Delivery times available on request.

Wall mounting with Basic/Comfort controller


Water-carrying
Useful Dimensions Rated operating Model No. SK Approvals
parts
cooling WxHxD voltage Page
output V4A mm V, Hz with Basic with Comfort
CuAL UL CUL DIN GS
(1.4571) controller controller
230, 1~, 50/60 3363.1041) 3363.5041) 106
375 W  280 x 550 x 92 115, 1~, 50/60 3363.1141) 3363.5141) 106
400, 2~, 50/60 3363.1441) 3363.5441) 106
230, 1~, 50/60 3363.100 3363.500   106
500 W  280 x 550 x 92 115, 1~, 50/60 3363.1101) 3363.5101)   106
400, 2~, 50/60 3363.1401) 3363.5401)   106
230, 1~, 50/60 3364.1041) 3364.5041) 106
750 W  280 x 550 x 142 115, 1~, 50/60 3364.1141) 3364.5141) 106
400, 2~, 50/60 3364.1441) 3364.5441) 106
230, 1~, 50/60 3364.100 3364.500   106
1000 W  280 x 550 x 142 115, 1~, 50/60 3364.1101) 3364.5101)   106
400, 2~, 50/60 3364.1401) 3364.5401)   106
230, 1~, 50/60 3373.1041) 3373.5041) 107
1500 W  400 x 950 x 142 115, 1~, 50/60 3373.1141) 3373.5141) 107
400, 2~, 50/60 3373.1441) 3373.5441) 107
230, 1~, 50/60 3373.100 3373.500   107
2000 W  400 x 950 x 142 115, 1~, 50/60 3373.1101) 3373.5101)   107
400, 2~, 50/60 3373.1401) 3373.5401)   107
230, 1~, 50/60 3374.1041) 3374.5041) 107
2250 W  400 x 950 x 142 115, 1~, 50/60 3374.1141) 3374.5141)   107
400, 2~, 50/60 3374.1441) 3374.5441) 107
230, 1~, 50/60 3374.100 3374.500   107
3000 W  400 x 950 x 142 115, 1~, 50/60 3374.1101) 3374.5101)   107
400, 2~, 50/60 3374.1401) 3374.5401)   107
230, 1~, 50/60 3375.1041) 3375.5041)   108
3750 W  450 x 1400 x 250 115, 1~, 50/60 3375.1141) 3375.5141)   108
400, 2~, 50/60 3375.1441) 3375.5441) 108
230, 1~, 50/60 3375.100 3375.500   108
5000 W  450 x 1400 x 250 115, 1~, 50/60 3375.1101) 3375.5101)   108
400, 2~, 50/60 3375.1401) 3375.5401)   108 Overview of products and approvals
1) Delivery times available on request.

Rittal System Climate Control 285


Overview of products and approvals

Direct Cooling Package


Cold Plate for frequency converters
For installation in Model No. DCP Approvals
Dimensions
Cooling Enclosure Enclosure
1) WxHxD Without With Page
output width depth UL CUL DIN GS TÜV
mm T-slot T-slot
mm (side) mm
2500 W 600 600 499 x 399 x 25 8616.610 8616.6002)  112
2500 W 600 600 499 x 399 x 25 8616.630 8616.6202)  112
3000 W 800 800 699 x 399 x 25 8616.810 8616.8002)  112
3000 W 800 800 699 x 399 x 25 8616.830 8616.8202)  112
5000 W 1000 1000 899 x 399 x 25 8616.010 8616.0002) 112
5000 W 1000 1000 899 x 399 x 25 8616.030 8616.0202) 112
6000 W 1200 – 1099 x 399 x 25 8616.210 8616.2002) 112
6000 W 1200 – 1099 x 399 x 25 8616.230 8616.2202) 112
1) With 25°C fluid inlet temperature,T = 40°C and DCP surface temperature = 40°C.
u
2) Versions with T-slot are 20 mm deep.

Cold Plate for frequency converters, manufacturer-specific


For installation in Dimensions Approvals
Enclosure width Enclosure depth WxHxD Model No. DCP Page
mm UL CUL DIN GS TÜV
mm mm
Suitable for Siemens SINAMICS S210 Booksize
600 600 499 x 449 x 20 8616.640  113
600 600 499 x 449 x 20 8616.6411)  113
800 800 699 x 449 x 20 8616.840  113
800 800 699 x 449 x 20 8616.8411)  113
Suitable for Danfoss VLT® Automation Drive FC300
600 600 499 x 299 x 20 8616.6501) 113
600 600 499 x 299 x 20 8616.6511) 113
800 800 699 x 299 x 20 8616.8501) 113
800 800 699 x 299 x 20 8616.8511) 113
1) Delivery times available on request.
Overview of products and approvals

Cooling Unit
Dimensions Model No. DCP Approvals
Power WxHxD Page
mm Add-on Stand-alone UL CUL DIN GS
400 W 252 x 572 x 205 8616.500 – 114
800 W 252 x 572 x 205 8616.5101) – 114
500 W 252 x 572 x 205 – 8616.5502) 114
900 W 252 x 572 x 205 – 8616.5602) 114
1) Space required behind the DCP = 110 mm
2) Cooling Unit asstand-alone with its own fluid connection (2 x G 1/4˝).
Delivery times available on request.

286 Rittal System Climate Control


Overview of products and approvals

Direct Cooling Package


Panel Cooling
Dimensions Model No. DCP Approvals
Power WxHxD Page
mm Stand-alone UL CUL DIN GS
150 W 300 x 250 x 50 8616.300 115
350 W 400 x 300 x 60 8616.310 115
Delivery times available on request.

TopTherm recooling systems for water


Mini
Dimensions Approvals
Cooling Voltage
WxHxD Model No. SK Page
output V, Hz UL CUL DIN GS
mm
3318.600  118
1.0 kW 600 x 400 x 430 230, 50/60
3318.610  118
3319.600  118
1.5 kW 600 x 400 x 430 230, 50/60
3319.610  118
400, 3~, 50/60/
3.0 kW 602 x 676 x 645 3320.600  119
460, 3~, 60
400, 3~, 50/60/
4.5 kW 602 x 676 x 645 3334.600  119
460, 3~, 60
602 x 1050 400, 3~, 50/60/
6.0 kW 3334.660  120
x 645 460, 3~, 60

Overview of products and approvals

Rittal System Climate Control 287


Overview of products and approvals

TopTherm recooling systems for water


Power Fluid Cooler
Dimensions Approvals
Cooling Voltage
WxHxD Model No. SK Page
output V, Hz UL CUL DIN GS
mm
7.5 kW 595 x 1305 x 800 400, 3~, 50 3234.090 121
10.0 kW 655 x 1280 x 1160 400, 3~, 50 3234.100 122
14.0 kW 655 x 1280 x 1160 400, 3~, 50 3234.110 122
16.0 kW 655 x 1280 x 1160 400, 3~, 50 3234.120 122
19.0 kW 755 x 1280 x 1360 400, 3~, 50 3234.130 122
21.0 kW 755 x 1280 x 1360 400, 3~, 50 3234.140 122
25.0 kW 755 x 1280 x 1360 400, 3~, 50 3234.150 122
32.0 kW 855 x 1500 x 1560 400, 3~, 50 3234.160 122
36.0 kW 855 x 1500 x 1560 400, 3~, 50 3234.170 122
47.0 kW 1040 x 1700 x 2000 400, 3~, 50 3234.180 122
59.0 kW 1040 x 1700 x 2000 400, 3~, 50 3234.190 122

