ANALYSIS
OF
ENERGY METERS
Note: External Burning is not the type of tampering but since External
Observation:
1. Extra PCB and remote circuit.
2. Soldering of extra circuit wires at
different locations on PCB.
Conclusion:
3. Meter is Tampered.
4. The presence of internal remote
circuit inside the meter means
that the meter was operated by
the Remote Control.
Single- phase energy meters
Conclusion:
3. Meter is Tampered.
4. The presence of internal
remote circuit inside the meter
means that the meter was
operated by the Remote
Control.
Observation:
1. Thermostatic / Magnetic
Switch fitted.
2. No effect on meter accuracy
when switch is OFF (NC/NO).
Conclusion:
3. Meter is Tampered.
4. Meter recording is as per
consumer choice by
thermal/ magnet
switch.
Due to the availability and low cost of resistances, this method is commonly
used to Tamper the energy meters.
Resistances are soldered to disturb either voltage circuit or current circuit
(signal value) or both of them.
On the basis of the circuit disturbed by the soldering of resistance we can
identify the type of Circuit Tampering, viz. voltage or current circuit
tampering.
Voltage Circuit Tampering: If the resistances are soldered across the voltage
circuit connections on PCB of the meter in order to drop the voltage then it is
said to be Voltage Circuit Tampering.
Current Circuit Tampering: If the resistances are soldered across the current
circuit connections on PCB of meter then it is said to be Current Circuit
Tampering.
Conclusion:
1. Meter is Tampered.
2. Extra resistances at current
connections drop the
current to be passed
through CT, thus meter
will record lowest energy .
Observation:
1. Extra resistors soldered
at current connections (CT4 &
CT-5) on meter PCB.
Conclusion:
1. Meter is Tampered.
2. Extra resistances at
current connections drop the
current to be passed through
CT, thus meter will record
lowest energy .
Observation:
1. Extra resistance at CT
connections.
Conclusion:
2. Meter is Tampered.
3. The soldering of
resistances across CT
connections will lead
lesser recording of
energy.
Single- phase energy meters
Conclusion:
3. Meter is Tampered.
4. Extra SMD resistors will
increase the current drop
across CT circuit.
5. The shorting of LEDs is done
to hide the indication of
Reverse and Earth Leakage.
Observation:
1. Extra soldering spots at
CT-4 & CT-5 location on
PCB.
2. Extra shorting at CT-6
location.
3. Externally burnt.
Conclusion:
4. Meter is Tampered.
5. Since terminals are not
burnt hence it is
externally burnt.
Observation:
1.Extra Resistance
component Soldered
on PCB
Conclusion:
1. Meter is Tampered.
Observation:
1.Extra Resistance soldered &
spots on PCB.
Conclusion:
1.Meter is Tampered.
Observation:
1.Extra Resistance soldered &
spots on PCB.
Conclusion:
1.Meter is Tampered.
Conclusion:
1. Meter is tempered.
Conclusion:
Meter is tempered.
Observation:
1. Meter is internally by-
passed by jumpers (shunt)
by tampering meter seals
and ultrasonic welding.
Conclusion:
1. Meter is Tampered.
2. Meters maximum current
flows through the jumpers.
3. Meter recording will be
much less 10- 15% only.
Observation:
1 Meter is internally by-
passed by jumpers
(shunt) by tampering
meter seals and
ultrasonic welding.
Conclusion:
1.Meter is Tampered.
2. Meters maximum
current flows through
the jumpers.
3. Meter recording will be
much less 10- 15% only.
Conclusion:
1.Meter is tempered
Observation:
1. Meter is working
satisfactorily at normal
condition.
Conclusion:
1. Meter is Tampered
externally by High Voltage
applied.
• Conclusion:
• 1. Meter is Tampered
externally by High Voltage
Observation:
1.Display blank/hang.
Meter start working accurately
after reset ON/OFF input
supply).
Conclusion:
Conclusion:
2. Meter is Tampered.
Meters maximum current flows
through the jumpers.
Meter recording will be much less
10- 15% only.
Conclusion:
1.Meter is Tampered.
Meters maximum current
flows through the jumpers.
Meter recording will be much
less 10- 15% only.
Conclusion:
1.Meter is Tampered.
Meters maximum current
flows through the jumpers.
Meter recording will be much
less 10- 15% only.
Conclusion:
Meter is Tampered.
Meters maximum current
flows through the jumpers.
Meter recording will be much
less 10- 15% only.
Conclusion:
Meter is Tampered.
Meters maximum current flows
through the jumpers.
Meter recording will be much less 10-
15% only.
Observation:
1.Meter top cover is badly burnt no
sparking observed
At terminals.
Normally externally burning for
hiding internal /external tempering
and actual reading of meter.
Conclusion:
1. Meter is externally burnt /
deliberately burnt .
Observation:
1.Meter top cover is badly burnt
no sparking observed
At terminals.
Normally externally burning for
hiding internal /external
tempering and actual reading of
meter.
Conclusion:
1. Meter is externally burnt /
deliberately burnt .
Observation:
1.Meter top cover is badly burnt no
sparking observed
At terminals.
Normally externally burning for
hiding internal /external tempering
and actual reading of meter.
Conclusion:
1. Meter is externally burnt /
deliberately burnt .
Observation:
1.Meter top cover is badly burnt no
sparking observed
At terminals.
Normally externally burning for hiding
internal /external tempering and actual
reading of meter.
Conclusion:
1. Meter is externally burnt /
deliberately burnt .