Section 0
Contents
1. Precautions ........................................................................................................ 1-1
1-1 Precautions for the Service.............................................................................................................................. 1-1
1-2 Precautions related to static electricity and PL ....................................................................................... 1-1
1-3 Precautions related to product safety ........................................................................................................ 1-2
1-4 Other precautions ............................................................................................................................................... 1-2
Samsung Electronics 1
Section 0
Contents
4-3-10 External Sensor Error (E221, E231, E251, E320)......................................................................... 4-35
4-3-11 Outdoor Unit Fan Error (E458, E475)............................................................................................. 4-36
4-3-12 Error of Compressor Startup and Rotation (E461, E467)....................................................... 4-37
4-3-13 Error of under-current error / PFC over-current (E462, E484) ............................................. 4-39
4-3-14 IPM Over-current Error (E464).......................................................................................................... 4-40
4-3-15 DC LINK Over-current and Low-voltage Error (E466)............................................................. 4-43
4-3-16 Gas Leakage Error (E554) ................................................................................................................... 4-45
4-3-17 Pipe Blocking Error (E422) ................................................................................................................. 4-47
4-3-18 Other .......................................................................................................................................................... 4-48
2 Samsung Electronics
Precautions
1. Precautions
O When repairing the equipment, connection of the harness parts must be firm and solid.
– A loose connection may cause noise or other malfunction.
O When assembling and disassembling the equipment while it is laid down, lay it on soft cloth.
– Otherwise it may scratch the back of the exterior of the product.
O Remove dust or dirt completely from the housing block, wiring block and service parts during repair.
– This helps prevent the danger of fire caused by tracking or short circuit.
O Fasten the valve caps of service valves and charging valves of outdoor unit as much as possible using adjustable wrenches.
O Check whether the installation location is at least two meters away from other electronic products such as TV, video, or
audio.
– Otherwise, the video quality might be degraded or noise might be generated.
O Do not bend the power cable with excessive force, and do not place a heavy weight on the case as it might damage the
cable.
– It might cause electric shock or fire.
O Unplug the power cable or turn off the auxiliary power switch for electric part replacement and repair service.
– Otherwise it might cause electric shock.
O Instruct end users to separate the batteries from the remote controllers and store them separately when the product is not
used for long time.
– Otherwise leakage from the dry cell may cause problems with the remote controller.
2. Product Specifications
2-1-1 Features
t &BTZJOTUBMMBUJPOPGVMUSBMJHIUXFJHIUJOEPPSVOJU
A filter that obviates the need for replacement and/or
maintenance up to 1,000~2,000 hours and retains its initial
cleanness. 35%
17kg 29kg
20Kg
20kg
Weight
4".46/(
HAUZEN
Other companies
[Comparison
[Comparison ofof weights
weights withwith
otherother companies
companies 11kg] 11kg]
t $PSOFSTFQBSBCMFQBOFMGPSTJNQMFMFWFMJOH
The panel structure with four corners that can be separated enables
convenient installation and service as only the required corner can
be separated to adjust leveling when necessary.
t .
BJOUBJOQMFBTBOUUFNQFSBUVSFXJUIGJOFUFNQFSBUVSFDPOUSPM
with a resolution of 0.1°C 2°C
t 4VQFSJPSIFBUJOHQFSGPSNBODFFWFOBU°C
The equipment achieves a stable heating performance with the
superior reliability of low temperature heating so that the indoor
unit blows air of 40°C or higher in a cold winter when the outside 0℃
temperature is below -15°C.
15℃
t 1MFBTBOUSPPNXJUIBDIFDLWBMWFGPSQSFWFOUJOHCBDLGMPX
A check valve is installed to prevent condensed water drained from the indoor unit flowing back into the indoor unit
for various reasons such as improper drain pipe installation or power cut, and indoor leak or bad smell by backflow
is fundamentally blocked.
t ' VODUJPOUPDPOUSPMPQUJNVNSPPNUFNQFSBUVSFUIBU
reduces temperature variation
Room temperature sense condition can be set to
‘Indoor + average of wired remote controller’ to minimize the
variation in temperature between the upper and lower levels
generated by the effects of indoor air flow so that optimum t5FNQFSBUVSFTFUUJOH "
*OEPPSVOJUUFNQFSBUVSFTFUUJOH
t5FNQFSBUVSFTFUUJOH #
8JSFESFNPUFDPOUSPMMFSUFNQFSBUVSFTFUUJOH
room temperature will be maintained.
t 0
CUBJOFE4UFSJMJ[BUJPO5SFBUNFOU4'NBSLUIBUSFNPWFT
the threat of mildew.
The equipment is very sanitary as an indoor heat exchange unit
and filters are treated with world-recognized sterilization treatment
technology to prevent the growth of mildew inside the unit.
t1BUFOUSFHJTUFSFEJO,PSFB
64"
+BQBO
BOE*UBMZ
(Patent number: Korea P-082555/ Italy 1294250/USA 5947
t $
POWFOJFOUDPOUSPMGPSIJHIDFJMJOHTXJUIXJOEWFMPDJUZ t*OEPPS1$#PQUJPOTFUUJOH
t $
POWFOJFOUGJMUFSDMFBOJOHXJUITNBSUBVUPNBUJDFMFWBUJOH
grille. (Optional)
Stability is secured with the four points support for the main
body
When the smart auto elevating grille function is used, the grille
can be separated easily with stable lowering through the four
points support for the main body so that cleaning and managing
the filter is more convenient.
/
PBEEJUJPOBMDFJMJOHIFJHIUJTBEEFE
TBWJOHJOTUBMMBUJPOTQBDF
Installation space can be saved further by applying the smart auto
elevating grille kit as the additional ceiling height is not necessary.
Ceiling height Low High
Auto stop (m) 2 4
t 5
XPHSJMMFEFTJHOT DMBTTJDQBUUFSOJOUFSJPSQBUUFSO
UPNBUDI
your style
While competing firms can only offer a variety of colors for
customers, we also provide different grille designs to further
diversity our products. This enables customers to select products
that are better suited to their preferences and geographic location.
<Interior pattern>
<Classic pattern>
t &BTJFSUIBO&WFSUP$MFBOUIF#MBEF
Other products require you to disassemble and remove the panel
in order to clean the blade, but our product is designed so that the
blade safely and easily detaches and re-attaches, enabling you to
easily clean it.
t 4
FMGEJBHOPTUJDGVODUJPOPGJOEPPSVOJUUPNJOJNJ[F
inconvenience in case of malfunction
If the indoor unit malfunctions due to equipment failure
during operation, the type of problem can be checked from
the panel display, and the service time and inconvenience can
be minimized by submitting a service request based on the
information from the self diagnostics of indoor unit.
t .