Recooling systems for water


In a floor standing enclosure
Dimensions Approvals
Cooling Voltage
WxHxD Model No. SK Page
output V, Hz UL CUL DIN GS TÜV
mm
400, 3~, 50/
2.1 kW 470 x 725 x 540 3336.100  123
460, 3~, 60
400, 3~, 50/
2.6 kW 485 x 965 x 650 3336.200  123
460, 3~, 60
400, 3~, 50/
3.4 kW 485 x 965 x 650 3336.300  123
Overview of products and approvals

460, 3~, 60
400, 3~, 50/
5.0 kW 595 x 1180 x 800 3336.500  123
460, 3~, 60
400, 3~, 50/
6.2 kW 595 x 1180 x 800 3336.600  123
460, 3~, 60
400, 3~, 50/
7.7 kW 595 x 1180 x 800 3336.650  123
460, 3~, 60
400, 3~, 50/
10.0 kW 615 x 1178 x 1160 3336.700  124
460, 3~, 60
400, 3~, 50/
14.4 kW 615 x 1178 x 1160 3336.710  124
460, 3~, 60
400, 3~, 50/
16.3 kW 615 x 1178 x 1160 3336.720  124
460, 3~, 60
400, 3~, 50/
18.5 kW 715 x 1178 x 1360 3336.730  124
460, 3~, 60
400, 3~, 50/
20.9 kW 715 x 1178 x 1360 3336.740  124
460, 3~, 60
400, 3~, 50/
25.2 kW 715 x 1178 x 1360 3336.750  124
460, 3~, 60
400, 3~, 50/
32.0 kW 815 x 1400 x 1560 3339.100  124
460, 3~, 60
400, 3~, 50/
36.2 kW 815 x 1400 x 1560 3339.200  124
460, 3~, 60
Delivery times available on request.

288 Rittal System Climate Control


Overview of products and approvals

Recooling systems for water


Power Fluid Cooler
Dimensions Approvals
Cooling Voltage
WxHxD Model No. SK Page
output V, Hz UL CUL DIN GS TÜV
mm
68.0 kW 1100 x 1606 x 2450 400, 3~, 50 3234.200 125
79.0 kW 1100 x 1606 x 2450 400, 3~, 50 3234.210 125
90.0 kW 1100 x 1606 x 2450 400, 3~, 50 3234.220 125
101.0 kW 1100 x 1606 x 2950 400, 3~, 50 3234.230 125
124.0 kW 1100 x 1875 x 2950 400, 3~, 50 3234.240 125
135.0 kW 1100 x 1875 x 2950 400, 3~, 50 3234.250 125
158.0 kW 1100 x 1875 x 2950 400, 3~, 50 3234.260 125
175.0 kW 1100 x 1875 x 2950 400, 3~, 50 3234.270 125
209.0 kW 1100 x 1875 x 3950 400, 3~, 50 3234.280 125
271.0 kW 2200 x 2450 x 3400 400, 3~, 50 3234.290 126
305.0 kW 2200 x 2450 x 3400 400, 3~, 50 3234.300 126
339.0 kW 2200 x 2450 x 3400 400, 3~, 50 3234.310 126
406.0 kW 2200 x 2450 x 4250 400, 3~, 50 3234.320 126
452.0 kW 2200 x 2450 x 4250 400, 3~, 50 3234.330 126
502.0 kW 2200 x 2450 x 4250 400, 3~, 50 3234.340 126

In the TS 8 Top enclosure system


Dimensions Approvals
Cooling Voltage
WxHxD Model No. SK Page
output V, Hz UL CUL DIN GS TÜV
mm
6.0 kW 600 x 2150 x 600 400, 3~, 50 3335.060 127
7.5 kW 600 x 2150 x 600 400, 3~, 50 3335.075 127
10.0 kW 800 x 2150 x 600 400, 3~, 50 3335.100 128
12.0 kW 800 x 2150 x 600 400, 3~, 50 3335.120 128
15.0 kW 800 x 2150 x 600 400, 3~, 50 3335.150 128
20.0 kW 1200 x 2150 x 600 400, 3~, 50 3335.200 128
25.0 kW 1200 x 2150 x 600 400, 3~, 50 3335.250 128
Delivery times available on request.

Overview of products and approvals

Mini, for wall mounting


Dimensions Approvals
Cooling Voltage
WxHxD Model No. SK Page
output V, Hz UL CUL DIN GS
mm
400, 3~, 50/60/
1.0 kW 400 x 950 x 310 3360.100 129
460, 3~, 60
400, 3~, 50/60/
2.5 kW 400 x 1580 x 290 3360.250 129
460, 3~, 60
400, 3~, 50/60/
4.0 kW 500 x 1580 x 390 3360.470 129
460, 3~, 60

Rittal System Climate Control 289


Overview of products and approvals

Recooling systems for oil


In a floor standing enclosure
Dimensions Approvals
Cooling Voltage
WxHxD Model No. SK Page
output V, Hz UL CUL DIN GS
mm
2.5 kW 485 x 965 x 650 400, 3~, 50 3337.200 130
3.4 kW 485 x 965 x 650 400, 3~, 50 3337.300 130
5.2 kW 595 x 1180 x 800 400, 3~, 50 3337.500 130
6.7 kW 595 x 1180 x 800 400, 3~, 50 3337.600 130
8.0 kW 595 x 1180 x 800 400, 3~, 50 3337.650 130
11.0 kW 615 x 1178 x 1160 400, 3~, 50 3337.700 131
15.5 kW 615 x 1178 x 1160 400, 3~, 50 3337.710 131
17.2 kW 615 x 1178 x 1160 400, 3~, 50 3337.720 131
19.0 kW 715 x 1178 x 1360 400, 3~, 50 3337.730 131
22.0 kW 715 x 1178 x 1360 400, 3~, 50 3337.740 131
26.0 kW 715 x 1178 x 1360 400, 3~, 50 3337.750 131
Delivery times available on request.

