Sie sind auf Seite 1von 26

Startup/Adjustments

Section 4
Application Series Section
Rate of Flow 40 Series 4-1
Pressure Relief 50 Series 4-2
Pump Control Valves 60 Series 4-3
Pressure Reducing 90 Series 4-4
Float Valves 120/420 Series 4-5
Solenoid Operated 130 Series 4-6
Altitude Valves 210 Series 4-7

193
194
Section
4-1 Rate Of Flow 40 Series
Start-up and Adjustments
Schematic Diagram 3

2
Item Description
1 Hytrol (Main Valve)
2 X58C Restricting Fitting D1

3 CDHS18 Differential Control


S
4 X52E Orifice Plate Assembly Y
C B1

Optional Features B2
B1 B1 D2
Item Description D3

A X46A Flow Clean Strainer


40-01/640-01 Rate of Flow Control B CK2 Cock (Isolation Valve)
C CV Flow Control (Closing) INLET OUTLET

D Check Valves with Cock 4


A
S CV Flow Control (Opening)
1
Y X43 "Y" Strainer

Rate of Flow Start-up and Adjustment Instructions 40-01/640-01

1. Install pressure gauges at main valve inlet/outlet. line it will be necessary to loosen the cover bolts
Place gauges in unused body tappings. Downstream between 10 o'clock and 2 o'clock to vent air from main
gauge can be installed in unused 3/8" CDHS-18 valve cover (Limit vertical installation to valves 6" and
Differential Control (item # 3) body tapping. In addition smaller). Tighten pipe plug or cover bolts after all air
a flow meter is required to set the rate of flow through is removed. Caution: only loosen pipe plug or cover
the valve. bolts enough to allow the air trapped in the cover to
escape. Loosen tubing nuts in high points in pilot sys-
2. Install X101 Valve Position Indicator in center cover tem to remove air from the pilot control system.
tapping of main valve (if available). Tighten tube nuts after all air is removed.

3. Make sure low pressure sensing line (not supplied 8. Open downstream isolation valve and establish a
by Cla-Val) is connected to the low pressure sensing flow in the system.
port on the X52A-1 Orifice Plate Assembly (item # 4)
from cover of CDHS-18 Differential Control (item # 3). 9. Slowly adjust the CDHS-18 Differential Control
Orifice plate assembly should be 1-5 pipe diameters (item # 3) observing the flow rate via the meter until
downstream of main valve. the desired flow rate is achieved (clockwise to
increase setting or counter-clockwise to decrease
4. Open all isolation valves in pilot system (valves 4" setting). Adjust CV flow controls until desired valve
and larger). Remove pilot caps and loosen all jam opening or closing speeds are obtained. Adjust open-
nuts. ing rate so that valve opens slowly to desired flow rate
and does not over shoot setting. Adjust closing rate
5. Adjust CV flow controls (opening/closing speeds) if so valve does not cause excessive system pressure
included in pilot system. Turn control clockwise until surging upon closing.
closed then back out three turns to start.
10. All valve adjustments are now set. Lockup all jam
6. Open inlet isolation valve slowly to pressurize main nuts to retain settings. Replace all pilot caps.
valve.

7. Bleed air from main valve cover by loosening pipe 4


plug in center of main valve cover or X101 Valve –
position Indicator housing. If valve is installed in vertical 1

195
Combination Rate of Flow Controller & Solenoid Shut-off Valve 43-01/643-01

Schematic Diagram
Item Description H
CS3
1 Hytrol (Main Valve) 3 2
SOLENOID DRAIN
1 4
2 X58C Restriction Fitting TO ATMOSPHERE

2 5
3 100-01 Hytrol (Reverse Flow)
4 CDHS18 Differential Control D1
B1
5 CS3 Solenoid Control
3
6 X52E Orifice Plate Assembly Y
S C

B2
Optional Features B1 D2
D3
Item Description B1

A X46A Flow Clean Strainer


43-01/643-01 Combination B CK2 Cock (Isolation Valve) INLET OUTLET

C CV Flow Control (Closing) 6


Rate of Flow Controller & A
D Check Valves with Cock
Solenoid Shut-off Valve H Solenoid Drain to Atmosphere
1

S CV Flow Control (Opening)


Y X43 “Y” Strainer

Combination Rate of Flow Controller & Solenoid Shut-off Valve and Adjustment Instructions 43-01/643-01

1. Install pressure gauges at main valve inlet/outlet. A. Energized to open main valve supply pressure
Place gauges in unused body tappings. Downstream comes to port # 3 on CS3 solenoid (item #5), port # 1
gauge can be installed in the unused 3/8" CDHS-18 is connected to the cover of the 3/8" auxiliary hytrol
Differential Control (item # 3) body tapping. In addition (item # 3), and port # 2 is vented to atmosphere (cat-
a flow meter is require to set the rate of flow through alog number suffix H) or to the downstream side of the
the valve. valve standard. Also check the Asco Solenoid catalog
number 8320G136 normally open.
2. Install X101 Valve Position Indicator in center cover
tapping of main valve (if available). B. De-energized to open main valve supply pressure
comes to port # 2 on CS3 solenoid (item # 5), port # 1
3. Open all isolation valves in pilot system (valves 4" is connected to the cover of the 3/8" auxiliary hytrol
and larger). Remove pilot caps and loosen all jam nuts. (item # 3), and port # 3 is vented to atmosphere (cat-
alog number suffix H) or to the downstream side of the
4. Make sure low pressure sensing line (not supplied valve standard. Also check the ASCO Solenoid cata-
by Cla-Val) is connected to the low pressure sensing log number 8320G132 normally closed.
port on the X52A-1 Orifice Plate Assembly (item # 6)
from the cover of the CDHS-18 Differential Control 7. Open inlet isolation valve slowly to pressurize main valve.
(item # 4). Orifice plate assembly should be 1-5 pipe
diameters downstream of main valve. 8. Bleed air from main valve cover by loosening pipe
plug in center of main valve cover or X101 Valve posi-
5. Adjust CV flow controls (opening/closing speeds) if tion Indicator housing. If valve is installed in a vertical
included in pilot system. Turn control clockwise until line it will be necessary to loosen the cover bolts
closed then back out three turns to start. between 10 o'clock and 2 o'clock to vent air from main
valve cover (Limit vertical installation to valves 6" and
6. Locate the CS3 Solenoid Control (item # 5) in the smaller). Tighten pipe plug or cover bolts after all air is
pilot system. Make sure proper voltage is supplied to removed. Caution: only loosen pipe plug or cover
the coil. If the unit is equipped with a manual operator bolts enough to allow the air trapped in the cover to
make sure it is backed all the way out counter-clock- escape. Loosen tubing nuts in high points in pilot sys-
wise (rotating the red thumb screw clockwise simu- tem to remove air from the pilot control system.
lates energization of the coil). Solenoid can be sup- Tighten tube nuts after all air is removed.
plied energized to open main valve or de-energized to
open main valve. You can determine the valve opera-
tion in two ways:

196
Combination Rate of Flow Controller & Solenoid Shut-off Valve 43-01/643-01

9. Open downstream isolation valve and establish a 11. All valve adjustments are now set. Lockup all jam
flow in the system. To accomplish this the CS3 solenoid nuts to retain settings. Replace all pilot caps.
(item #5) must be electrically energized to open the
main valve under command of the CDHS-18 12. To close the main valve on solenoids energized to
Differential Control (item # 4) in valves so equipped. If open remove electrical power from the solenoid. This
the valve is de-energized to open no electrical power will connect ports 3 & 1 on the solenoid directing inlet
is required to open the main valve. In valves so pressure into the cover of the 3/8" auxiliary hytrol closing
equipped if the CS3 solenoid (item #5) is energized it. This will in turn direct inlet pressure into the cover
the main valve closes. The porting sequence for the of the main valve closing it.
CS3 solenoid (energized to open or de-energized to
open) appears in the valve schematic. Always check 13. To close the main valve on solenoids de-energized
the effect in the system before starting. to open apply electrical power to the solenoid. This will
connect ports 2 & 1 on the solenoid directing inlet
10. Slowly adjust the CDHS-18 Differential Control pressure into the cover of the 3/8" auxiliary hytrol closing
observing the flow rate via the meter until the desired it. This will in turn direct inlet pressure into the cover of
flow rate is achieved (clockwise to increase setting or the main valve closing it.
counter-clockwise to decrease setting). Adjust CV flow
controls until the desired valve opening or closing
speeds are obtained. Adjust the opening rate so that
valve opens slowly to the desired flow rate and does
not over shoot the setting. Adjust closing rate so the
valve does not cause excessive system surging upon
closing.

