Note: 1. The relay in the 61F-GP-N8H/-N8Y de-energizes when there is water present across the Electrodes, whereas the relay in the
61F-GP-N8HY energizes when there is water present across the Electrodes.
2. The length when using completely-insulated, 600-V, 3-conductor (0.75 mm2) cabtire cables. Usable cable lengths will become
shorter as the cable diameter or number of conductors becomes larger.
3. The insulation resistance and dielectric strength indicate values between power terminals and Electrode terminals, between power
terminals and contact terminals, and between Electrode terminals and contact terminals.
4. Possible to use with 10 kΩ or less, however, this may cause reset failure.
21
61F-GP-N8j 61F-GP-N8j
8 V (see note) 8V
24 V
61F-GP-N8Y 61F-GP-N8-V50
Power supply Power supply
24 V Control circuit
24 V Control circuit
8V 24 V
3 4 2
22
61F-GP-N8j 61F-GP-N8j
Connections
61F-GP-N8
E3 E3 Pump OFF
• Connect electromagnetic switch coil terminal A to terminal 2. • Connect the electromagnetic switch coil terminal A to terminal 3.
• The pump stops when the water level reaches E1 (indicator ON) • The pump starts when the water level reaches E1 (indicator ON)
and starts when the water level drops below E2 (indicator OFF). and stops when the water level drops below E2 (indicator OFF).
2 1 8 7
MCCB U
0V 8V
24 V Control circuit U
200 V
(See note 1 U
below.)
3 4 5 6
Contactor
(See note 2
below.) PS-3S
Stop
THR E1
Water tank Start
E2
E3
Reservoir
M P
ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ
Note:
ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ
1. The diagram shows the connections for the water supply. When draining, change the connection from terminal 2 to terminal 3.
2. The ground terminal must be grounded.
23
61F-GP-N8j 61F-GP-N8j
6 5 4 3
U Control 24 V
circuit
8V
U Transformer
7 8 1 2
A
*
Electromagnetic switch
E1 Stop
Water tank
E2
Start
Water supply source E3
ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ
P
M
ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ
Note:
ÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉÉ
Be sure to ground terminal 1.
24