ELECTRICAL NOTES

1.0 ALL ELECTRICAL INSTALLATION HEREIN AND OTHER RELATED WORKS TO BE DONE ON THIS BUILDING SHALL
CONFORM IN ACCORDANCE WITH THE PROVISIONS AND CODE STANDARD OF THE
FOLLOWING:

1.1 LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE (PEC/NEC)


1.2 REPUBLIC ACT 7920 OTHERWISE KNOWN AS THE NEW ELECTRICAL ENGINEERING LAW
1.3 NATIONAL BUILDING CODE LEGEND:
1.4 FIRE CODE OF THE PHILIPPINES
1.5 EXISTING LOCAL UTILITY COMPANY
1.6 EXISTING CITY / MUNICIPALITY ORDINANCES AND THE
1.7 REQUIREMENTS OF THE BUREAU OF LABOR STANDARDS

2.0 ELECTRICAL INSTALLATION HEREIN SHALL BE DONE UNDER THE DIRECT SUPERVISION OF A DULY REGISTERED
ELECTRICAL PANEL S TWO-GANG
BOX SWITCH
ELECTRICAL ENGINEER. THE ELECTRICAL ENGINEER SHALL BE RESPONSIBLE I N THE INTERPRETATION OF THE DESIGN 2
INTENT, PLANS AND SPECIFICATIONS AND THE REQUIRED STANDARD OF THE ELECTRICAL
CODE. DUPLEX CONVENIENCE
CIRCUIT RUN AND
NUMBER OUTLET
3.0 SERVICE ENTRANCE TO THE BUILDING SHALL BE THREE PHASE (3∅), 3-WIRE + 1-GROUND WIRE, 60HZ, 230V,
THROUGH 750KVA TRANSFORMER BANK.

4.0 MATERIALS AND EQUIPMENT TO BE USED (BALLAST, FLUORESCENT TUBE, WIRING DEVICES, CIRCUIT BREAKERS,
SWITCH EMERGENCY LIGHTS
CONDUIT AND PIPES, ENCLOSURES, WIRES AND CABLES, ETC...) SHALL HAVE IMPORTED COMMODITY CLEARANCE (ICC) RUN CONVENIENCE
LABEL FOR FOREIGN MADE PRODUCTS AND P.S. MARK FOR LOCAL IN NATURE OF THE BUREAU OF PRODUCT STANDARDS E
L OUTLET
(BPS).
CIRCUIT KILOWATT-HOUR
5.0 PROVIDE GROUNDING AND NEUTRAL WIRE TO ALL OUTLETS AND LIGHTING CIRCUITS. ALL NON-CURRENT CARRYING BREAKER M METER
METAL PARTS SHALL BE GROUNDED AND BONDED

6.0 ALL PANEL BOARDS, MAIN DISTRIBUTIONS PANEL, ETC SHALL HAVE GROUNDING BUS FOR BRANCH CIRCUITS AND
TRANSFORM G13 LED T8 Tubelight
SUB-FEEDER GROUNDING SYSTEM, MAIN GROUNDING SYSTEM SHALL BE BONDED TO THE NEAREST METAL WATER PIPE
IN SERVICE. ER 1200mm 18w LED
1600Lm
7.0 MOUNTING HEIGHTS FOR ALL WIRING DEVICES AND PANEL BOARDS SHALL BE AS FOLLOWS:
7.1 LIGHTING SWITCHES: 1.20 M ABOVE FLOOR FINISH FUSE
7.2 CONVENIENCE OUTLET: 0.30 M ABOVE FLOOR FINISH DISCONNECT EMERGENCY
7.3 TELEPHONE OUTLET: 0.30 M ABOVE FLOOR FINISH LIGHTS
7.4 PANEL BOARDS AND CABINETS: 1.8m ON TOP ABOVE FLOOR FINISH
7.5 MOTOR CONTROL AND ECB: 1.8m ON TOP ABOVE FLOOR FINISH GROUN
7.6 MANUAL TRANSFER SWITCH: 1.8m ON TOP ABOVE FLOOR FINISH D
7.7 EMERGENCY LIGHT FIXTURE: 0.8m BELOW CEILING LINE