4

1

197
Combination Rate of Flow & Pressure Reducing Valve 49-01/649-01
Schematic Diagram
Item Description 3
1 Hytrol (Main Valve) D1 2
5

2 X58A Restriction Fitting


3 CRA Pressure Reducing Control
4 X52E Orifice Plate Assembly
5 CDHS18 Differential Control B1

C
S
Y D2
Optional Features
D3 B2

Item Description B1

A X46A Flow Clean Strainer B1

B CK2 Cock (Isolation Valve)


C CV Flow Control (Closing)
INLET OUTLET
D Check Valves with Cock
49-01/649-01 Combination Rate of S CV Flow Control (Opening) A
4

Flow & Pressure Reducing Valve Y X43 "Y" Strainer 1

Combination Rate of Flow & Pressure Reducing Valve Start-up and Adjustment Instructions 49-01/649-01
1. Install pressure gauges at main valve inlet/outlet. 7. Open inlet isolation valve slowly to pressurize main
Place gauges in unused body tappings. Downstream valve.
gauge can be installed in unused 3/8" CDHS-18
Differential Control (item # 3) body tapping. In addition 8. Bleed air from main valve cover by loosening pipe
a flow meter is required to set the rate of flow through plug in center of main valve cover or X101 Valve posi-
the valve. tion Indicator housing. If valve is installed in vertical
line it will be necessary to loosen the cover bolts
2. Install X101 Valve Position Indicator in center cover between 10 o'clock and 2 o'clock to vent air from main
tapping of main valve (if available). valve cover (Limit vertical installation to valves 6" and
smaller.) Tighten pipe plug or cover bolts after all air
3. Open all isolation valves in pilot system (valves 4" is removed. Caution: only loosen pipe plug or cover
and larger). Remove pilot caps and loosen all jam bolts enough to allow the air trapped in the cover to
nuts. escape. Loosen tubing nuts in high points in pilot sys-
tem to remove air from the pilot control system.
4. Observe the setting on the CRA Pressure Reducing Tighten tube nuts after all air is removed.
Control (item #3). There is a tag attached to the pilot
cover with the factory setting. If the pilot has a 15-75 9. Open downstream isolation valve and establish a
PSI spring range each 360 degree turn in/out changes low flow in the system. Refer to minimum flow require-
the setting 9 PSI. The 30-300 PSI spring range has a ments for each valve size to set CRA Pressure
27 PSI change for each 360 degree turn in/out. Alter Reducing Control. Always check the effect in the sys-
the factory setting (turn adjustment clockwise/counter- tem before starting.
clockwise) until the set point of the control is close to
the required setting. This setting is approximate and
may have to be changed once the valve is pressur- Size Minimum Flow (gpm)
ized. Actual pressure settings must be made under a 1 1/4-1 1/2” 15
flowing condition. 2” 15
2 1/2” 20
3” 30
5. Adjust CV flow controls (opening/closing speeds) if
4” 50
included in pilot system. Turn control clockwise until 115
6”
closed then back out three turns to start. 8” 200
10” 300
6. Make sure low pressure sensing line (not supplied 12” 400
by Cla-Val) is connected to the low pressure sensing 14” 500
port on the X52A-1 Orifice Plate Assembly (item # 4) 16” 650
from the cover of the CDHS-18 Differential Control 24” 1500
(item # 5). Orifice plate assembly should be 1-5 pipe
diameters downstream of main valve.

198
Combination Rate of Flow & Pressure Reducing Valve 49-01/649-01

10. Slowly adjust the CRA Pressure Reducing Control during adjustment (clockwise to increase flow rate and
(item #3) observing the down stream pressure gauge counter-clockwise to decrease flow rate). The adjust-
until the desired pressure is achieved (clockwise to ment range on the control is 30-480 inches of water.
increase setting or counter-clockwise to decrease set- This is the only spring range supplied for this pilot. In
ting). Adjust CV flow controls until desired valve open- most cases the orifice bore supplied in the orifice
ing or closing speeds are obtained. Adjust opening plate assembly is sized to produce a minimum of 100
rate so that valve opens slowly to desired outlet pres- inches of differential at the rated flow.
sure and does not over shoot setting. Adjust closing
rate so valve does not cause excessive system pres- 12. All valve adjustments are now set. Lockup all jam
sure surging upon closing. nuts to retain settings. Replace all pilot caps.

11. Next adjust CDHS-18 Differential Control until


desired flow rate is achieved. Observe flow meter

4

1

199
Section
4-2 Pressure Relief 50 Series
Start-up and Adjustments

Schematic Diagram F
Item Description 3

1 Hytrol (Main Valve)


2 X42N-2 Strainer & Needle Valve
3 CRL Pressure Relief Control 2
B2

S
Optional Features D1

Item Description
B CK2 Cock (Isolation Valve) B1 B1 D2
D3 H
D Check Valves with Cock
F Remote Pilot Sensing DRAIN TO
ATMOSPHERE
H Drain to Atmosphere
S CV Speed Control (Opening) INLET OUTLET

50-01/650-01 Pressure Relief,


Pressure Sustaining Valve 1

Pressure Relief, Pressure Sustaining Valve Start-up and Adjustment Instructions 50-01/650-01

1. Install pressure gauge at main valve inlet. Place Position Indicator housing. If valve is installed in a ver-
gauge in unused inlet body tapping. tical line it will be necessary to loosen the cover bolts
between 10 o'clock and 2 o'clock to vent air from main
2. Install X101 Valve Position Indicator in center cover valve cover. Tighten pipe plug or cover bolts after all
tapping of main valve (If available). air is removed. Caution: only loosen pipe plug or
cover bolts enough to allow the air trapped in the cover
3. Open all isolation valves in pilot system ( valves 4" to escape. Loosen tubing nuts in high points in pilot
and larger). Remove pilot caps and loosen all jam system to remove air from the pilot control system.
nuts. Tighten tube nuts after all air is removed. It may be
necessary to loosen several screws on the cover of the
4. Adjust needle valve in X42N-2 (Item # 2). Open nee- CRL Pressure Relief Control (item # 3) to completely
dle valve 1/4 turn to start. Do not close needle valve exhaust air from the control. This depends on the
all the way or main valve will not close. The needle orientation of the control in the pilot system.
valve may require further adjustment depending on
valve size. 8. Raise normal system operating pressure 10 PSI
under a flowing condition. Always check the effect in
5. Close the CRL Pressure Relief Control (Item # 3) all the system before starting. Slowly adjust the CRL
the way by turning the adjustment clockwise. Observe Pressure Relief Control (item # 3) counter-clockwise to
the setting on the control. There is a tag attached to allow the main valve to just begin to open then stop.
the pilot cover with the factory setting. If the pilot has a turn CRL adjustment clockwise until main valve closes.
0-75 PSI spring range each 360 degree turn in/out Lower system pressure to its normal flowing setting.
changes the setting 9 PSI. The 20-200 PSI spring Pressure relief valve is now set approximately 10 PSI
range has a 27 PSI change for each 360 degree turn above normal operating pressure. Using the above
in/out. Increase the factory setting (turn adjustment procedure the relief valve can be set at any pressure
clockwise) until the set point of the control is at least above normal system operating pressure.
20 PSI above the normal system operating pressure.
This setting is approximate and may have to be 9. Raise the system pressure to test the relief valve set
increased once the valve is pressurized. point and opening speed. The relief valve is designed
to open quickly and close slowly. If the opening speed
6. Open inlet isolation valve slowly to pressurize main requires adjustment change setting on needle valve of
valve. If relief valve begins to open adjust CRL X42N-2. Turn needle valve clockwise to increase
Pressure Relief Control clockwise until valve closes. opening speed response and counter-clockwise to
decrease opening speed response.
7. Bleed air from main valve cover by loosening pipe
plug in center of main valve cover or X101 Valve
200
Pressure Relief, Pressure Sustaining Valve 50-01/650-01

10. All valve adjustments are now set. Lockup all jam or cover bolts enough to allow the air trapped in the
nuts to retain settings. Replace all pilot caps. cover to escape. Loosen tubing nuts in high points to
remove air from the pilot control system. Tighten tube
Note: The 50-01/650-01 Pressure Relief Valve can nuts after all air is removed. It may be necessary to
also be used as a pressure sustaining or back pressure loosen several screws on the cover of CRL
control valve. There are no modifications required to Pressure Relief Control ( item # 3) to complete-
the main valve or pilot control system to use this valve ly exhaust air from the control. This depends on
in a pressure sustaining or back pressure application. the orientation of the control in the pilot system. 4
However the adjustment procedure is different. Refer
to items 1,2,&3 to start the adjustment procedure.

15. Open the down stream isolation valve and
establish a flow in the system. Always check the
2
Then: effect in the system before starting.
11. Adjust needle valve in X42n-2 (item # 2). Open
needle valve 1/2 turn to start. Do not close needle 16. Slowly adjust the CRL Pressure Relief Control
valve all the way or main valve will not close. The nee- (item #3) observing the inlet pressure gauge until the
dle valve may require further adjustment depending on desired back pressure is achieved.
valve size.
17. All valve adjustments are now set. Lock up all jam
12. Observe the setting on the CRL Pressure Relief nuts to retain settings. Replace all pilot caps.
Control (item # 3). There is a tag attached to the pilot
cover with the factory setting. If the pilot has a 15-75
PSI spring range each 360 degree turn in/out changes
the setting 9 PSI. The 20-200 PSI spring range has a Note: The 50-01/650-01 control valve uses the X42N-2
27 PSI change for each 360 degree turn in/out. Using Strainer and Needle Valve Assembly. The strainer
this information adjust the pilot control setting to the screen in this assembly has a small surface area. This
desired back pressure. This setting is approximate screen can clog up quickly especially on the start up of
and may have to be changed under a flowing condition. a new system. When the screen clogs up the valve
malfunctions due to loss of the supply pressure to the
13. Open inlet isolation valve slowly to pressurize pilot control system. Check the screen periodically.
main valve.