Immersible recooling systems for oil


Dimensions Approvals
Cooling Voltage
WxHxD Model No. SK Page
output V, Hz UL CUL DIN GS
mm
400, 3~, 50
2.4 kW 785 x 1650 x 785 3338.020 132
460, 3~, 60
400, 3~, 50
3.2 kW 785 x 1650 x 785 3338.040 132
460, 3~, 60
400, 3~, 50
4.6 kW 785 x 1650 x 785 3338.060 132
460, 3~, 60
400, 3~, 50
5.6 kW 785 x 1650 x 785 3338.080 132
460, 3~, 60
400, 3~, 50
8.5 kW 785 x 1650 x 785 3338.100 133
460, 3~, 60
400, 3~, 50
10.5 kW 785 x 1650 x 785 3338.120 133
460, 3~, 60
400, 3~, 50
12.0 kW 785 x 1650 x 785 3338.140 133
460, 3~, 60
Overview of products and approvals

400, 3~, 50
13.6 kW 785 x 1650 x 785 3338.160 133
460, 3~, 60
400, 3~, 50
15.3 kW 785 x 1650 x 785 3338.180 133
460, 3~, 60
400, 3~, 50
17.3 kW 785 x 1650 x 785 3338.200 133
460, 3~, 60
400, 3~, 50
21.0 kW 785 x 1650 x 1830 3338.220 134
460, 3~, 60
400, 3~, 50
31.0 kW 785 x 1650 x 1830 3338.240 134
460, 3~, 60
400, 3~, 50
35.0 kW 785 x 1650 x 1830 3338.260 134
460, 3~, 60
400, 3~, 50
46.0 kW 1830 x 1650 x 1830 3338.280 134
460, 3~, 60
400, 3~, 50
49.0 kW 1830 x 1650 x 1830 3338.300 134
460, 3~, 60
400, 3~, 50
61.0 kW 1830 x 1650 x 1830 3338.320 134
460, 3~, 60
400, 3~, 50
73.0 kW 1830 x 1650 x 1830 3338.340 134
460, 3~, 60
400, 3~, 50
78.0 kW 1830 x 1650 x 1830 3338.360 134
460, 3~, 60
Delivery times available on request.

290 Rittal System Climate Control


Overview of products and approvals

Immersible recooling systems for emulsion


Dimensions Approvals
Cooling Voltage
WxHxD Model No. SK Page
output V, Hz UL CUL DIN GS
mm
400, 3~, 50
2.4 kW 785 x 1650 x 785 3338.500 132
460, 3~, 60
400, 3~, 50
3.2 kW 785 x 1650 x 785 3338.520 132
460, 3~, 60
400, 3~, 50
4.6 kW 785 x 1650 x 785 3338.540 132
460, 3~, 60
400, 3~, 50
5.6 kW 785 x 1650 x 785 3338.560 132
460, 3~, 60
400, 3~, 50
8.5 kW 785 x 1650 x 785 3338.580 133
460, 3~, 60
400, 3~, 50
10.5 kW 785 x 1650 x 785 3338.600 133
460, 3~, 60
400, 3~, 50
12.0 kW 785 x 1650 x 785 3338.620 133
460, 3~, 60
400, 3~, 50
13.6 kW 785 x 1650 x 785 3338.640 133
460, 3~, 60
400, 3~, 50
15.3 kW 785 x 1650 x 785 3338.660 133
460, 3~, 60
400, 3~, 50
17.3 kW 785 x 1650 x 785 3338.680 133
460, 3~, 60
400, 3~, 50
21.0 kW 785 x 1650 x 1830 3338.700 134
460, 3~, 60
400, 3~, 50
31.0 kW 785 x 1650 x 1830 3338.720 134
460, 3~, 60
400, 3~, 50
35.0 kW 785 x 1650 x 1830 3338.740 134
460, 3~, 60
400, 3~, 50
46.0 kW 1830 x 1650 x 1830 3338.760 134
460, 3~, 60
400, 3~, 50
49.0 kW 1830 x 1650 x 1830 3338.780 134
460, 3~, 60
400, 3~, 50
61.0 kW 1830 x 1650 x 1830 3338.800 134
460, 3~, 60
400, 3~, 50
73.0 kW 1830 x 1650 x 1830 3338.820 134
460, 3~, 60
400, 3~, 50
78.0 kW 1830 x 1650 x 1830 3338.840 134
460, 3~, 60
Delivery times available on request.

Overview of products and approvals

Rittal System Climate Control 291


Overview of products and approvals

CRAC systems
Without heater
Useful Dimensions Model No. SK Approvals
Voltage
cooling WxHxD Without Page
V, Hz UL CUL DIN GS
output mm heater
23 kW 1100 x 1950 x 650 400/50 3301.620 138
39 kW 1100 x 1950 x 850 400/50 3301.660 138
78 kW 1800 x 1950 x 850 400/50 3301.830 138
118 kW 2600 x 1950 x 850 400/50 3301.870 138
18 kW 1100 x 1950 x 850 400/50 3300.510 138
30 kW 1100 x 1950 x 850 400/50 3300.560 138
43 kW 1400 x 1950 x 850 400/50 3300.710 138
54 kW 1800 x 1950 x 850 400/50 3300.760 138

With heater
Useful Dimensions Model No. SK Approvals
Voltage
cooling WxHxD With Page
V, Hz UL CUL DIN GS
output mm heater
23 kW 1100 x 1950 x 650 400/50 3301.630 138
39 kW 1100 x 1950 x 850 400/50 3301.670 138
78 kW 1800 x 1950 x 850 400/50 3301.840 138
118 kW 2600 x 1950 x 850 400/50 3301.880 138
18 kW 1100 x 1950 x 850 400/50 3300.520 138
30 kW 1100 x 1950 x 850 400/50 3300.570 138
43 kW 1400 x 1950 x 850 400/50 3300.720 138
54 kW 1800 x 1950 x 850 400/50 3300.770 138

With humidifier
Useful Dimensions Model No. SK Approvals
Voltage
cooling WxHxD With Page
V, Hz UL CUL DIN GS
output mm humidifier
23 kW 1100 x 1950 x 650 400/50 3301.640 138
39 kW 1100 x 1950 x 850 400/50 3301.680 138
78 kW 1800 x 1950 x 850 400/50 3301.850 138
118 kW 2600 x 1950 x 850 400/50 3301.890 138
18 kW 1100 x 1950 x 850 400/50 3300.530 138
30 kW 1100 x 1950 x 850 400/50 3300.580 138
43 kW 1400 x 1950 x 850 400/50 3300.730 138
54 kW 1800 x 1950 x 850 400/50 3300.780 138

With heater and humidifier


Useful Dimensions Model No. SK Approvals
Voltage
cooling WxHxD With heater Page
V, Hz UL CUL DIN GS
Overview of products and approvals

output mm and humidifier


23 kW 1100 x 1950 x 650 400/50 3301.650 138
39 kW 1100 x 1950 x 850 400/50 3301.690 138
78 kW 1800 x 1950 x 850 400/50 3301.860 138
118 kW 2600 x 1950 x 850 400/50 3301.990 138
18 kW 1100 x 1950 x 850 400/50 3300.540 138
30 kW 1100 x 1950 x 850 400/50 3300.590 138
43 kW 1400 x 1950 x 850 400/50 3300.740 138
54 kW 1800 x 1950 x 850 400/50 3300.790 138

292 Rittal System Climate Control


Overview of products and approvals

Aisle containment
Model No. SK Approvals
Page
UL CUL DIN GS
Roof element 3300.170 3300.180 – 139
Door element – – 3300.160 139
Width of element
600 800 –
(identical to enclosure width), mm
Width of cold aisle mm 1200 1200 1200
Height of cold aisle mm – – 2000

Liquid Cooling Package


LCP Standard
Dimensions Approvals
Useful cooling Voltage
WxHxD Model No. SK Page
output V, Hz UL CUL GS
mm
Up to 20 kW 300 x 2000 x 1000 230, 50/60 3301.230    141
Up to 20 kW 300 x 2000 x 1000 115, 50/60 3301.210    141
Up to 20 kW 300 x 2000 x 1200 230, 50/60 3301.420 141

LCP Plus
Dimensions Approvals
Useful cooling Voltage
WxHxD Model No. SK Page
output V, Hz UL CUL GS
mm
Up to 30 kW 300 x 2000 x 1200 230, 50/60 3301.4801)    142
Up to 40 kW 300 x 2400 x 1200 230, 50/60 on request 142
1) Delivery times available on request.
Overview of products and approvals

Rittal System Climate Control 293


Overview of products and approvals

Liquid Cooling Package


LCP Extend
Dimensions Approvals
Useful cooling Voltage
WxHxD Model No. SK Page
output V, Hz UL CUL GS
mm
12 kW 520 x 1910 x 160 230, 50/60 3301.4901)  143
1) Delivery times available on request.