JOJNVNJOTUBMMBUJPODPTUCZCVJMUJOIJHIIFBEESBJOQVNQ
The high head pump is built into the indoor unit and the
condensed water generated during the cooling operation will
be drained to the outside. The pumping height can be up to
750mm so that drain pip installation can be easier and save
time and cost of installation.
t * OEJWJEVBM#MBEF$POUSPM
- Capable of realizing optimal air current in accordance to
customer preference and diverse structures located in
different directions through individual control of each of the
4 blades.
- Individual control can be realized through both cable and
wireless remote control.
NS0714DXEA/RC071DHXEA NS0714PXEA/RC071PHXEA
ITEM
NS0714DXEASTK/RC071DHXEASTK NS0714PXEA/XSA/RC071PHXEA/XSA
Indoor Unit
Remote Controller
NS1004ZXEA/ NS1404PXEA/
RC100ZHXEA/ RC140PHXEA/ NS1404PXEA/
ITEM
NS1004ZXEA/XSA/ NS1404PXEA/XSA/ RC140PHXGA
RC1004ZHXEA/XSA RC140PHXEA/XSA
Indoor Unit
Outdoor Unit
IMAGE
Remote Controller
Indoor Unit
Outdoor Unit
IMAGE
Remote Controller
Power Product 1Φ, 220~240V/50Hz 3Φ, 380~415V/50Hz 1Φ, 220~240V/50Hz 1Φ, 220~240V/50Hz
Indoor LxHxD mm 840 x 246 x 840 840 x 246 x 840 840 x 246 x 840 840 x 288 x 840
Panel LxHxD mm 950 x 45 x 950 950 x 45 x 950 950 x 45 x 950 950 x 45 x 950
Outdoor LxHxD mm 940 x 998 x 330 940 x 998 x 330 940 x 998 x 330 940 x 998 x 330
Indoor Product kg(Net) 16.0 16.0 16.0 18.0
Outdoor Product kg(Net) 72.0 81.0 72.0 72.0
Cooling(STD) W 10,000 10,000 9,000 9,000
Capacity
Heating(STD) W 11,200 11,200 10,000 10,000
Indoor Unit
Outdoor Unit
IMAGE
Remote Controller
Indoor Unit
Outdoor Unit
IMAGE
Remote Controller
Indoor Unit
Outdoor Unit
IMAGE
Remote Controller
Indoor Unit
Outdoor Unit
IMAGE
Remote Controller
*5&. "$'#%&) "$'#%&) "$'#1&) "$'#%&) "$'#1&) "$'#%&) "$'#%&) "$'#1&) "$'#1&) "$'#'&)
"$'$"%&) "$'$"%&) "$'$"1&) "$'$"%&) "$'$"1&) "$'$"%&) "$'$"%() "$'$"1&) "$'$"1() "$'$"'&)
Indoor Unit
Outdoor Unit
IMAGE
Remote Controller
Power Product 1Φ, 220~240V/ 50Hz 1Φ, 220~240V/ 50Hz 1Φ, 220~240V/ 50Hz 1Φ, 220~240V/ 50Hz 1Φ, 220~240V/ 50Hz 1Φ, 220~240V/ 50Hz 3Φ, 380-415V/ 50Hz 1Φ, 220~240V/ 50Hz 3Φ, 380-415V/ 50Hz 1Φ, 220~240V/ 50Hz
Indoor unit LxHxD mm 840*204*840 840*204*840 840*204*840 840*246*840 840*288*840 840*246*840 840*246*840 840*288*840 840*288*840 840*288*840
Product
Panel LxHxD mm 950*45*950 950*45*950 950*45*950 950*45*950 950*45*950 950*45*950 950*45*950 950*45*950 950*45*950 950*45*950
Outdoor unit Product LxHxD mm 790*285*548 880*798*310 880*798*310 940*998*330 940*998*330 940*998*330 940*998*330 940*1210*330 940*1210*330 940*1420*330
Indoor unit Product kg(Net) 15.0 15.0 15.0 16.0 18.0 16.0 16.0 20.0 20.0 20.0
Outdoor unit Product kg(Net) 38.5 55.0 55.0 72.0 72.0 72.0 81.0 88.0 91.0 98.0
Cooling(STD) W 5100 7100 7100 9000 9000 10 000 10 000 10 000 10 000 10 000
Capacity
Heating(STD) W 5700 8000 8000 10 000 10 000 11 200 11 200 11 200 11 200 11 200
Cooling(STD) W 1540 2210 1970 2990 2650 3320 3320 2500 2500 2380
Power consumption
Heating(STD) W 1460 2220 2100 2930 2630 3280 3280 2600 2600 2460
Cooling(STD) A 7.2 10.0 9.5 12.7 13.3 15.1 5.3 11.6 4.2 11.5
Operation current
Heating(STD) A 7.0 10.0 9.8 12.5 13.0 14.6 5.1 11.9 4.3 11.8
Indoor In case of 42 43 45 46 47 48 48 50 50 50
unit strongest air blow dB
Noise 42 43 45 46 47 48 48 50 50 50
(Cooling/Heating) 58 60 60 58 57 61 59 58 58 59
Outdoor In case of dB
unit strongest air blow 58 60 60 60 59 63 63 60 60 60
Refrigerant g 1400 1800 1800 3000 3000 3000 3100 3400 3400 3800
Liquid mm 6.35 6.35 6.35 9.52 9.52 9.52 9.52 9.52 9.52 9.52
Connecting Pipe
Gas mm 12.7 15.88 15.88 15.88 15.88 15.88 15.88 15.88 15.88 15.88
Additional Refrigerant g/m 10 25 25 50 50 50 50 50 50 50
Standard m 5 5 5 5 5 5 5 5 5 5
Extension length(Total) m 30 50 50 50 50 50 50 75 75 75
Extension length(Elevation) m 20 30 30 30 30 30 30 30 30 30
014077-1660C8-273437- 014077-1660C8-274750- 014077-1560D8-274750- 0140 77-1560E8-275A64- 014077-156219-275A64- 014077-156219-276470- 014077-156219-276470- 014077-157239-276470- 014077-157239-276470- 014077-156249-276470-
370000 370000 370020 370000 370000 370000 370000 370000 370000 370000
Option Code 020000-100000-200000- 020000-100000-200000- 020000-100000-200000- 020000-100000-200000- 020000-100000-200000- 020000-100000-200000- 020000-100000-200000- 020000-100000-200000- 020000-100000-200000- 020000-100000-200000-
300000 300000 300000 300000 300000 300000 300000 300000 300000 300000
03483B-104045- 034642-104546-246424- 034443-104046-244434- 033D3D-103B3C-23D3D3- 033D3F-10393B-23D3F3- 03413E-104341-2403B2- 03413E-104341-2403B2- 033D37-10272B-23E382- 033D37-10272B-23E382- 033D37-10292A-23D372-
2483B4-304500 354600 304600 3B3C00 393B00 3F2F00 3F2F00 372B00 372B00 392A00
Indoor Unit
Outdoor Unit
IMAGE
Remote Controller
2-3-1 Accessories
Cable-tie DB65-00191A 5
Essential Offer
(Indoor Unit)
Essential Offer
Drain Plug DB67-00806A 1
(Outdoor Unit)
BOLT-FLANGE 6011-003975 4
Accessories (cont.)
