V200R001C00
User Manual
Issue 09
Date 2019-10-25
and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.
Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees or
representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.
Website: https://e.huawei.com
Purpose
This document describes the ICC50 in terms of its overview, components, routine
maintenance, troubleshooting, and parts replacement.
The figures provided in this document are for reference only.
Intended Audience
This document is intended for:
Hardware installation engineers
Installation and commissioning engineers
Field maintenance engineers
System maintenance engineers
Sales engineers
Symbol Conventions
The symbols that may be found in this document are defined as follows.
Symbol Description
Indicates a hazard with a high level of risk which, if not avoided, will
result in death or serious injury.
Indicates a hazard with a medium level of risk which, if not avoided,
could result in death or serious injury.
Indicates a hazard with a low level of risk which, if not avoided, could
result in minor or moderate injury.
Symbol Description
Supplements the important information in the main text.
NOTE is used to address information not related to personal injury,
equipment damage, and environment deterioration.
Change History
Changes between document issues are cumulative. The latest document issue contains all the
changes made in earlier issues.
Issue 09 (2019-10-25)
Modified contents about the rectifier and the SSU.
Issue 08 (2019-09-12)
Deleted contents about the app.
Issue 07 (2019-01-31)
Added LIVE APP.
Issue 06 (2018-06-20)
Added ESM-4850A1 and ESM-4875A1.
Issue 05 (2018-03-16)
Updated the cabinet operating temperature range.
Issue 04 (2017-04-17)
Added the regulatory compliance statements.
Issue 03 (2016-11-20)
Updated section "Replacing the M48300N1."
Issue 02 (2016-07-06)
Updated the tool list.
Issue 01 (2016-06-14)
Added the configurations of ICC50T-HDA and ICC50T-HDT.
Contents
4 Routine Maintenance............................................................................................................. 71
4.1 Maintenance Preparations .....................................................................................................................................71
4.2 PV Modules Routine Maintenance ........................................................................................................................72
4.3 Cabinet Routine Maintenance ...............................................................................................................................74
4.4 ICC Routine Maintenance.....................................................................................................................................75
4.5 Routine Maintenance for Poles .............................................................................................................................75
4.6 PoE Adapter Routine Maintenance ........................................................................................................................76
4.7 Lead-Acid Battery Routine Maintenance...............................................................................................................76
5 Troubleshooting ..................................................................................................................... 81
5.1 General Troubleshooting Procedure ......................................................................................................................81
5.2 Troubleshooting Component .................................................................................................................................82
5.2.1 Troubleshooting PV modules .............................................................................................................................82
5.2.2 Troubleshooting Lead-Acid Batteries .................................................................................................................82
5.2.3 Troubleshooting Lithium Battery .......................................................................................................................83
5.2.4 Troubleshooting a PSU ......................................................................................................................................84
5.2.5 Troubleshooting a PoE Adapter ..........................................................................................................................84
5.2.6 Inverter Troubleshooting ....................................................................................................................................85
1 Safety Precautions
Bolts should be tightened with a torque wrench and marked using red or blue color. After
the installation personnel confirm that the screws are tightened, mark the screws using
blue color. After the inspector confirms that the screws are tightened, mark the screws
using red color. (The marks should cross the edges of the screws, as shown in the
following figure.)
Ensure that all slots are installed with boards or filler panels. Avoid hazards caused by
hazardous voltages or energy on boards. Ensure that the air channel is normal, control
electromagnetic interference, and prevent dust and other sundries on the backplane,
baseplate, and boards.
After installing the equipment, remove idle packing materials such as cartons, foam,
plastics, and cable ties from the equipment area.
In the case of a fire, immediately leave the building or the equipment area, and turn on
the fire alarm bell or make an emergency call. Do not enter the building on fire in any
case.
Do not stop protective devices. Pay attention to the warnings, cautions, and related
precautionary measures in this document and on the nameplates. Promptly replace
warning labels that have worn out.
Keep irrelevant people far away from the equipment.
Use wooden or fiberglass ladders when you need to perform live working at heights.
Use insulated tools or tools with insulated handles, as shown in the following figure.
All cable holes should be sealed. Seal the cable holes with firestop putty. Seal the unused
cable holes with the caps delivered with the cabinet. The following figure shows the
criteria for correct sealing with firestop putty.
Do not use water, alcohol, oil, or other solvents to clean electrical components inside and
outside a cabinet.
Symbol Description
Indicates a part exposed to high voltage. This symbol warns
operators that both direct and indirect contact with the power grid is
fatal. Such areas include hazardous voltage points or protective
power supply covers that may be removed during maintenance.
Warns users of overheating. This symbol is attached to a device
surface that may overheat and cause scalding. It warns users not to
touch the surface during operation or maintenance. Users should
wear heat insulation gloves before operation to prevent scalding.
Indicates protective grounding. This symbol is attached near the
or protective ground terminal and is used beside a terminal through
which a device is connected to an external grounding grid. A device
ground cable is connected from the protective ground terminal to the
external ground bar.
Indicates equipotential bonding. This symbol is used for an
equipotential bonding terminal. That is, this symbol is attached to
each equipotential bonding terminal inside a device.
Is an ESD symbol and attached to any areas with electrostatic
sensitivity. If you see such a symbol, wear a pair of ESD gloves or
an ESD wrist strap before operating a device.
Indicates that the device can be safely used only in areas with an
altitude lower than 2000 meters.
Symbol Description
ports. Connect cables according to the rated power output and
configuration parameter information in the instruction.
3. If there are multiple slots, use the symbol near the slot
information. For details, see the description of slot information,
restrictions on boards, and usage conditions in the instruction.