LCP Smart
Dimensions Approvals
Useful cooling Voltage Model No.
WxHxD Page
output V, Hz SK UL CUL GS
mm
200 – 230, 1~, 50/60
Up to 20 kW 300 x 2000 x 1000 3301.460 144
400, 3~, 50/60

LCP Inline
Dimensions Approvals
Useful cooling Voltage
WxHxD Model No. SK Page
output V, Hz UL CUL DIN GS
mm
Overview of products and approvals

230, 1~, 50/60


Up to 30 kW1) 300 x 2000 x 1200 3301.470 145
400, 3~, 50/60
1) Achievable with 15°C cold water inlet temperature, volumetric flow 35 l/min and ΔT of 20°C on the air side.

294 Rittal System Climate Control


Overview of products and approvals

Chillers for IT cooling


Dimensions Approvals
Voltage
Cooling output WxHxD Model No. SK Page
V, Hz UL CUL DIN GS
mm
15.0 kW 815 x 1400 x 1560 400, 3~, 50 3232.700 148
24.0 kW 815 x 1400 x 1560 400, 3~, 50 3232.710 148
35.0 kW 815 x 1400 x 1560 400, 3~, 50 3232.720 148
48.0 kW 1000 x 2180 x 2000 400, 3~, 50 3232.730 148
61.0 kW 1100 x 1606 x 2450 400, 3~, 50 3232.740 148
72.0 kW 1100 x 1606 x 2450 400, 3~, 50 3232.750 148
82.0 kW 1100 x 1606 x 2450 400, 3~, 50 3232.760 148
92.0 kW 1100 x 1606 x 2950 400, 3~, 50 3232.770 148
113.0 kW 1100 x 1875 x 2950 400, 3~, 50 3232.780 148
123.0 kW 1100 x 1875 x 2950 400, 3~, 50 3232.790 148
145.0 kW 1100 x 1875 x 2950 400, 3~, 50 3232.800 149
161.0 kW 1100 x 1875 x 2950 400, 3~, 50 3232.810 149
193.0 kW 1100 x 1875 x 3950 400, 3~, 50 3232.820 149
248.0 kW 2200 x 2450 x 3400 400, 3~, 50 3232.830 149
280.0 kW 2200 x 2450 x 3400 400, 3~, 50 3232.840 149
312.0 kW 2200 x 2450 x 3400 400, 3~, 50 3232.850 149
372.0 kW 2200 x 2450 x 4250 400, 3~, 50 3232.860 149
415.0 kW 2200 x 2450 x 4250 400, 3~, 50 3232.870 149
462.0 kW 2200 x 2450 x 4250 400, 3~, 50 3232.880 149
Delivery times available on request.

Water/water heat exchangers


Dimensions Approvals
Voltage
Cooling output WxHxD Model No. SK Page
V, Hz UL CUL DIN GS
mm
25.0 kW 1200 x 1900 x 800 400, 3~, 50 3232.900 153 Overview of products and approvals
50.0 kW 1200 x 1900 x 800 400, 3~, 50 3232.910 153
75.0 kW 1200 x 1900 x 800 400, 3~, 50 3232.920 153
100.0 kW 1200 x 1900 x 800 400, 3~, 50 3232.930 153
150.0 kW 1200 x 1900 x 800 400, 3~, 50 3232.940 153
200.0 kW 2000 x 1900 x 800 400, 3~, 50 3232.950 153
250.0 kW 2000 x 1900 x 800 400, 3~, 50 3232.960 153
Delivery times available on request.

Rittal System Climate Control 295


Overview of products and approvals

Cooling units for CS modular enclosures


Dimensions Useful cooling output
Mounting EN 814 Rated operating Model No.
WxHxD Page
position voltage CS
mm L35 L35 L35 L50
535 x 390 x 400 Roof mounting 900 W 750 W 230 V AC, 50/60 Hz 9762.012 160
430 x 1070 x 210 Door mounting 900 W 650 W 230 V AC, 50/60 Hz 9768.100 160
515 x 1170 x 151.5 Wall mounting 900 W 750 W 230 V AC, 50/60 Hz 9761.012 160
695 x 1132 x 151.5 Wall mounting 1400 W 1050 W 230 V AC, 50/60 Hz 9761.032 160
776 x 1100 x 250 Wall mounting 2500 W 2000 W 230 V AC, 50/60 Hz 9761.042 160
400 x 1050 x 310 Universal built-in 1500 W 1250 W 230 V AC, 50/60 Hz 9768.150 160
Delivery times available on request.

Approvals CS 9761.032:
● UL
● C-UL

Heat exchangers for CS modular enclosures


Dimensions Specific
Mounting Model No.
WxHxD thermal Heater1) Rated operating voltage Page
position CS
mm output
470 x 158 x 380 Roof mounting 30 W/K without 48 V DC 9764.040 161
535 x 390 x 400 Roof mounting 60 W/K 400 W 48 V DC 9764.012 161
515 x 1170 x 151.5 Wall mounting 60 W/K 400 W 48 V DC 9763.012 161
480 x 1005 x 110 Door mounting 40 W/K 400 W 48 V DC 9768.032 162
510 x 1005 x 150 Door mounting 60 W/K 400 W 48 V DC 9768.012 162
445 x 1050 x 150 Door mounting 85 W/K without 48 V DC 9768.042 162
575 x 1050 x 195 Door mounting 120 W/K without 48 V DC 9768.062 162
Overview of products and approvals

1) Ratedoperating voltage 230 V AC, 50/60 Hz


Delivery times available on request.

296 Rittal System Climate Control


Overview of products and approvals

Climate control units for Toptec CR


Useful cooling
Dimensions output Specific Rated operating Model No.
WxHxD Installation EN 814 Page
thermal output voltage CS
mm
L35 L35 L35 L50
Heat exchangers
Universal
500 x 1000 x 150 – – 85 W/K 48 V DC 9776.100 163
built-in
Universal
500 x 1000 x 200 – – 105 W/K 48 V DC 9776.150 163
built-in
Cooling units
Universal
500 x 1000 x 150 1000 W 650 W – 230 V AC, 50/60 Hz 9776.500 163
built-in
Universal
500 x 1000 x 260 1600 W 1200 W – 230 V AC, 50/60 Hz 9776.550 163
built-in
Delivery times available on request.

