Warning Daikin Industries, Ltd.’s products are manufactured for export to numerous countries throughout the
world. Daikin Industries, Ltd. does not have control over which products are exported to and used in a
particular country. Prior to purchase, please therefore confirm with your local authorized importer,
distributor and/or retailer whether this product conforms to the applicable standards, and is suitable for
use, in the region where the product will be used. This statement does not purport to exclude, restrict
or modify the application of any local legislation.
Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorized parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the User's Manual carefully before using this product. The User's Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any inquiries, please contact your local importer, distributor and/or retailer.
JMI-0107 JQA-1452
“ design, development, manufacture,
installation, and supplementary
service” of products manufactured at EC99J2044 JQA-E-90108
organisation as having an appropriate
programme of environmental protection
procedures and activities to meet the
For high outdoor temperature use
A s p e c ia l a ir c o nd itio ning s y s te m d e s ig ne d
Dealer fo r s ma ll o ffic e s a nd s ho p s
Head Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global/
c All rights reserved
HE AT P UM P
Printed in Japan 08/06/003 Y.K
Specifications, designs and other content appearing in this brochure are current as of August 2006 but subject to change without notice. Printed on 100% recycled paper with soy ink.
Heat P ump Type 50 Hz
The ideal air conditioning system for
small offices and shops
E xtending the c ore “ 5S ” c onc ept—S pac e s aving, S uffic ient c apac ity, S lim des ign,
S ound- reduc ed operation and S ingle phas e power s upply—Daikin’ s VR V III- S
offers added value with the “ 2E ” c onc ept—E as y ins tallation and E as y
maintenanc e. W ith all thes e features and more, we proudly pres ent the ideal air
c onditioning s ys tem des igned for s mall- s ized buildings .
S
The VRV III-S is highly space saving, featuring slim and compact outdoor units.
The 5S +2E c onc epts of It is suitable for small offices and shops with the capacity of 6 HP.
5S
concept S pac e s aving
S uffic ient c apac ity
S lim des ign
S ound-reduc ed operation
S ingle phas e power s upply
E
Outdoor unit can be installed
on a balcony
E as y maintenanc e The compact, trunk-shaped outdoor unit can easily
E as y ins tallation 2E
concept
be installed on a balcony, realizing complete system
installation within each floor. This enables more
useful utilization of the space on the building rooftop.
Content
Introduction..............page 1 Indoor units line up.....page 15 Option list..........................page 35
Indoor units ..............page 35
Main features...........page 3 Specifications.................page 27 Outdoor units ...........page 37
Indoor units ............page 27 C ontrol s ys tems ......page 37
1 Control systems.....page 9 Outdoor units ........page 34 2
MAIN FEATURERS
A slim outdoor unit and a wide range of indoor units
T o s uit the variety of rooms found in s mall
offic es and s hops , the VR V III- S s ys tem offers a
s lim outdoor unit and a wide range of indoor
units .
Indoor units
15 types 82 models
VR V III- S indoor and outdoor units are almos t
as eas y to ins tall as res idential air c onditioning A wide range of indoor units includes 82
models in 15 types. The indoor units can be
s ys tems , making them ideal for s mall offic es
New selected to match every room and
preference.
FXDQ-PVET
(without drain-up pump) (700 mm width type)
New FXDQ-NAVE
(with drain-up pump)
FXDQ-NVET
(without drain-up pump) (900/1,100 mm width type)
Ceiling mounted
built-in FXSQ-M
Ceiling mounted
New duct
FXMQ-MA
Ceiling suspended
New FXHQ-MA
Wall mounted
New FXAQ-MA
Floor standing
New FXLQ-MA
Concealed
New
floor standing FXNQ-MA
Notes: • R410A VRV system indoor units are not compatible with the R22 VRV system.
Capacity RT 0.6 ton 0.8 ton 1.0 ton 1.3 ton 1.6 ton 2.3 ton 3.2 ton 4.0 ton
Type Btu 7500 9600 12300 15400 19100 27300 38200 47800
HP 0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 3 HP 4 HP 5 HP
Index 20 25 31.25 40 50 71 100 125
Connection Unit — BEVQ71MAVE BEVQ100MAVE BEVQ125MAVE
Ceiling suspended
New cassette — — — — — FXUQ71MAV1 FXUQ100MAV1 FXUQ125MAV1
Notes: • Indoor units in the 63 class are not available for the above model.
Conversion rates
• BEV units are necessary for Connection unit series indoor units. Refer to the Connection unit series catalog for details.
Btu/h = kW x 3412
RT = kW x 0.284
3 4
MAIN FEATURERS
Energy efficiency and quiet operation A collection of cutting-edge technologies
realizes efficient and quiet operation.
Outdoor units have been newly des igned us ing the new c ompres s or
to realize energy s aving performanc e and quiet operation. Improving the high efficiency compressor
5
to achieve a higher COP 3
1 Reluctance DC Scroll Compressor
Higher COP during both cooling Overheating losses are reduced by pressurizing the area 2
around the motor, boosting energy saving performance in
and heating operations conjunction with other features.
its energy efficiency. It achieves high COP Cooling 6 HP 3.03 reactive force from the fixed scroll is added
4
to the internal force, thereby reducing 1
during cooling and heating operations by thrust losses. This results in improved
employing the new compressor. Heating 6 HP 3.62 efficiency and suppressed sound levels.
Neodymium magnet
magnets.
latest technologies and features are Smooth Air Inlet Bell Mouth and Aero Spiral Fan
applied to the outdoor units.
Heating 6 HP 55 2
Neo aero spiral fan blade tips
These two new features work to significantly Conventional Newly developed
reduce noise. Guides are added to the bell
mouth intake to reduce turbulence in the
airflow generated by fan suction. The new
Nighttime quiet operation function Aero Spiral Fan features fan blades with the
Operation sound level selectable bent blade edges, further reducing
from 3 steps for the night mode Mode 1. Automatic mode Escaping eddies are sucked
turbulence. in by the bent blade edges,
Mode 1. Automatic mode reducing overall turbulence.
Set on the outdoor PCB. Time of maximum
DC fan motor
Capacity %
Efficiency (%)
(Step 1), 44 dB (Step 2) and 41 dB (Step 3). 60
Approx.
DC fan motor structure 20%
increase
For a 6 HP installation
New Automatic test operation
Simply press the test operation button and the unit performs an automatic system check,
1 2 3 4
including wiring, shutoff valves, sensors, and refrigerant volume. The results are returned
automatically after the check finishes.