14. Bleed air from main valve cover by loosening the


pipe plug in the center of the main valve cover or X101
Valve Position Indicator housing. If valve is installed in
a vertical line it will be necessary to loosen the cover
bolts between 10 o'clock and 2 o'clock to vent air from
the main valve cover. Tighten pipe plug or cover bolts
after all air is removed. Caution: only loosen pipe plug

201
Fire Pump Relief Valve 50B-4KG-1/2050B-4KG1

Schematic Diagram
Item Description
4 3
1 100-06 Hytrol (Main Valve)
2 CRL Pressure Relief Control
3 X144A Strainer & Orifice Assembly 5
4 81-01 Check Valve
5 Pressure Gauge
6 X46A Flow Clean Strainer
INLET OUTLET
6
50B-4KG-1/2050B-4KG-1
Fire Pump Relief Valve
1

Fire Pump Relief Valve Start-up and Adjustment Instructions 50B-4KG-1/2050B-4KG-1

1. Install pressure gauge at main valve inlet. Place the CRL Pressure Relief Control (item # 2) to completely
gauge in unused inlet body tapping of main valve. exhaust air from the control. This depends on the
orientation of the control in the pilot system. Please
2. Install X101C Valve Position Indicator in center note that for vertical turbine pump systems the air
cover tapping of main valve (If available). bleeding procedure can only be performed when the
pump is running and there is flow through the valve.
3. Remove pilot cap and loosen jam nut on CRL Always check the effect in the system before starting.
Pressure Relief Control (item # 2).
7. Start the pump and observe the flow through the
4. Observe the setting on the control. There is a tag valve with the system sight cone and X101C valve
attached to the pilot cover with the factory setting. position indicator. On vertical turbine pump systems
The 20-200 PSI spring range has a 28 PSI change for perform the air bleeding procedure at this time before
each 360 degree turn in/out. The 100-300 PSI spring adjusting the pilot control. Adjust the relief valve inlet
range has an 18 PSI change for each 360 degree turn pressure by changing the setting on the CRL Pressure
in/out. Change the factory setting (turn adjustment Relief Control (item # 2) and observing the inlet pressure
clockwise to increase setting or counter-clockwise to gauge. Make setting changes slowly. Turn the adjust-
decrease setting) until the required set point of the ment clockwise to increase the inlet pressure and
control is obtained. This setting is approximate and counter-clockwise to decrease the inlet pressure. The
the final pilot control setting must be made under a 50B-4KG-1 Fire Pump Relief Valve is designed to
flowing condition. open quickly and close slowly. The valve pilot control
system includes a check valve (item # 4) and a pressure
5. On centrifical pump systems, open an isolation gauge in the valve cover (item # 5). When cover pres-
valve in the system and slowly pressurize the valve sure is higher then inlet pressure, the check valve
using the pump suction pressure only. For vertical tur- (item # 4) closes. This maintains the higher pressure
bine pump systems the pump must be started to sup- in the main valve cover chamber keeping the main
ply pressure to the relief valve. valve closed. The cover pressure gauge (item # 5)
should always indicate a positive pressure even when
6. Bleed air from main valve cover by loosening the the valve is closed.
pipe plug in the center of main valve cover or the bush-
ing gland on the X101C Valve Position Indicator. If 8. The valve adjustment is now set. Lockup the jam
valve is installed in a vertical line it will be necessary nut on the CRL Pressure Relief Control (item # 2)to
to loosen the cover bolts between 10 o'clock and 2 retain the setting and replace the pilot cap. Turn off the
o'clock to vent air from main valve cover. Tighten pipe pump after the initial test is complete.
plug, cover bolts, or bushing gland after all air is
removed. Caution: only loosen pipe plug, cover bolts
or bushing gland enough to allow the air trapped in the
cover to escape. Loosen tubing nuts in high points in Note: Periodic cleaning of the strainer screen in the X44A
pilot system to remove air from the pilot control system. Strainer & Orifice assembly (item #3) is recommended.
Tighten tube nuts after all air is removed. It may be
necessary to loosen several screws on the cover of

202
Combination Back Pressure & Solenoid Shut-Off Valve 58-01/658-01

Schematic Diagram 4
H
CS3
Item Description 3
1
2
DRAIN TO
ATMOSPHERE
1 Hytrol (Main Valve) F 3

REMOTE
2 X42N-3 Strainer & Needle Valve SENSING
2

3 CRL Pressure Relief Control


5
4 CS3 Solenoid Control D1 B2

5 100-01 Hytrol (Reverse Flow) S


D2

Optional Features B1 B1
D3

Item Description 4
58-01/658-01 Combination Back
B
D
Shutoff Cocks - Isolates Pilot System
Check Valves with Cock
INLET OUTLET

Pressure & Solenoid Shut-off Valve
F
H
Remote Pilot Sensing
Drain to Atmosphere 1 2
S CV Speed Control (Opening)

Combination Back Pressure & Solenoid Shut-Off Valve Start-up and Adjustment Instructions 58-01/658-01

1. Install pressure gauges at main valve inlet/outlet. Place gauges atmosphere (catalog number suffix H) or to the downstream side
in unused body tappings. of the valve standard. Also check the ASCO Solenoid catalog num-
ber 8320G132 normally closed.
2. Install X101 Valve Position Indicator in center cover tapping of
main valve (if available). 8. Open inlet isolation valve slowly to pressurize main valve.

3. Open all isolation valves in pilot system (valves 4" and larger). 9. Bleed air from main valve cover by loosening pipe plug in cen-
Remove pilot caps and loosen all jam nuts. ter of main valve cover or X101 Valve position Indicator housing. If
valve is installed in a vertical line it will be necessary to loosen the
4. Observe the setting on the CRL Pressure Relief Control (item # cover bolts between 10 o'clock and 2 o'clock to vent air from main
3). There is a tag attached to the pilot cover with the factory set- valve cover (Limit vertical installations of valves to 6" and smaller).
ting. If the pilot has a 0-75 PSI spring range each 360 degree turn Tighten pipe plug or cover bolts after all air is removed. Caution:
in/out changes the setting 8.5 PSI. The 20-200 PSI spring range only loosen pipe plug or cover bolts enough to allow the air trapped
has a 28 PSI change for each 360 degree turn in/out. Alter the in the cover to escape. Loosen tubing nuts in high points in pilot
factory setting (turn adjustment clockwise/counter-clockwise) system to remove air from the pilot control system. Tighten tube
until the set point of the control is close to the required setting. This nuts after all air is removed.
setting is approximate and may have to be changed once the valve
is pressurized. Actual pressure settings must be made under a flow- 10. Open downstream isolation valve and establish a low flow in
ing condition. the system. To accomplish this the CS3 solenoid (item # 5) must
be electrically energized to open the main valve under command
5. Adjust CV flow control (opening speed) if included in pilot sys- of the CRL Pressure Relief Control (item #3) in valves so
tem. Turn control clockwise until closed then back out three turns equipped. If the valve is de-energized to open no electrical power
to start. is required to open the main valve. In valves so equipped if the
CS3 solenoid (item #4) is energized the main valve closes.The
6. Adjust X42N-3 Needle Valve and Strainer Assembly (item # 2). porting sequence for the CS3 solenoid (energized to open or de-
Loosen jam nut and close needle valve all the way clockwise. Then energized to open appears in the valve schematic) Refer to mini-
back out 1/2 turn to start. Needle valve may require further adjust- mum flow requirements for each valve size. Always check the effect
ment depending on valve size. in the system before starting.

7. Locate the CS3 Solenoid Control (item # 4) in the pilot system. 11. All valve adjustments are now set. Lock all jam nuts to retain
Make sure proper voltage is supplied to the coil. If the unit is settings. Replace all pilot caps.
equipped with a manual operator make sure it is backed all the way
out counter-clockwise (rotating the red thumb screw clockwise sim- 12. To close the main valve on solenoids energized to open
ulates energization of the coil.) Solenoid can be supplied ener- remove electrical power from the solenoid. This will connect ports
gized to open main valve or de-energized to open main valve. You 3 & 1 on the solenoid directing inlet pressure into the cover of the
can determine the valve operation in two ways: main valve closing it.
A) Energized to open main valve supply pressure comes to port # To close the main valve on solenoid de-energized to open apply
3 on solenoid, port # 1 is connected to the cover of the 3/8" auxil- electrical power to the solenoid.
iary hytrol (item # 5), and port # 2 is vented to atmosphere (catalog This will connect ports 2 & 1 on the solenoid directing inlet pres-
number suffix H. or to the downstream side of the valve standard. sure into the cover of the 3/8” auxilliary hytrol (item #5) closing it.
Also check the ASCO Solenoid catalog number 8320G136 nor- This will inturn direct inlet pressure into the cover of the main valve
mally open. closing it.