■8JSFMFTTSFNPUFDPOUSPMMFS .3%)
<$PEF/P%##>
Accessories (cont.)
■8JSFESFNPUFDPOUSPMMFS .838&
<$PEF/P%##>
Optional
Accessories (cont.)
■$FOUSBMDPOUSPMMFS .$."%
<$PEF/P%##>
Optional
M4 X 16 Screw 6002-000474 7
Accessories (cont.)
■'VODUJPODPOUSPMMFS .$."
<$PEF/P%#">
Optional
* PC control and DMS cannot be used when using the function controller
Accessories (cont.)
■3FMBZ .*.#%
<$PEF/P%#">
Relay DB93-12203A 1
■3FMBZ .*.#&
<$PEF/P%#+
Relay DB93-03568D 1
Basic/
Dust filter DB63-02739A
Water wash
Item Remarks
+SCREW DRIVER
Adjustable Wrench
(8mm, 10mm, 13mm)
Q3$%)63$1)63$%)6"$'$"%&)"$'$"1&)
QAC090FCA6&)"$'$"%6
/P Parts Procedure Remark
Q3$1)63$%)6/AC100FCAP6"$'$"'&)
Q"$'$"%&)
No Parts Procedure Remark
4. Troubleshooting
▶ Set the indoor unit address and installation option with remote controller option.
Set the each option separately since you cannot set the ADDRESS setting and indoor unit installation setting option at the
same time.You need to set twice when setting indoor unit address and installation option.
Mode change
Step 1 &OUFSJOHNPEFUPTFUPQUJPO
2. Insert batteries and enter the option setting mode while pressing High Temp button and Low Temp button .
After entering the option setting status, select the option as listed below.
4FUUJOH4&(
4&(PQUJPO
Press Low Fan button(∨) to enter SEG2 value.
Press High Fan button(∧) to enter SEG3 value.
Each time you press the button, ĺ ĺ… ĺ will be selected in rotation. SEG2 SEG3
4FUUJOH4&(
4&(PQUJPO
Press Low Fan button(∨) to enter SEG4 value.
Press High Fan button(∧) to enter SEG5 value.
Each time you press the button, ĺ ĺ … ĺ will be selected in rotation. SEG4 SEG5
4FUUJOH4&(
4&(PQUJPO
Press Low Fan button(∨) to enter SEG6 value.
Press High Fan button(∧) to enter SEG8 value.
Each time you press the button, ĺ ĺ … ĺ will be selected in rotation. SEG6 SEG8
4FUUJOH4&(
4&(PQUJPO
Press Low Fan button(∨) to enter SEG9 value.
Press High Fan button(∧) to enter SEG10 value.
Each time you press the button, ĺ ĺ … ĺ will be selected in rotation. SEG9 SEG10
4FUUJOH)FBUNPEF
Press Mode button to be changed to HEAT mode in the ON status.
4FUUJOH4&(
4&(PQUJPO
Press Low Fan button(∨) to enter SEG11 value.
Press High Fan button(∧) to enter SEG12 value.
Each time you press the button, ĺ ĺ … ĺ will be selected in rotation. SEG11 SEG12
4FUUJOH4&(
4&(PQUJPO
Press Low Fan button(∨) to enter SEG16 value.
Press High Fan button(∧) to enter SEG17 value.
Each time you press the button, ĺ ĺ … ĺ will be selected in rotation. SEG16 SEG17
4FUUJOH4&(
4&(PQUJPO
Press Low Fan button(∨) to enter SEG18 value.
Press High Fan button(∧) to enter SEG20 value.
Each time you press the button, ĺ ĺ … ĺ will be selected in rotation. SEG18 SEG20
4FUUJOH4&(
4&(PQUJPO
Press Low Fan button(∨) to enter SEG21 value.
Press High Fan button(∧) to enter SEG22 value.
Each time you press the button, ĺ ĺ … ĺ will be selected in rotation. SEG21 SEG22
4FUUJOH)FBUNPEF
Press Mode button to be change to HEAT mode in the OFF status.
4FUUJOH4&(
4&(NPEF
Press Low Fan button(∨) to enter SEG23 value.
Press High Fan button(∧) to enter SEG24 value.
Each time you press the button, ĺ ĺ … ĺ will be selected in rotation. SEG23 SEG24
After setting option, press button to check whether the option code you input is correct or not.
¤ ¤ ¤ ¤ ¤
¤ ¤ ¤ ¤
Press operation button with the direction of remote control for set.
For the correct option setting, you must input the option twice.
1. Reset the indoor unit by pressing the RESET button of indoor unit or outdoor unit.
2. Take the batteries out of the remote controller and insert them again and then press the operation button.
1) To use the various additional functions of the wired remote controller, press the [Save] and [Exit] buttons at the same time for more than
three seconds.
• Moves to the setting of additional functions and then [Main Menu] is displayed.
2) Select the menu you want by referring to the list of additional functions of the wired remote controller on the next page.
• Use [^] or [∨] buttons to select the number of the main menu and press the [>] button to move into the submenu-setting step.
• Use [^] or [∨] buttons to select the number of the submenu and press the [>] button to move into the date-setting step.
• When it moves to the setting step, the current setting value is displayed.
• By referring to the table, set each of the data.
• Use [^] or [∨] buttons to change the current setting value and press the [>] button to move into the next setting value.
• Press the [Save] button to save the setting value and exit to the setting step of the submenu.
• Press the [Exit] button to exit to the normal mode.
• Please set the option after completing the communication with the wired remote controller and the indoor unit.