9 units
5 6 7 8
Long piping design possible >> Super wiring system >> REFNET piping system
A super wiring system is used to enable shared use of the Daikin’s advanced REFNET piping system makes
The VRV III-S provides the long piping wiring between indoor and outdoor units and the central installation easy. Only two main refrigerant lines are
length possibility of 150 m, with a total piping control wiring, with a relatively simple wiring operation. required in any one system. REFNET greatly reduces the
length of 300 m. If the outdoor unit is The DIII-NET communication system is employed to imbalances in refrigerant flow between units, while using
installed above indoor units the height
50 m*1 enable the use of advanced control system. small-diameter piping.
Height
difference can be up to a maximum of 50 m. difference
15 m
These generous allowances facilitate an *2 Level difference
Outdoor unit
between indoor
extensive variety of system designs. units. Central
remote
controller
Actual piping length Total piping length
Indoor unit
150 m 300 m Note:*1. 40 m when the outdoor unit is installed below indoor units.
*2. Maximum piping length between the indoor unit and the first branch is 40 m.
Cooling
Easy maintenance
50°C DB VR V III-S features a self-diagnosis function for outdoor units that can determine the
The versatile operating range of the VRV III-S system works to 50
reduce limitations on installation locations. The operating 40
status of each component. Also, a new memory function helps to identify the problem if
temperature range for heating goes all the way down to -20°C, 30 Heating
while cooling can be performed with outdoor temperatures as 15.5°C WB
20
high as 50°C. Both these achievements are due to the
employment of a high-pressure dome-type compressor. 10 New Memory function for operation data
0
* Refer to the Engineering Data for cooling/heating capacities. -5°C DB
Operating data for the preceding 3 minutes is automatically stored in memory. Should a
* Please contact your distributor to confirm cooling/heating capacities when outdoor
temperatures are 46°C or higher.
-10
–20°C WB malfunction occur, this speeds up the process of identifying and fixing the cause of the problem.
-20
7 8
CONTROL SYSTEMS
Control systems
T he VR V III- S s ys tem us es the s ame DIII- NE T c ommunic ation s ys tem
as the VR V, enabling the us e of advanc ed c ontrol s ys tems .
the remote controller that makes The rubber switch and the oil-resisting
possible more comfortable room resin casing have been adopted for
temperature control. durability.
Signal receiver unit
Enables you to select cool/heat/fan * When the auto-swing function is not available, the (Separate type)
message, THIS FUNCTION IS NOT AVAILABLE is
operation mode with the indoor displayed when the wind direction adjustment button
BRC1C62 remote controller of your choice is pressed. Signal receiver unit
Wireless remote
without using the cool/heat selector. controller (Installed type)
Wired remote controller with weekly schedule timer (Optional) * Refer to the page 35 for the model names.
Adds new, advanced functions to those of the above wired remote Simple remote controller (Optional)
controller.
The remote controller has
Includes ventilation mode and airflow rate switching, the main functions of HRV series. centralized its frequently used
24-hour clock function (1-hour backup for power failures) operation selectors and
switches (on/off, operation
Programming function for each day of week. mode, temperature setting and
Scheduling possible of start/stop and temperature limit (5 settings/day) airflow volume), making itself
suitable for use in hotel rooms
Programming can be enabled or disabled. or conference rooms.
Copy function for programmed schedules. The exposed type remote
Concealed type controller is fitted with a
Notes: 1. Standard remote controllers (BRC1C62) not required. (For hotel use) thermostat sensor.
2. If the BRC1D61 is connected to the centralized remote controller, (BRC3A61)
BRC1D61
the schedule function is not available.
Exposed type
(BRC2C51) The concealed-type remote controller smartly fits into a
The wired remote controller supports a wide range of control functions night table or console panel in a hotel room.
Control of Cool/Heat In all the series of VRV, Cool/Heat changeover in the same refrigerant
Wide variation of remote controllers for indoor units
changeover circuit can be changed by the remote controller of the indoor unit. 1 Control by two remote controller
FXCQ FXFQ FXZQ FXKQ FXDQ FXSQ FXMQ FXHQ FXAQ FXL(N)Q FXUQ
The indoor unit can be connected by the two
remote controller, for example one in the room
Group control and the other one in the control room, which
Equipment One remote controller can can control the operation of indoor unit freely. Wired remote controller
Outdoor
related to the control the operation of max.16 (The last command has a priority.) Of course,
unit indoor units at the same time.
central control the group control by two remote controller is
also possible.
Wired remote controller
with weekly schedule timer
2 Remote control
Indoor unit
Remote controller The wiring of remote controller can be
Remote controller
extended to max.500m and it is possible to Wireless remote controller
install the remote controllers for the (Installed signal receiver unit)
different indoor units in one place.
Remote
controller 3 Control for the combined operation Wireless remote controller
(Separate type signal receiver unit)
The operation of HRV can be controlled by
Forced OFF the remote controller of the indoor unit. Of
input
course, the remote controller can display
the time to clean the filter.
HRV Simple remote controller
(Exposed type)
Remote controller Remote
controller Remote controller
Remote controller Remote controller 4 Expansion of system control
The system can be expanded to add Simple remote controller
1 2 3 4 several controllers, such as BMS, Forced (Concealed type: for Hotel use)
OFF input and etc.
9 10
Refer to page 7 for the total number of indoor units that can be connected to the outdoor unit.
CONTROL SYSTEMS
Centralized control systems
Up to 64 groups of indoor units (128 units) can be centrally controlled. System integration with various air-conditioning peripheral
equipment such as HRV (Heat Reclaim Ventilation) is easy.
Optional controllers for centralized control can be combined freely, and
system can be designed in accordance with building scale and purpose. Wiring can be run up to a total length of 2 km, and adapts easily to
large-scale system expansion.
Central remote
connected.
Schedule timer (Optional)
Interface adaptor for SkyAir
controller Max. 128 indoor units can be operated as programmed schedule.
(DCS302CA61) series (built-in indoor unit)
(DTA102A52) • Max. 128 indoor units controllable
Up to 2 units
connectable
• When used in combination with a central remote controller, a maximum of 8 weekly schedule
patterns can be set, while the central controller can be used to select desired zones. Up to 2
Operation/Stop pairs can be set per day.
