Sie sind auf Seite 1von 20

RECTIFIER MODULE

SMR-DM 48V-1800W -B
VOCABULARY

AC Alternating Current
ADC Amps, Direct Current
BTS Base Transceiver Station
℃ Temperature in degrees centigrade
dB Decibel
DC Direct current
EMC Electro Magnetic Compatibility
EN Europe Norm
FCC Federal Communications Commission
℉ Temperature in degrees Fahrenheit
Hz Frequency in hertz
IEC International Elektrotechnical Commission
I/O Input / Output, bi-directional
IP Ingress protection
ISO International Standards Organization
Kg Kilo grams
LED Light emitting diode
Lbs Pounds
mA Milli Amps
MHz Mega Hertz
mm Milli meter
ms Milli second
m/s Meters per second
MTBF Mean time between failure
NS Not Specified
OVP Over voltage protection
RH Relative humidity
VAC Alternating current voltage
VDC Direct current voltage
UL Underwriter’s Laboratories
CONTENTS
1. FEATURES, BENEFITS & DESCRIPTIONS ....................................................4

2. ELECTRICAL SPECIFICATIONS - INPUT PARAMETERS ..............................5

3. ELECTRICAL SPECIFICATIONS - OUTPUT PARAMETERS ..........................7

4. PROTECTION ..................................................................................................9

5. INDICATORS & ADJUSTMENT ......................................................................10

6. MECHANICAL SPECIFICATIONS ..................................................................12

7. OUTLINE DIMENSIONS.................................................................................13

8. STANDARD (CONTINUED)............................................................................15

9. ENVIRONMENTAL .........................................................................................16

10. LIFE TIME.....................................................................................................17

11. SETTINGS AND CONTROLS .......................................................................18

12. OUTPUT CONNECTOR DESCRIPTION ......................................................20


1. Features, Benefits & Descriptions

Features & Benefits


2U/3U height form factors
Modular design for scalable, cost effective expansion
Modular can be positioned in vertical (3U) or horizontal (2U) type
Hot swappable- no system shutdown for maintenance
Light weight plug-in modules for simple installation and maintenance
High power density saves valuable floor space
Unity power factor correction
High efficiency
Temperature compensation - Voltage correction for VRLA batteries
Advanced load share technology
Front access for simplified operation and maintenance
Fan cooling
Full protection function

Description
Sunlight’s SMR-DM 48V-1800W -B is a compact and very reliable family of front
end modules offering 1800W at the output. The module can be inserted into 2U
(horizontal) or 3U (vertical) racks, convenient to customers applications. These
UL Listed SMR-DM Series Plug-in modules are rated at 30 Amps for -48VDC
operation. These features afford you the flexibility to meet both today’s power
requirements and future growth as you increase your network demands.
2. Electrical Specifications - Input Parameters
Item Specification/Function Standard/Comment
Number of
Phase/Number of Wire - Single phase/two wire with
grounding wire

Input Voltage
- Nominal voltage - 220V, Single Phase

- Input voltage range - 176V~275V: full load operation,


150V~175V: 80% load operation,
90V~150V: 50% load operation,
-
- No damage operation 276V-300V
Input Current
- Maximum r.m.s. - 12A At low line 176Vac
current input, rated power

Input Power Factor


- > 0.99 Full load, Nominal
line
Input Frequency
- Input frequency range - 45Hz~65Hz

Efficiency
- >91% (Full Load) At Nominal Line
Input, Rated Output
Voltage, Full Load
Inrush Current
- <12A (peak) Full load cold start,
Nominal line, Rated
output voltage.

Current Total Harmonic Full load, Nominal


Distortion - ≦ 5% line, Rated output
voltage

IEC1000-3-2: Limits
for harmonic current
emissions.
2. Electrical Specifications - Input Parameters (Continued)
Item Specification/Function Standard/Comment
Start Time Delay(Walk-in)
- 3 ~ 10 seconds Full load, Nominal
line, Rated output
voltage

DC and Signal Connector


- Supplier Positronic BERG

- Component No. 5145-001

- Standard UL/CSA approved

AC Connector
- Type Sunlight Standard 15ME2

- Standard UL/CSA/VDE/SEV approved

Input Protection(Fuse)
- Type Fuse
- Rating 20A
- Standard UL/VDE approved
- Allocation On Board

GND wiring character Resistance value < 0.1 at current 30A Standard
3. Electrical Specifications - Output Parameters
Item Specification/Function Standard/Comment
Maximum Output Power
- 1800W 60V/30A output

Output Voltage
- Nominal output voltage - 54.3V

- Output voltage range 40V~60V

Rated Output Current


30A
Current Limit
Maximum 110% of rated output
current
Dynamic Response
- Overshoot - ≦ ±5% of rated output voltage Load Change:
10%~90%
- Recovery time
- <1ms, Recover to≦ ±1% of rated
output voltage