8.0 WIRING METHOD SHALL BE AS FOLLOWS


8.1 FEEDER AND RISER ---------------------------------INTERMEDIATE METALLIC CONDUIT (IMC)
8.2 LIGHTING AND POWER SYSTEM-------------ELECTRICAL METALLIC TUBING (EMT)-FOR
EXPOSED CONDUITS OR USED ABOVE CEILING
AND WOODEN PARTITIONS, POLYVINYL
CHLORIDE (PVC) - IF EMBEDDED IN CONCRETE
OR HOLLOW BLOCK.
8.3 TELEPHONE AND CATV SYSTEM ------------POLYVINYL CHLORIDE (PVC)
8.4 ALL VIBRATING EQUIPMENT--------------------LIQUID TIGHT FLEXIBLE CONDUIT
8.5 JUNCTION BOX TO LIGHTING
FIXTURE AND HEAT/ -------------------------------------FLEXIBLE METAL CONDUIT, 10mm∅ (WITH CONNECTOR)

* NOTE: ALL INDICATED CONDUIT SIZES ARE INSIDE DIAMETERS.

9.0 LIGHTING FIXTURES WITH FLUORESCENT TUBE SHALL HAVE THERMAL PROTECTOR HIGH-POWER FACTOR BALLAST
(PRE-HEAT)

10.0 ALL CABLE SPLICED AND TERMINATIONS AT BUS BARS AND CIRCUIT BREAKERS SHALL BE CRIMP-TYPE TERMINAL
LUGS.
11.0 MECHANICAL EQUIPMENT WITH HIGH VIBRATION MOVEMENTS SHALL HAVE FLEXIBLE CONDUIT CONNECTION FROM
MOTOR TERMINAL BOX TO OVER CURRENT DEVICE ENCLOSURE
(ECB).

12.0 PRIOR TO ITS MOUNTING AND TERMINATION OF LIGHTING FIXTURES, WIRING DEVICES, EQUIPMENT, ETC.
CONTRACTOR SHALL ENGAGE WITH THE CONSULTANT OR OWNER'S REPRESENTATIVE FOLLOWING FIELD ACCEPTANCE
TEST AND MATERIAL
INSPECTION:

12.1 BRANCH CIRCUITS AND SUB-FEEEDER INSULATION RESISTANCE TEST MEASUREMENT


12.2 POLARITY TEST ON WIRING DEVICES
12.3 GROUND RESISTANCE TEST MEASUREMENT
12.4 MATERIALS QUALITY INSPECTION AS REQUIRED IN THE ABOVE SPECIFICATION
12.5 GROUND WELL RESISTANCE TEST MEASUREMENT FOR THE LIGHTNING SYSTEM

13.0 NO CHANGE AND MODIFICATION SHALL BE MADE WITHOUT THE CONSULTANT / DESIGNER'S WRITTEN CONSENT.

PROJECT NO PROJECT TITLE ISSUE DATE & TIME OWNER SHEET NAME SHEET NUMBER

UP BAGUIO POWERHOUSE UPGRADING AND 5/2/2018 2:12:41 PM


Project Number ELECTRICAL NOTES
ARISTOTLE MARC J. GO MODERNIZATION
DATE REVISION DESCRIPTION
ARCHITECT ENGINEER CHECKED BY: LOCATION
UNIVERSITY OF THE PHILIPPINES -
E.1
PRC NO:19205 TIN NO: 912671574 PRC NO: TIN NO:
Checker Baguio City BAGUIO
PTR NO:
PLACE:BAGUIO CITY
DATE: PTR NO:
PLACE:
DATE:
FOR BIDDING
CONSTRUCTION
SCALE As indicated @ A3
THIS DOCUMENT IS THE COPYRIGHT OF 90 DESIGN STUDIO. ALL DIMENSIONS AND SITE CONDITIONS TO BE VERIFIED ON SITE PRIOR TO COMMENCEMENT OF ANY WORK OR PREPARATION OF SHOP
DRAWINGS AND/OR THE FABRICATION OF ANY COMPONENTS. SHOULD THERE BE ANY DISCREPANCIES REFER TO ARCHITECT PRIOR TO COMMENCEMENT OF THE WORK. DO NOT SCALE DRAWINGS -
REFER TO FIGURED DIMENSIONS ONLY. DRAWINGS TO BE READ IN CONJUNCTION WITH RELEVENT DOCUMENTATION FROM ENGINEER AND OTHER SPECIALIST SUB CONSULTANTS. THIS DOCUMENT
DESCRIBES THE DESIGN INTENT, DESIGN DETAILS AND / OR FINISHES, SIZES AND RELATIONSHIPS OF ROOMS, BUILDING ENVELOPE AND ARCHITECTURAL EXPRESSION.
1 2 3 4