Professionals: personnel who are trained or experienced in equipment operations and are clear of the
sources and degree of various potential hazards in equipment installation, operation, and
maintenance
Trained personnel: personnel who are technically trained, have required experience, are aware of
possible hazards on themselves in certain operations, and are able to take protective measures to
minimize the hazards on themselves and other people
Users or operators: operation personnel, except trained personnel and professionals, who may handle
the equipment
The power system is powered by high-voltage power sources. Direct or indirect contact
(especially through damp objects) with the power sources may result in electric shock.
Non-standard and improper operations may result in fire or electric shocks.
Do not install or remove power cables with power on. Transient contact between the core
of a power cable and a conductor may generate electric arcs or sparks, which may cause
fire or hurt human eyes.
If the power supply to the equipment is permanently connected, install an easily
accessible disconnector at the exterior of the equipment.
Before making electrical connections, switch off the disconnector on the upstream device
to cut the power supply if people may contact energized components.
If a "high electricity leakage" tag is attached on the power terminal of a device, you must
ground the protective ground terminal on the device enclosure before connecting the AC
power supply; otherwise, electric shock as a result of electricity leakage may occur.
Before installing or removing a power cable, turn off the power circuit breaker.
Before connecting a power cable, check that the label on the power cable is correct.
Before connecting the power supply, ensure that electrical connections are correct.
If the equipment has multiple inputs, disconnect all the inputs before operating the
equipment.
When routing power cables, ensure that there is no coiling or twisting. Do not join or
weld power cables. If necessary, use a longer cable.
Installation at Heights
Working at heights refers to operations that are performed at least 2 meters above the ground.
Stop working at heights if the steel pipes are wet or other potential danger exists. After any of
the preceding conditions no longer exists, the safety director and relevant technical personnel
need to check the involved equipment. Operators can begin working only after obtaining
consent.
When working at heights, comply with local relevant laws and regulations.
Only trained and qualified personnel are allowed to work at heights.
Before working at heights, check the climbing tools and safety gears such as safety
helmets, safety belts, ladders, springboards, scaffolding, and lifting equipment. If they do
not meet the requirements, take corrective measures or disallow working at heights.
Wear personal protective equipment such as the safety helmet and safety belt or waist rope
and fasten it to a solid structure. Do not mount it on an insecure moveable object or metal
object with sharp edges. Make sure that the hooks will not slide off.
Set a forbidden area and eye-catching signs for working at heights to warn away irrelevant
personnel.
Carry the operation machinery and tools properly to prevent them from falling off and
causing injuries.
Personnel involving working at heights are not allowed to throw objects from the height to
the ground, or vice versa. Objects should be transported by tough slings, hanging baskets,
highline trolleys, or cranes.
Do not perform operations on the upper and lower layers at the same time. If unavoidable,
install a dedicated protective shelter between the upper and lower layers or take other
protective measures. Do not pile up tools or properties on the upper layer.
Ensure that guard rails and warning signs are set at the edges and openings of the area
involving working at heights to prevent falls.
Do not pile up scaffolding, springboards, or other sundries on the ground under the area
involving working at heights. Do not allow people to stay or pass under the area involving
working at heights.
Inspect the scaffolding, springboards, and workbenches used for working at heights in
advance to ensure that their structures are solid and not overloaded.
Dismantle the scaffolding from top down after finishing the job. Do not dismantle the
upper and lower layers at the same time. When removing a part, ensure that other parts
will not collapse.
Before climbing up a ladder, ensure that the ladder is secure and free of cracks The angle
between the ladder and the ground should be 75°. When a step ladder is used, ensure that
the pull ropes are secured and the ladder is held firm.
Do not loiter when working at heights. Do not sleep at heights.
Any violations must be promptly pointed out by the site manager or safety supervisor and
the involved personnel should be prompted for correction. Personnel who fail to stop
violations may be forbidden from working and the suspension is considered as
absenteeism.
Operators who violate the safety regulations are responsible for accidents caused. The
supervisor has to bear the responsibility accordingly.
When heavy objects are being hoisted, do not walk under the cantilever or the objects.
Only trained and qualified personnel should perform hoisting operations.
Check that hoisting tools are available and in good condition.
Before hoisting objects, ensure that hoisting tools are firmly fixed onto a weight-bearing
object or wall.
Ensure that the angle formed by two hoisting cables is no more than 90 degrees, as
shown in the following figure.
Do not drill holes into the cabinet without permission. Incorrect drilling operations may affect
the electromagnetic shielding of the cabinet and damage cables inside. Metal shavings from
drilling may short-circuit boards inside the cabinet.
Wear goggles and protective gloves when drilling holes.
When drilling holes, protect the equipment from metal shavings. After drilling, clean up
any metal shavings that have accumulated inside or outside the equipment.
Do not connect a metal conductor to the battery poles or touch the battery terminals.
Otherwise, the battery may be short-circuited and heat up, which can cause injuries such
as burning.
Dispose of batteries in accordance with local laws and regulations. Do not dispose of
batteries as household waste. If a battery is disposed of improperly, it may explode.
Do not drop, squeeze, or puncture a battery. Protect batteries from external high pressure
to prevent internal short circuits and overheating.
Do not use damaged batteries.
To prevent injury or explosion, do not allow children or pets to swallow or bite a battery.
If batteries experience discoloration, deformation, abnormal heating, or other
abnormalities during working, charging, or storage, stop using the batteries and replace
them with new ones.
Secure battery cables or copper bars to the torque specified in battery documentation.
Loose connections will result in excessive voltage drops or cause batteries to burn out
when the current increases.
Before operating batteries, carefully read the safety precautions for battery handling and
connection.
Battery short circuits can generate high instantaneous current and release a great amount of
energy, which may cause equipment damage or personal injury.
If permitted, disconnect the batteries in use before performing any other operations.
Lead-acid batteries emit flammable gas if they work abnormally. Store lead-acid batteries in a
place with good ventilation, and take fire safety precautions.