• Max. 48 hours back up power supply
6 cores 7 cores max. Interlink Building Management System Schedule timer • Max. wiring length 1,000 m (Total: 2,000 m)
(host computer monitor panel) also possible
DST301BA61 • Compact size casing (Thickness: 16 mm)
Schedule timer (DST301BA61)
1 unit connection possible ; Unification adaptor for computerized
• Combination with Central Remote controller, Unified ON/OFF controller and BMS system
1. Refer to page 7 for the total number of indoor units that can be connected to the outdoor unit.
• Certain indoor units limit the functions of some control systems.
For more details, please refer to the Engineering Data.
11 12
CONTROL SYSTEMS
Advanced control systems
Special
Auto heat/cool change-over Function 7 Simple Interlock Function
Temperature limitation
History of 500 actions
Air Conditioning Network Service System (Optional Maintenance Service)
Simple Interlock Function
Special
Function 4 Air Conditioning Unification adaptor Unified ON/OFF and
Network Service System for computerized control status monitoring from
modem for connections [DCS302A52] the central monitoring panel
Special RS-232C
Function 2 Special Special
Function 5 Function 1 Dio Unit (DEC102A51)
DCS601C51 Control pump,
Remote monitoring and control Pi Port lighting
Trouble reports D -NET
E-mail
Special
Function 3 • Connection to power consumption
Special meter when using power proportional DIII-NET Monitoring of room
Function 3 distribution function. (Optional) Plus Adapter Indoor Unit HRV enter/exit sign
(option)
Trouble reports (DCS601A52) Di Unit (DEC101A51) Special
Function 6
Mobile Phone Number of indoor unit expanded from 64 to 128.
Special
Function 7 Simple Interlock Function
13 14
INDOOR UNITS LINE UP
RT 0.6 ton 0.8 ton 1.0 ton 1.3 ton 1.6 ton 2.0 ton 2.6 ton 3.2 ton 4.0 ton
Btu 7500 9600 12300 15400 19100 24200 30700 38200 47800
Type Model name Capacity
Ceiling Mounted
Cassette
(Double-flow)
FXCQ-MVE
(double-flow) type
Ceiling Mounted
Cassette
FXFQ-MVE
(Multi-flow)
Super Cassette FXCQ20M /FXCQ25M /FXCQ32M
600X600 FXCQ40M /FXCQ50M /FXCQ63M
multi flow
ceiling mounted
FXZQ-M7V1B FXCQ80M /FXCQ125M
cassette
Ceiling Mounted
New
Cassette Corner FXKQ-MAVE
350mm
FXDQ-NVET without
(900/1,100 mm drain-up
width type) pump
(When a high-efficiency filter is attached, the
unit's height is 400mm.)
Ceiling Mounted FXSQ-MVE
Built-in
Low operating sound (dB(A))
0° 0°
7 discharge patterns in 2 to 4 directions can be selected to suit Can also be installed in high ceilings.
60° 60°
the requirements of installation site or the shape of the room.
Number of discharge outlets used
The number of installation method using ducts has increased FXFQ25M-80M FXFQ100M-125M
as shown below. 4-way air 3-way air 2-way air 4-way air 3-way air 2-way air
discharge discharge discharge discharge discharge discharge
Single branch– 8 patterns Standard 2.7m 3.0m 3.5m 3.2m 3.6m 4.2m
Ceiling
height High ceiling 1 3.0m 3.3m 3.8m 3.6m 4.0m 4.2m
Branched High ceiling 2 3.5m 3.5m – 4.2m 4.2m –
Note: Set standard 4-way discharge when shipped. Settable to 5 different
High ceiling types 1 and 2 will be set for remote control operation levels between 0° and 60°
Closed Piping
location Angles can be set on site to prevent drafts (0°-35°)
There are 3 patterns in auto swing operation or soiling of the ceiling (25°-60°)
Pattern Pattern Pattern
1 Standard setting 2 Draft Prevention 3 Setting to prevent Switch box is inside the unit, which
setting soiling of ceiling
makes maintainance and installation
2 branches –2 patterns easy.
25˚ 25˚ 10˚ 10˚ 35˚ 35˚
Branched Closed 40˚ 40˚
60˚ 60˚ 65˚ 65˚
17 18
INDOOR UNITS LINE UP
NE W
Compliant with the RoHS Directive *
Air dis c harge grille * For FXDQ-PVE and FXDQ-NAVE models only.
(option)
External static pressure selectable by remote
controller switching make this indoor unit a very
comfortable and flexible model.
Downward discharge is shut off and air is blown straight out 10 Pa-30 Pa/factory set: 10 Pa for FXDQ-P models.
(front discharge). 15 Pa-44 Pa/factory set: 15 Pa for FXDQ-N(A) models.
Slim body needs only 220 mm space above the FXDQ-P and FXDQ-N(A) models are available in
ceiling. If you use panel spacer (optional), the two types to suit different installation conditions
FXDQ-PVE, FXDQ-NAVE:
unit can be installed in the min. space of 195 mm. with a drain-up pump (750 mm lift) as a standard accessory
FXDQ-P(N)VET: without a drain-up pump
Min.195 mm Low operating sound (dB(A))
Panel s pac er Class 20 25 32 40 50 63
20 mm Operating
33/29 33/29 33/29 34/30 35/31 36/32 750mm
sound (H/L)
A long-life filter (maintenance free up to one The values of operation sound level represent those for rear-suction operation.
Sound level values for bottom-suction operation can be obtained by adding 5 dB.
year) is equipped as standard accessory. Values are based on the following conditions:
FXDQ-P: external static pressure of 10 Pa; FXDQ-N(A): external static pressure of 15 Pa. Ceiling
* RoHS Directive: The RoHS (Restriction of Hazardous Substances (in electrical and electronic equipment)) Directive is an environmental directive enacted to regulate the use of designated * RoHS Directive: The RoHS (Restriction of Hazardous Substances (in electrical and electronic equipment)) Directive is an environmental directive enacted to regulate the use of designated
19 chemical substances (lead, cadmium, hexavalent chromium, mercury, polybrominated biphenyls and polybrominated diphenylether) in electrical equipment. All household chemical substances (lead, cadmium, hexavalent chromium, mercury, polybrominated biphenyls and polybrominated diphenylether) in electrical equipment. All household 20
products subject to this Directive and sold in Europe from July 1, 2006 are legally bound to comply with the RoHS Directive. products subject to this Directive and sold in Europe from July 1, 2006 are legally bound to comply with the RoHS Directive.