EXHAUST FAN

80 mm2 Bare Copper wire


Grounding Rod
FOR EMERGENCY EF
A LIGHTS
EL
to switchboard

EL
CKT2 a a
LPP b
bEF

LPP

a a
EXHAUST FAN
EF
SWITCHBOARD
CKT1
LPP
aEF

PROJECT NO PROJECT TITLE ISSUE DATE & TIME OWNER SHEET NAME SHEET NUMBER

UP BAGUIO POWERHOUSE UPGRADING AND 5/2/2018 2:12:42 PM


Project Number ELECTRICAL LAYOUT
ARISTOTLE MARC J. GO MODERNIZATION
DATE REVISION DESCRIPTION
ARCHITECT ENGINEER CHECKED BY: LOCATION
UNIVERSITY OF THE PHILIPPINES -
E.2
PRC NO:19205 TIN NO: 912671574 PRC NO: TIN NO:
Checker Baguio City BAGUIO
PTR NO:
PLACE:BAGUIO CITY
DATE: PTR NO:
PLACE:
DATE:
FOR CONSTRUCTION
BIDDING
SCALE 1 : 50 @ A3
THIS DOCUMENT IS THE COPYRIGHT OF 90 DESIGN STUDIO. ALL DIMENSIONS AND SITE CONDITIONS TO BE VERIFIED ON SITE PRIOR TO COMMENCEMENT OF ANY WORK OR PREPARATION OF SHOP
DRAWINGS AND/OR THE FABRICATION OF ANY COMPONENTS. SHOULD THERE BE ANY DISCREPANCIES REFER TO ARCHITECT PRIOR TO COMMENCEMENT OF THE WORK. DO NOT SCALE DRAWINGS -
REFER TO FIGURED DIMENSIONS ONLY. DRAWINGS TO BE READ IN CONJUNCTION WITH RELEVENT DOCUMENTATION FROM ENGINEER AND OTHER SPECIALIST SUB CONSULTANTS. THIS DOCUMENT
DESCRIBES THE DESIGN INTENT, DESIGN DETAILS AND / OR FINISHES, SIZES AND RELATIONSHIPS OF ROOMS, BUILDING ENVELOPE AND ARCHITECTURAL EXPRESSION.
DIAGRAM
NOTE: USE SPARE PANEL IN SWITCHBOARD

2 - 14mm2 THHN W/ 5.5mm2 THHN GRND

50 AT, 230V, 2P

15 AT , 2P 20 AT , 2P

CKT. 1 CKT. 2

PROJECT NO PROJECT TITLE ISSUE DATE & TIME OWNER SHEET NAME SHEET NUMBER

UP BAGUIO POWERHOUSE UPGRADING AND 5/2/2018 2:12:43 PM


Project Number ELECTRICAL SCHEDULE
ARISTOTLE MARC J. GO MODERNIZATION
DATE REVISION DESCRIPTION
ARCHITECT ENGINEER CHECKED BY: LOCATION
UNIVERSITY OF THE PHILIPPINES -
E.3
PRC NO:19205 TIN NO: 912671574 PRC NO: TIN NO:
Checker Baguio City BAGUIO
PTR NO:
PLACE:BAGUIO CITY
DATE: PTR NO:
PLACE:
DATE:
FOR CONSTRUCTION
BIDDING
SCALE 1 : 100 @ A3
THIS DOCUMENT IS THE COPYRIGHT OF 90 DESIGN STUDIO. ALL DIMENSIONS AND SITE CONDITIONS TO BE VERIFIED ON SITE PRIOR TO COMMENCEMENT OF ANY WORK OR PREPARATION OF SHOP
DRAWINGS AND/OR THE FABRICATION OF ANY COMPONENTS. SHOULD THERE BE ANY DISCREPANCIES REFER TO ARCHITECT PRIOR TO COMMENCEMENT OF THE WORK. DO NOT SCALE DRAWINGS -
REFER TO FIGURED DIMENSIONS ONLY. DRAWINGS TO BE READ IN CONJUNCTION WITH RELEVENT DOCUMENTATION FROM ENGINEER AND OTHER SPECIALIST SUB CONSULTANTS. THIS DOCUMENT
DESCRIBES THE DESIGN INTENT, DESIGN DETAILS AND / OR FINISHES, SIZES AND RELATIONSHIPS OF ROOMS, BUILDING ENVELOPE AND ARCHITECTURAL EXPRESSION.
NOTE:
METERS ARE LOCATED AT THE
METER CENTER AREA. 23KV,3 PHASE INCOMING SUPPLY
3 - 167 KVA, 23KV/240V,3
PHASE, 5 Z%
G 350 KVA, 230 V, 3 PHASE,
1200A,3P 60 HZ DIESEL GENERATOR
ATS
M.I.
1200A,3P 1200A,3P
E.I.

