EXTERIOR CAMPUS
LIGHTING STANDARDS
Updated July 2009
EXTERIOR CAMPUS LIGHTING STANDARDS
Table of Contents
Purpose 1
General Campus Guidelines 2
Technical Design Guidelines 3-5
Technical Design Requirements 6-10
Approved Products 11-35
Appendix 35-48
Exterior Campus Lighting Standards and Guidelines
A. PURPOSE
The goal of this lighting plan is to provide strategies which will ensure a
consistently well-lit, safe and attractive campus. In addition,
implementing these standardized specifications and practices will reduce
light pollution and energy consumption campus-wide.
1 of 48
B. GENERAL CAMPUS GUIDELINES
2 of 48
C. TECHNICAL DESIGN GUIDELINES
3 of 48
campus. HPS lamps are the primary street lighting source used by
the City of Athens and there may be instances on adjoining streets
adjacent to campus boundaries where the use of HPS lamps is
necessary. This allows the campus to maintain or improve visual
consistency with the City standards. If HPS lamps are to be used for
a specific project, written authorization from the Office of University
Architects must be obtained prior to the installation of the fixtures.
The use of Low Pressure Sodium (LPS) or Mercury Vapor (MV) light
sources shall not be allowed without prior approval due to the poor
color rendering values and visibility issues, as well as poor energy
efficiency (in case of MV).
4 of 48
illuminance, glare, uniformity and heat are equally important in
lighting design.
Compliance with the IES guidelines and the light levels prescribed in
this document will ensure adequate illumination for safety.
5 of 48
D. TECHNICAL DESIGN REQUIREMENTS
1. REGULATIONS
a. All outdoor lighting installed on UGA property shall conform with
the requirements established herein.
2. FIXTURE SELECTION
a. All outdoor light fixtures installed on UGA property shall be either
selected from the product group specified in this document, or
submitted as alternates with all supporting data to be approved
by The Office of University Architects for Facilities Planning.
3. EXCEPTIONS
a. Exceptions to this standard include sports lighting, temporary
lighting, lighting integral to historic structures, and emergency
lighting.
b. Exceptions shall be reviewed by the Office of University Architects
for Facilities Planning on a case by case basis.
4. PROHIBITIONS
a. Laser Source Light. The use of laser source light or any similar
high intensity light projected above the horizontal shall not be
permitted.
b. Searchlights. The operation of searchlights shall not be permitted
without prior approval by the Office of University Architects for
Facilities Planning on a case by case basis.
c. Low Pressure Sodium and Mercury Vapor Lamps in new
installations shall not be permitted.
6 of 48
Fixtures illuminating signage shall be controlled so as not to throw
light beyond the sign. Whenever possible, signage should be
illuminated from above, using shielded fixtures with metal halide
lamps or fluorescent lamps.
d. BUILDING ENTRIES
e. PARKING
1. SURFACE AREAS
Illuminance levels for most campus parking lots are based on low-
use criteria, while a few parking areas fall into the medium-use
category. Uniformity and glare control are the most important
factors in parking area lighting design because they contribute the
most to nighttime visibility. These factors should take precedence
over measured light levels.
All parking lots on campus shall be illuminated in the same way.
Maintain a minimum level of 0.2 footcandle at the ground plane, a
minimum vertical illuminance of 0.1 footcandle measured 5’-0”
above the ground plane and a max/min uniformity ratio of 20:1
(this means that if the minimum is 0.2 footcandle, the maximum
8 of 48
footcandle level shall not be higher than 4.0 footcandles.) These
values are in accordance with the Ninth Edition of the IES
Handbook. Justification for exceeding the minimum standards
shall be submitted to the Office of University Architects for
Facilities Planning during the design phase.
2. PARKING GARAGES
f. ROADS
9 of 48
d. Uplighting of new building facades and new landscaping unless
authorized in writing by the Office of University Architects for
Facilities Planning.
c. SIGNAGE
7 of 48
footcandles). These values are in accordance with the IES
Handbook, Ninth Edition.