INDOOR UNITS LINE UP
Highly flexible for various application High static pressure allows flexible duct design
NE W
Highly flexible installation is possible Installation examples ( Optional parts) Compliant with the RoHS Directive*
with a complete line-up of optional Standard Cassette style (standard filter) More than 150 Pa of external static pressure
kits to satisfy the various needs,
Long-life filter
such as the design concept, interior Air s uc tion
High external static pressure allows extensive
decoration and so on.
Long-life filter c anvas bellows duct work for flexible applications.
Air s uc tion panel
Full line-up of 8 models from 40 to 250 type.
The unit can be installed, if there is With duct (case 1)
a space of 350 mm above ceiling. Cassette style (high efficiency filter)
(when suction panel is used.) High effic ienc y Optional accessories include a drain-up kit,
filter
S c reening
Ac c es s panel Air s uc tion
high-efficiency filters (65% and 95% NBS) and
door
Min.
c anvas bellows a long-life filter (maintenance free up to 1 year).
350 mm
Air s uc tion panel
Without drain Drain-up pump is
With duct (case 2) Long-life filter Ceiling return equipped as optional
Drain-up pump is equipped as
Long-life filter accessory with 750 mm
standard accessory with 250 mm lift. S c reening
Ac c es s panel door Ac c es s panel Min
390mm 450 mm
250 mm 750mm
Operating 220V 37/32 37/32 38/32 38/32 41/36 42/35 43/37 43/37 46/41
Sound (H/L)
240V 39/34 39/34 40/34 40/34 43/38 44/37 45/39 45/39 48/43
* RoHS Directive: The RoHS (Restriction of Hazardous Substances (in electrical and electronic equipment)) Directive is an environmental directive enacted to regulate the use of designated
chemical substances (lead, cadmium, hexavalent chromium, mercury, polybrominated biphenyls and polybrominated diphenylether) in electrical equipment. All household
21 products subject to this Directive and sold in Europe from July 1, 2006 are legally bound to comply with the RoHS Directive. 22
INDOOR UNITS LINE UP
FXAQ20MA /FXAQ25MA
FXHQ32MA /FXHQ63MA
New New FXAQ32MA/FXAQ40MA
FXHQ100MA
FXAQ50MA /FXAQ63MA
290 mm
–200 mm
1,050 mm
Turbulent flow Quiet s tream fan
is produc ed Dras tic 10 kg weight reduc tion from 24 kg
S traightening vane
to 14 kg.
Volume reduc ed by 22%.
Low operating sound (220V-240V)(dB(A))
S pac e s avings of up to 47%.
Class 32 63 100
Operating sound
36/31 39/34 45/37 Low operating sound (220V-240V)(dB(A))
(H/L)
Class 20 25 32 40 50 63
Operating
Installation is easy sound (H/L)
35/29 36/29 37/29 39/34 42/36 46/39
E as y-to-c lean flat des ign distribution. The louver closes automatically
Maintenanc e is eas ier bec aus e everything when the unit stops.
Wide air discharge openings produce a 1,000mm
spreading 100° air flow. c an be performed from below the unit. 5 steps of discharge angle can be set by
A long-life filter (maintenanc e free up to remote controller.
Indoor unit
one year) is equipped as s tandard Drain-up kit
Discharge angle is automatically set at the
same angle as the previous operation when Flexible installation.
New model restarts. (Initial setting; 10˚ for cooling and 70˚ Drain pipe c an be fitted to from either left
100° for heating) or right s ides .
* RoHS Directive: The RoHS (Restriction of Hazardous Substances (in electrical and electronic equipment)) Directive is an environmental directive enacted to regulate the use of designated * RoHS Directive: The RoHS (Restriction of Hazardous Substances (in electrical and electronic equipment)) Directive is an environmental directive enacted to regulate the use of designated
chemical substances (lead, cadmium, hexavalent chromium, mercury, polybrominated biphenyls and polybrominated diphenylether) in electrical equipment. All household chemical substances (lead, cadmium, hexavalent chromium, mercury, polybrominated biphenyls and polybrominated diphenylether) in electrical equipment. All household
23 products subject to this Directive and sold in Europe from July 1, 2006 are legally bound to comply with the RoHS Directive. products subject to this Directive and sold in Europe from July 1, 2006 are legally bound to comply with the RoHS Directive. 24
INDOOR UNITS LINE UP
Concealed floor
standing type Only one unit is needed to distribute comfortable air
throughout an L-shaped store.
FXNQ20MA /FXNQ25MA
New FXNQ32MA/FXNQ40MA
FXNQ50MA /FXNQ63MA
A great unit to be concealed in the skirting-wall of perimeter New Connection unit Connection unit is the device for connecting above indoor units to VRV III-S.
NE W NE W
Compliant with the RoHS Directive* Compliant with the RoHS Directive*
Refrigerant piping layout External wiring layout *1 Maximum piping length
The unit is concealed in skirting-wall of perimeter, that enables Connection unit for indoor unit Model between the BEV unit
and the indoor units.
to create high class interior design. FXUQ-MAV1 5m
VR V -S s eries
outdoor unit
Notes:
The connecting port faces Liquid G as pipe
BEVQ-MAVE S uper wiring ( DIII-NE T ) • When connecting centralized-control device, it is
necessary to install an interface adaptor for an
S ingle-phas e 220-240 V
downward, greatly facilitating
pipe
power s upply indoor unit (DTA102A52).
• Connection unit BEVQ-MA is necessary for each
indoor unit.
on-site piping work. C onnec ting
port
Indoor unit
• The refrigerant piping height difference between
the indoor units and the BEV unit must be within
4 m.
R efrigerant • The BEV unit must be installed within a
A long-life filter (maintenance piping Piping length*1 Indoor unit
maximum height difference between indoor units
of 15 m.
• Branching of the refrigerant piping is not
free up to one year) is equipped R emote c ontroller possible downstream of the BEV unit.