High battery temperature may result in battery distortion, damage, and electrolyte overflow.
If the battery temperature is higher than 60°C, check the battery for electrolyte overflow. If
the electrolyte overflows, handle the leakage immediately.
When the electrolyte overflows, absorb and neutralize the electrolyte immediately.
When moving or handling a battery whose electrolyte leaks, note that the leaking electrolyte
may hurt human bodies. Neutralize and absorb the electrolyte with sodium bicarbonate
(NaHCO3) or sodium carbonate (Na2CO3) before moving the batteries.
When handling lithium batteries, do not place them upside down, tilt them, or bump
them against the ground.
Keep the battery loop disconnected during installation and maintenance.
When the ambient temperature is lower than the lower limit of the operating temperature,
do not charge the battery (0°C Charging is not allowed). Otherwise, a short circuit occurs
inside the battery.
Do not throw a lithium battery in fire.
When maintenance is complete, return the waste lithium battery to the maintenance
office.
Before installation and maintenance, put on a safety helmet, goggles, insulation gloves,
and protective clothing to avoid personal injury.
Before installing and maintaining PV modules, cover all PV modules totally using opaque
materials to avoid electric shocks caused by generated currents.
Never focus sunlight on PV modules using a mirror or lens, because this may damage PV
modules and cause personal injury.
When moving PV modules, do not hold connection boxes or power cables, because they
are not designed to support the weight of PV modules.
Exercise caution when moving PV modules to avoid collision. Improper movement and
placement may cause the glass plates on PV modules to break and lose electrical
performance, which renders the PV modules useless.
In strong wind, do not install PV modules at heights.
To install or maintain a high support, you must set up a support platform and use a safety
helmet or safety belt.
Do not drill holes in, step on, or place heavy objects on PV modules, because these
actions may damage PV modules.
At least two persons are required to move and install PV modules. Only the aluminum
frame of the PV modules can be raised. Exerting force on the front or rear surface of the
PV modules using your head is prohibited. This may cause hidden cracks in the PV
modules.
2 Solution Overview
2.1 Positioning
Huawei PowerCube 500 hybrid power supply solution applies to safe and smart city projects.
It provides power and support for cameras in video surveillance systems, and provides power
and space for data backhaul devices. Meanwhile, it can also provide power and support for
devices such as solar street lamps and hot spot coverage.
The PowerCube 500 supports mains and solar power supplies. It includes the solar power
supply solution, grid power supply solution, and solar-grid power supply solution, applicable
to diverse scenarios with or without mains power supply.
The PowerCube 500 supports multiple output voltage modes at the same time, including 12 V
DC, 24 V AC, 48 V DC, and 220 V AC. It can provide power for cameras and transmission
equipment such as the small-sized router, passive optical network (PON), customer premises
equipment (CPE), and access point (AP).
2.2 Features
Huawei PowerCube 500 hybrid power supply solution is simple, reliable, and intelligent.
Simple: The MIMO technology supports multiple energy input and multiple output
voltage modes.
Reliable: It features integrated design, carrier-class reliability, and dual-antitheft design.
Intelligent: You can access a power supply using the mobile phone app, facilitating site
deployment. You can also manage sites using a remote NMS.
2.3 Solutions
Grid Power Supply Solution
The grid power supply solution works circularly as follows. The power source preference
sequence is mains > battery.
1. If the mains is normal, the mains supplies power to loads and batteries.
2. If the mains is abnormal, batteries supply power to loads.
2.4 Configurations
Table 2-1 Configurations for the grid power supply solution
Item ICC50-HDT
PDU DCDU-80A1
SMU SMU02B
UIM UIM05D
SSU S4820G1
Energy storage One string of TCB-100C
unit (ESU)
Sensor Smoke sensor and temperature and humidity sensor
Component Inverter (optional), PoE module (optional), and M48300N1 module
Pole Solar pole
PV module 150 W, or 200 W PV module
Transmission AR531 (optional), AR550 (optional), AR550C (optional), MA5671
equipment (optional), MA5621 (optional), NE05E-SK (optional),
GPX147-FSM1101-12
3 Component Description
3.1 PV Module
Exterior
Specifications
3.2 ICC50-HDA
Interior
(1) Space for customer (2) DCDU-80A1 (3) Temperature and humidity
equipment sensor
(4) Space for the ESMU (5) Space for batteries (6) Fan
Specifications
Item Specifications
Dimensions (H x W x D) 900 mm x 650 mm x 650 mm (excluding the base)
Weight About 80 kg
Cooling Energy control compartment: heat exchanger
Battery compartment: direct ventilation unit
Operating temperature 0–45°C
Cabling mode Routed in and out from the bottom
Maintenance mode Operated and maintained from the front
Space for customer 2U
equipment
Installation mode Mounted on a pole or the ground
Battery Two strings of ESU-A2400Wh/D, ESM-4850A1 or
ESM-4875A1
Operating environment Class B