Load Regulation - ≦ ±0.5%


At output
<Mainland China Spec.> :
43.2v,54.3v,57.6v
V − VH
Equation : × 100% voltage, 0-50% load,
VH 50%-100% load
V − VF
Equation : H × 100%
VF

- ≦ ±1%
At output
<Sunlight Spec.> : 43.2v,54.3v,57.6v
V − VF voltage, 0-100% load
Equation : × 100%
VF
V : No Load Voltage;
VH: Half Load Voltage
VF: Half Load Voltage
Current Sharing
≦ ±5% of rated output current
3. Electrical Specifications - Output Parameters (Continued)
Item Specification/Function Standard/Comment
Voltage Stability ≦ ±0.6% Include load change
Accuracy and line change

Line Regulation - ±0.1 %


<Sunlight Spec. >: At rated output
VA − VB Voltage, 0~ 100%
Equation : × 100% Load, Input Voltage
VB -20%~+25% Range
VA: Output Voltage, At Input voltage Normal Voltage 220v
-20%~+25% Range
VB: Output Voltage, At Nominal Line
Input voltage, Load 0~100%

Noise
- Audio band - ≦ 24 dBrnc Connect battery
No Connect battery
- ≦ 40 dBrnc Or ≦ -54.26dbmp
CCITT
- <2mV
<Note> dBmp + 2.5 = 20 Log
(V/0.7746)
- Wide band
- ≦ 20 mVrms (10KHz~100MHz)
- Peak to peak ripple Oscilloscope band
voltage - ≦ 100 mV set to 20 MHz

- Narrow band 3.4KHZ~150KHz


- ≦ 5 mV 150KHZ~200KHz
200KHZ~500KHz
- ≦ 3 mV 500KHZ~30MHz
- ≦ 2 mV
- Acoustic - ≦ 1 mV at 1 meter in front of
SMR

- ≦ 55dBA
Temperature Coefficient <200PPM
4. Protection
Item Condition Protection
Input
- Power Brown Out - 0~80% Of Rated Input Voltage No damage to SMR

- Mains overvoltage - 310V ±10V SMR shut down, SMR


restart after input voltage
return to nominal line
voltage range

- Mains undervoltage - 80V ±10V SMR shut down , SMR


restart after input
voltage return to nominal
line voltage range

Output
- O/P voltage abnormal - >59.5±0.5V Shut down and latch

- Over Current - 120%~135% Of Rated Current Shutdown and restart

- Output Short Circuit - Output short before start up or Cause no damage to


short after start up. SMR, SMR current limit,
restart after fault release

Other Protection
- Overtemperature - 95±5℃ (Output-Diode heat sink) Shutdown and restart
(Environment)

- DC bus voltage - >440V ± 10V Shut down and restart


abnormal - <320V ± 10V Shut down and restart

- Fan Failure Fan Failure Rectifier Fail Alarm LED


light, shutdown
5. Indicators & Adjustment
Item Specification/Function Standard/Comment
Line
- Function - AC line ON - The LED lights when AC
- Component type - LED line is normal.
- Color - Green
- On condition - Line exceeds 70V (Typical)
- Off condition - No line or line under 50V
(Typical)
R.F.
- Function - Rectifier Failed
- Component type - LED
- Color - Red
- On condition - Rectifier Fail
- Off condition - Rectifier Normal

C.L.
- Function - Current Limited - The LED lights when the
- Component type - LED output current exceeds
- Color - Yellow 110% (default) of rated
- On condition - Output current is limited. load.
- Off condition - Output current under 110% - The current limited point
of rated load. Output can be programmed by
current is not limited. CSU.

I+, I-
- Function -Output Current Test Points - The I+, I- will send a
voltage value, which can
be transferred, to output
current.
0.1V =1A
FLO
- Function - Float Voltage -Variable Resistor
Adjustment(40-60V) Adjustment
- Increase in clockwise,
decrease in
counterclockwise.
5. Indicators & Adjustment (Continued)
Item Specification/Function Standard/Comment
CL
- Function - Current Limit (30-110%) - Variable Resistor
Adjustment
- Increase in clockwise,
decrease in
counterclockwise
6. Mechanical Specifications
Item Specification/Function Standard/Comment
Width
- Module Case - 3.3" / 83.6mm

Height
- Module Case - 5.2" / 132mm

Depth
- Module Case - 10.35" / 263mm -The dimension does
not include the length
of front panel screw
and rear panel
connector
Weight - 7.26b / 3.3kg

Marking Language - English

Color - Front Panel: Pantone cool gray 5C


- Case : Zn Plated, color : yellow
7. Outline Dimensions

263.0

298.7
83.6 25.2 263.0
ON

CL A
RF
CL

I- I+
AC

O
FL

120.5
132.0

AC

F
ON OF

7.9
12.3
8. Standard
Item Specification/Function Standard/Comment
Safety Mark
- UL/CUL - IEC 950
- TUV/CE - EN 60950