* RoHS Directive: The RoHS (Restriction of Hazardous Substances (in electrical and electronic equipment)) Directive is an environmental directive enacted to regulate the use of designated
* RoHS Directive: The RoHS (Restriction of Hazardous Substances (in electrical and electronic equipment)) Directive is an environmental directive enacted to regulate the use of designated
chemical substances (lead, cadmium, hexavalent chromium, mercury, polybrominated biphenyls and polybrominated diphenylether) in electrical equipment. All household
chemical substances (lead, cadmium, hexavalent chromium, mercury, polybrominated biphenyls and polybrominated diphenylether) in electrical equipment. All household
products subject to this Directive and sold in Europe from July 1, 2006 are legally bound to comply with the RoHS Directive.
25 products subject to this Directive and sold in Europe from July 1, 2006 are legally bound to comply with the RoHS Directive. 26
SPECIFICATIONS
INDOOR UNIT S INDOOR UNIT S
C e ilin g M o u n te d C a s s e tte <D o u b le f lo w > T y p e 600X600 Multi Flow Ceiling Mounted Cassette Type
MODEL FXCQ20MVE FXCQ25MVE FXCQ32MVE FXCQ40MVE FXCQ50MVE FXCQ63MVE FXCQ80MVE FXCQ125MVE MODEL FXZQ20M7V1B FXZQ25M7V1B FXZQ32M7V1B FXZQ40M7V1B FXZQ50M7V1B
Power supply 1 phase, 220-240 V, 50 Hz
Power supply 1 phase, 220-240 V, 50 Hz
Cooling capacity RT 0.7/0.6 0.8/0.8 1.1/1.0 1.3/1.3 1.6/1.6
Cooling capacity RT 0.7/0.6 0.8/0.8 1.1/1.0 1.3/1.3 1.6/1.6 2.1/2.0 2.6/2.6 4.1/4.0 (*1)/(*2)
(*1)/(*2) Btu/h 7,800/7,500 9,900/9,600 12,600/12,300 16,000/15,400 19,800/19,100
Btu/h 7,800/7,500 9,900/9,600 12,600/12,300 16,000/15,400 19,800/19,100 24,900/24,200 31,700/30,700 49,500/47,800
kcal/h 2,000/1,900 2,500/2,400 3,200/3,100 4,000/3,900 5,000/4,800
kcal/h 2,000/1,900 2,500/2,400 3,200/3,100 4,000/3,900 5,000/4,800 6,300/6,100 8,000/7,700 12,500/12,000 kW 2.3/2.2 2.9/2.8 3.7/3.6 4.7/4.5 5.8/5.6
kW 2.3/2.2 2.9/2.8 3.7/3.6 4.7/4.5 5.8/5.6 7.3/7.1 9.3/9.0 14.5/14.0 RT
Heating capacity 0.7 0.9 1.1 1.4 1.8
Heating capacity RT 0.7 0.9 1.1 1.4 1.8 2.3 2.8 4.5 (*3) Btu/h 8,500 10,900 13,600 17,100 21,500
(*3)
Btu/h 8,500 10,900 13,600 17,100 21,500 27,300 34,100 54,600 kcal/h 2,200 2,800 3,400 4,300 5,400
kcal/h 2,200 2,800 3,400 4,300 5,400 6,900 8,600 13,800 kW 2.5 3.2 4.0 5.0 6.3
kW 2.5 3.2 4.0 5.0 6.3 8.0 10.0 16.0 Casing Galvanized steel plate
Casing Galvanized steel plate Air flow rate (Hi/Lo) m3/min 50Hz 9/7 9/7 9.5/7.5 11/8 14/10
cfm 50Hz 318/247 318/247 335/265 388/282 494/353
Air flow rate (Hi/Lo) m /min
3
7/5 9/6.5 9/6.5 12/9 12/9 16.5/13 26/21 33/25
Sound level (Hi/Lo) dB(A) 240V 32/26 32/26 34/28 37/29 42/35
cfm 247/177 318/230 318/230 424/318 424/318 582/459 918/741 1,165/883
Dimensions (HX WX D) mm 260X 575X 575
Sound level (Hi/Lo) dB 50 Hz/60 Hz 220V 32/27 34/28 34/28 34/29 34/29 37/32 39/34 44/38
Machine weight kg 18
(A) 50 Hz 240V 34/29 36/30 36/30 37/32 37/32 39/34 41/36 46/40
Piping connections Liquid(Flare)mm 6.4 6.4 6.4 6.4 6.4
Dimensions (HX WX D) mm 305X775X600 305X775X600 305X775X600 305X990X600 305X990X600 305X1,175X600 305X1,665X600 305X1,665X600
Gas(Flare)mm 12.7 12.7 12.7 12.7 12.7
Machine weight kg 26.0 26.0 26.0 31.0 32.0 35.0 47.0 48.0
Drain piping VP20 (External Dia, 26/Internal Dia, 20)
Piping connections Liquid(Flare)mm 6.4 6.4 6.4 6.4 6.4 9.5 9.5 9.5 Panel (Option) Model BYFQ60B7W1
Gas(Flare)mm 12.7 12.7 12.7 12.7 12.7 15.9 15.9 15.9 Colour White (6.5Y9.5/0.5)
Drain piping VP25 (External Dia, 32/Internal Dia, 25) Dimensions mm 55X 700X 700 55X 700X 700 55X 700X 700 55X 700X 700 55X 700X 700
(HX WX D)
Panel(Option) Model BYBC32G-W1 BYBC50G-W1 BYBC63G-W1 BYBC125G-W1 weight kg 2.7 2.7 2.7 2.7 2.7
kW 2.9/2.8 3.7/3.6 4.7/4.5 5.8/5.6 7.3/7.1 9.3/9.0 11.6/11.2 14.5/14.0 kcal/h 2,800 3,400 4,300 6,900
kW 3.2 4.0 5.0 8.0
Heating capacity RT 0.9 1.1 1.4 1.8 2.3 2.8 3.6 4.5
(*3) Casing Galvanized steel plate
Btu/h 10,900 13,600 17,100 21,500 27,300 34,100 42,700 54,600
Air flow rate (Hi/Lo) m3/min 50 Hz 11/9 11/9 13/10 18/15
kcal/h 2,800 3,400 4,300 5,400 6,900 8,600 10,800 13,800
cfm 50 Hz 388/318 388/318 459/353 635/530
kW 3.2 4.0 5.0 6.3 8.0 10.0 12.5 16.0
Sound level (Hi/Lo) dB 50 Hz/60 Hz 220V 38/33 38/33 40/34 42/37
Casing Galvanized steel plate (A) 50 Hz 240V 40/35 40/35 42/36 44/39
Air flow rate (Hi/Lo) m3/min 13/10 13/10 15/11 16/11 18.5/14 20/15 26/21 30/24 Dimensions (HX WX D) mm 215X 1,110X 710 215X 1,110X 710 215X 1,110X 710 215X 1,310X 710
cfm 459/353 459/353 530/388 565/388 653/494 706/530 918/741 1,059/847 Machine weight kg 31.0 31.0 31.0 34.0
Sound level (Hi/Lo) dB(A) 30/27 30/27 31/27 32/27 33(34) /28 36/31 39/33 42(43) /36 Piping connections Liquid(Flare)mm 6.4 6.4 6.4 9.5
Gas(Flare)mm 12.7 12.7 12.7 15.9
Dimensions (HX WX D) mm 246X 840X 840 246X 840X 840 246X 840X 840 246X 840X 840 246X 840X 840 246X 840X 840 288X 840X 840 288X 840X 840
Drain piping VP25 (External Dia, 32/Internal Dia, 25)
Machine weight kg 24.0 24.0 24.0 24.0 25.0 25.0 29.0 29.0
Panel (Option) Model BYK45FJW1 BYK71FJW1
Piping connections Liquid(Flare)mm 6.4 6.4 6.4 6.4 9.5 9.5 9.5 9.5 Colour White (10Y9/0.5)
Gas(Flare)mm 12.7 12.7 12.7 12.7 15.9 15.9 15.9 15.9 Dimensions mm 70X 1,240X 800 70X 1,240X 800 70X 1,240X 800 70X 1,440X 800
(HX WX D)
Drain piping VP25 (External Dia, 32/Internal Dia, 25) weight kg 8.5 8.5 8.5 9.5
Panel(Option) Model BYCP125D-W1 Note : Specifications are based on the following conditions;
Conversion rates •Cooling : (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35.0°CDB. (*2) Indoor temp. of 27°CDB, 19.0°CWB, and outdoor temp. of 35.0°CDB.