B. De-energized to open main valve supply pressure comes to port Refer to valve schematic for location of pilot controls.
# 2 on CS3 solenoid (item # 5), port # 1 is connected to the cover
of the 3/8" auxiliary hytrol (item # 5), and port # 3 is vented to

203
Section
4-3 Pump Control Valve 60 Series
Start-up and Adjustments

Schematic Diagram
S 3
2A
Item Description 2 1
1 Powercheck (Main Valve) D 2B
2 CV Flow Control
3 CSM11-A2-2 Solenoid Control 4
4 X105LCW Switch Assembly
5 CVS-1 Shuttle Valve

Optional Features
A OUTLET
B INLET
Item Description B
Y
A X46A Flow Clean Strainer Y
B CK2 Cock (Isolation Valve) A 1
2 3
Y X43 "Y" Strainer COM. 1
60-11/660-11 Booster Pump Control Valve 5

Booster Pump Control Valve Start-up and Adjustment Instructions 60-11/660-11


1. Install pressure gauges at main valve inlet/outlet 7. Bleed air from main valve cover by loosening packing
using main valve body tappings. gland nut on the X105 Micro Switch Assembly.
(item # 4) Tighten packing gland nut after all air is
2. Open all isolation valves in pilot system (valves 4" removed. Caution: only loosen packing gland nut
and larger). enough to allow the air trapped in the cover to escape.
Loosen tubing nuts in high points in pilot system to
3. Adjust CV Flow Controls (opening speed item remove air from the pilot control system. Tighten tube
2B/closing speed item 2A) in pilot system. Turn control nuts after all air is removed.
clockwise until closed then back out three turns to start.
8. Open upstream isolation valve and start the pump to
4. Adjust X105 Micro Switch (item # 4) collar on actu- establish a flow and open the valve. To accomplish
ating stem. Loosen collar set screws and slide collar this the CSM-11 solenoid (item # 3) must be electrical-
along stem until it contacts micro switch arm roller. ly energized to open the valve. As the valve opens the
Slide collar to push back micro switch arm to open collar on the actuating stem of the micro switch (item
switch. You will hear a click indicating the switch is #4) travels upward, away from the micro switch arm.
open. Tighten set screws in collar at this point. This closes the micro switch and locks the pump
starter circuit on line. Always check the effect in the
5. Locate the CSM-11 Solenoid Control (item #3) in system before starting.
the pilot system. Make sure proper voltage is supplied
to the coil. Make sure the plunger style manual operator 9. Observe the opening rate of the valve and adjust
is not engaged. Rotate the plunger clockwise and push the CV opening speed control (item # 2B) to prevent
down at the same time to activate the manual operator the pump starting surge from being transmitted into
feature. This simulates energization of the coil. The the system. Turning the adjustment clockwise decreas-
manual operator will lock in this position. Rotate the es the valve opening speed. Turning the adjustment
manual operator counter-clockwise and the spring load counter-clockwise increases the valve opening speed.
in the coil will return the plunger to its original or “up”
position.

6. Open outlet isolation valve slowly to pressurize the


main valve.

204
Booster Pump Control Valve 60-11/660-11

10. Engage the pump stopping sequence. The pump the valve closes the actuating stem collar moves
should continue to run and the CSM-11 solenoid toward the micro switch (item # 4) opening it and stop-
(item# 3) should de-energize. This initiates the closing ping the pump.
cycle of he valve. Observe the closing rate of the valve 11. All valve adjustments are now set. Lockup all jam
and adjust the CV closing speed control (item # 2A.) nuts to retain settings.
to prevent the pump stopping surge from being trans- Refer to the valve schematic for location of pilot controls.
mitted into the system. Turning the adjustment clock-
wise decreases the closing rate. Turning the adjust-
ment counter-clockwise increases the closing rate. As

Suitable for 60 & 61 Series Valves

Wiring Diagram
Off
4
Auto-Off-Hand = Selector Switch
Auto Hand

L2

1CR = Relay, DPST Normally Open
L1
A
SW1
3CR3
1CR
3
2CR = Relay, DPST Normally Open
3CR = Relay, TPST Normally Open H
SW1 = Switch, Remote Start,Automatic
SW2 = Switch, SPDT, Valve Limit Switch 1CR
PVS
Connect to N.C. Terminal
1CR 3CR1
PVS = Pilot Valve Solenoid 2CR
M = Pump Motor Starter
N.C. 2CR
COM. 3CR
Note: SW2 and PVS supplied by Cla-Val. All other electri-
cal items supplied by customer. SW2 is included in the SW2 N.O.
X105L switch assembly which is mounted on the pump 3CR2
control valve cover. 2CR
M

205
Booster Pump Control Valve 60-31/660-31

Schematic Diagram CS3


3 2
3

1
7B
Item Description 2
1 Hycheck (Main Valve) N.C. COM.

2 102C-3H Three Way Hytrol N.O.

3 CS3SM Solenoid Control 7B

4 X105LCW Switch Assembly


5 CDC Disk Check Valve 5 6
4
6 CDC/CSC Check Valve
7 CNA Angle Valve Y
7A B

8 CK2 Cock (Isolation Valve) B


B 8

Item Description
A X46A Flow Clean Strainer INLET OUTLET

60-31/660-31 Booster Pump B CK2 Cock (Isolation Valve)


A

Control Valve Y X43 "Y" Strainer 1

Booster Pump Control Valve Start-up and Adjustment Instructions 60-31/660-31


1. Install pressure gauges at main valve inlet/outlet 8. Open upstream isolation valve and start the pump
using main valve body tappings. to establish a flow and open the valve. To accomplish
2. Open all isolation valves in pilot system. this the CS3SM solenoid (item # 3) must be electrically
energized to open the valve. As the valve opens the
3. Adjust CNA Angle valve (opening speed item # collar on the actuating stem of the micro switch (item
7B/closing speed item # 7A) in pilot system. Turn control #4) travels upward, away from the micro switch arm.
clockwise until closed then back out three turns to This closes the micro switch and locks the pump
start. Do not leave these controls closed all the way or starter circuit on line. Always check the effect in the
the valve will not open or close. system before starting.

4. Adjust X105 Micro Switch (item # 4) collar on actuating 9. Observe the opening rate of the valve and adjust the
stem. Loosen collar set screws and slide collar along CNA angle valve opening speed control (item # 7B) to
stem until it contacts micro switch arm roller. Slide col- prevent the pump starting surge from being transmit-
lar to push back micro switch arm to open switch. You ted into the system. Turning the adjustment clockwise
will hear a click indicating the switch is open. Tighten decreases the valve opening speed. Turning the
set screws in collar at this point. adjustment counter-clockwise increases the valve
opening speed.
5. Locate the CS3SM Solenoid Control (item # 3) in
the pilot system. Make sure proper voltage is supplied 10. Engage the pump stopping sequence. The pump
to the coil. Make sure the manual operator is not should continue to run and the CS3SM solenoid
engaged. Rotate the red thumb screw all the way out (item# 3) should de-energize. This initiates the closing
counter-clockwise to disengage the manual operator cycle of he valve. Observe the closing rate of the valve
feature. Rotating the red thumb screw clockwise sim- and adjust the CNA angle valve closing speed control
ulates energization of the coil. (item # 7A) to prevent the pump stopping surge from
being transmitted into the system. Turning the adjust-
6. Open outlet isolation valve slowly to pressurize the ment clockwise decreases the closing rate. Turning
main valve. the adjustment counter-clockwise increases the clos-
ing rate. As the valve closes the actuating stem collar
7. Bleed air from main valve cover by loosening pack- moves toward the micro switch (item # 4) opening it
ing gland nut on the X105 Micro Switch Assembly. and stopping the pump.
(item # 4) Tighten packing gland nut after all air is
removed. Caution: only loosen packing gland nut 11. All valve adjustments are now set. Lockup all jam
enough to allow the air trapped in the cover to escape. nuts to retain settings.
Loosen tubing nuts in high points in pilot system to
remove air from the pilot control system. Tighten tube
nuts after all air is removed.

206
Pump Control Valve 61-02/661-02
5 6 7
INDEPENDENT
OPERATING
Schematic Diagram PRESSURE
2

1 2
Item Description D
1 Powertrol (Main Valve) 3A 3B

2 CSM11-A2-2 Solenoid Control


4
3 CV Flow Control
4 X105LOW Switch Assembly
5 CK Cock (Isolation Valve)
6 X43 "Y" Strainer
7 Union
INLET OUTLET
61-02/661-02 Pump
Control Valve 1

Pump Control Valve Start-up and Adjustment Instructions 61-02/661-02


1. Install pressure gauge at main valve inlet using main
valve body tapping.
will open. When the valve is completely open
the air can be vented from the main valve power
4
section by loosening the tubing nut by the clos- –
2. Open isolation valve in pilot system. ing speed control (item # 3B). Tighten tube nut 3
after all air is vented. Always check the effect in
3. Adjust CV Flow Controls (opening speed item the system before starting.
3A/closing speed item 3B) in pilot system. Turn control
clockwise until closed then back out three turns to start. 7. Start the pump to establish a flow through the valve.
The CSM-11 solenoid (item # 2) must be electrically
4. Adjust X105 Micro Switch (item # 4) collar on actu- energized to close the valve. As the valve closes the
ating stem. Loosen collar set screws and slide collar collar on the actuating stem of the micro switch (item #
along stem until it contacts micro switch arm roller. 4) travels downward, away from the micro switch arm.
Slide collar to push back micro switch arm to open This closes the micro switch and locks the pump
switch. You will hear a click indicating the switch is starter circuit on line. Always check the effect in the
open. Tighten set screws in collar at this point. system before starting.