225A, 225A, 150A, 150A, 200A, 200A, 100A, 100A, 100A, 100A, 100A, 100A, 150A, 150A, 200A, 200A, 225A, 225A,
2P 2P 2P 2P 2P 2P 2P 2P 2P 2P 2P 2P 2P 2P 2P 2P 2P 2P

M M M M M M M M M

CAC DORMITORY KA AUDITORIUM ADMIN - B CSS-A ADMIN-A HKP CSS-B


NEW CSS-B

M.I.
150A, 150A, 125A, 125A, 600A, 600A, 300A, 300A, 400A, 400A, 200A, 200A, 100A, 100A, 100A, 100A, 100A, 100A,
2P 2P 2P 2P 3P 3P 3P 3P 3P 3P 2P 2P 3P 3P 3P 3P 3P 3P

M M M M M M M M M

LIBRARY CARP/ALUM NEW KA NEW GALERYA NEW C.HUB NEW CAC SPARE SPARE SPARE

PROJECT NO PROJECT TITLE ISSUE DATE & TIME OWNER SHEET NAME SHEET NUMBER

UP BAGUIO POWERHOUSE UPGRADING AND 5/2/2018 2:12:43 PM


Project Number SINGLE LINE DIAGRAM OVERALL
ARISTOTLE MARC J. GO MODERNIZATION
DATE REVISION DESCRIPTION
ARCHITECT DISTRIBUTION E.4
CHECKED BY: LOCATION
UNIVERSITY OF THE PHILIPPINES -
PRC NO:19205 TIN NO: 912671574
Checker Baguio City BAGUIO
PTR NO:
PLACE:BAGUIO CITY
DATE:
FOR CONSTRUCTION
BIDDING
SCALE 1 : 10 @ A3
THIS DOCUMENT IS THE COPYRIGHT OF 90 DESIGN STUDIO. ALL DIMENSIONS AND SITE CONDITIONS TO BE VERIFIED ON SITE PRIOR TO COMMENCEMENT OF ANY WORK OR PREPARATION OF SHOP
DRAWINGS AND/OR THE FABRICATION OF ANY COMPONENTS. SHOULD THERE BE ANY DISCREPANCIES REFER TO ARCHITECT PRIOR TO COMMENCEMENT OF THE WORK. DO NOT SCALE DRAWINGS -
REFER TO FIGURED DIMENSIONS ONLY. DRAWINGS TO BE READ IN CONJUNCTION WITH RELEVENT DOCUMENTATION FROM ENGINEER AND OTHER SPECIALIST SUB CONSULTANTS. THIS DOCUMENT
DESCRIBES THE DESIGN INTENT, DESIGN DETAILS AND / OR FINISHES, SIZES AND RELATIONSHIPS OF ROOMS, BUILDING ENVELOPE AND ARCHITECTURAL EXPRESSION.
MAIN DISTRIBUTION SWITCHBOARD LAYOUT (MDS) :

3 PHASE BUS, 1,200 A WITH CODING INSULATION

V A 2P 2P 2P 2P 2P 2P
Sv Sa 225A 225A 150A 150A 200A 200A 100A 100A 100A 100A 100A M.I. 100A

CAC UP DORM KA AUDI ADMIN-B CSS-A


ON OFF

L1 L2 L3 2P 2P 2P 2P 2P 3P
GROUND FAULT 150A 150A 200A 200A 225A 225A 150A 150A 125A 125A 600A 600A
INDICATOR 80
M
ADMIN-A HKP CSS-B&NEW CSS LIBRARY CARP/ALUM NEW KA
3P,600V
M.I. 1200A
1200A E.I. 3P 3P 2P 3P 3P 3P
300A 300A 400A 400A200A 200A 100A 100A 100A M.I. 100A 100A 100A
NP GP
INCOMING FEEDER
BOTTOM ENTRY NEW GALERYA NEW C.HUB NEW CAC SPARE SPARE SPARE