Enclosure heaters
Without fan
Continuous thermal Approvals
Voltage
output at Model No. SK Page
Volt UL CUL DIN GS VDE
Tu = 10°C
10 W 100 – 240 (AC/DC) 3105.110 169
20 W 100 – 240 (AC/DC) 3106.120 169
30 W 100 – 240 (AC/DC) 3115.130 169
50 W 100 – 240 (AC/DC) 3116.140 169
75 W 100 – 240 (AC/DC) 3107.150 169
100 W 100 – 240 (AC/DC) 3107.160 169
150 W 100 – 240 (AC/DC) 3102.170 169

With fan
Continuous thermal Model No. SK Approvals
Voltage
output at Page
Volt 110 V 230 V UL CUL DIN GS VDE
Tu = 10°C
250 W1) 115 or 240 (AC/DC) 3105.210 3105.180 169
Overview of products and approvals
400 W1) 115 or 240 (AC/DC) 3105.220 3105.190 169
800 W1) 115 or 240 (AC/DC) 3105.230 3105.200 169
1) Output with fan.

Rittal System Climate Control 297


Service
Rittal Global Service – for system climate control

A central point of contact, decentralised implementation, short response times – this is the successful concept

behind Rittal Global Service. High-tech system climate control must offer a permanently high level of reliability

in enclosure cooling as well as in machine and process cooling.

With this in mind, we offer fast and reliable response times worldwide – thanks to our network of local service

engineers.

Customer satisfaction from the outset

Pre-Sales Implementation After-Sales


We face up to our responsibilities Because we are pleased to be on board We smooth the way for your decision.
when you arrive at a solution.
● Requirement analysis ● Service contracts
● Load tests ● Installation/integration ● Maintenance/servicing
● Thermal imaging ● Commissioning ● Repairs
● Simulation and calculation ● Instruction ● Spare parts management
● Certification ● Training

Rittal Global Service – always on hand, whenever you need us!

Our worldwide Rittal Global Service hubs

Europe: North America: South America: China: India:


service@rittal.de service@rittal.us service@rittal.com.br service@rittal.cn service@rittal-india.com
Tel. +49(0)2772 5051855 Tel. +1800 477 4000 Tel. +55 11 36 22 23 77 Tel. +86 800 820 0866 Tel. +91 80 22 890 783

 Five global service support points in the world's major economic hubs

 Over 60 other service sites with

 more than 250 qualified partners and our own technical specialists, worldwide!

298 Rittal System Climate Control


Service
Rittal climate checks

Service packages for every aspect


of system climate control

Load tests
482.6 mm (19˝) slide-in equipment which simu-
lates the thermodynamic response of servers
allows you to determine in advance whether
your cooling system is adequate for any planned
extensions. Furthermore, after installing the LCP
family, the cooling response can be tested
directly, without the presence of a server.

Load tests as the optimum basis for


planning.

Intelligent wireless sensor


technology
Sensors the size of a button record the tempera-
ture and humidity at specified locations in the
rack. The location and time-dependent readings
are extracted and displayed. The result is a 3D
analysis of the data centre's cooling response.

With sensor technology for 3D


analyses.

Piping network calculation


The Rittal specialists use a software package to
design and dimension the pipe networks of liquid
cooling systems, taking into consideration the
architectural conditions. The specifications cre-
ated allow the local installation engineer to start
work immediately.

Perfect dimensioning of pipe networks.

CFD (Computational Fluid


Dynamics)
A 3D computer simulation is used to visualise
the thermodynamic response of the planned
data centre with server racks and climate control
system. Predicting the temperature, speed, pres-
sure and hence flow conditions in the data centre
facilitates fast response times.

Forward planning with CFD.

Thermography
Using a thermal imaging camera illustrates the
temperature conditions (surface) inside the data
centre with colour coding, hot-spots can be
located and eliminated.

Localisation of hot-spots
via thermography.

Rittal System Climate Control 299


List of model numbers
2102.180 to 3302.110
Model No. Page Model No. Page Model No. Page Model No. Page Model No. Page
2102.180 58 3149.840 54 3213.320 176 3267.200 190 3300.760 138
2102.190 58 3159.100 195 3213.330 176 3273.500 76 3300.770 138
2102.320 58 3164.115 55 3214.100 105 3273.515 76 3300.780 138
2102.400 58 3164.230 55 3215.100 105 3284.200 190 3300.790 138
2102.410 58 3164.610 55 3216.470 109 3284.210 190 3301.210 141
2102.490 58 3164.620 55 3216.480 109 3285.000 189 3301.221 188
2541.235 183 3164.810 55 3232.700 148 3285.200 190 3301.230 141
2542.235 183 3164.820 55 3232.710 148 3286.000 189 3301.250 186
2543.235 183 3165.024 59 3232.720 148 3286.100 189 3301.290 186
3102.170 169 3165.048 59 3232.730 148 3286.110 189 3301.310 187
3105.110 169 3165.115 59 3232.740 148 3286.120 190 3301.320 186
3105.180 169 3165.230 59 3232.750 148 3286.200 190 3301.330 187
3105.190 169 3165.615 59 3232.760 148 3286.210 190 3301.340 187
3105.200 169 3165.624 59 3232.770 148 3286.230 190 3301.350 188
3105.210 169 3165.630 59 3232.780 148 3286.240 190 3301.351 188
3105.220 169 3165.648 59 3232.790 148 3286.250 190 3301.360 188
3105.230 169 3165.815 59 3232.800 149 3286.260 183 3301.370 186
3106.120 169 3165.824 59 3232.810 149 3286.270 183 3301.380 186
3107.150 169 3165.830 59 3232.820 149 3286.280 183 3301.390 186
3107.160 169 3165.848 59 3232.830 149 3286.300 189 3301.400 188
3108.024 55 3169.007 54 3232.840 149 3286.310 190 3301.420 141
3108.100 55 3171.100 191 3232.850 149 3286.400 189 3301.421 188
3108.115 55 3172.100 191 3232.860 149 3286.410 190 3301.460 144
3110.000 178 3173.100 191 3232.870 149 3286.500 189 3301.470 145
3110.200 178 3174.000 191 3232.880 149 3286.510 190 3301.480 142
3114.024 177 3175.000 194 3232.900 153 3286.520 190 3301.490 143
3114.100 177 3176.000 193 3232.910 153 3286.600 189 3301.560 192
3114.115 177 3177.000 189 3232.920 153 3286.610 190 3301.570 192
3115.130 169 3181.100 191 3232.930 153 3286.700 182 3301.580 192
3116.140 169 3182.100 191 3232.940 153 3286.780 175 3301.590 192
3118.000 178 3183.100 191 3232.950 153 3286.800 182 3301.600 192
3120.000 179 3201.030 192 3232.960 153 3286.850 175 3301.608 192
3120.115 179 3201.050 191 3234.090 121 3286.860 175 3301.610 192
3121.000 195 3201.100 82 3234.100 122 3286.870 174 3301.612 192
3124.000 180 3201.200 97 3234.110 122 3286.880 175 3301.620 138
3124.100 180 3201.300 97 3234.120 122 3286.900 182 3301.630 138
3124.200 179 3202.100 82 3234.130 122 3286.970 174 3301.640 138
3125.800 62 3209.100 102 3234.140 122 3286.980 175 3301.650 138
3126.100 63 3209.104 102 3234.150 122 3286.990 174 3301.660 138
3126.115 63 3209.110 102 3234.160 122 3288.200 190 3301.670 138
3126.410 64 3209.114 102 3234.170 122 3289.200 190 3301.680 138
3126.424 64 3209.140 102 3234.180 122 3294.100 189 3301.690 138
3127.100 63 3209.144 102 3234.190 122 3294.200 190 3301.790 186
3127.115 63 3209.500 102 3234.200 125 3300.040 71 3301.800 76
3128.100 63 3209.504 102 3234.210 125 3300.050 71 3301.830 138
3128.115 63 3209.510 102 3234.220 125 3300.060 71 3301.840 138
3128.410 64 3209.514 102 3234.230 125 3300.070 71 3301.850 138
3128.424 64 3209.540 102 3234.240 125 3300.080 71 3301.860 138
3129.100 63 3209.544 102 3234.250 125 3300.090 71 3301.870 138
3129.115 63 3210.100 103 3234.260 125 3300.110 71 3301.880 138
3129.410 64 3210.104 103 3234.270 125 3300.120 71 3301.890 138
3129.424 64 3210.110 103 3234.280 125 3300.160 139, 293 3301.900 194
3129.800 62 3210.114 103 3234.290 126 3300.170 139, 293 3301.910 194
3130.100 63 3210.140 103 3234.300 126 3300.180 139, 293 3301.920 194
3130.115 63 3210.144 103 3234.310 126 3300.510 138 3301.930 194
3130.410 64 3210.500 103 3234.320 126 3300.520 138 3301.940 194
3130.424 64 3210.504 103 3234.330 126 3300.530 138 3301.950 194
3144.000 53 3210.510 103 3234.340 126 3300.540 138 3301.955 194
3145.000 53 3210.514 103 3248.000 65 3300.560 138 3301.957 194
3148.007 54 3210.540 103 3253.000 189 3300.570 138 3301.960 194
3149.007 54 3210.544 103 3253.010 189 3300.580 138 3301.965 194
3149.410 54 3212.024 104 3253.200 190 3300.590 138 3301.967 194
3149.420 54 3212.115 104 3253.220 190 3300.710 138 3301.980 186
3149.440 54 3212.230 104 3254.000 189 3300.720 138 3301.990 138
3149.810 54 3213.300 176 3254.200 190 3300.730 138 3302.100 84
3149.820 54 3213.310 176 3267.100 189 3300.740 138 3302.110 84