10 of 48
Approved Products
E. APPROVED PRODUCTS
E.1.c Pole
11 of 48
E.1.a. PEDESTRIAN WALKWAYS/BIKEWAYS (adjacent to roadways,
distant from roadways), ROADWAYS – FIXTURE FOR ALL NEW
CONSTRUCTION
SPACING CRITERIA: The maximum center to center spacing between poles for
all new construction shall not exceed the following:
12 of 48
13 of 48
14 of 48
> Remote Ballast
15 of 48
> Ballast Tray Details
16 of 48
E.1.b. PEDESTRIAN WALKWAYS/BIKEWAYS (adjacent to roadways,
distant from roadways), ROADWAYS – REPLACEMENT OF EXISTING
FIXTURES ONLY
SPACING CRITERIA: The maximum center to center spacing between poles for
all replacement of existing fixtures shall not exceed the following:
17 of 48
18 of 48
19 of 48
> Remote Ballast
20 of 48
> Ballast Tray Details
21 of 48
E.1.c. POLE – ALL NEW CONSTRUCTION AND REPLACEMENT OF
EXISTING FIXTURES
22 of 48
23 of 48
24 of 48
E.3. PARKING SURFACE AREA – FIXTURE
25 of 48
26 of 48
E.3. PARKING SURFACE AREA – POLE
SPECIFICATIONS: KIM Lighting PTRS series round steel tapered pole, 20, 25
or 30 ft height as required, cast aluminum pole cap as required, thickness to
be confirmed by structural engineer. Finish shall be matched to fixture color in
all cases.
27 of 48
28 of 48
E.4. PARKING GARAGES
HID FIXTURE SPECIFICATIONS: KIM Lighting PGL5 fixture, 175W metal halide
lamping with HPF magnetic ballast, UV stabilized acrylic refractor lens, tamper
resistant latches and integral quartz standby as required, standard white
finish.
29 of 48
30 of 48
31 of 48
FLUORESCENT FIXTURE SPECIFICATIONS: GUTH Lighting vandal resistant
DURASEAL fixture, acrylic lens with smooth outer surface, specular reflector,
2 – 32W T8 lamping with electronic instant start ballast, tamper-resistant and
tool free latches, standard finish.
32 of 48
33 of 48
6. GLOSSARY
34 of 48
LAMP: The component of a luminaire that produces the light (the
bulb).
LIGHT TRESPASS: The shining of light produced by a luminaire
beyond the boundaries of the property on which it is located.
LUMEN: A unit of luminous flux. One footcandle is one lumen
per square foot. For the purposes of this standard, the
lumen-output values shall be the INITIAL lumen output
ratings of a lamp.
LUMINAIRE: A complete lighting system, and includes a lamp or
lamps and a fixture.
35 of 48
Appendix
7. APPENDIX
36 of 48
E.1.a. PEDESTRIAN WALKWAYS / BIKEWAYS (Adjacent to Roadways)
FIXTURE FOR ALL NEW CONSTRUCTION AREAS
37 of 48
38 of 48
E.1.b. PEDESTRIAN WALKWAYS / BIKEWAYS (Adjacent to Roadways)
FIXTURE FOR REPLACEMENT OF EXISTING CAMPUS POLES ONLY
39 of 48
40 of 48
E.1.a. PEDESTRIAN WALKWAYS / BIKEWAYS (Distant from Roadways)
FIXTURE FOR ALL NEW CONSTRUCTION AREAS
41 of 48
42 of 48
E.1.b. PEDESTRIAN WALKWAYS / BIKEWAYS (Distant from Roadways)
FIXTURE FOR REPLACEMENT OF EXISTING CAMPUS POLES ONLY
43 of 48
44 of 48
E.1.a. ROADWAYS
FIXTURE FOR ALL NEW CONSTRUCTION AREAS
45 of 48
46 of 48
E.1.b. ROADWAYS
FIXTURE FOR REPLACEMENT OF EXISTING CAMPUS POLES ONLY
47 of 48
48 of 48