5. Locate the CSM-11 Solenoid Control (item # 2) in 8. Observe the closing rate of the valve and adjust the
the pilot system. Make sure proper voltage is supplied CV closing speed control (item # 3B) to prevent the
to the coil. Make sure the plunger style manual operator pump starting surge from being transmitted into the
is not engaged. Rotate the plunger clockwise and system. Turning the adjustment clockwise decreases
push down at the same time to activate the manual the valve opening speed. Turning the adjustment
operator feature. This simulates energization of the counter-clockwise increases the valve opening speed.
coil. The manual operator will lock in this position.
Rotate the manual operator counter-clockwise and the 9. Engage the pump stopping sequence. The pump
spring load in the coil will return the plunger to its should continue to run and the CSM-11 solenoid
original or normal position. (item# 2) should de-energize. This initiates the opening
cycle of the valve. Observe the opening rate of the
6. This valve is held open by the static system pres- valve and adjust the CV opening speed control (item #
sure. To bleed the air from the main valve cover, power 3A) to prevent the pump stopping surge from being
section, and pilot system turn the manual operator on the transmitted into the system. Turning the adjustment
CSM-11 Solenoid Control (item # 2) as indicated in clockwise decreases the opening rate. Turning the
paragraph # 5 to close the valve. When the valve is adjustment counter-clockwise increases the opening
completely closed bleed the air from the main valve rate. As the valve opens the actuating stem collar
cover by loosening packing gland nut on the X105 moves toward the micro switch (item # 4) opening it
Micro Switch Assembly. (item # 4) Tighten packing and stopping the pump.
gland nut after all air is removed. Caution: only loosen
packing gland nut enough to allow the air trapped in 10. All valve adjustments are now set. Lockup all jam
the cover to escape. Loosen tubing nuts in high points nuts to retain settings.
in pilot system to remove air from the pilot control
system. Tighten tube nuts after all air is removed.
Return the manual operator on the CSM-11 Solenoid Refer to the valve schematic for location of pilot controls.
Control (item # 2) to its normal position and the valve
207
Section
4-4 Pressure Reducing Valve 90 Series
Start-up and Adjustments
Schematic Diagram
3
Item Description D1 2

1 Hytrol (Main Valve)


2 X58 Restriction Fitting S
3 CRD Pressure Reducing Control B

Y D2
C
Optional Features
Item Description
A X46A Flow Clean Strainer B
B
D3
B CK2 Cock (Isolation Valve)
C CV Flow Control (Closing)*
D Check Valves with Cock INLET OUTLET
S CV Flow Control (Opening)
90-01/690-01 Y X43 "Y" Strainer A
1
Pressure Reducing Valve *The closing speed control (optional) on this valve should
always be open at least three (3) turns off its seat.

Pressure Reducing Valve Start-up and Adjustment Instructions 90-01/690-01

1. Install pressure gauges at main valve inlet and outlet. the cover to escape. Loosen tubing nuts in high points in
Place gauges in unused body tappings. Downstream gauge pilot system to remove air from the pilot control system.
can be installed in unused 3/8" CRD Pressure Reducing Tighten tube nuts after all air is removed.
Control (item # 3) body tapping.
8. Open downstream isolation valve and establish a low flow
2. Install X101 Valve Position Indicator in center cover tap- in the system. Refer to minimum flow requirements for
ping of main valve (if available). each valve size Always check the effect in the system
before starting.
3. Open all isolation valves in pilot system (valves 4" and
larger). Remove pilot caps and loosen all jam nuts. 9. Slowly adjust the CRD Pressure Reducing Control (item
# 3) observing the down stream pressure gauge until the
4. Observe the setting on the CRD Pressure Reducing desired pressure is achieved (clockwise to increase setting
Control (item #3). There is a tag attached to the pilot cover or counter-clockwise to decrease setting). Adjust CV flow
with the factory setting. If the pilot has a 15-75 PSI spring controls until desired valve opening or closing speeds are
range each 360 degree turn in/out changes the setting 9 obtained. Adjust opening rate so that valve opens slowly to
PSI. The 30-300 PSI spring range has a 27 PSI change for desired outlet pressure and does not over shoot setting.
each 360 degree turn in/out. Alter the factory setting (turn Adjust closing rate so valve does not cause excessive sys-
adjustment clockwise/counter-clockwise) until the set point tem pressure surging upon closing.
of the control is close to the required setting. This setting is
approximate and may have to be changed once the valve is 10. All valve adjustments are now set. Lockup all jam nuts to
pressurized. Actual pressure settings must be made under a retain settings. Replace all pilot caps.
flowing condition.
5. Adjust CV flow controls (opening/closing speeds) if
Size Minimum Flow (gpm)
included in pilot system. Turn control clockwise until closed
1 1/4-1 1/2” 15
then back out three turns to start. CV opening speed includ-
2” 15
ed as standard equipment on valves 3" and smaller.
2 1/2” 20
3” 30
6. Open inlet isolation valve slowly to pressurize main valve.
4” 50
6” 115
7. Bleed air from main valve cover by loosening pipe plug in
8” 200
center of main valve cover or X101 Valve position Indicator
10” 300
housing. If valve is installed in vertical line it will be neces-
12” 400
sary to loosen the cover bolts between 10 o'clock and 2
14” 500
o'clock to vent air from main valve cover. Tighten pipe plug
16” 650
or cover bolts after all air is removed. Caution: only loosen
24” 1500
pipe plug or cover bolts enough to allow the air trapped in

208
Pressure Reducing Valve 90-48/690-48
Schematic Diagram
Item Description 4
D4

1 Hytrol (Main Valve)


3
2 X47A Ejector 2

3 CRD Pressure Reducing Control 5


D1

4 990 Pressure Reducing Control C

Y B 5
D2

Optional Features B
S B

Item Description D3

A X46A Flow Clean Strainer


B CK2 Cock (Isolation Valve)
90-48/690-48 C CV Flow Control (Closing)*
INLET OUTLET
Pressure Reducing Valve with D Check Valves with Cock
Low Flow By-Pass S CV Flow Control (Opening) 1
A

Y X43 "Y" Strainer

Pressure Reducing Valve Start-up and Adjustment Instructions 90-48/690-48


1. Install pressure gauges at main valve inlet/outlet. Place 9. Slowly adjust the CRD Pressure Reducing Control (3)
gauges in unused body tappings. Downstream gauge can observing the down stream pressure gauge until the
be installed in unused 3/8" CRD Pressure Reducing Control desired pressure is achieved (clockwise to increase
(item # 3) body tapping. setting or counter-clockwise to decrease setting).
Adjust CV flow controls until desired valve opening or
2. Install X101 Valve Position Indicator in center cover tap-
ping of main valve (if available).
closing speeds are obtained. Adjust opening rate so
that valve opens slowly to desired outlet pressure and
4
does not over shoot setting. Adjust closing rate so –
3. Open all isolation valves in pilot system (valves 4" and
larger). Remove pilot caps and loosen all jam nuts.
valve does not cause excessive system pressure
surging upon closing.
4
4. Observe the settings on the CRD Pressure Reducing 10. Next adjust the 990 Pressure Reducing Control
Controls (3) and 990 (4). There is a tag attached to the pilot (4). This is the low flow bypass. This control must be set 5
cover with the factory setting. If the pilot has a 15-75 PSI PSI higher then the CRD Pressure Reducing Control (3).
spring range each 360 degree turn in/out changes the set- Use the CK2 isolation valves in the pilot system to isolate
ting 9 PSI. The 30-300 PSI spring range has a 27 PSI each pressure reducing pilot before attempting to adjust the
change for each 360 degree turn in/out. You can alter the control. The capacity of the low flow bypass is very small 4-
factory setting (turn adjustment clockwise/counter-clock- 5 GPM. So lower the system flow to with in these limits
wise) using this information until the set point of the control before setting the low flow bypass. Example: If the system
is close to the required setting. This setting is approximate pressure is to be maintained at 140 PSI set the low flow
and may have to be changed once the valve is pressur- bypass 990 (4) at 140 PSI and set the other CRD (3) at 135
ized. Actual pressure settings must be made under a flow- PSI. Set CRD (3) first, then set 990 (4) second.
ing condition.
11. All valve adjustments are now set. Lockup all jam nuts
5. Adjust CV flow controls (opening/closing speeds) if to retain settings. Replace all pilot caps.
included in pilot system. Turn control clockwise until closed
then back out three turns to start. CV opening speed includ-
ed as standard equipment on valves 3" and smaller.
Size Minimum Flow (gpm)
6. Open inlet isolation valve slowly to pressurize main valve. 1 1/4-1 1/2” 15
2” 15
7. Bleed air from main valve cover by loosening pipe plug in 2 1/2” 20
center of main valve cover or X101 Valve position Indicator 3” 30
housing. If valve is installed in vertical line it will be neces- 4” 50
sary to loosen the cover bolts between 10 o'clock and 2 6” 115
o'clock to vent air from main valve cover. Tighten pipe plug 8” 200
or cover bolts after all air is removed. Caution: only loosen 10” 300
pipe plug or cover bolts enough to allow the air trapped in 12” 400
the cover to escape. Loosen tubing nuts in high points in
14” 500
pilot system to remove air from the pilot control system.
Tighten tube nuts after all air is removed. 16” 650
24” 1500
8. Open downstream isolation valve and establish a low flow
in the system. Refer to minimum flow requirements for
each valve size. Always check the effect in the system
before starting.