300 Rittal System Climate Control


List of model numbers
3302.200 to 3366.540
Model No. Page Model No. Page Model No. Page Model No. Page Model No. Page
3302.200 84 3305.640 87 3327.607 49 3337.200 130 3352.115 52
3302.210 84 3307.700 70 3327.617 49 3337.300 130 3352.230 52
3302.300 83 3307.710 70 3327.700 191 3337.500 130 3352.500 52
3302.310 83 3307.740 70 3328.100 89 3337.600 130 3355.100 52
3303.100 84 3310.700 70 3328.104 92 3337.650 130 3356.100 52
3303.104 91 3310.710 70 3328.110 89 3337.700 131 3357.100 52
3303.110 84 3310.740 70 3328.114 92 3337.710 131 3359.100 74
3303.114 91 3318.600 118 3328.140 89 3337.720 131 3359.110 74
3303.200 84 3318.610 118 3328.144 92 3337.730 131 3359.140 74
3303.210 84 3319.600 118 3328.200 89 3337.740 131 3359.200 74
3303.500 84 3319.610 118 3328.210 89 3337.750 131 3359.210 74
3303.504 91 3320.600 119 3328.240 89 3338.020 132 3359.240 74
3303.510 84 3321.027 44 3328.500 89 3338.040 132 3359.500 74
3303.514 91 3321.047 44 3328.504 92 3338.060 132 3359.510 74
3303.600 84 3321.107 44 3328.510 89 3338.080 132 3359.540 74
3303.610 84 3321.117 44 3328.514 92 3338.100 133 3359.600 74
3304.100 86, 87 3321.207 193 3328.540 89 3338.120 133 3359.610 74
3304.104 91 3321.267 48 3328.544 92 3338.140 133 3359.640 74
3304.110 87 3321.607 48 3328.600 89 3338.160 133 3360.100 129
3304.114 91 3321.617 48 3328.610 89 3338.180 133 3360.250 129
3304.130 94 3321.700 191 3328.640 89 3338.200 133 3360.470 129
3304.140 87 3321.800 193 3329.100 89 3338.220 134 3361.100 85
3304.142 93 3322.027 44 3329.104 92 3338.240 134 3361.110 85
3304.144 91 3322.047 44 3329.110 89 3338.260 134 3361.140 85
3304.160 94 3322.107 44 3329.114 92 3338.280 134 3361.200 85
3304.200 87 3322.117 44 3329.140 89 3338.300 134 3361.210 85
3304.210 87 3322.207 193 3329.144 92 3338.320 134 3361.240 85
3304.240 87 3322.267 48 3329.200 89 3338.340 134 3361.500 85
3304.500 86, 87 3322.607 48 3329.210 89 3338.360 134 3361.510 85
3304.504 91 3322.617 48 3329.240 89 3338.500 132 3361.540 85
3304.510 87 3322.700 191 3329.500 89 3338.520 132 3361.600 85
3304.514 91 3322.800 193 3329.504 92 3338.540 132 3361.610 85
3304.530 94 3323.027 45 3329.510 89 3338.560 132 3361.640 85
3304.540 87 3323.047 45 3329.514 92 3338.580 133 3363.100 106
3304.542 93 3323.107 45 3329.540 89 3338.600 133 3363.104 106
3304.544 91 3323.117 45 3329.544 92 3338.620 133 3363.110 106
3304.560 94 3323.207 193 3329.600 89 3338.640 133 3363.114 106
3304.600 87 3323.267 48 3329.610 89 3338.660 133 3363.140 106
3304.610 87 3323.607 48 3329.640 89 3338.680 133 3363.144 106
3304.640 87 3323.617 48 3329.903 191 3338.700 134 3363.500 106
3304.700 86 3323.800 193 3329.904 191 3338.720 134 3363.504 106
3304.740 95 3324.027 45 3332.140 90 3338.740 134 3363.510 106
3304.800 86 3324.047 45 3332.240 90 3338.760 134 3363.514 106
3305.100 87 3324.107 45 3332.540 90 3338.780 134 3363.540 106
3305.104 91 3324.117 45 3332.640 90 3338.800 134 3363.544 106
3305.110 87 3324.607 49 3334.600 119 3338.820 134 3364.100 106
3305.114 91 3324.617 49 3334.660 120 3338.840 134 3364.104 106
3305.130 94 3324.800 193 3335.060 127 3339.100 124 3364.110 106
3305.140 87 3325.027 46 3335.075 127 3339.200 124 3364.114 106
3305.142 93 3325.047 46 3335.100 128 3340.024 52 3364.140 106
3305.144 91 3325.107 46 3335.120 128 3340.115 52 3364.144 106
3305.160 94 3325.117 46 3335.150 128 3340.230 52 3364.500 106
3305.200 87 3325.207 193 3335.200 128 3341.024 52 3364.504 106
3305.210 87 3325.267 49 3335.250 128 3341.115 52 3364.510 106
3305.240 87 3325.607 49 3336.100 123 3341.230 52 3364.514 106
3305.500 87 3325.617 49 3336.200 123 3342.024 52 3364.540 106
3305.504 91 3326.107 47 3336.300 123 3342.115 52 3364.544 106
3305.510 87 3326.117 47 3336.500 123 3342.230 52 3366.100 88
3305.514 91 3326.207 193 3336.600 123 3342.500 52 3366.110 88
3305.530 94 3326.267 49 3336.650 123 3350.024 52 3366.140 88
3305.540 87 3326.607 49 3336.700 124 3350.115 52 3366.200 88
3305.542 93 3326.617 49 3336.710 124 3350.230 52 3366.210 88
3305.544 91 3326.800 193 3336.720 124 3351.024 52 3366.240 88
3305.560 94 3327.107 47 3336.730 124 3351.115 52 3366.500 88
3305.600 87 3327.117 47 3336.740 124 3351.230 52 3366.510 88
3305.610 87 3327.147 47 3336.750 124 3352.024 52 3366.540 88