3.3 ICC50T-HDA
Interior
(1) Ground bar (2) Space for customer (3) Heater (behind the
equipment cabling panel)
(4) DCDU-80A1 (5) Temperature and (6) Space for the ESMU
humidity sensor
(7) Space for batteries (8) Heater (9) Fan
(10) Fan (11) Space for a PoE adapter (12) Smoke sensor
(13) Space for transmission
equipment
Specifications
Item Specifications
Dimensions (H x W x D) 900 mm x 650 mm x 650 mm (excluding the base)
Weight About 80 kg
Item Specifications
Cooling Energy control compartment: heat exchanger
Battery compartment: direct ventilation unit
Operating temperature –30°C to +45°C
Cabling mode Routed in and out from the bottom
Maintenance mode Operated and maintained from the front
Space for customer equipment 2U
Installation mode Mounted on a pole or the ground
Battery Two strings of ESU-A2400Wh/D
Operating environment Class B
3.4 ICC50-HDT
Interior
(4) Temperature and humidity (5) Space for customer (6) Space for batteries
sensor equipment
(7) Fan (8) Fan (9) Space for a PoE
adapter
(10) Smoke sensor (11) Space for transmission
equipment
Specifications
Item Specifications
Dimensions (H x W x D) 900 mm x 650 mm x 650 mm (excluding the base)
Weight About 80 kg
Cooling Energy control compartment: heat exchanger
Battery compartment: direct ventilation unit
Operating temperature –5°C to +45°C
Cabling mode Routed in and out from the bottom
Maintenance mode Operated and maintained from the front
Space for customer 4U
equipment
Installation mode Mounted on a pole or the ground
Battery One string of TCB-60C or TCB-100C
Operating environment Class C
3.5 ICC50T-HDT
Interior
(1) Ground bar (2) Space for customer (3) Heater (behind the
equipment cabling panel)
(4) DCDU-80A1 (5) Temperature and (6) Space for customer
humidity sensor equipment
(7) Space for batteries (8) Heater (9) Fan
(10) Fan (11) Space for a PoE adapter (12) Smoke sensor
(13) Space for transmission
equipment
Specifications
Item Specifications
Dimensions (H x W x D) 900 mm x 650 mm x 650 mm (excluding the base)
Weight About 80 kg
Item Specifications
Cooling Energy control compartment: heat exchanger
Battery compartment: direct ventilation unit
Operating temperature –30°C to +45°C
Cabling mode Routed in and out from the bottom
Maintenance mode Operated and maintained from the front
Space for customer 4U
equipment
Installation mode Mounted on a pole or the ground
Battery One string of TCB-60C or TCB-100C
Operating environment Class C
3.6 DCDU-80A1
Exterior and Interior
(1) –48 V DC output 1 wiring (2) –48 V DC output 1 circuit (3) Battery circuit
terminal breaker breaker
(4) –48 V DC output 2 wiring (5) SMU02B (6) UIM05D
terminal
(7) AC input circuit breakers and (8) Battery wiring terminal (9) M48300N1
terminals module slot
(10) PSU slot (11) SSU slot (12) Ground screw
Specifications
Item Specifications
Frame Dimensions (H x W 87.9 mm x 442 mm x 330 mm
x D)
Weight About 10 kg
Cabling mode Routed in and out from the left and right, routed in
and out from the front
Maintenance mode Operated and maintained from the front
Installation mode Mounted on a 19-inch rack
Configuration DC output One 80 A battery wiring terminal, one 40 A load
wiring terminal, and one 30 A load quick-connect
terminal
SMU SMU02B
UIM UIM05D
AC input One 2-pole 32A circuit breaker supporting 220 V
AC single-phase or 110 V AC dual-live-wire AC
Item Specifications
input
M48300N1 module An M48300N1 module can be installed in the
M48300N1 module slot
PSU (optional) A PSU can only be installed in the PSU slot
A maximum of one R4850G2, or one R4850N2
SSU (optional) An SSU can be installed in the SSU slot
Conceptual Diagram
3.6.1 SMU02B
Panel
Indicators
Buttons
NOTE
The LCD screen becomes dark if no button is pressed within 30 seconds.
To increase (or decrease) the LCD contrast ratio, hold down and (or ) for 2
seconds.
USB Ports
You can quickly deploy a site, import and export configuration files, export running logs, and
upgrade software by inserting the USB flash drive that is specially used for site deployment
into the USB port.
After installing the specific WiFi module using the USB port, you can access the WebUI
locally, which facilitates operations.
Using WiFi modules provided by another vendor may cause data loss or function exception.
Consequences arising from this will not be borne by Huawei.
Communications Ports
NOTE
All these ports are protected by a security mechanism.
3.6.2 UIM05D
Interior
(1) COM2/CAN port (2) COM1 port (3) Dry contact output ports
(4) Dry contact input ports (5) Sensor ports (6) Handle
(7) Locking latch (8) Cable outlet
(1) Sensor ports (2) Internal circulation fan port (3) External circulating fan ports
Ports
Communication Port
Pins
3.6.3 M48300N1
Exterior and Panel
Specifications
Item Description
Dimensions (L x W x H) 281 mm x 105 mm x 40.8 mm
Weight ≤ 1.5 kg
Operating voltage 40–60 V DC
Max. input current 13A
Output voltage Four 12 V DC outputs
Four 24 V AC outputs
Max. output power 100W (12 V DC)
200W (24 V AC)
Surge protection 12 V DC output port: differential mode ±3 kA, common
mode ±5 kA
24 V AC output port: differential mode ±2 kV/2 ohm,
common mode ±6 kV/12 ohm
The ON/OFF switch on the The ON/OFF switch on the panel can be used to control the
panel M48300N1 output.
Indicators
3.6.4 Rectifier
A rectifier converts AC input power into stable DC power.