GROUND BUS,1200 A
LEGEND :

M.I. - - - MECHANICAL INTERLOCK V --- VOLTMETER


E.I. - - - ELECTRICAL INTERLOCK
A --- AMMETER
NP - - - NORMAL POWER
GP - - - GENERATOR POWER Sv --- VOLTMETER SELECTOR SWITCH, 3 PHASE
ATS - - - AUTOMATIC TRANSFER SWITCH --- AMMETER SELECTOR SWITCH, 3 PHASE
Sa
- - - MOLDED CASE CIRCUIT BREAKER
--- LED ON INDICATOR BULB,GREEN COLOR
M --- KILLOWATT-HOUR METER,3 PHASE ON
--- LED GROUND FAULT INDICATOR --- LED OFF INDICATOR BULB,RED COLOR
L1 OFF

PROJECT NO PROJECT TITLE ISSUE DATE & TIME OWNER SHEET NAME SHEET NUMBER

UP BAGUIO POWERHOUSE UPGRADING AND 5/2/2018 2:12:44 PM


Project Number MAIN DISTRIBUTION
ARISTOTLE MARC J. GO MODERNIZATION
DATE REVISION DESCRIPTION
ARCHITECT ENGINEER SWITCHBOARDS LAYOUT (MDS) E.5
CHECKED BY: LOCATION
UNIVERSITY OF THE PHILIPPINES -
PRC NO:19205 TIN NO: 912671574 PRC NO: TIN NO:
Checker Baguio City BAGUIO
PTR NO:
PLACE:BAGUIO CITY
DATE: PTR NO:
PLACE:
DATE:
FOR CONSTRUCTION
BIDDING
SCALE 1 : 50 @ A3
THIS DOCUMENT IS THE COPYRIGHT OF 90 DESIGN STUDIO. ALL DIMENSIONS AND SITE CONDITIONS TO BE VERIFIED ON SITE PRIOR TO COMMENCEMENT OF ANY WORK OR PREPARATION OF SHOP
DRAWINGS AND/OR THE FABRICATION OF ANY COMPONENTS. SHOULD THERE BE ANY DISCREPANCIES REFER TO ARCHITECT PRIOR TO COMMENCEMENT OF THE WORK. DO NOT SCALE DRAWINGS -
REFER TO FIGURED DIMENSIONS ONLY. DRAWINGS TO BE READ IN CONJUNCTION WITH RELEVENT DOCUMENTATION FROM ENGINEER AND OTHER SPECIALIST SUB CONSULTANTS. THIS DOCUMENT
DESCRIBES THE DESIGN INTENT, DESIGN DETAILS AND / OR FINISHES, SIZES AND RELATIONSHIPS OF ROOMS, BUILDING ENVELOPE AND ARCHITECTURAL EXPRESSION.
BURRIED CABLE LAYOUT
FROM SWITCHBOARDS
Grade Level

250
300
Sand Backfill
Warning Tape
Red Concrete Tile
600

Sand Backfill

F1 F1 F2 F3 80mm2 Bare Copper Wire WIRE GUTTER


100mm 100mm

500 2P 2P 2P 2P 2P 2P 2P 2P 2P

M M M M M M M M M
DETAIL A-A 2P 2P 3P 3P 3P 2P 3P 3P 3P

FEEDER

F1
LOAD DECRIPTION

NEW KA
SIZE OF FEEDER

2 Sets,3-250mm2
ESTIMATED LEGHTH

200 mtrs
LOCATION

UP SITE PLAN
M M M M M M M M M
F2 NEW GALERYA 3 - 250 mm2 300 mtrs UP SITE PLAN
F3 CULTURAL HUB 3 - 250 mm2 150 mtrs UP SITE PLAN