Colour White (10Y9/0.5) •Heating : (*3) Indoor temp. of 20°CDB, 7.0°CDB and outdoor temp. of 6°CWB.
kcal/h = kW x 860 • Equivalent piping length : 7.5m
Dimensions mm 45X 950X 950 45X 950X 950 45X 950X 950 45X 950X 950 45X 950X 950 45X 950X 950 45X 950X 950 45X 950X 950 Btu/h = kW x 3412 • Level difference : 0m
(HX WX D) RT = kW x 0.284 • Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See ENGINEERING DATA for details.)
weight kg 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 cfm = m3/min x 35.3 • Sound level (FXZQ-M) Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit center.
Note : Specifications are based on the following conditions; (FXKQ-MA) Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.
Conversion rates •Cooling : (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35.0°CDB. (*2) Indoor temp. of 27°CDB, 19.0°CWB, and outdoor temp. of 35.0°CDB. During actual operation, these values are normally somewhat higher as a result of ambient conditions.
•Heating : (*3) Indoor temp. of 20°CDB, 7.0°CDB and outdoor temp. of 6°CWB.
kcal/h = kW x 860 •Equivalent piping length : 7.5m
Btu/h = kW x 3412 •Level difference : 0m
RT = kW x 0.284 •Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See ENGINEERING DATA for detail.)
cfm = m3/min x 35.3 •Sound level : Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit center.
27 During actual operation, these values are normally somewhat higher as a result of ambient conditions. 28
: The values of Hi mode Sound level represent those during cooling operation.Those during heating operation are shown in brackets for two models only.
SPECIFICATIONS
INDOOR UNIT S INDOOR UNIT S
S lim C e ilin g M o u n te d D u c t T y p e C e ilin g M o u n t e d B u ilt - in T y p e
with
drain-up pump FXDQ20PVE FXDQ25PVE FXDQ32PVE MODEL FXSQ20MVE FXSQ25MVE FXSQ32MVE FXSQ40MVE FXSQ50MVE FXSQ63MVE FXSQ80MVE FXSQ100MVE FXSQ125MVE
MODEL without
FXDQ20PVET FXDQ25PVET FXDQ32PVET Power supply 1 phase, 220-240 V, 50 Hz
drain-up pump
Cooling capacity RT 0.7/0.6 0.8/0.8 1.1/1.0 1.3/1.3 1.6/1.6 2.1/2.0 2.6/2.6 3.3/3.2 4.1/4.0
Power supply 1 phase, 220-240 V, 50 Hz (*1)/(*2)
Btu/h 7,800/7,500 9,900/9,600 12,600/12,300 16,000/15,400 19,800/19,100 24,900/24,200 31,700/30,700 39,600/38,200 49,500/47,800
Cooling capacity RT 0.7/0.6 0.8/0.8 1.1/1.0 kcal/h 2,000/1,900 2,500/2,400 3,200/3,100 4,000/3,900 5,000/4,800 6,300/6,100 8,000/7,700 10,000/9,600 12,500/12,000
(*1)/(*2)
Btu/h 7,800/7,500 9,900/9,600 12,600/12,300 kW 2.3/2.2 2.9/2.8 3.7/3.6 4.7/4.5 5.8/5.6 7.3/7.1 9.3/9.0 11.6/11.2 14.5/14.0
kcal/h 2,000/1,900 2,500/2,400 3,200/3,100 Heating capacity RT 0.7 0.9 1.1 1.4 1.8 2.3 2.8 3.6 4.5
(*3)
Btu/h 8,500 10,900 13,600 17,100 21,500 27,300 34,100 42,700 54,600
kW 2.3/2.2 2.9/2.8 3.7/3.6
kcal/h 2,200 2,800 3,400 4,300 5,400 6,900 8,600 10,800 13,800
Heating capacity RT 0.7 0.9 1.1
(*3) kW 2.5 3.2 4.0 5.0 6.3 8.0 10.0 12.5 16.0
Btu/h 8,500 10,900 13,600 Casing Galvanized steel plate
kcal/h 2,200 2,800 3,400 Air flow rate (Hi/Lo) m3/min 50 Hz 9/6.5 9/6.5 9.5/7 11.5/9 15/11 21/15.5 27/21.5 28/22 38/28
kW 2.5 3.2 4.0 cfm 50 Hz 318/230 318/230 335/247 406/318 530/388 741/547 953/759 988/777 1,341/988
Casing Galvanized steel plate External static pressure Pa 50 Hz 88-39-20 1 88-39-20 1 64-39-15 1 88-49-20 1 88-59-29 1 88-49-20 1 113-82 2 107-75 2 78-39 2
Air flow rate (Hi/Lo) m3/min 8.0/6.4 8.0/6.4 8.0/6.4 Sound level (Hi/Lo) dB 220V 37/32 37/32 38/32 38/32 41/36 42/35 43/37 43/37 46/41
50 Hz
(A) 240V 39/34 39/34 40/34 40/34 43/38 44/37 45/39 45/39 48/43
cfm 282/226 282/226 282/226
Dimensions(HX WX D) mm 300X550X800 300X550X800 300X550X800 300X700X800 300X700X800 300X1,000X800 300X1,400X800 300X1,400X800 300X1,400X800
External static pressure Pa 30-10 1