3.6.5 S4820G1
Figure 3-20 Appearance
Indicators
Technical Specifications
Item Specifications
Dimensions (H x W x D) 43.5 mm x 482.6 mm x 286 mm
(including mounting ears)
Rated output capacity 1000 VA/700 W
DC input Rated voltage 48 V DC
Rated current 17 A
Item Specifications
AC input Rated voltage 220 V AC
Rated frequency 50 Hz
AC output Rated output voltage 220 V AC±3%
Output frequency 50±1% Hz
Output mode One wiring terminal AC output + one
universal socket AC output
Indicators
Pin Description
1, 2 Dry contact signal for a DC input abnormality alarm, open when DC
input is normal, closed when DC input is abnormal
1, 3 Dry contact signal for a DC input abnormality alarm, closed when
DC input is normal, open when DC input is abnormal
4, 5 Dry contact signal for an inverter abnormality alarm, open when the
inverter is normal, closed when the inverter is abnormal
4, 6 Dry contact signal for an inverter abnormality alarm, closed when
the inverter is normal, open when the inverter is abnormal
Technical Specifications
Item Specifications
DC input voltage range 10 V DC-30 V DC
DC output voltage range 47 V DC-52 V DC
Rated output power 35 W
Efficiency (with full load) > 80%
Dimensions (H x W x D) 50 mm x 72 mm x 230 mm
Specifications
Item Specifications
Dimensions (H x W x L) 44.5 mm x 44.5 mm x 484 mm
Weight About 2.4 kg
Operating voltage 220–240 V AC
Output voltage 220–240 V AC
Output current 10 A for each route; maximum system output: 32 A
Specifications
Item Specifications
Dimensions (H x W x D) 43.6 mm x 100 mm x 100 mm
Weight ≤ 1 kg
Item Specifications
Operating voltage range 36–75 V DC
Rated operating voltage 48 V DC
Rated power 300 W
Operating temperature range –40°C to +65°C
Start temperature 5±3°C
Shutdown temperature 15±3°C
Operating humidity 5%–95% RH
Altitude 0–4000 m. When the altitude ranges from 2000 m to
4000 m, the operating temperature decreases by 1°C
for each additional 200 m.
Interior
(1) COM_OUT port (2) COM_ELU (3) Resistance DIP switch (4) Resistance DIP
port corresponding to the CAN switch (reserved)
port
(5) Address DIP (6) ESU-A (7) Power switch (8) Power port
switch (ADDRESS) sampling port
(9) Battery– port (10) –48V BUS (11) Status indicator (12) CONSOLE
port port
(13) COM_IN port
Functions
Function Description
Status monitoring Monitors the voltage and temperature of each electrochemical
cell, and voltage and current of the ESU string.
Alarm detection and Detects alarms for hardware faults, overvoltage, undervoltage,
reporting overcurrent, high temperatures, and low temperatures, and
reports alarms to the host over a CAN port.
ESU connection control Disconnects ESUs when an alarm is generated and connects
ESUs after exceptions are eliminated.
Cascading A maximum of 12 ESMUs can be cascaded.
Equalization Supports real-time equalization and adaptive equalization:
Real-time equalization: Equalizes cell capacities to delay
electrochemical cell deterioration and prolong the service
life of cells. Such cell capacity imbalance is caused by the
increase of charge/discharge cycles.
Adaptive equalization: Equalizes cell capacities to facilitate
ESU maintenance and replacement in the mixture of
different electrochemical cells, which improves ESU
adaptability. Such cell capacity imbalance is caused by
ESU maintenance and replacement.
The controller identifies the electrochemical cell with the
lowest voltage and adjusts its output current.
SOH Monitors the ESU health status and reports the information to
the host over a CAN port.
Electronic label Identifies ESUs by displaying their models, bar codes, and
production dates.
Technical Specifications
Item Specifications
Dimensions (H x W x D) 41.6 mm x 442 mm x 312 mm
Weight ≤ 5 kg
Disconnection protection 44–46 V
voltage Typical value: 45 V
Forcible disconnection voltage: 44 V
Busbar activation voltage 46–48 V
Typical value: 47 V
Forcible activation voltage: 48 V
Maximum charge/discharge ESMU-02A: 100 A
current
Operating conditions Ambient temperature: –20°C to +55°C
Humidity: 5%–95% RH
Atmospheric pressure: 70–106 kPa
Altitude: ≤ 4 km
Reliability Mean time between failures (MTBF) ≥ 30,000 hours;
annual repair ratio < 1%
The ESMU-02A current detection precision: ±0.5 A (< 50 A), ±1 A (50–100 A). When the battery
current is less than 0.5 A, the displayed value is 0 A.
3.11.2 ESU-A2400Wh/D
Appearance
(1) Positive wiring terminal (2) COM_ELU IN port (3) COM_ELU OUT port
(4) ESU sampling port (5) Negative wiring terminal (6) Handle
Functions
An ESU-A2400Wh/D is made of a new type of material and features safety, long lifespan,
small size, light weight, and has good performance at high temperatures. It can be charged or
discharged with large power and does not pollute the environment.
If batteries charge or discharge beyond the battery operating temperature range, the battery
performance and safety will be affected.
Charging is not allowed when the battery cell voltage is below 2.0 V.
Technical Specifications
Item Specifications
Dimensions (H x W x D) 125 mm x 435 mm x 420 mm
Weight 37.5 kg
Voltage 48 V DC
Capacity 2400 Wh
Cycle life Can be charged and discharged 4500 times at 35°C when the
depth of discharge (DOD) is 85%.
Item Specifications
Battery operating Discharging process: –20°C to +55°C
temperature Charging process: 0–55°C
3.11.3 ESM-4850A1
The ESM is an energy storage unit composed of lithium-ion batteries. It features better charge
and discharge performance, longer service life, and less self-discharge loss than ordinary
batteries.
The ESM consists of electrochemical cells, an energy storage management unit (ESMU),
power and signal terminals, and mechanical parts. It can be used as an independent 48 V unit,
supports the mix use of old and new batteries as well as lithium and lead-acid batteries, and
can collaborate with third-party power systems.
3.11.3.1 Appearance
LED Indicators
NOTE
Major alarm: The ESM needs to be maintained immediately.
Minor alarm: The ESM does not require maintenance, but sends a reminder to remote maintenance personnel.
Blinking at long intervals: on for 1s and then off for 1s
Blinking at short intervals: on for 0.125s and then off for 0.125s
All indicators are blinking: The ESM has entered the maintenance mode.
When the ESM is in sleep mode, the fault indicator is off except for reverse-connection protection.