4FUUJOHBOJOEPPSVOJUBEESFTT ."*/3.$
3. Before installing the indoor unit, assign an address to the indoor unit according
to the air conditioning system plan.
Remote
Controller
Display
Indication Details Indication Details Indication Details RESERVED RESERVED Indication Details
No Main
0
Indication address
and Details Main A single
0 A 0~3
address digit
1
setting
mode
Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
Setting RMC
Explanation PAGE Group channel(*16) Group address
address
Remote
Controller
Display
Indication Details RESERVED Indication Details RESERVED Indication Details Indication Details
No RMC
0
Indication address
and Details 1 RMC RMC1 0~2 RMC2 0~F
address
1
setting
mode
t :PVDBOTFUUIF.BJOBEESFTTGSPN_SBOHFBOEJGZPVJOQVUPUIFSOVNCFST
hDPNNVOJDBUJPOFSSPShXJMMPDDVS
t 8IFOi"w_w'wJTFOUFSFEUP4&(_
UIFJOEPPSVOJU."*/"%%3&44JTOPUDIBOHFE
t *GZPVTFUUIF4&(BT
UIFJOEPPSVOJUXJMMNBJOUBJOUIFQSFWJPVT."*/"%%3&44FWFOJGZPVJOQVUUIFPQUJPOWBMVFPG4&(_
t *GZPVTFUUIF4&(BT
UIFJOEPPSVOJUXJMMNBJOUBJOQSFWJPVT3.$"%%3&44FWFOJGZPVJOQVUUIFPQUJPOWBMVFPG4&(_
4-1-5 Setting an indoor unit installation option (Suitable for the condition of each installation location)
3. Set the installation option according to the installation condition of an air conditioner.
- 5IFEFGBVMUTFUUJOHPGBOJOEPPSVOJUJOTUBMMBUJPOPQUJPOJTi
w
- Individual control of a remote controller(SEG20) is the function that controls an indoor unit individually when there is more
than one indoor unit.
▶ 1WAY/2WAY/4WAY MODEL : Drain pump(SEG8) will be set to 'USE + 3minute delay' even if the drain pump is set to 0.
▶ 1 WAY/2WAY/4WAY,DUCT MODEL : Number of hours using filter(SEG18) will be set to '1000hour' even if the SEG18 is set to
exept for 2 or 6.
▶ If you input a number other than 0~4 of the individual control of the indoor unit(SEG20), the indoor is set as "indoor 1".
▶ 4WAY MODEL : Even when the value of Heating setting compensation(SEG21) is set to '0', it wil be recognized as '5°C'.
Remote
Controller
RESERVED RESERVED
Display
Remote
Controller
Display RESERVED RESERVED RESERVED
Remote
Controller
Display
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
Thermo Use of 1000
Indication 0 Disuse 0 0 Disuse 0 2
on buzzer Hour
and ON/OFF
Details 2 1
Control Operation Non use 2000
1 1 Use 1 6
OFF on of buzzer Hour
2
Control
Option SEG19 SEG20 SEG21
Individual control of Heating setting
Explanation PAGE
a remote controller compensation
Remote
Controller
Display
Remote
Controller
Display
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
Indication The
and Details Option Tens’ digit Unit digit
0 D 0~F 0~9 0~9 changed 0~F
mode of SEG of SEG
value
t 8IFODIBOHJOHBEJHJUPGBOJOEPPSVOJUBEESFTTTFUUJOHPQUJPO
TFUUIF4&(BTA"
t 8IFODIBOHJOHBEJHJUPGJOEPPSVOJUJOTUBMMBUJPOPQUJPO
TFUUIF4&(BTA
&Y
8IFOTFUUJOHUIFhCV[[FSDPOUSPMhJOUPEJTVTFTUBUVT
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
The option The tens’ digit of The unit digit of
Explanation PAGE MODE mode you want an option SEG an option SEG The changed
to change value
you will change you will change
Indication 0 D 2 1 7 1
Model SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
Remocon
display
NS0714DXEA 0 1 4 0 7 7 1 6 6 0 C 8
NS0714PXEA 0 1 4 0 7 7 1 3 6 0 D 8
NS0904DXEA 0 1 4 0 7 7 1 5 6 0 E 8
NS0904PXEA 0 1 4 0 7 7 1 5 6 2 1 9
NS1004DXEA 0 1 4 0 7 7 1 5 6 2 1 9
NS1004PXEA 0 1 4 0 7 7 1 5 7 2 3 9
NS1004ZXEA 0 1 4 0 7 7 1 5 6 2 4 9
NS1254DXEA 0 1 4 0 7 7 1 5 7 2 3 A
NS1254PXEA 0 1 4 0 7 7 1 5 7 2 3 A
NS1404DXEA 0 1 4 0 7 7 1 5 7 2 3 B
NS1404PXEA 0 1 4 0 7 7 1 5 6 2 4 B
NS0724DXBA 0 1 4 0 7 7 1 6 6 0 C 7
NS1004DXBA 0 1 4 0 7 7 1 5 6 2 1 9
NS1454DXBA 0 1 4 0 7 7 1 5 7 2 3 B
AC052FB4DEH 0 1 4 0 7 7 1 6 6 0 C 8
AC071FB4DEH 0 1 4 0 7 7 1 6 6 0 C 8
AC071FB4PEH 0 1 4 0 7 7 1 5 6 0 D 8
AC090FB4DEH 0 1 4 0 7 7 1 5 6 0 E 8
AC090FB4PEH 0 1 4 0 7 7 1 5 6 2 1 9
AC100FB4DEH 0 1 4 0 7 7 1 5 6 2 1 9
AC100FB4PEH 0 1 4 0 7 7 1 5 7 2 3 9
AC100FB4FEH 0 1 4 0 7 7 1 5 6 2 4 9
Model SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
Remocon
display
NS0714DXEA 2 7 4 7 5 0 3 7 0 0 0 0
NS0714PXEA 2 7 4 7 5 0 3 7 0 0 2 0
NS0904DXEA 2 7 5 A 6 4 3 7 0 0 2 0
NS0904PXEA 2 7 5 A 6 4 3 7 0 0 4 0
NS1004DXEA 2 7 6 4 7 0 3 7 0 0 4 0
NS1004PXEA 2 7 6 4 7 0 3 7 0 0 2 0
NS1004ZXEA 2 7 6 4 7 0 3 7 0 0 4 0
NS1254DXEA 2 7 7 D 8 C 3 7 0 0 4 0
NS1254PXEA 2 7 7 D 8 C 3 7 0 0 4 0
NS1404DXEA 2 7 8 C A 0 3 7 0 0 4 0
NS1404PXEA 2 7 8 C A 0 3 7 0 0 4 0
NS0724DXBA 2 7 4 8 5 6 3 7 0 0 0 0
NS1004DXBA 2 7 6 4 7 8 3 7 0 0 2 0
NS1454DXBA 2 7 9 1 A 7 3 7 0 0 4 0
AC052FB4DEH 2 7 3 4 3 7 3 7 0 0 0 0
AC071FB4DEH 2 7 4 7 5 0 3 7 0 0 0 0
AC071FB4PEH 2 7 4 7 5 0 3 7 0 0 2 0
AC090FB4DEH 2 7 5 A 6 4 3 7 0 0 0 0
AC090FB4PEH 2 7 5 A 6 4 3 7 0 0 0 0
AC100FB4DEH 2 7 6 4 7 0 3 7 0 0 0 0
AC100FB4PEH 2 7 6 4 7 0 3 7 0 0 0 0
AC100FB4FEH 2 7 6 4 7 0 3 7 0 0 0 0
Key
K
Ke
eeyy Sw
SSwitch
wit
itc