209
Combination Pressure Reducing Sustaining & Pressure Sustaining 92-01/692-01

Schematic Diagram F
4
Item Description REMOTE SENSING 3
1 Hytrol (Main Valve)
2 X44A Strainer & Orifice
3 CRD Pressure Reducing Control 2 C B
4 CRL Pressure Relief Control
D1
5 CV Flow Control (Opening) 5

Optional Features B
B D2
D3
Item Description
B CK2 Cock (Isolation Valve)
92-01/692-01 Combination C CV Flow Control (Closing)* INLET OUTLET

Pressure Reducing Sustaining & D Check Valves With Cock


Pressure Sustaining Valve F Remote Pilot Sensing 1

Combination Pressure Reducing & Pressure Sustaining Start-up and Adjustment Instructions 92-01/692-01
1. Install pressure gauges upstream/downstream of 8. Establish a low flow in the system. Adjust CV
valve. Place inlet gauge in unused main valve body Opening Speed Control clockwise to decrease open-
inlet tapping. Downstream gauge can be placed in ing rate and counter-clockwise to increase opening rate.
unused 3/8" CRD body tapping in pilot system. A slow valve opening rate will prevent the pump start-
ing surge from being transmitted into the system.
2. Open all isolation valves in pilot system. Isolation
valves included in pilot systems on 4" and larger 9. Adjust CRD Pressure Reducing Control to provide
valves standard (4 CK2 Isolation Valves Total). desired outlet pressure. A clockwise adjustment
Remove all pilot caps and loosen all jam nuts. increases outlet pressure and a counter-clockwise
adjustment decreases outlet pressure.
3. Adjust CV Opening Speed Control (Item # 5). Turn
adjusting screw clockwise until its all the way in. Back 10. Establish the maximum flow rate for this system.
out adjustment 3 full turns to start. Turn on the maximum number of sprinklers the pump
is designed to handle. Then slowly adjust the CRL
4. Back out adjustment on the CRL Back pressure Back pressure Control clockwise until the outlet pressure
Control (Item # 4) all the way. drops off 3-5 PSI then stop. Next slowly turn CRL
adjustment counter-clockwise until outlet pressure
5. Observe setting on CRD Pressure Reducing returns to normal. Then stop setting is complete.
Control (Item # 3). There is a tag attached to the pilot
cover with the factory setting. You can change the 11. All valve adjustments are now set. Lockup all jam
pressure setting by using the following information. If nuts to retain settings. Replace all pilot caps. Vary flow
the CRD has a 15-75 PSI spring range each 360 rates in system to make sure valve is set properly.
degree turn in or out changes the setting 9 PSI. The
30-300 PSI spring range has a 27 PSI change for
each 360 degree turn in or out. You can approximate
the downstream pressure by changing the factory setting
using this information. Actual pressure settings must
be made under a flowing condition.

6. Open inlet and outlet system isolation valves slowly


to pressurize valve. Make sure downstream pressure
stays within system limits.

7. Bleed air from main valve cover and high points in


pilot system. Tighten nut after all air is removed.
Loosen tubing nuts in high points in pilot system to
remove air from the pilot control system. Tighten tube
nuts after all air is removed.

210
Pressure Reducing Valve & Solenoid 93-01/693-01

Schematic Diagram CS3


Supply
CS3
Drain
Supply 2 3 Drain 3 2
1 1
Item Description Cover Cover
DE-ENERGIZE TO ENERGIZE TO
1 Hytrol (Main Valve) OPEN OPEN

5 H
2 X58C Restriction Assembly CS3

3 CRD Pressure Reducing Control 3


1
2
SOLENOID DRAIN
TO ATMOSPHERE
2
4 100-01 Hytrol (Reverse Flow)
5 CS3 Solenoid Control
4
3
Optional Features D1
C

Item Description S
Y B
A X46A Flow Clean Strainer D2

B CK2 Cock (Isolation Valve) B D3


C CV Flow Control (Closing)* B

D Check Valves with Cock


93-01/693-01 H Solenoid Drain To Atmosphere
Pressure Reducing Valve & S CV Flow Control (Opening) INLET OUTLET
Solenoid Shut-off Y X43 "Y" Strainer
4 1
*The closing speed control (optional) on this valve should
always be open at least three (3) turns off its seat.

Pressure Reducing Valve & Solenoid Shut-Off Start-up and Adjustment Instructions 93-01/693-01
1. Install pressure gauges at main valve inlet and outlet. .Solenoid can be supplied energized to open main 4
Place gauges in unused body tappings. Downstream gauge
can be installed in the unused 3/8" CRD Pressure Reducing
valve or de-energized to open main valve. You can
determine the valve operation in two ways:

Control (item # 3) body tapping. 4
A. Energized to open main valve supply pressure
2. Install X101 Valve Position Indicator in center cover tap- comes to port # 3 on solenoid, port # 1 is connect-
ping of main valve (if available). ed to the cover of the 3/8" auxiliary hytrol (item # 4), and port
#2 is vented to atmosphere (catalog number suffix H. or to
3. Open all isolation valves in pilot system (valves 4" and the downstream side of the valve standard. Also check the
larger). Remove pilot caps and loosen all jam nuts. Asco Solenoid catalog number 8320G136 normally open.

4. Observe the setting on the CRD Pressure Reducing B. De-energized to open main valve supply pressure comes
Control (item # 3). There is a tag attached to the pilot cover to port # 2 on CS3 solenoid (item # 5), port # 1 is connect-
with the factory setting. If the pilot has a 15-75 PSI spring ed to the cover of the 3/8" auxiliary hytrol (item #4), and port
range each 360 degree turn in/out changes the setting 9 # 3 is vented to atmosphere (catalog number suffix H) or to
PSI. The 30-300 PSI spring range has a 27 PSI change for the downstream side of the valve standard. Also check the
each 360 degree turn in/out. Alter the factory setting (turn ASCO Solenoid catalog number 8320G132 normally closed.
adjustment clockwise/counter-clockwise) until the setpoint
of the control is close to the required setting. This setting is 7. Open inlet isolation valve slowly to pressurize main valve.
approximate and should have to be changed once the valve
is pressurized. Actual pressure settings must be made 8. Bleed air from main valve cover by loosening pipe plug in
under a flowing condition. center of main valve cover or X101 Valve position Indicator
housing. If valve is installed in a vertical line it will be nec-
5. Adjust CV flow controls (opening/closing speeds) if essary to loosen the cover bolts between 10 o'clock and 2
included in pilot system. Turn control clockwise until closed o'clock to vent air from main valve cover. Tighten pipe plug
then back out three turns to start. CV opening speed includ- or cover bolts after all air is removed. Caution: only loosen
ed as standard equipment on valves 3" and smaller. pipe plug or cover bolts enough to allow the air trapped in
the cover to escape. Loosen tubing nuts in high points in
6. Locate the CS3 Solenoid Control (item # 5) in the pilot pilot system to remove air from the pilot control system.
system. Make sure proper voltage is supplied to the coil. If Tighten tube nuts after all air is removed.
the unit is equipped with a manual operator make sure it is
backed all the way out counter-clockwise (rotating the red
thumb screw clockwise simulates energization of the coil.)

211
Pressure Reducing Valve & Solenoid 93-01/693-01

9. Open downstream isolation valve and establish a 11.) All valve adjustments are now set. Lockup all jam
low flow in the system. To accomplish this the CS3 nuts to retain settings. Replace all pilot caps.
solenoid (item # 5) must be electrically energized to 12. To close the main valve on solenoids energized to
open the main valve under command of the CRD open remove electrical power from the solenoid. This
Pressure Reducing Control (item # 3) in valves so will connect ports 3 & 1 on the solenoid directing inlet
equipped. If the valve is de-energized to open no elec- pressure into the cover of the 3/8" auxiliary hytrol closing
trical power is required to open the main valve. In it. This will in turn direct inlet pressure into the cover
valves so equipped if the CS3 solenoid (item # 5 ) is of the main valve closing it.
energized the main valve closes. The porting
sequence for the CS3 solenoid (energized to open or To close the main valve on solenoids de-energized to
de-energized to open appears in the valve schematic) open apply electrical power to the solenoid. This will
Refer to minimum flow requirements for each valve connect ports 2 & 1 on the solenoid directing inlet
size. Always check the effect in the system before pressure into the cover of the 3/8" auxiliary hytrol closing
starting. it. This will in turn direct inlet pressure into the cover of
the main valve closing it.
Size Minimum Flow (gpm)
1 1/4-1 1/2” 15
2” 15
2 1/2” 20
3” 30
4” 50
6” 115
8” 200
10” 300
12” 400
14” 500
16” 650
24” 1500

10. Slowly adjust the CRD Pressure Reducing Control


observing the down stream pressure gauge until the
desired pressure is achieved (clockwise to increase
setting or counter-clockwise to decrease setting)
.Adjust CV flow controls until the desired valve open-
ing or closing speeds are obtained. Adjust the open-
ing rate so that valve opens slowly to the desired out-
let pressure and does not over shoot the setting.
Adjust closing rate so the valve does not cause exces-
sive system pressure surging upon closing.