Machine weight kg 30.0 30.0 30.0 30.0 31.0 41.0 51.0 51.0 52.0
Sound level (Hi/Lo) 2 3 dB(A) 33/29 33/29 33/29
Piping connections Liquid(Flare)mm 6.4 6.4 6.4 6.4 6.4 9.5 9.5 9.5 9.5
Dimensions(HX WX D) mm 200X 700X 620 200X 700X 620 200X 700X 620
Gas(Flare)mm 12.7 12.7 12.7 12.7 12.7 15.9 15.9 15.9 15.9
Machine weight kg 23.0 23.0 23.0 Drain piping VP25 (External Dia, 32/Internal Dia, 25)
Piping connections Liquid(Flare)mm 6.4 6.4 6.4 Panel(Option) Model BYBS32DJW1 BYBS32DJW1 BYBS32DJW1 BYBS45DJW1 BYBS45DJW1 BYBS71DJW1 BYBS125DJW1 BYBS125DJW1 BYBS125DJW1
Gas(Flare)mm 12.7 12.7 12.7 Colour White (10Y9/0.5)
Drain piping VP20 (External Dia, 26/Internal Dia, 20) Dimensions mm 55X650X 500 55X650X 500 55X650X 500 55X800X 500 55X800X 500 55X1,100X500 55X1,500X500 55X1,500X500 55X1,500X500
(HX WX D)
weight kg 3.0 3.0 3.0 3.5 3.5 4.5 6.5 6.5 6.5
29 30
SPECIFICATIONS
INDOOR UNIT S INDOOR UNIT S
31 32
SPECIFICATIONS
INDOOR UNIT S OUT DOOR UNIT S
kcal/h = kW x 860
Btu/h = kW x 3412
RT = kW x 0.284
cfm = m3/min x 35.3
33 34
OPTION LIST
INDOOR UNIT S INDOOR UNIT S
C e ilin g m o u n te d c a s s e tte c o r n e r ty p e W a ll m o u n t e d t y p e
No. Type FXKQ25MA,FXKQ32MA,FXKQ40MA FXKQ63MA Type FXAQ20MA
Item No. FXAQ25MA FXAQ32MA FXAQ40MA FXAQ50MA FXAQ63MA
Decoration Panel BYK45FJW1 BYK71FJW1
Item
1 Panel related 1 Drain pump kit K-KDU572CVE
Panel Spacer KPBJ52F56W KPBJ52F80W
Long life replacement filter KAFJ521F56 KAFJ521F80
Air inlet and air
Air discharge grille K-HV7AW K-HV9AW
2 discharge outlet
Air discharge blind panel KDBJ52F56W KDBJ52F80W
F lo o r s t a n d in g ty p e
related
Flexible duct (with shutter) KFDJ52FA56 KFDJ52FA80 No. Type FXLQ20MA FXLQ25MA FXLQ32MA FXLQ40MA FXLQ50MA FXLQ63MA
Item
1 Long life replacement filter KAFJ361K28 KAFJ361K45 KAFJ361K71
S lim c e ilin g m o u n te d d u c t ty p e (70 0 mm w id t h t y p e 1)
No.
Type C o n c e a le d f lo o r s t a n d in g ty p e
FXDQ20P,FXDQ25P,FXDQ32P
Item Type FXNQ20MA FXNQ25MA FXNQ32MA FXNQ40MA FXNQ50MA FXNQ63MA
No. Item
1 Insulation kit for high humidity KDT25N32
Note: 1 For without drain-up pump type only. 1 Long life replacement filter KAFJ361K28 KAFJ361K45 KAFJ361K71
S lim c e ilin g m o u n te d d u c t ty p e ( 9 0 0 / 1, 10 0 mm w id t h t y p e 1)
C e ilin g s u s p e n d e d c a s s e tte ty p e
Type
No. FXDQ20N, FXDQ25N, FXDQ32N, FXDQ40N, FXDQ50N FXDQ63N No.
Type
FXUQ71MAV1 FXUQ100MAV1 FXUQ125MAV1
Item Item
1 Insulation kit for high humidity KDT25N50 KDT25N63 1 Replacement long-life filter KAFJ495F140
Note: 1 For without drain-up pump type only. 2 Sealing member of air discharge outlet (*1) KDBHJ49F80 KDBHJ49F140
3 Decoration panel for air discharge KDBTJ49F80 KDBTJ49F140
4 Vertical flap kit KDGJ49F80 KDGJ49F140
5 L-shape piping kit KHFP49M140
Note: (*1): This option is necessary for setting up 2-way (opposing directional) air flow when the air conditioner is installed.
35 36
OPTION LIST
OUT DOOR UNIT S C ONT R OL S Y S T E M S
H e a t p u m p ty p e S y s te m c o n f ig u r a t io n
No. Part name Model No. Function
No. RXYMQ6PV4A
Note 2,
1 Central remote controller DCS302CA61
1 Cool/Heat Selector KRC19-26A •Up to 64 groups of indoor units(128 units) can be connected, and ON/OFF, temperature setting and
monitoring can be accomplished individually or simultaneously. Connectable up to 2 controllers in one
1-1 Fixing Box KJB111A system.
1-1 Electrical box with earth terminal (3 blocks) KJB311A
KHRP26M22H (Max. 4 branch) Note 2
2 REFNET Header 2 Unified ON/OFF controller
DCS301BA61
KHRP26M33H (Max. 8 branch) •Up to 16 groups of indoor units(128 units) can be turned, ON/OFF individually or simultaneously, and
2-1 Electrical box with earth terminal (2 blocks) KJB212A operation and malfunction can be displayed. Can be used in combination with up to 8 controllers.