Rittal System Climate Control 301


List of model numbers
3366.600 to 9776.550
Model No. Page Model No. Page Model No. Page Model No. Page
3366.600 88 3383.500 75 7886.000 58 9761.042 160
3366.610 88 3383.510 75 7886.100 58 9762.012 160
3366.640 88 3383.540 75 7886.200 58 9763.012 161
3373.100 107 3383.600 75 7966.035 56 9764.012 161
3373.104 107 3383.610 75 7968.035 56 9764.040 161
3373.110 107 3383.640 75 7980.000 56 9765.050 180
3373.114 107 3383.740 79 7980.100 56 9765.051 160
3373.140 107 3384.100 77 7980.148 56 9765.105 180
3373.144 107 3384.110 77 7986.035 56 9765.110 180
3373.500 107 3384.140 77 7988.035 56 9765.115 180
3373.504 107 3384.200 77 8616.000 112 9768.012 162
3373.510 107 3384.210 77 8616.010 112 9768.032 162
3373.514 107 3384.240 77 8616.020 112 9768.042 162
3373.540 107 3384.500 77 8616.030 112 9768.062 162
3373.544 107 3384.510 77 8616.200 112 9768.100 160
3374.100 107 3384.540 77 8616.210 112 9768.150 160
3374.104 107 3384.600 77 8616.220 112 9769.002 52
3374.110 107 3384.610 77 8616.230 112 9776.100 163
3374.114 107 3384.640 77 8616.300 115 9776.150 163
3374.140 107 3385.100 77 8616.310 115 9776.500 163
3374.144 107 3385.110 77 8616.500 114 9776.550 163
3374.500 107 3385.140 77 8616.510 114
3374.504 107 3385.200 77 8616.550 114
3374.510 107 3385.210 77 8616.560 114
3374.514 107 3385.240 77 8616.600 112
3374.540 107 3385.500 77 8616.610 112
3374.544 107 3385.510 77 8616.620 112
3375.100 108 3385.540 77 8616.630 112
3375.104 108 3385.600 77 8616.640 113
3375.110 108 3385.610 77 8616.641 113
3375.114 108 3385.640 77 8616.650 113
3375.140 108 3386.140 78 8616.651 113
3375.144 108 3386.240 78 8616.700 184
3375.500 108 3386.540 78 8616.710 184
3375.504 108 3386.640 78 8616.720 184
3375.510 108 3387.140 78 8616.750 184
3375.514 108 3387.240 78 8616.751 184
3375.540 108 3387.540 78 8616.760 184
3375.544 108 3387.640 78 8616.761 184
3377.000 182 4127.000 176 8616.762 184
3377.100 88 6730.600 183 8616.763 185
3377.110 88 7000.670 58 8616.764 185
3377.140 88 7000.680 58 8616.765 185
3377.200 88 7109.035 177 8616.800 112
3377.210 88 7507.760 57 8616.810 112
3377.240 88 7526.964 179 8616.820 112
3377.500 88 7826.360 58 8616.830 112
3377.510 88 7826.362 58 8616.840 113
3377.540 88 7826.366 58 8616.841 113
3377.600 88 7826.368 58 8616.850 113
3377.610 88 7826.369 58 8616.851 113
3377.640 88 7826.382 58 8801.300 181
3382.100 74 7826.480 58 8801.310 181
3382.110 74 7826.486 58 8801.320 181
3382.200 74 7826.488 58 8801.330 181
3382.210 74 7826.489 58 8801.340 181
3382.500 74 7856.360 58 8801.350 181
3382.510 74 7856.362 58 8801.360 181
3382.600 74 7856.366 58 8801.380 182
3382.610 74 7856.368 58 8801.410 181
3383.100 75 7856.380 58 8801.420 181
3383.110 75 7856.388 58 8801.430 181
3383.140 75 7858.488 57 8801.440 181
3383.200 75 7885.000 58 8801.920 181
3383.210 75 7885.100 58 9761.012 160
3383.240 75 7885.200 58 9761.032 160

302 Rittal System Climate Control


Index

A Cover bungs
Cover plates
– for fan panels FlatBox
Covers
175

57
Flexible hose
Flow regulator valve
Fluid distribution manifold
Front cover
184
194
184
145, 186
Accessories 171 – 195
– for fan-and-filter units/outlet filters 193 – for LCP Inline 145
– Air routing 174 – 176
– for LCP Standard 187 Front outlet grille 2 U
– Control/regulation 177 – 180
CRAC systems 136 – for tangential fans 193
– Filter technology 189 – 191
CS Outdoor climate control 157 – 165
– for Cold Plate 184, 185
– for Liquid Cooling Package 186 – 188
– General 192 – 194
– Mounting accessories
– Software
Active kit for TE
181 – 183
195
58 D H
Adaptor frame 109 Heat exchangers
– for wall-mounted cooling units 183 DC fan mounting plate – Air/air 62 – 65
Add-on cover 188 – for TS 57 – Air/water 102 – 109
Adjustable frame DCP Cold Plate 112, 113 – for CS modular enclosures 161, 162
– for air/air heat exchangers 183 DCP Cooling Unit 114 – for Toptec CR 163
Air diverter 176 DCP Panel Cooling 115 – LCP Extend 143
Air duct system Deflector for air duct system, 90° 174 – LCP Plus 142
– for TopTherm roof-mounted Digital enclosure internal temperature – LCP Standard 141
cooling units and air/water display and thermostat 177 – Water/water 150 – 153
heat exchangers 174 Direct cooling package 110 – 115 Heaters 167 – 169
Air routing 174 Direct fluid connection 184 Hood
Air/air heat exchangers 60 – 65 Door-mounted fan – for fan-and-filter units/outlet filters 193
– Roof-mounted 65 – for server enclosures TS, TE 59 Hose-proof hoods
– Wall-mounted, Door-operated switch 176 – for fan-and-filter units/outlet filters 193
railway-compatible version 64 Double-nipple coupling 185 Hygrostat 178
Air/water heat exchangers 100 – 109
Aisle containment 139
Approvals and product overview 270 – 297