212
Section
4-5 Float Valves 120/420 Series Start-up and Adjustments

Schematic Diagram 2
2

Item Description 1
S
1 Hytrol (Main Valve) D
2 CF1-C1 Float Control
Y C

Optional Features S

Item Description F
B
B
A X46A Flow Clean Strainer
B CK2 Cock (Isolation Valve) INDEPENDENT
OPERATING
C CV Flow Control (Closing) PRESSURE
F Independent Operating Pressure
124-01/624-01 Float Valve S CV Flow Control (Opening) INLET OUTLET

Y X43 "Y" Strainer A 1

Float Valve Start-up and Adjustment Instructions 124-01/624-01


1. Install pressure gauge at main valve inlet. 6. Open inlet isolation valve slowly to establish flow
through main valve. Most float valve applications only
2. Install X101 Valve Position Indicator in center cover have one inlet isolation valve because they discharge
tapping of main valve (if available). directly to atmosphere.

3. Open all isolation valves in pilot system (valves 4" 7. Bleed air from main valve cover by loosening
and larger). pipe plug in center of main valve cover or X101 4
Valve position Indicator housing. If valve is –
4. Adjust CV flow controls (opening/closing speeds) if
included in pilot system. Turn control clockwise until
installed in vertical line it will be necessary to
loosen the cover bolts between 10 o'clock and 2
5
closed then back out three turns to start. o'clock to vent air from main valve cover.
Tighten pipe plug or cover bolts after all air is
5. Balance the CF1-C1 Float Control (item #2) by removed. Caution: only loosen pipe plug or cover
removing the float rod and float from the control. bolts enough to allow the air trapped in the cover to
Remove the float from the float rod and leave on the escape. Loosen tubing nuts in high points in pilot sys-
stop collars. Reinstall the float rod on the CF1-C1 tem to remove air from the pilot control system.
Float Control. Loosen set screw on counterweight and Tighten tube nuts after all air is removed.
move weight in or out until float control is balanced.
Tighten set screw. Push down on the float rod assembly 8. All valve adjustments are now set. Lockup all jam
and make sure the control returns to its balanced nuts to retain settings.
position. When balancing is achieved reinstall the
float. Set the stop collars the required distance apart.
Several different counterweights are available. Use
counter weight:
P/N Float Rod Length
V006903J (standard) 2 Feet
V6230G 3-6 Feet
V6231E 7-12 Feet
Do not exceed 12 feet of float rod.
A stilling well (8" minimum diameter) should be provided
for the float to minimize the effects of turbulence, ripples
or wind.

213
Modulating Float Valve 428-01/628-01

Schematic Diagram 2

Item Description
1 Hytrol Main Valve
2 CFM-9 Float Control
Y D1
3 CK2 Cock (Isolation Valve)
3

D2

Optional Features F D3
428-01/628-01 3

Modulating Float Valve Item Description INDEPENDENT


OPERATING 3
PRESSURE
A X46A Flow Clean Strainer
D Check Valves with Cock INLET OUTLET
F Independent Operating Pressure
A
Y X43 “Y” Strainer 1

Modulating Float Valve Start-up and Adjustment Instructions 428-01/628-01


1. 428-01 main valve should be installed in a horizontal P/N Float Rod Length
pipe, cover up. Install pressure gauge at main valve inlet. V006903J (standard) 2 Feet
V6230G 3-6 Feet
2. The CFM-9 Float Control must be installed in an V6231E 7-12 Feet
accessible location at any elevation above the valve
providing that the amount of flowing line pressure in Do not exceed 12 feet of float rod. A stilling well (8"
PSI is equal to or greater then the vertical distance in minimum diameter) should be provided for the float to
feet between the valve and the float control. minimize the effects of turbulence, ripples or wind.

3. The float control discharge must be piped back to 7. Open inlet isolation valve slowly to establish flow
the main valve outlet port. Both lines connecting the through main valve. Most float valve applications only
valve and the float control (not supplied by Cla-Val) have one inlet isolation valve because they discharge
must be large enough to minimize pressure drop directly to atmosphere.
under maximum flow conditions. Use 3/4" I.D. pipe up
to 20 feet and 1" pipe to 30 feet. Do not exceed 30 feet 8. Bleed air from main valve cover by loosening tube
in any one run of pipe and try to minimize the number nut on the pilot control line from main valve inlet.
of elbows used. Loosen tubing nuts in high points in pilot system to
remove air from the pilot control system. Tighten tube
4. Install pressure gauge at main valve inlet. nuts after all air is removed.

5. Open all isolation CK2 valves in pilot system 9. All valve adjustments are now set.
(valves 4" and larger).

6. Balance the CFM-9 Float Control (item #2) by


removing the float rod and float from the control.
Remove the float from the float rod and leave on the
stop collars. Reinstall the float rod on the CFM-9 Float
Control. Loosen set screw on counterweight and
move weight in or out until float control is balanced.
Tighten set screw. Push down on the float rod assembly
and make sure the control returns to its balanced
position. When balancing is achieved reinstall the
float. For best performance, lock the stop collars on
either side of the float. Several different counter-
weights are available. Use counter weight:

214
Section
4-6 Solenoid Control
Valves
136 Series
Start-up and Adjustments

CS3 CS3

Schematic Diagram Supply 2


1
3 Drain Supply 3
1
2 Drain

Cover Cover

Item Description DE-ENERGIZE TO


OPEN
D1 C
ENERGIZE TO
OPEN

1 Hytrol (Main Valve) 2


2 CS3 Solenoid Control S
CS3
Y 3 2
1

Optional Features
B D2
Item Description F B
D2
A X46A Flow Clean Strainer B

INDEPENDENT
B CK2 Cock (Isolation Valve) OPERATING
H

PRESSURE
C CNA Closing Speed Control DRAIN TO
ATMOSPHERE
136-01/636-01 D Check Valves with Cock
Solenoid Control Valve S CNA Needle Valve INLET OUTLET
Y X43 "Y" Strainer A 1

Solenoid Control Valve Start-up and Adjustment Instructions 136-01/636-01


1. Install pressure gauges at main valve inlet/outlet using essary to loosen the cover bolts between 10 o'clock and 2
main valve body tappings. o'clock to vent air from main valve cover (Limit vertical
installations to valves 6" and smaller). Tighten pipe plug or
2. Install X101 Valve Position Indicator in center cover tap- cover bolts after all air is removed. Caution: only loosen
ping of main valve (if available). pipe plug or cover bolts enough to allow the air trapped in
the cover to escape. Loosen tubing nuts in high points in
3. Open all isolation valves in pilot system (valves 4" and pilot system to remove air from the pilot control system.
larger). Tighten tube nuts after all air is removed.

5. Adjust CNA speed controls (opening/closing speeds) if 9. Open downstream isolation valve and establish a
included in pilot system. Turn control clockwise until closed flow in the system. To accomplish this the CS3 sole-
then back out three turns to start. noid (item # 2) must be electrically energized to

6. Locate the CS3 Solenoid Control (item # 2) in the pilot


open the main valve in valves so equipped. If the
valve is de-energized to open no electrical power is
4
system. Make sure proper voltage is supplied to the coil. If required to open the main valve. In valves so –
the unit is equipped with a manual operator make sure it is
backed all the way out counter-clockwise (rotating the red
equipped if the CS3 solenoid (item # 2 ) is energized
the main valve closes. The porting sequence for the
6
thumb screw clockwise simulates energization of the coil). CS3 solenoid (energized to open or de-energized to
Solenoid can be supplied energized to open main valve or open appears in the valve schematic) Always check
de-energized to open main valve. You can determine the the effect in the system before starting.
valve operation in two ways:
A. Energized to open main valve supply pressure comes to 10. Adjust CNA speed controls until the desired valve open-
port # 3 on solenoid, port # 1 is connected to the cover of ing or closing speeds are obtained. Adjust the opening rate
the main valve (item #1), and port # 2 is vented to atmos- so that valve opens slowly (Turning counter-clockwise
phere (catalog number Suffix "H") or to the downstream side increases valve opening speed/ Turning clockwise decreas-
of the valve standard. Also check the ASCO Solenoid cata- es valve opening speed). Adjust closing rate so the valve
log number 8320G136 normally open. does not cause excessive system pressure surging upon
B. De-energized to open main valve supply pressure comes closing (Turning counter-clockwise increases valve closing
to port # 2 on CS3 solenoid (item # 2), port # 1 is connect- rate and turning clockwise decreases valve closing rate).
ed to the cover of the main valve (item # 1), and port # 3 is
vented to atmosphere (catalog number Suffix "H") or to the 11. All valve adjustments are now set. Lockup all jam nuts
downstream side of the valve standard. Also check the to retain settings.
ASCO Solenoid catalog number 8320G132 normally
closed. 12. To close the main valve on solenoids energized to open
remove electrical power from the solenoid. This will connect
7. Open inlet isolation valve slowly to pressurize the main ports 3 & 1 on the solenoid directing inlet pressure into the
valve. cover of the main valve closing it. To close the main valve on
solenoids de-energized to open apply electrical power to the
8. Bleed air from main valve cover by loosening pipe plug in solenoid. This will connect ports 2 & 1 on the solenoid direct-
center of main valve cover or X101 Valve position Indicator ing inlet pressure into the cover of the main valve closing it.
housing. If valve is installed in a vertical line it will be nec-
215
Solenoid Control Valve 136-03/636-03
Schematic Diagram CS3 CS3
Supply Drain Supply 3 2 Drain
2 3 4
Item Description 1 1
Cover
1 Hytrol (Main Valve) Cover
DE-ENERGIZE TO
OPEN
ENERGIZE TO
OPEN
2 CS3 Solenoid Control 3
CS3
2