tch
77-segment
7-
-sseeg
-s eg
gm
meent
nt display
nt disp
sp
pla
pl
lay
ay
7-segment display
Key Switch
[RC090/100/125/140/1456HX66,AC090/100FCA666] [RC072DHXBA]
Long press once Main MICOM version Year (Hex) Month (Hex) Date (Two digits) Date (One digit)
Short press once Inverter MICOM version Year (Hex) Month (Hex) Date (Two digits) Date (One digit)
Short press once E2P version Year (Hex) Month (Hex) Date (Two digits) Date (One digit)
※ Press the K4 button long (Main MICOM version) ĺ Press once more shortly ĺ Press shortly one more time (E2P version)
ON (Default) OFF
Switch 1 Set an auto address. Set a manual address.
Switch 2 - -
Switch 3 Snowdrift prevention control not used Snowdrift prevention control used
Switch 4 - -
※ When the snowdrift prevention control is used, the eco mode (standby power mode) does not work.
&DP.PEF<1PXFS4BWJOH.PEF>
[RC090/100/125/140/1456HX66,AC090/100FCA66H]
- Display with the eco mode displaying lamp.
&DP.PEF<1PXFS4BWJOH.PEF> (Continued)
[RC072DHXBA]
- No separate eco mode is displayed.
t$IFDLUIFDPOOFDUJPOPGNPUPSDPOOFDUPS
X X X Error of fan motor in the indoor unit operation-off operation-off operation-off -
t$IFDLUIFTQFFEPGUIFNPUPSGBO
t$IFDLGMPBUTXJUDIDPOOFDUJPO
X X Detection of the float switch operation-off operation-off operation-off -
t$IFDLXIFUIFSUIFESBJOIBTCFFOGJMMFEXJUIXBUFS
t$IFDLUIFJOEPPSNPEFMUPTFUUIFPQUJPOT
EEPROM option error operation-off operation-off operation-off -
t*OTQFDUJPOGPSNBUDICFUXFFOJOEPPSBOEPVUEPPSNBDIJOFNPEFMT
: On : Blink X : Off
Product operation in
error condition
&SSPSNPEF Contents .FBTVSF &SSPSUZQF
Outdoor unit/
Compressor/Indoor unit
Indoor unit communication Check the communication cable of indoor unit. Check Communication
Operation Off
error the DC output voltage at the communication terminal error
Indoor temperature sensor Check indoor unit room temperature sensor. Check Indoor sensor
Operation Off
(open/short error) indoor unit PCB connector CN41 (White) error
Indoor unit Eva In sensor Check indoor unit pipe sensor. Check indoor PCB Indoor sensor
Operation Off
(Open/Short) connector CN41(White) error
Indoor floating switch Check indoor unit float sensor. Check indoor PCB Self diagnostic
Operation Off
secondary detection connector CN5 (black) error
Product operation in
error condition
&SSPSNPEF Contents .FBTVSF Outdoor unit/ &SSPSUZQF
Compressor/Indoor
unit
Outdoor unit
Capacities not matched Check the option code of the indoor unit Operation Off protection
control error
Communication error between
Check the connection wire between the indoor unit and Wired remote
the indoor unit and wired Normal operation
the wired remote controller controller error
remote controller
Communication error between
Check the option switch for defining the Master and Wired remote
the Master and Slave wired Normal operation
Slave (only one Master and one Slave can exist) controller error
remote controllers
COM1/COM2 cross installation Check that wired remote controller is connected to the Wired remote
Normal operation
error COM2 terminal of the indoor unit controller error
Is indoor temperature
Yes
sensor disconnected from the
connector in PCB?
<Temperature sensor
resistance value>
Current
Resistance
temperature
(kΩ)
(°C)
40 5.800
35 6.900
In this case, is the resistance Yes
value out of range in the temperature 30 8.300
table on the right? 25 10.00
20 12.10
No Indoor temperature sensor 15 14.70
failure (replace)
10 18.00
Restart the system after replacing the PCB 5 22.00
0 28.30
-5 33.90
-10 42.30
Current
Resistance
temperature
(kΩ)
(°C)
40 5.800
35 6.900
In this case, is the resistance Yes
value out of range in the temperature table 30 8.300
on the right? 25 10.00
20 12.10
Failure of the indoor heat
No 15 14.70
exchanger temperature sensor
(replace) 10 18.00
Restart the system after replacing the PCB
5 22.00
0 28.30
-5 33.90
-10 42.30
*OEPPS'"/FSSPS
Symptom Indoor unit fan does not run /Runs at excessive high speed and stops.
. Motor connector break away
Failure
. Indoor unit FAN does not run : Defective motor or PBA
Connect the
connector to PCB
No
No
Symptom Communication error between the indoor and outdoor unit for two minutes
Failure Communication error between the indoor unit and outdoor unit
Is there a response from the indoor PCB? No Check the communication cable and
(LED01 (RED) is not ON) replace the indoor unit PCB
Yes LED01
Good
Bad
+0.7V
-0.7V
Symptom The indoor unit floating sensor is open and that state is maintained for more than one minute
Increase in the drain pan water level due to failure of the indoor unit drain pump,
Failure
or float sensor failure
Error occurs
No
Same error occurs again
Is the water level in the drain pan high?
Yes
Yes No
Replace the indoor unit PCB
Reset the indoor unit power and Normal operation
check the operation of the drain pump.