E I
B Elbow coupling
Electric condensate evaporator
EMC
– Fan-and-filter units, outlet filters
185
192

48, 49
Immersible recooling systems
– for oil/emulsion
Integrated louvres
Interface card for TopTherm
132 – 134
183
179
Bottom-mounted adaptor
– for enclosure internal thermostat Enclosure heaters 167 – 169
and hygrostat 178 Enclosure internal fan
BUS system SK 180 – for TS 8 55
Enclosure internal temperature display
and thermostat, digital
Enclosure internal thermostat
177
178 L
C EPLAN Cabinet
Explosion-proof cooling units
Ex-proof climate control systems
195
94
164
LCP Inline
LCP Smart
LCP Extend
LCP Plus
145
144
143
142
Cable connection kit
– for CS outdoor cooling units 180 LCP Standard 141
– for CS outdoor heat exchangers 180 Lint screen 191
Chillers for IT cooling
Climate control components,
Outdoor
146 – 149

160 – 165
F Liquid cooling IE
Liquid cooling IT
Liquid Cooling Package
99 – 134
135 – 155
136, 140 – 145
Climate control doors 71 Fan expansion kit 56 Louvred grille
CO2 cooling units 79 – for door-mounted fan TS 59 – for lint screen 191
Cold Plate Fan mounting plate
– for frequency converters 112, 113 – for TS 56, 57
Condensate collecting bottle 192 Fan roof, modular, two-piece
Condensate hose
Connection hose
Cool Efficiency
192
188

Cooling medium for recooling systems 194


86
– for TS 8, FR(i)
Fan systems
– for TS 8
Fan unit, active
58
50 – 59
54 M
Metal filters 190
Cooling module 70 – for TE 58 Micro air/water heat exchanger 104
– for LCP Standard 141 Fan-and-filter unit Mini cooling unit in horizontal format 83
– for LCP Standard and Smart 186 – EMC 48, 49 Mini recooling systems 118 – 120, 129
Cooling Unit 114 Fan-and-filter units 42 – 47 – for wall mounting 129
Cooling units 66 – 97 Filter holder for roof ventilation 194 Modular climate control concept 68 – 71
– Cool Efficiency 86 Filter mats Monitoring 235 – 237
– for CS modular enclosures 160 – for tangential fans/ Mounting accessories 181 – 183
– for precision machine tools 93 front outlet grilles 189 Mounting adaptor
– for Toptec CR 163 – for discontinued – for speed control 179
– for VIP 6000 command panels 82 climate control doors 190
– Mini in horizontal format 83 – for discontinued cooling units 189, 190
– NEMA 4x design 91, 92 – for heat exchangers 190
– Roof-mounted 74 – 79 – for Mini recooling systems 190
– Roof-mounted, stainless steel

– Wall-mounted
74, 75,
77, 78
82 – 95
– for TopTherm climate control door/
section door
– for TopTherm cooling units
190
189, 190
N
– Wall-mounted, stainless steel 84, 85, Filter technology 189 – 191 NEMA 4x
87 – 90 Fine filter mats – Cooling units 91, 92
Cooling with ambient air 41 – 65 – for fan-and-filter units/outlet filters 191

Rittal System Climate Control 303


Index

O Stainless steel
– Cooling units – roof-mounted

– Cooling units – wall-mounted


74, 75,
77, 78
84, 85,
RAL-colours
Colour
RAL
Description
Outdoor climate control 157 – 165
87 – 90
Outlet filter 193
Stoppers 3001 signal red
– EMC 48, 49
– for roof-mounted cooling units 175
Overflow valve 194
System accessories 171 – 195
Overview of products 5002 ultramarine blue
System attachment
and approvals 270 – 297
– for frequency converters 184
System solutions 14 – 29 5005 signal blue

P 5018 turquoise blue

Panel Cooling
Piping systems
115 T 7015

7022
slate grey

umbra grey
Tangential fans 50, 53
– in the data centre 154, 155
Technical details 239 – 268
Power Fluid Cooler 121, 122, 125, 126
Temperature display and thermostat, 7024 graphite grey
Power packs 24 V (DC)
digital 177
– for thermoelectric cooler 192
Temperature sensor TF25 185
Project planning 30 – 39 7030 stone grey
Test adaptor
– for CS Outdoor
climate control equipment 180 7032 pebble grey
Therm Software 195

Q Thermoelectric coolers
Thermostat
– Digital
96, 97
178
177
7033 cement grey

Quick-action vent valve 184 Tips and tricks 197 – 237 7035 pale grey
Quick-change frame Touchscreen display
– for TopTherm roof-mounted – for LCP Smart 186
cooling units 182 Trim frame 7044 silky grey
Quick-release fastener 188 – for slimline cooling units 182
8019 grey brown

R V
9005 jet black

9006 white aluminium


Rack-mounted fans 482.6 mm (19˝) 50, 52 Vent attachment 54
Raised-floor, CRAC system 138 – TS 182 9011 graphite black
Recooling systems 116 – 134 Vent valve 188
– for oil 130, 131 VIP small cooling units 82
– for water 118 – 129 9017 traffic black
– immersible, oil/emulsion 132 – 134
RiDiag II 195
Roof plates
– DK-TS
– TS
Roof-mounted
181
181 W We reserve the right to further develop-
ments and technical modifications of our
Wall-mounted cooling units 80 – 95
– Air/air heat exchangers 65 products. Such modifications, along with
– Cool Efficiency 86
– Air/water heat exchangers 102, 103 errors and printing errata, shall not con-
– Thermoelectric coolers 96, 97
– Cooling units 72 – 79 stitute grounds for compensation.
Wall-mounted heat exchangers
Roof-mounted fan 54 We refer customers to our Terms of Sale
– Air/air 62, 63
– for the office sector 55 and Delivery.
– Air/water 104 – 109
RTT roof-mounted fans 54
Wide-range power pack
– for thermoelectric cooler 192

S
Section doors for cooling modules 71
Service 298, 299
Shallow air duct system 175
Shallow duct extension 175
Shielding
– Horizontal 187
– Vertical 186
SK BUS system 180
Software service 195
Spare filter mat
– for fan-and-filter units/outlet filters 191
– for filter holder 191
– for thermoelectric cooler 191
Speed control 179

304 Rittal System Climate Control


All in all – solutions from Rittal

Industrial Enclosures

Power Distribution

Electronic Packaging

System Climate Control Cooling units  Recooling units  Heat exchangers


Fan-and-filter units  19˝ climate control  Heaters  IT cooling

IT Solutions

Communication Systems

Rittal has one of the largest ranges of enclosures available Fully assembled and functional. Wherever in the world you
04/09  E384

for immediate delivery. However, Rittal also supplies inte- develop and implement solutions for yourself and your
grated solutions – up to Level 4. This comprises mechanical customers, we are close at hand. The global alliance
installation, power supply, electronic components, climate between production, distribution and service guarantees
control and central monitoring. For all of your requirements. closeness to the customer. Worldwide!