3 102C-3H Three-Way Valve D1


2
1

4 CNA Needle Valve (Closing) 3 S

Y COM. N.C.

Optional Features B
N.O.

B D2
F
Item Description D3 B

A X46 Flow Clean Strainer INDEPENDENT H


OPERATING
B CK2 Cock (Isolation Valve) PRESSURE
DRAIN TO
136-03/636-03 Solenoid Control D Check Valves With Cock ATMOSPHERE

Valve F Independent Operating Pressure INLET OUTLET


H Atmospheric Drain
S CNA Needle Valve (Opening) A
1
Y X43 "Y" Strainer

Solenoid Control Valve Start-up and Adjustment Instructions 136-03/636-03


1. Install pressure gauges at main valve inlet/outlet using 8. Bleed air from main valve cover by loosening pipe plug in
main valve body tappings. center of main valve cover or X101 Valve position Indicator
housing. If valve is installed in a vertical line it will be nec-
2. Install X101 Valve Position Indicator in center cover tap- essary to loosen the cover bolts between 10 o'clock and 2
ping of main valve (if available). o'clock to vent air from main valve cover (Limit vertical
installations to valves 6" and smaller). Tighten pipe plug or
3. Open all isolation valves in pilot system (valves 4" and cover bolts after all air is removed. Caution: only loosen
larger). pipe plug or cover bolts enough to allow the air trapped in
the cover to escape. Loosen tubing nuts in high points in
5. Adjust CNA speed controls (opening/closing speeds) if pilot system to remove air from the pilot control system.
included in pilot system. Turn control clockwise until closed Tighten tube nuts after all air is removed.
then back out three turns to start.
9. Open downstream isolation valve and establish a flow in
6. Locate the CS3 Solenoid Control (item #2) in the pilot the system. To accomplish this the CS3 solenoid (item # 2)
system. Make sure proper voltage is supplied to the coil. If must be electrically energized to open the main valve in
the unit is equipped with a manual operator make sure it is valves so equipped. If the valve is de-energized to open
backed all the way out counter-clockwise (Rotating the red no electrical power is required to open the main valve. In
thumb screw clockwise simulates energization of the coil). valves so equipped if the CS3 solenoid (item # 2 ) is ener-
Solenoid can be supplied energized to open main valve or gized the main valve closes. The porting sequence for the
de-energized to open main valve. You can determine the CS3 solenoid (energized to open or de-energized to open
valve operation in two ways: appears in the valve schematic) Always check the effect in
A. Energized to open main valve supply pressure comes to the system before starting.
port # 3 on solenoid, port # 1 is connected to the cover of
the 1/2" 102C-3H three way valve (item # 3), and port # 2 is 10. Adjust CNA speed controls until the desired valve open-
vented to atmosphere (catalog number Suffix "H") or to the ing or closing speeds are obtained. Adjust the opening rate
downstream side of the valve standard. Also check the so that valve opens slowly (Turning counter-clockwise
ASCO Solenoid catalog number 8320G136 normally open. increases valve opening speed/ Turning clockwise decreas-
B. De-energized to open main valve supply pressure comes es valve opening speed). Adjust closing rate so the valve
to port # 2 on CS3 solenoid (item # 2), port # 1 is connect- does not cause excessive system pressure surging upon
ed to the cover of the 1/2" 102C-3H three way valve (item # closing (Turning counter-clockwise increases valve closing
3), and port # 3 is vented to atmosphere (catalog number rate and turning clockwise decreases valve closing rate).
Suffix "H") or to the downstream side of the valve standard. 11. All valve adjustments are now set. Lockup all jam nuts
Also check the ASCO Solenoid catalog number 8320G132 to retain settings.
normally closed.
12. To close the main valve on solenoids energized to open
7. Open inlet isolation valve slowly to pressurize the main remove electrical power from the solenoid. This will connect
valve. ports 3 & 1 on the solenoid directing inlet pressure into the
cover of the main valve closing it. To close the main valve on
solenoids de-energized to open apply electrical power to the
solenoid. This will connect ports 2 & 1 on the solenoid
directing inlet pressure into the cover of the main valve closing it.

216
Section
4-7 Altitude Valves 210 Series
Start-up and Adjustments
Schematic Diagram
2
Item Description B2 4
1 Hytrol (Main Valve) D1 RESERVOIR
Y
2 CDS6 Altitude Control SENSING
S 1
3 X101 Valve Position Indicator D
4 Bell Reducer
5 CV Flow Control (Closing) S
5 H
Optional Features B1 B1 3
Item Description F D2
A X46A Flow Clean Strainer D3
B CK2 Cock (Isolation Valve) INDEPENDENT
D Check Valve with Cock OPERATING
PRESSURE
F Independent Operating Pressure INLET OUTLET
210-01/610-01 Altitude H Dry Drain
Valve for One-Way Flow S CV Flow Control (Opening) A 1
Y X43 "Y" Strainer
Altitude Valve for One-Way Flow Start-up and Adjustment Instructions 210-01/610-01

1. Install pressure gauges at main valve inlet and be corrected under actual conditions.
outlet using the inlet /outlet body tappings on the 5. Adjust CV flow controls (opening/closing
main valve. speeds) if included in pilot system. Turn control
clockwise until closed then back out three turns to
2. The CDS6 Altitude Control (item # 2) sensing start. CV closing speed included as standard
line (not supplied by Cla-Val) should run from the equipment on all altitude valves.
pilot control directly to the storage tank. This way
the pilot control senses the static height of the liq- 6. Open inlet isolation valve slowly to pressurize
uid in the tank directly. Accurate and consistent main valve.
valve performance is achieved with this approach.
7. Bleed air from main valve cover by loosening
3. Open all isolation valves in pilot system (valves pipe plug in center of X101 Valve Position Indicator
4" and larger) and loosen all pilot control jam nuts. housing (standard on all altitude valves).
Tighten pipe plug after all air is removed.
4. Observe the adjustment on the CDS6 Altitude Caution: only loosen pipe plug enough to 4
Control (item #2). There is a tag attached to the allow the air trapped in the cover to escape. –
pilot with the factory setting. There are 5 spring Loosen tubing nuts in high points in pilot sys- 7
ranges available with this pilot control: tem to remove air from the pilot control sys-
tem. Tighten tube nuts after all air is removed.
Springs Range
1 5-40 Feet
2 30-80 Feet 8. Open downstream isolation valve and establish
3 70-120 Feet a flow to the tank (Always check the effect in the
4 110-160 Feet system before starting). It may be necessary to
5 150-200 Feet
increase the setting on the CDS6 Altitude Control
to allow the valve to open. The water in the
cover of the valve will discharge to atmosphere
Using this information you can change the factory through the altitude control (unless supplied with
setting to approximate the shut-off height of the dry drain feature Suffix "H"). The volume of water
valve. This setting is not exact and may have to will depend on the valve size: Make provision for

217
Altitude Valve 210-01/610-01

this discharge to be handled safely.

Size Cover Capacity


2” .032
2 1/2” .042
3” .080
4” .169
6” .513
8” 1.26
10” 2.51
12” 4.0
14” 6.50
16” 9.57
24” 29.0

9. As the water level rises to the shutoff point in


the tank slowly adjust the CDS6 Altitude Control
(item # 2) until the valve starts to close when the
desired level is achieved (clockwise to increase
water level or counter-clockwise to decrease
water level). Adjust CV flow controls until desired
valve opening or closing speeds are obtained.
Adjust opening rate so that valve opens slowly
(turn clockwise to decrease valve opening rate
and counter-clockwise to increase valve opening
rate). Adjust closing rate so valve does not cause
excessive system pressure surging upon clos-
ing (Turn clockwise to decrease valve closing
rate and counter-clockwise to increase valve
closing rate).

10. All valve adjustments are now set. Lockup all


jam nuts to retain settings.

218

Das könnte Ihnen auch gefallen