(it vibrates when operating)
Yes
Is the water level in No
drain pan decreasing?
Yes Replace the drain pump Replace the indoor unit PCB
Normal operation
t 'MPBUTFOTPSFSSPSJTDMFBSFEPOMZ
Replace the drain pump when the indoor power is reset
&&130.DJSDVJUGBJMVSF
No
2. Check procedure
Check the power to the indoor unit. No Check the connection of the power line of the
terminal block.
1. Is the line voltage 220 Vac? 1. Check wires are correctly connected by
(Yes) 1(L)׳2(N) referring to the electrical circuit.
Yes
Yes
Continued
Continued
Outdoor main PBA checking part Outdoor EMI PBA checking part
Fuse
12V power EMI PBA Fuse
Bridge Diode
Yes
Fuse
Fan Motor
Connector
2. Check procedure
RC090/100/125/140/1456HXE6, RC072DHXB6
RC100DHXB6
Yes
RC090/100/125/140/1456HXE6,
RC100DHXB6 RC072DHXB6
Yes
Continued
Fuse
Yes
Indoor control PBA checking part Display PBA checking part
12V power
Front Fuse
[RC072DHXB6]
Fan Motor
Connector
[RC090/100/125/140/1456HXE6, [RC072DHXB6]
RC100DHXB6]
*OEPPSPVUEPPSDPNNVOJDBUJPOFSSPS NJO
&SSPS$PEF&
3$6666)966, AC666FCA666 Common)
1. Test Item
1) Check the communication and power connection.
2) Check the communication connector connection.
- RC072DHXB* : Outdoor Unit Inverter PBA CN301
- RC090/100/125/140/145*HX**, AC***FCA*** : Outdoor Unit Main PBA CN31
3) Check the communication circuit on the PBA.
2. Check procedure
No
Does the communication error occur?? End the service.
TVS-Diode
Yes
TVS-Diode
Continued
Yes
Communication B (#7)
Communication A
(#6)
Location
$PNNVOJDBUJPOFSSPSCFUXFFOPVUEPPSVOJU*/7׳."*/.*$0. NJO
2. Check procedure
No
Does the communication error occur?? End the service.
Yes
Is there a problem
in the connections of communications No
Check the communication connections.
between the outdoor unit inverter (CN31)
and main PBA (CN39)?
[RC6666HXG6, RC145DHXH6, AC100FCA6GH Confirmation Matters]
1 2
Yes
Power OFF
Yes
[RC090/100/125/140/14566666, [RC072DHXB6]
AC666FCA666]
[RC090/100/125/140/14566666, [RC072DHXB6]
AC666FCA666]
(Example) COND. sensor/outdoor unit temperature sensor measuring resistance value by temperature: E231, E221
(Example) OLP sensor/discharge temperature sensor measuring resistance value by temperature: E320, E251.
Does the same error occur again No After confirming the state is normal,
after power is on? end the service.
Yes
0VUEPPS6OJU'BO&SSPS
&SSPS$PEF&
&3$6666)966,AC666FCA666 Common)
1. Test Item
1) Check the connection of fan connectors (CN90, CN91). [In case of RC072DHXB6, CN901]
2) Check the voltage of the fan motor connector in the inverter PBA of the outdoor unit.
3) Check the power supply of the inverter PBA of the outdoor unit.
4) Check the single fan motor. (Do not forget to separate the motor connector 30 seconds after power off!)
2. Check procedure
Yes
Yes
ఐ At least 30 seconds after power is OFF, attach/detach the fan motor connector! ױThreatened to cause secondary damage to the motor and the PBA.
ఐ Check the single inverter PBA or fan motor and only if there is a fault, replace!
ఐ Do not replace the main PBA of the outdoor unit relating to the fault in the fan motor!
ఐ If the error is indicated on 7-segment of the main PBA of the outdoor unit, the main PBA of the outdoor unit has no fault.
ఐ In case of a control problem, it is possible to solve with S/W update.
&SSPSPG$PNQSFTTPS4UBSUVQBOE3PUBUJPO
&SSPS$PEF&
&3$6666)966,AC666FCA666 Common)
1. Test Item
1) Check the power supply / Check the restart-up after power is reset.
2) Check the compressor and the state of the compressor wire assembling.
3) Check the fault of the single compressor wire.
2. Check procedure
Check power. /
Check the restart-up after power is reset.
1. Is there any problem in input power? No
(Single-phase: 220Vac, 3-phase: 380Vac) End the service.
2. Does the error occur again after power rest?
Yes
Yes
Yes
Continued
&SSPSPG$PNQSFTTPS4UBSUVQBOE3PUBUJPO
&SSPS$PEF&
&3$6666)966,AC666FCA666 Common) (Continued)
Continued
Yes
W
V
Yes U W
V
: After replacing the inverter PBA of the U
outdoor unit, check normal startup.
ױEnd the service. [RC6666HXG6, [RC090/100/125/140/14566666,
RC6666HXH6, AC666FCA666]
AC100FCA6GH]
ఐ͑͑E461, E467 Error-related, EMI / outdoor unit Main / Indoor unit Main PBA do not replace!
ĺ This error is related to the compressor and Inverter PBA. (Not related to the above PBA) V
W
ఐ͑Because it is an error regarding the inverter PBA, it is not related to the aforementioned PBA. W
ఐ͑Ensure that the service valve is open! V U
ఐ͑͑While the service valve is closed and the COMP. starts, it is possible to cause a fault due to
differential pressure. U
PBA connecting connector COMP connecting connector
[RC072DHXB6]
&SSPSPGVOEFSDVSSFOUFSSPS1'$PWFSDVSSFOU
&SSPS$PEF&
&3$6666)966,AC666FCA666 Common)
1. Test Item
1) Check the power supply. / Check the re-startup after the power is reset. Error Code Description Model
Error of the outdoor unit RC6666HX66,
2) Check the outdoor unit installation environment. E462
under-current AC666FCA666
ױCheck the disconnection of the wires regarding the inverter PBA of Limited to RC6666HXE6,
Error of the outdoor unit
the outdoor unit and check the installation environment. E484 RC6666HXB6,
PFC over-current
AC666FCA*EH
3) Check the indoor unit installation environment.
4) Check the opening of the service valve.
2. Check procedure
No
Has the service valve been completely open? Open the valve.
Yes
No
Does the compressor work correctly? Replace the compressor.
Yes
After replacing the inverter PBA of the outdoor unit, check
normal startup. ͑ױEnd the service.