1. MANUAL ON/OFF is a contact button. The interval for pressing the button should be greater than
0.5s; otherwise, the operation will be ineffective.
2. If you power off the ESM that is in charging, discharging, or disconnect mode by holding down the
MANUAL ON/OFF button, you need to hold down this button again to reactivate the ESM.
3.11.4 ESM-4875A1
The ESM is an energy storage unit composed of lithium-ion batteries. It features better charge
and discharge performance, longer service life, and less self-discharge loss than ordinary
batteries.
The ESM consists of electrochemical cells, an energy storage management unit (ESMU),
power and signal terminals, and mechanical parts. It can be used as an independent 48 V unit,
supports the mix use of old and new batteries as well as lithium and lead-acid batteries, and
can collaborate with third-party power systems.
3.11.4.1 Appearance
7 PWR ESMU port for connecting The ESM can be activated if the PWR port is
to an external power source supplied with a voltage of 43.2–58 V. For
details, see 3.11.4.3 Activation and Startup.
8 + ESM positive terminal Positive and negative ports of the ESM. They
are secured by M6 screws. Appropriate OT
- ESM negative terminal terminals should be used. Required torque: 4
N·m; recommended cable size: ≥ 16 mm2. If
the ESM is used at a temperature below 45°C,
the cable size can be smaller but should be at
least 10 mm2.
LED Indicators
CHG Charge indicator Green Steady on: The ESM is being charged.
Off: The ESM is open-circuited or discharging.
DCHG Discharge indicator Green Steady on: The ESM is discharging.
Off: The ESM is open-circuited or being charged.
NOTE
Major alarm: The ESM needs to be maintained immediately.
Minor alarm: The ESM does not require maintenance, but sends a reminder to remote maintenance personnel.
Blinking at long intervals: on for 1s and then off for 1s
Blinking at short intervals: on for 0.125s and then off for 0.125s
All indicators are blinking: The ESM has entered the maintenance mode.
When the ESM is in sleep mode, the fault indicator is off except for reverse-connection protection.
Activation through the MANUAL ON/OFF button: Hold down the MANUAL ON/OFF
button on the ESM panel for at least 5s and less than 15s.
Activation through the power port: Supply a DC voltage of 43.2–58 V to the power port
on the ESM panel for at least 5s.
1. MANUAL ON/OFF is a contact button. The interval for pressing the button should be greater than
0.5s; otherwise, the operation will be ineffective.
2. If you power off the ESM that is in charging, discharging, or disconnect mode by holding down the
MANUAL ON/OFF button, you need to hold down this button again to reactivate the ESM.
3.11.5 TCB-C
Exterior
Specifications
3.11.6 FCB-B
Appearance
Specifications
Item FCB-100B
Dimensions (L x W x H) 391 mm x 108 mm x 287 mm
Weight 35 kg
Rated voltage 12 V DC
Rated capacity 100 Ah
Maximum charge current 30 A
3.12 Pole
Exterior
(1) Top cable hole (2) Middle cable hole (3) Maintenance window
(1) Top cable hole (2) Middle cable hole (3) Maintenance window
Specifications
4 Routine Maintenance
Preparing Tools
After the PowerCube 1000 is energized, turning off the manual switch on the ESMU front
panel cannot enable the ESMU to consume less power. If the PowerCube 1000 has been
powered off for more than 10 days, ESU-As may bulge due to overdischarge.
To solve the problem, turn off the manual switch on the front panel, and then disconnect the
four DB15 cables between the ESMU and ESU-As to reduce power consumption.
5 Troubleshooting
The yellow Overtemperature pre-alarm. Ensure that the vent of the PSU is
indicator is unblocked.
steady on.
AC input undervoltage or Check that the AC input voltage is normal.
overvoltage occurs.
The PSU is hibernated. (only In PowerCube, the PSU in hibernating is
the yellow indicator is lit, normal.
and no alarm is generated)
The red Output overvoltage occurs. Remove the PSU and then install it again. If
indicator is there is still no output, replace the PSU.
steady on.
The fan is faulty. Replace the PSU.
Overtemperature occurs. Ensure that the vent of the PSU is
unblocked.
6 Parts Replacement
Figure 6-1 Removing the solar input cable from the SSU inside the cabinet
Step 2 Transport maintenance personnel to the PV module installation position by using a crane.
Step 3 Disconnect the cable delivered with the damaged PV module from the extension cable.
Step 4 Unscrew the PV module using a wrench and remove the PV module from the support.
Step 5 Install a new PV module and secure it to the support by tightening the screws using a wrench.
Step 6 Reconnect the cable delivered with the PV module and the extension cable.
Step 7 Reconnect the solar input cable to the SSU.
----End
Figure 6-3 Switching the AC input circuit breaker on the DCDU to OFF
Step 2 Switch off the upstream AC input circuit breaker for the DCDU, and attach labels such as "No
operations allowed."
Step 3 Switch the battery circuit breaker on the DCDU to OFF.
Figure 6-4 Switching the battery circuit breaker on the DCDU to OFF
Step 4 Record the cables connected to the DCDU and label the cables.
When disconnecting the battery cables, disconnect the positive battery cable first, then
disconnect the negative cable, and insulate the cables.
Insulate all the removed power cables.
Before connecting the input power cable to the SSU, ensure that the battery cables have been
connected and the positive and negative battery terminals are properly connected.
Step 10 Connect the cables to the DCDU based on the cable labels.
Step 11 Switch the battery circuit breaker on the DCDU to ON.
Step 13 Switch on the upstream AC input circuit breaker for the DCDU.
----End
Procedure
Step 1 Record the cable connection positions on the SMU02B and label the cables.
Step 2 Remove the cables from the SMU02B.
Step 3 Push the locking latch towards the left.
Step 4 Pull out the handle of the SMU02B to remove it from the subrack.