3 REFNET Joint KHRP26M22T
2-1 Noise filter (for electromagnetic interface use only) KEK26-1
4 Central drain plug KKPJ5F180 3 Schedule timer
Note 2 •Programmed time weekly schedule can be controlled by unified control for up to 64 groups of indoor units
DST301BA61 (128 units). Can turn units ON/OFF twice per day.
5 Fixture for preventing overturning KPT-60B160
4 Interface adaptor for SkyAir-series For SkyAir, FD(Y)M-FA, FDY-KA
6 Wire fixture for preventing overturning K-KYZP15C DTA102A52 •Adaptors required to connect products other than those of the VRV System to the high-speed DIII-NET
FDYB-KA, FDY-KA, FVY(P)J-A
communication system adopted for the VRV System.
5 Central control adaptor kit For UAT(Y)-K(A),FD-K DTA107A55
* To us e any of the above optional c ontrollers , an appropriate adaptor mus t be ins talled on the
produc t unit to be c ontrolled.
6 Wiring adaptor for other air-conditioner DTA103A51
C ONT R OL S Y S T E M S 2. For FXUQ-MAV1, an interface adaptor (DTA102A52) for the SkyAir series is necessary.
O p e r a t io n c o n t r o l s y s t e m o p t io n a l a c c e s s o r ie s
No.
Type
FXCQ-M FXFQ-M FXZQ-M FXKQ-MA FXDQ-P FXSQ-M FXMQ-MA FXHQ-MA FXAQ-MA FXLQ-MA FXUQ-MA
B u ild in g m a n a g e m e n t s y s te m
Item FXDQ-N(A) FXNQ-MA
No. Part name Model No. Function
Wireless H/P BRC7C62 BRC7E61W BRC7E61W BRC4C61 BRC4C62 BRC4C62 BRC4C62 BRC7E63W BRC7E618 BRC4C62 BRC7C528W 1 Basic Hardware intelligent Touch Controller DCS601C51 •Air-Conditioning management system that can be controlled by a compact all-in-one unit.
1 Remote controller
Wired BRC1C62 1-1 intelligent Touch Hardware DIII-NET plus adaptor DCS601A52 •Additional 64 groups (10 outdoor units) is possible.
2 Wired remote controller with weekly schedule timer BRC1D61 1-2 Controller Option Software P. P. D. DCS002C51 •P. P. D.: Power Proportional Distribution function
3 Simplified remote controller (Exposed type) — BRC2C51 — BRC2C51 — 1-1
1-3 Web DCS004A51 •Monitors and controls the air conditioning system using the Internet and a Web browser application on a PC.
4 Remote controller for hotel use (Concealed type) — BRC3A61 — BRC3A61 — 1-4 Electrical box with earth terminal (4 blocks) KJB411A •Wall embedded switch box.
5 Adaptor for wiring KRP1B61 KRP1B59 KRP1B57 KRP1B61 KRP1B56 KRP1B61 KRP1B3 — KRP1B61 — 128 units DAM602B52
6-1 Wiring adaptor for electrical appendices (1) KRP2A61 KRP2A62 KRP2A61 KRP2A53 KRP2A61 KRP2A62 KRP2A61 KRP2A61 KRP2A62 256 units DAM602B51
Number of
6-2 Wiring adaptor for electrical appendices (2) KRP4A51 KRP4A53 KRP4A51 KRP4A54 KRP4A51 KRP4A52 KRP4A51 KRP4A51 KRP4A53 2 Basic Hardware units to be 512 units DAM602B51x 2 •Air conditioner management system that can be controlled by personal computers.
connected
7 Remote sensor KRCS01-1 — KRCS01-1 768 units DAM602B51x 3
Note 2,3 Note 2,3 Note 4,6 Note 4,6 Note 5 Note 3 Note 2,3 intelligent Manager III 1024 units DAM602B51x 4
8 Installation box for adaptor PCB KRP1B96 KRP1D98 KRP1B101 — KRP1B101 KRP4A91 — KRP1C93 KRP4A93 — KRP1B97
2-1 P.P.D. DAM002A51 •Power Proportional Distribution function
External control adaptor for outdoor unit —
9 (Must be installed on indoor units) DTA104A61 DTA104A62 DTA104A61 DTA104A53 DTA104A61 DTA104A62 DTA104A61 DTA104A61
2-2 Option Software Web DAM004A51 •Monitors and controls the air conditioning system using the Internet and a Web browser application on a PC.
Note: 1. Installation box is necessary for each adaptor marked . 4. Up to 2 installation boxes can be installed for each indoor unit.
2. Up to 2 adaptors can be fixed for each installation box. 5. Installation box is necessary for second adaptor. 2-3 Eco DAM003A51 •ECO (Energy saving functions.)
3. Only one installation box can be installed for each indoor unit. 6. Installation box is necessary for each adaptor.
2-4 Optional DIII Ai unit DAM101A51 •External temperature sensor for intelligent Manager.
2-5 Di unit DEC101A51 •8 pairs based on a pair of On/Off input and abnormality input.
2-6 Dio unit DEC102A51 •4 pairs based on a pair of On/Off input and abnormality input.
•Interface unit to allow communications between VRV and BMS. Operation and monitoring of air-
Communication line
3 *1 Interface for use in BACnet ®
DMS502A51 conditioning systems through BACnet communication.
®
•Expansion kit, installed on DMS502A51, to provide 3 more DIII-NET communication ports. Not usable
3-1 Optional DIII board DAM411A1 independently.
•Expansion kit, installed on DMS502A51, to provide 16 more wattmeter pulse input points. Not usable
3-2 Optional Di board DAM412A1 independently.
•Interface unit to allow communications between VRV and BMS. Operation and monitoring of air-
4 *2 Interface for use in LONWORKS ®
DMS504B51 conditioning systems through LONWORKS communication.
®
5 Parallel interface DPF201A51 •Enables ON/OFF command, operation and display of malfunction; can be used in combination with up to
Basic unit 4 units.
Contact/analog
6 Temperature DPF201A52 •Enables temperature measurement output for 4 groups; 0-5VDC.
measurement units
signal
7 Temperature DPF201A53 •Enables temperature setting input for 16 groups; 0-5VDC.
setting units
8 Unification adaptor for DCS302A52 •Interface between the central monitoring board and central control units.
computerized control
Note : *1. BACnet is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).
®
37 38