*1.0WFSDVSSFOU&SSPS
&SSPS$PEF&3$6666)966,AC666FCA666Common)
1. Test Item
1) Check the power supply. / Check the re-startup after the power is reset.
2) Check the outdoor unit installation environment.
ױCheck the disconnection of the wires regarding the inverter PBA of the outdoor unit and check the installation environment.
ױAt the site where several units were installed at the same time, check whether communication connections and pipes have been wrongly connected!
3) Check the indoor unit installation environment.
4) Check the opening of the service valve.
5) Check the compressor and the state of the compressor wire assembling.
6) Check for fault of the single compressor wire.
2. Check procedure
30 seconds after power off, power on. Check the outdoor unit installation
environment. ױCheck everything is normal at
re-start͑͑͟ױEnd the service.
1. Check the wire disconnection of the inverter
PBA of the outdoor unit.
No 2. Remove the obstacles of the suction pipes
Has the outdoor unit been correctly installed? of the outdoor unit and secure the space.
Have the pipes and wires of indoor and No Re-install correctly under the product
outdoor units been correctly installed? specifications.
Yes
Continued
ᐭ ᐮ ᐯ
Pipe
Wire Poor installation
*1.0WFSDVSSFOU&SSPS
&SSPS$PEF&3$6666)966,AC666FCA666 Common)(Continued)
Continued
Are the connections of the compressor No Check the state of the connection
correctly connected with the compressor? of the compressor.
Yes
Yes
Yes
Yes
Continued
*1.0WFSDVSSFOU&SSPS
&SSPS$PEF&RC6666)966,AC666FCA666 Common)(Continued)
Continued
Yes
Yes W
V
U W
Replace the PCB.
V
U
[RC6666HXG6, [RC090/100/125/140/1456HX66,
RC6666HXH6, AC666FCA666]
ఐ͑͑E464 Error-related, EMI / outdoor unit Main / Indoor unit Main PBA do not AC100FCA6GH]
replace! ĺ This error is related to the compressor and Inverter PBA.
(Not related to the above PBA)
V
W
W
V U
U
COMP connecting
PBA connecting connector
connector
[RC072DHXB6 Series]
%$-*/,0WFSDVSSFOUBOE-PXWPMUBHF&SSPS
&SSPS$PEF&3$6666)966,AC666FCA666 Common)
1. Test Item
1) Check the power supply. / Check the re-startup after the power is reset. ͑ױIs there a fault in input power?
͑ױDoes the error occur again at operation after power is reset?
2) Check the connection of the power, and check whether the jointed power connection exists.
3) Check the reactor and its connecting wires.
4) Check the fuses of EMI PBA.
5) Check the terminal block and power terminal box and the wire assembly.
2. Check procedure
Power OFF
No
Is the power cable correctly connected? Reconnect the power cable.
Yes
[RC6666HXE6, RC100DHXB6, AC666FCA666Common:
Fault in connection of the jointed power cable]
Check the reactor and its 1. Connect the Wire normally (Reactor and
connecting wires. the outdoor unit Inverter PBA) ĺ
1. Is the wire between the reactor and the inverter Check the normal operation ĺ
PBA of the outdoor unit correctly connected? No Shut down the service
2. Is there any fault such as scratch, or pressing of 2. Replace the reactor ĺ
the reactor or broken or Check the normal operation ĺ
loosened terminal? Shut down the service
[RC6666HXG6, RC145DHXH6, AC100FCA6GH Confirmation Matters]
Continued
%$-*/,0WFSDVSSFOU-PX7PMUBHF&SSPS
&SSPS$PEF&3$6666)966,AC666FCA666Common)
Continued
Yes
Yes
Is the fuse of the EMI PBA disconnected? Replace the fuse.
Yes
(Short-Normal, Open-Fault)
[RC072DHXB6]
No
2. Check procedure
No
Did the error occur? End the service.
Yes
Yes
Have the pipes and wires of indoor and No Re-install correctly under
outdoor units been correctly installed? the product specifications.
Yes
ᐭ ᐮ ᐯ
Continued
Yes
Yes
No
Is the indoor EVA sensor correctly connected? Re-connect the sensor connector.
Yes
No
Has the refrigerant been charged? Charge the refrigerant.
Yes
2. Check procedure
Check the opening of the outdoor unit No Check whether the pipe is empty and open all
service valve. the service valves on the gas and liquid pipes.
Yes
Yes
Yes
0UIFS
1. Current sensor error: Upload EEPROM to the main PBA of the outdoor unit.
After checking for normal operation of PCB, replace the inverter PCB.
2. Compressor Vlimit error: E465
If the compressor is abnormally run, replace the compressor and then ensure that it works normally.
ĺ If the compressor is normally run, check the assembling between the heatproof plate and the inverter PBA and then if there is no abnormality,
replace the inverter PBA."
3. OTP error: E471
Upload EEPROM to the main PBA of the outdoor unit.
4. Capacity inconsistence error: E556
Check the model name between the outdoor and indoor unit and re-enter the option code to the indoor unit.
5. 3-phase power cable disconnection: E424
Check for disconnection of the 3-phase (open) power cable, and check the disconnected EMI PBA fuse.
6. Outdoor unit freezing detection (at the stop of the compressor): E403
Outdoor overload protection control (at the stop of the compressor): E404
- Check whether the fan and the motor operate normally.
- Check the operation of EEV.
- Check the temperature sensor of the indoor unit heat exchanger.
- Check the indoor unit inlet blocking.
7. Outdoor unit compressor discharging temperature protection control: E416
- Check for lack of refrigerant.
- Check the blocking of the solenoid valve.
- Check the malfunction of the exhaust temperature sensor.
- Check EEV.
8. Error of impossibility to operate heating at outdoor temperature exceeding 30°C: E440
Error of impossibility to operate cooling at outdoor temperature of -5°C or under: E441
- It is not the error code in the product and it is a specification to protect the product by limiting the temperature scope of use.
- Use by referring to the temperature scope of use on the product manual, etc.
9. OLP overheating and compressor stop: E463
- Check the opening of the sub-valve.
- Check the amount of the cooling water.
- Check OLP sensor.
10. Current sensor error: E468
- Check EEPROM data.
- Check PCB operation.
11. IPM (IGBT Module) or PFCM temperature sensor error: E474
IPM overheat error for outdoor unit inverter compressor: E500
- Check whether IPM is correctly assembled on the heatproof plate.
- Check whether the inlet is blocked.
- If there is a defect, replace IPM.