Step 5 Insert the new SMU02B into the slot, push the locking latch towards the left, and pull out the
handle.
Step 6 Gently push the SMU02B along the guide rails into the subrack. Close the handle, and push
the locking latch towards the right.
Step 7 Connect the cables to the new SMU02B based on the cable labels.
Step 8 Set the cabinet model.
Follow-up Procedure
Pack the removed component and return it to the local Huawei warehouse.
Procedure
Step 1 Connect the ground cable to the ESD wrist strap, and put on the ESD wrist strap and ESD
gloves.
Step 2 Record all the cable connection positions on the UIM05D, and remove the cables.
Step 3 Push the locking latch towards the left. Pull out the handle of the UIM05D to remove it from
the subrack.
Step 4 Insert the new UIM05D into the slot, push the locking latch towards the left, and pull out the
handle. Gently push the UIM05D along the guide rails into the subrack. Close the handle, and
push the locking latch towards the right.
Step 5 Connect the cables to the new UIM05D panel based on the recorded information.
Step 6 Disconnect the ground cable from the ESD wrist strap, and take off the ESD wrist strap and
ESD gloves.
----End
Follow-up Procedure
Pack the removed component and return it to the local Huawei warehouse.
Procedure
Step 1 Turn the switch on the M48300N1 module panel to OFF.
Figure 6-13 Turning the switch on the M48300N1 module panel to OFF
Step 2 Record the cable connection positions on the M48300N1 module and label the cables.
Step 3 Remove the cables from the M48300N1 module.
Step 4 Push the locking latch to the left.
Step 5 Pull out the handle of the M48300N1 module to remove it from the subrack.
Step 6 Insert the new M48300N1 module into the slot, push the locking latch to the left, and pull out
the handle.
Step 7 Gently push the M48300N1 module along the guide rails into the subrack. Close the handle,
and push the locking latch to the right.
Step 8 Connect the cables to the new M48300N1 module based on the recorded information.
Step 9 Turn the switch on the new M48300N1 module to ON.
----End
Follow-up Procedure
Pack the removed component and return it to the local Huawei warehouse.
To prevent burns, exercise caution when removing a PSU because the PSU may be hot as
a result of continuous operation.
In the scenario where the system is configured with ESU-As and is operating, replace or
remove the PSU only when the system is powered by the mains. Otherwise, the stable
power supply to the system will be affected.
Procedure
Step 1 Push the locking latch on the right side of the PSU panel towards the left.
Step 2 Gently pull out the handle to separate the handle from the subrack, and remove the PSU from
the subrack.
Step 3 Push the locking latch on the new PSU towards the left, and pull out the handle.
Step 4 Place the new PSU in the correct slot.
Step 5 Gently slide the PSU along the guide rails, close the handle, and push the locking latch
towards the right to lock the handle.
----End
Follow-up Procedure
Pack the removed component and return it to the local Huawei warehouse.
To prevent burns, exercise caution when removing an SSU because the SSU may be hot as a
result of continuous operation.
Procedure
Step 1 Remove cables from the SSU panel and label the cables.
Step 2 Push the locking latch on the right side of the SSU panel towards the left.
Step 3 Gently pull out the handle to separate the handle from the subrack, and remove the SSU from
the subrack.
Step 4 Push the locking latch on the new SSU towards the left, and pull out the handle.
Step 5 Place the new SSU in the correct slot.
Step 6 Gently slide the SSU along the guide rails, close the handle, and push the locking latch
towards the right to lock the handle.
Step 7 Connect cables to the new SSU based on the recorded information.
----End
Follow-up Procedure
Pack the removed component and return it to the local Huawei warehouse.
Procedure
Step 1 Record and remove the cables on the UIM05D.
Step 2 Pull out the UIM05D and remove the temperature and humidity sensor cable.
Figure 6-23 Removing the temperature and humidity sensor cable from the UIM05D
Step 5 Connect the temperature and humidity sensor cable to the J10 terminal on the UIM05D.
Step 6 Reinstall the UIM05D and reconnect the cables to the UIM05D panel based on the recorded
information.
----End
Follow-up Procedure
Pack the removed component and have it sent to the local Huawei warehouse.
Procedure
Step 1 Remove the smoke sensor cable from the UIM05D panel.
Follow-up Procedure
Pack the removed component and have it sent to the local Huawei warehouse.
Procedure
Step 1 Record and disconnect the fan cable transfer terminal.
Step 2 Remove the fan.
1. Remove the fan fastener.
2. Separate the fan from the fastener.
Ensure that the airflow direction arrow on the new fan points inwards.
Follow-up Procedure
Pack the removed component and have it sent to the local Huawei warehouse.
Procedure
Step 1 Record and disconnect the fan cable transfer terminal.
Step 2 Remove the fan cover.
Step 4 Record the airflow direction arrow on the fan and separate the fan from the fastener.
Step 5 Install the new fan on the fastener based on the airflow direction arrow.
Follow-up Procedure
Pack the removed component and have it sent to the local Huawei warehouse.
Procedure
Step 1 Remove the DC power cable from the heater.
Step 2 Remove the heater.
Follow-up Procedure
Pack the removed component and have it sent to the local Huawei warehouse.
Procedure
Step 1 Remove the cable ties from the cabling panel.
Step 2 Remove the cabling panel.
Follow-up Procedure
Pack the removed component and have it sent to the local Huawei warehouse.
Procedure
Step 1 Switch the circuit breaker connected to the inverter on the DCDU to OFF.
Figure 6-38 Switching the -48V DC output 1 circuit breaker on the DCDU to OFF
Step 3 Record the cables connected to the inverter and label the cables.
Step 4 Remove cables from the inverter and insulate the cables.
Step 5 Remove the inverter and record the DIP switch on the back of inverter.
Step 6 Set the DIP switch for the new inverter based on the recorded information.