EMI/RFI - System Meet : FCC Class B


CISPR 22 Class B - FCC Part 15 Subpart J
- SMR Meet : FCC Class A - EN55022,
CISPR 22 Class A BS6527 Class B
EMS - EN 61000-3-3, EN
- Voltage Fluctuation 60555-3
Flicker
- EN 61000-4-2 Level 4 ,
- Electrostatic Discharge - 15KV Air Discharge, 8KV IEC 1000-4-2, IEC 801-2
(ESD) Contact Discharge Level 4

- IEC 1000-4-3, IEC 801-3


- Electromagnetic - 10V/m Level 3
Compatibility(EMC)/Ra
diated Susceptibility - EN 61000-4-4 Level 4,
- Electrical Fast - 4KV IEC 1000-4-4, IEC 801-4
Transient(EFT) Level 4

- IEC 1000-4-6 Level 3


- Conducted - 10V/m
Susceptibility - IEC 1000-4-5 Level
- Lightning/Surge - 6KV Special & ANSI/IEEE
C62.41-1991 B3
- Test Condition:
1.Combination wave
1.2/50us, 8/20us, 2Ω,
3KA
2. Ring wave 100KHz,
500A
8. Standard (Continued)
Item Specification/Function Standard/Comment
Current Harmonic
- EN 61000-3-2, EN
60555-2, IEC 1000-3-2
Class A

Insulation Resistance
- Input to output>2 MΩ (At Test Condition:
500Vdc) - Humidity 90% R.H.,
- Input to frame ground > 2 MΩ Non condensing, 25℃
(At 500Vdc) condition
- Output to frame ground >2 MΩ - Disconnect the FG
(At 500Vdc) wire from the case
(Input to frame ground)
Withstand voltage
(High Pot) - Input To Output 4242 Vdc 1
Minute (Or 3000 Vac 50Hz
≤30mA)
- Input to Frame Ground 2837 Vdc
1 Minute (Or 2006 Vac 50Hz
≤30mA)
- Output to Frame Ground 707
-For China market,
Vdc 1 Minute (Or 500 Vac 50Hz
1500VDC
≤30mA)

Leakage Current
- <3.5mA

Vibration
- (1) Sine Wave, 5.5 ~ 500Hz,
3.5G acceleration, duration: 30
minutes
- (2) Sine Wave, 10 ~ 55Hz,
0.35mm amplitude, duration: 30
minutes
9. Environmental
Item Specification/Function Standard/Comment
Operation Temperature
- 0℃ ~ +50℃ (32℉ ~ +122℉)

Operation Humidity
- 0 ~ 95% Relative Humidity
(Non-Condensing)

Storage Temperature
- -40℃ ~ +85℃ (-40℉ ~ +185℉)

Storage Humidity
- 0 ~ 95% Relative Humidity
(Non-Condensing)

Altitude
- -152m~3048m (-500~10000
Feet)
10. Life Time
Item MTBF Standard/Comment
Rectifier
- >150K hours At 25℃, rated load

Cooling Fan
- > 5 years
11. Settings and Controls
Setting from CSU
Settings Description Comment
Floating/equalize
charging voltage
- Function - Floating/equalize charging voltage
can be set from CSU
- Setting Window - 53.3VDC-55.3VDC
- Default - 54.3VDC

Current Limited
- Function - Current limited can be set from CSU
- Setting Window - 0-110% , 1% per step
- Default - 110%

DC High Voltage Shutdown


- Function - High voltage shutdown can be set
from CSU
- Setting Window - 57.5VDC~59.5VDC
- Default - 57.5VDC

DC High Voltage Alarm


- Function - High voltage alarm can be set from
CSU
- Setting Window - 58VDC~59VDC
- Default - 57.5VDC

DC Low Voltage Alarm


- Function - Low voltage alarm can be set from
CSU
- Setting Window - 44VDC~48VDC
- Default - 44VDC
11. Settings and Controls (Continued)
Setting from CSU
Settings Description Comment
Remote SMR On/Off
- Function - Remote SMR on/off capability exists
through the CSU control.

- Description - CSU automatically shuts down SMR in


case of DC high voltage.
- Users can manually shut down SMR
from CSU for optimizing energy
operation purpose.

Floating/equalize status
- Function - SMR floating/equalize status can be set
through the CSU control.

- Description - CSU automatically transfer SMR to


floating mode in case of
(1). Periodical operation (Settable from Actual Date or
CSU) Periods Base
(2). Mains recover after deep discharge
resulted from blackout/battery test
- Users can manually set SMR to floating
or equalize from CSU.
12. Output Connector Description

24 19

VO - 6 1 VO+

Signal
Pin Meaning
1 COM
2 NC
3 ITP1
4 RFA
7 NO
9 IBUS
15 VASJ
16 STDN
20 CLL
21 ICOM
22 I (A/M)

Das könnte Ihnen auch gefallen