17 15 8 13 10
1 2 18 3 4 5 16 6 7 14 9 11 12
① TB01- INPUT POWER ② CN74 - AC Drain Pump ③ CN73-BLDC FAN MOTOR ④ CN42-EVA IN/OUT TemperatureSensor
1(L) : Phase L # 1 : Phase N #1 : DC310V #2 : Not used #1 : EVA IN temperature sensor
2(N) : Phase N # 3 : Phase L #3 : AGND #4 : DC15V #2 : GND
#5 : FAN RPM #6 : RPM FEEDBACK #3 : EVA OUT temperature sensor
#4 : GND
⑨ CN81-External Contack control check ⑩ CN88-AS-PRO ⑪ DC DRAIN PUMP ⑫ TB02- COM1/COM2 Communication
#1 : DC 12V #2 : ERROR check Downloading #1: DC12V F1 : Communication signal F1
#3 : DC 12V #4 : Operating Check #2 : Drain pump signal F2 : Communication signal F2
V1 : DC 12V
V2 : GND
F3 : Communication signal F3
F4 : Communication signal F4
⑬ CN60-LOUVER1/2 ⑭ CN60-LOUVER3/4 ⑮ CN91-DISPLAY ⑯ CN83-External signal(ON/OFF)
#1 : DC12V #1 : DC12V #1 : DC 12V #1 : ON/OFF contack signal
#2 5 : Louver control signal #2 5 : Louver control signal #2 5 : LED control signal # 2 : GND
#6 : DC 12V #6 : DC 12V #6 : Remocon signal out
#7 10 : Louver control signal #7 10 : Louver control signal #7 8 : Not used
#9 : Remocon signal IN
#10 : GND
#11 : DC 5V
① CN01-DISPLAY
#1 : DC 12V
#2 5 : LED control signal
#6 : Remocon signal out
#7 8 : Not used
#9 : Remocon signal IN
#10: GND
#11: DC 5V
1 2 6 7 3 4 5
9 8
⑨ CN600-REACTOR
#1-#2 : DCL Reactor
2 3 1
■ Main PCB
- RC090DH✳, RC100DH✳, RC100PH✳, RC100ZH✳, RC125DH✳, RC125PH✳, RC140DH✳, RC140PH✳, RC145DHXHA
1 5 2 6 3 16 4 7 9 11 13
15 8 10 12 14
■ Main PCB
- RC071DHXEA, RC071PHXEA, RC071DHXEASTK, RC071PHXEA/XSA, RC072DHXBA
6 7 8 9 10 11
■ Sub PCB
- RC071DHXEA, RC071PHXEA, RC071DHXEASTK, RC071PHXEA/XSA, RC072DHXBA (cont.)
1 2 3
■ Main PCB
- AC052FCADEH
5 4 3 2 1 6 7 8 9 10 11 12
① CN030 : 4WAY VALVE ② CN951 : SIGNAL TO SUB PCB ③ CN252 : THERMISTOR ④ CN851:S-NET Communication
#1-#3 : AC220V #1 #28 : SIGNAL TO SUB PCB #1 #2 : OLP THERMISTOR #1 : DC12V
#2 : RXD
#3 : TXD
#4 : GND
⑨ CN901 : BLDC MOTOR ⑩ CN551: Downloader ⑪ CN451 : COMP POWER ⑫ CN051 : Reactor
#1: DV310V #1 #10 : Download #1 : COMP U-Phase #1 #2 : Reactor
#3: GND #2 : COMP V-Phase
#4: DC15V #3 : COMP W-Phase
#5: FAN_PWM
#6: FAN_Feedback
■ SUB PCB
- AC052FCADEH
1 2
2 1 3 4 5 8
6 7
1 3 6 7 5 2 8
4
1 2
Louver part
Sensor part
6-5
Samsung Electronics Samsung Electronics
6-5
7. Reference Sheet
Model Code
AH CH 1H 0H 0H FH BH 4H DH EH HH /H EH UH
※ "/" can be removed from the buyer card if there are not enough digits.
Model Code
NS
H 100
H HH HH XH EH AH /H SER
H
Buyer Name
※ "/" can be removed from the buyer card if there are not enough digits.
Model Code
AH CH 1H 0H 0H FH CH AH DH EH HH /H EH UH
Model Code
RC
H 140
H DH H HH XH GH AH /H SER
H
★
Buyer Name
Refrigerant
R R-22
X R410A
★
※ MCD: Dummy mock-up model
※ “/” can be removed from the buyer card if there are not enough digits.
7-1-5 Panel
Model Code
PH CH 4N
H BH AH KH 1H
★
Product design classification Color Panel version
P Panel B Black 1, 2, .... Korean market use
E WINE Export/
A, B, ....
U White foreign market use
Product Type V Ivory
C CST
TYPE
Product classification Automatic
A
1N Standard 1 way boarding/slide
1B Large-size 1 way S STANDARD
2N 2 WAY H PREMIUM
CST
4N 4 WAY
4S MINI 4 WAY
★
Language
4R Round
K Korean
C Chinese
M 8 Languages
E English
★
Only display the Global 4 way with Korean/
English K separator.
3-way valve
Liquid pipe
4-way valve
Gas pipe
Compressor
Oil separator
Cooling
Heating
Leak check points
■ CONDENSER
High temperature and high pressure gas state coolant discharged from the compressor is converted to a liquid state as it is cooled
down by the heat emission in the outdoor condenser unit, and sent to the evaporator.
■ COMPRESSOR
Low temperature and low pressure coolant is compressed and sent to the cycling system
■ EVAPORATOR
Liquid coolant sucked in through the capillary tubes cools down the room by absorbing the surrounding heat as it evaporates
(converting from liquid to gas). (Absorbing heat required for evaporation)
■ SERVICE VALVE
You can open the valve by turning the need valve counterclockwise using hex wrench, and it is used for vacuum, gas purging, coolant
injection, coolant purging, and indoor-outdoor unit connection.
■ ACCUMULATOR
Accumulator prevents the flow of liquid-state coolant into the compressor. (Liquid-state coolant flowing into the compressor will
overload the compressor.)
Cooling ✳ Cooling
10.0
Indoor (°C)
9.5
Outdoor(°C) 32/23 27/19 21/15
9.0
Pressure(kgf/cm²G)
Outdoor Temp.(°C)
Heating ✳ Heating
Indoor (°C)
Outdoor(°C) 28/18 27/19 20/15
Pressure(kgf/cm²G)
Outdoor Temp.(°C)
Asia gspn2.samsungcsportal.com
China china.samsungportal.com