Step 10 Switch the circuit breaker connected to the inverter on the DCDU to ON.
Figure 6-42 Switching the circuit breaker connected to the inverter on the DCDU to ON
----End
Follow-up Procedure
Pack the removed component and return it to the local Huawei warehouse.
Procedure
Step 1 Record the cables connected to the PoE module and label the cables.
Step 2 Remove the cables from the PoE module.
Step 3 Remove the old PoE module.
Step 5 Connect the cables to the new PoE module based on the recorded information.
----End
Follow-up Procedure
Pack the removed component and return it to the local Huawei warehouse.
Procedure
Step 1 Switch the inverter circuit breaker to OFF.
Follow-up Procedure
Pack the removed component and have it sent to the local Huawei warehouse.
Context
During the replacement of an ESU-A and ESMU, batteries are disconnected, then sorted, and
finally connected in sequence. When batteries are all disconnected, power supply to the site
may be disconnected if the AC input fails. To ensure power supply to the site, perform
operations in strict accordance with ESU-A and ESMU Replacement Operation Guide. Obtain
the document from support.huawei.com.
In the ESU-A and ESMU Replacement Operation Guide, a 50 Ah ESU-A is used as an example. The
procedure for replacing the ESU-A2400Wh/D and ESU-A2400Wh/N is similar to that for replacing the
ESU-A.
Follow-up Procedure
Put the replaced component into the ESD box or bag and then place the ESD box or bag
into the carton box with foams or the bag of the new component.
Fill in the fault card with the information about the replaced component.
Context
ESM replacement may cause a system power failure. To prevent power failures, ensure that
other power sources, such as the mains, diesel generator, or a third-party DC power source,
provide continuous power supply.
Replacement Requirements
Conditions for the ESM to enter and exit the maintenance mode:
1. Hold down the Manual ON/OFF button for at least 15s in any state to enter the
maintenance mode.
2. Hold down the Manual ON/OFF button for at least 15s to exit the maintenance mode.
Before replacing an ESM in an actual maintenance scenario, hold down the Manual ON/OFF
button for the ESM to power off. After the ESM is replaced, hold down the Manual ON/OFF
button for at least 15s on the new ESM to exit the maintenance mode.
Follow-up Operations
Put the removed component into the ESD box or bag and then place the ESD box or bag
into the carton box with foams or the bag of the new component.
Fill in the fault card with the information about the removed component.
Contact your local Huawei office to handle the faulty component.
If the battery string is to be replaced partially, new batteries must be of the same type and
from the same manufacturer as the replaced ones.
If the battery string is to be replaced as a whole, new batteries must be of the same type
and batch and from the same manufacturer as the replaced ones.
Do not short-circuit or reversely connect the positive and negative battery terminals.
Insulate tools such as wrenches and screwdrivers when handling the batteries to avoid
personal injury and damage to the batteries.
Exercise caution when taking or removing a battery to prevent it from falling off.
Procedure
Step 1 Put on the ESD wrist strap or ESD gloves.
Step 2 Switch the battery circuit breaker on the DCDU to OFF.
Figure 6-47 Switching the battery circuit breaker on the DCDU to OFF
You are advised to fully charge the old battery string before replacing it to avoid voltage bias and current
bias. This is because the new battery string has full capacity.
If the DCDU is powered on, disconnect the positive battery terminal before replacing the
negative battery cable.
This requirement also applies to scenarios where other power systems are used or negative
battery cables are involved.
Step 3 Disconnect the cable between the positive battery string terminal and the positive transfer
busbar.
Step 4 Disconnect the cable between the negative battery string terminal and the negative transfer
busbar.
Step 5 Replace the faulty batteries with new ones.
Step 6 Reconnect the cable between the negative battery string terminal and the negative transfer
busbar.
Step 7 Reconnect the cable between the positive battery string terminal and the positive transfer
busbar.
Step 8 After the battery string has been charged for 10 minutes, check the voltage of each battery
using a multimeter. If the voltage of each battery is 12.6 V, the battery string is working
properly.
Step 9 Switch the battery circuit breaker on the DCDU to ON.
Step 10 Take off the ESD wrist strap or gloves and put all the tools away.
----End
Follow-up Procedure
Put the replaced component into the ESD box or bag and then place the ESD box or bag
into the carton box with foams or the bag of the new component.
Fill in the fault card with the information about the replaced component.
Regulatory Compliance Statement For regulatory compliance statements, see the file in the
following URL:PowerCube 500 V200R001 ICC30T&50T Regulatory Compliance Statement
Regulatory Compliance Statement For regulatory compliance statements, see the file in the
following URL:PowerCube 500 V200R001 ICC30&50 Regulatory Compliance Statement
Regulatory Compliance Statement For regulatory compliance statements, see the file in the
following URL:PowerCube 500 V200R001 ICC30T&50T Regulatory Compliance Statement
Regulatory Compliance Statement For regulatory compliance statements, see the file in the
following URL:PowerCube 500 V200R001 ICC30&50 Regulatory Compliance Statement
When the battery voltage is less than 48 V, the battery power supply can be disconnected
manually, and according to low battery voltage.
When the battery voltage is greater than or equal to 48 V, the battery power supply cannot be
disconnected manually, and according to low battery voltage.
A
APP application
AR access router
C
CPE customer premises equipment
D
DCDU direct current distribution unit
E
ESMU energy storage management unit
ESU energy storage unit
H
HTTP Hypertext Transfer Protocol
I
ICC integrated control cabinet
ITS intelligent transportation system
L
LCD liquid crystal display
P
PMU power monitoring unit
PSU power supply unit
PON passive optical network
PoE power over Ethernet
S
SMU site monitoring unit
SNMP Simple Network Management Protocol
SSU solar supply unit
T
TCB Temperature cycle battery
U
UIM user interface module