FFL

PROJECT NO PROJECT TITLE ISSUE DATE & TIME OWNER SHEET NAME SHEET NUMBER

UP BAGUIO POWERHOUSE UPGRADING AND 5/2/2018 2:12:44 PM


Project Number BURRIED CABLE LAYOUT PLAN
ARISTOTLE MARC J. GO MODERNIZATION
DATE REVISION DESCRIPTION
ARCHITECT ENGINEER AND METER CENTER DETAILS E.6
CHECKED BY: LOCATION
UNIVERSITY OF THE PHILIPPINES -
PRC NO:19205 TIN NO: 912671574 PRC NO: TIN NO:
Checker Baguio City BAGUIO
PTR NO:
PLACE:BAGUIO CITY
DATE: PTR NO:
PLACE:
DATE:
FOR CONSTRUCTION
BIDDING
SCALE As indicated @ A3
THIS DOCUMENT IS THE COPYRIGHT OF 90 DESIGN STUDIO. ALL DIMENSIONS AND SITE CONDITIONS TO BE VERIFIED ON SITE PRIOR TO COMMENCEMENT OF ANY WORK OR PREPARATION OF SHOP
DRAWINGS AND/OR THE FABRICATION OF ANY COMPONENTS. SHOULD THERE BE ANY DISCREPANCIES REFER TO ARCHITECT PRIOR TO COMMENCEMENT OF THE WORK. DO NOT SCALE DRAWINGS -
REFER TO FIGURED DIMENSIONS ONLY. DRAWINGS TO BE READ IN CONJUNCTION WITH RELEVENT DOCUMENTATION FROM ENGINEER AND OTHER SPECIALIST SUB CONSULTANTS. THIS DOCUMENT
DESCRIBES THE DESIGN INTENT, DESIGN DETAILS AND / OR FINISHES, SIZES AND RELATIONSHIPS OF ROOMS, BUILDING ENVELOPE AND ARCHITECTURAL EXPRESSION.
MRL

BURRIED CONDUIT LAYOUT


HKP

Grade Level NEW KA


CANTEEN
BALAY

250
SALUN

300
NEW
Sand Backfill ALUMNI IDR KA
Warning Tape
ISKOLAR NG
Red Concrete Tile BAYAN

GALERYA
MUSEUM

Sand Backfill 32mmØ PVC Pipe for electrical


BULWAGANG JUAN LUNA
14mm2 Bare Copper Wire (CULTURAL HUB)

CSS
BUILDING
TO REHABILITATE

500 LIBRARY
POWER HOUSE

EXISTING
TRANSFORMER

CAC
BUILDING

DETAIL A-A

FEEDER LOAD DECRIPTION SIZE OF FEEDER ESTIMATED LEGHTH LOCATION

F1 UPB LIBRARY PPACU 3-30mm2 40 mtrs UP SITE PLAN

PROJECT NO PROJECT TITLE ISSUE DATE & TIME OWNER SHEET NAME SHEET NUMBER

UP BAGUIO POWERHOUSE UPGRADING AND 5/2/2018 2:12:46 PM


Project Number BURRIED CABLE LAYOUT
ARISTOTLE MARC J. GO MODERNIZATION
DATE REVISION DESCRIPTION
ARCHITECT ENGINEER CHECKED BY: LOCATION
UNIVERSITY OF THE PHILIPPINES -
E.7
PRC NO:19205 TIN NO: 912671574 PRC NO: TIN NO:
Checker Baguio City BAGUIO
PTR NO:
PLACE:BAGUIO CITY
DATE: PTR NO:
PLACE:
DATE:
FOR CONSTRUCTION
SCALE As indicated @ A3
THIS DOCUMENT IS THE COPYRIGHT OF 90 DESIGN STUDIO. ALL DIMENSIONS AND SITE CONDITIONS TO BE VERIFIED ON SITE PRIOR TO COMMENCEMENT OF ANY WORK OR PREPARATION OF SHOP
DRAWINGS AND/OR THE FABRICATION OF ANY COMPONENTS. SHOULD THERE BE ANY DISCREPANCIES REFER TO ARCHITECT PRIOR TO COMMENCEMENT OF THE WORK. DO NOT SCALE DRAWINGS -
REFER TO FIGURED DIMENSIONS ONLY. DRAWINGS TO BE READ IN CONJUNCTION WITH RELEVENT DOCUMENTATION FROM ENGINEER AND OTHER SPECIALIST SUB CONSULTANTS. THIS DOCUMENT
DESCRIBES THE DESIGN INTENT, DESIGN DETAILS AND / OR FINISHES, SIZES AND RELATIONSHIPS OF ROOMS, BUILDING ENVELOPE AND ARCHITECTURAL EXPRESSION.