Beruflich Dokumente
Kultur Dokumente
1
and its Jacobian Dz F jo has a zero eigenvalue (or zero singu- Vl
2
theory [13]. The ATC is then formally dened here as the dif-
k m ference on active power
owing into a system area between
C
the base case and the voltage collapse (saddle-node bifurca-
I
tion) point for a given generation and load pattern. Thus,
L to compute the ATC value, one has to rst dene the power
transaction to be studied, i.e., the generation and load pattern,
and then determine the voltage collapse point using any of the
Zero Switching
Crossing Logic
techniques developed to calculate this point; in this paper, the
continuation method is used to determine this point, as de-
Magnitude
scribed in detailed in [13]. If there is no bifurcation point for
the system under analysis, as in the case of the Italian System
I ref α
with voltage dependent load model, the ATC will be dened
as the maximum change in area power
ow.
Controller
Fig. 2. Basic TCSC structure. A detailed description of the techniques used to determine
the optimal location and size of the FACTS controllers to max-
imize the ATC dened in this paper follows.
connected in series with a transmission line [10]. Due to the se- A. Bifurcation-based Tools
ries connection, there is no need in this case for a transformer
bank to change the controller voltages. Figure 2 depicts the In [5], the author studies in detail the eect of the control-
typical basic structure and control strategy of this controller. lable parameters p on the bifurcation behavior of equations
The device is usually designed to directly control line cur- (1), proposing a series of numerical techniques to compute
rents, but various other strategies can be used to control line the optimal values of p that maximize the \distance" to a bi-
impedance or power
ows, damp oscillations, etc. furcation point. The paper demonstrates the advantages of
The limits on the ring angle for the TCSC controller are maximizing this distance from the point of view of system
dierent than the ones used for the SVC, as there is a reso- stability, since the system becomes generally \more stable" as
nance region where the controller becomes an open circuit and, the distance to a bifurcation point is increased. In [8], the
hence, it must be avoided in a series connection. Furthermore, authors use these basic concepts and some of the related nu-
the controller is designed to mainly operate in the capacitive merical techniques to design FACTS controllers to maximize
region in steady state, to reduce harmonic pollution of the cur- the system distance to collapse, and hence improve system
rent waveforms. Thus, for this paper, r < < 180 , where stability.
r corresponds to the resonant point (this value depends on The techniques used here to determine the optimal location
the ratio XC =XL ). and size of SVCs and TCSCs to increase ATC are based on
The following fundamental frequency, steady state model the methodologies proposed in [8], and are summarized below.
proposed in [8] is used here to model this controller: The original techniques are based on determining a saddle-
P + Vk Vm Be sin(k , m ) = 0 (4) node bifurcation point; however, in the current paper these are
modied to consider systems that do not present a bifurcation
,Vk2 Be + Vk Vm Be cos (k , m ) , Qk = 0 point and only have a maximum area power transfer point,
,Vm2 Be + Vk Vm Be cos(k , m ) , Qm = 0 which is dened here as the ATC point.
,
Be , kx4 , 2kx2 + 1 cos kx ( , )= 1. For the given generation and load pattern, determine the
,
XC kx4 cos kx ( , ) collapse or bifurcation point. If there is no bifurcation
, cos kx ( , ) , 2 kx4 cos kx ( , ) point, determine the maximum area power transfer equi-
librium point. Either one of these equilibrium points
+2 kx cos kx ( , ) , kx4 sin 2 cos kx ( , )
2
yields the desired ATC value, and is referred to as the
+kx sin 2 cos kx ( , ) , 4 kx3 cos2 sin kx ( , )
2 ATC point in this paper.
,4 kx2 cos sin cos kx ( , ) = 0 2. The largest entries corresponding to bus voltage mag-
p
P 2 + Q2k , I Vk = 0 nitudes in the \zero" right eigenvector at the collapse
point can then be used to pinpoint the buses or area
where Vk 6 k and Vm 6 m are the terminal phasor voltages of where SVCs may be located to have the most eect on
the controller; Qk and Qm are the reactive power injections at distance to collapse. For systems without bifurcation,
both controller terminals; P and I are the active power and use the maximum voltage entries in the tangent vector,
current
owing through the controller, respectively; Be is the i.e., dx=djo in equations (2), at the corresponding ATC
equivalent susceptance of the TCR-xed-capacitor combina- point.
tion; XC and XL are the p fundamental frequency reactances
of C and L; and kx = XC =XL . By xing the value of one 3. The lines that present the largest change in power
ow
of the controller variables, one can model dierent types of between the base case and the ATC point are considered
controls; for example, by dening the value of I , equations to be the best candidates for placing TCSC controllers.
(4) can be used to simulate a TCSC controller operating in 4. Determine the manifold of ATC points with respect to
current control (droop could be also included). the controllable parameters p. The simplest way of ob-
taining this manifold is to continuously vary p and com-
III. Analysis Techniques pute the corresponding collapse or ATC points; however,
more ecient continuation techniques may be used here
As previously discussed, the denition of ATC used in this as proposed in [5].
paper, for the purpose of designing FACTS controllers to
\maximize" system transfer capability, is based on basic volt- 5. To determine the \optimal" controller size from the ATC
age collapse concepts that are in turn grounded on bifurcation point of view, one should dene a cost function that takes
3
into account the change on the ATC (ATC ) due to the where the three dimensional array H is the Hessian of equa-
controller and the cost of this controller. In the case of tions (2) evaluated at zo , i.e., H = Dz2 F jo , or of an appropriate
the SVC, the controller size (the size of the TCR and ca- subset of equations. A change in the rth singular value of J
pacitor bank), and hence its cost, is dened in terms of its following a change p on the controllable system parameters
reactive power rating, whereas for the TCSC the size is p may be determined by
dened by the impedance of the corresponding transmis-
r = , U T H J ,1 p V rr
sion line and the desired compensation levels. Thus, the
controller cost functions used in this paper are dened as In particular, for the minimum singular value,
ATC [MW] min = cT p
fSV C = QSV C [Mvar] (5)
where ,
fTCSC = ATC [MW] (6) cT = ,v1T uT1 H J ,1 Jp
X [%]e and Jp = DpF jo in (2). To evaluate the sensitivities of the
The optimal SVC and TCSC controllers would be the minimum singular value with respect to power injections in the
ones that maximize functions (5) and (6), respectively. load
ow equations, Jp becomes the unit matrix. On the other
hand, if p corresponds to a branch admittance used to evaluate
6. The SVC and TCSC XC =XL ratio and control set points, the eect of series compensation in the load
ow equations,
droops and limits are dened based on stability studies; Jp presents four nonzero elements corresponding to the P and
for this paper, typical values are used. Thus, for the SVC, Q mismatch equations at the two buses i and j connected by
a 1 pu set point and a 2 % voltage droop are used here, the branch.
i.e., VREF = 1, and XSL = 0:02 in equations (3); and Since max = 1=min , the change max in the maximum
XL = 0:52XC , so that QSV Cmax ,QSV Cmin . For the singular value max of J ,1 may be computed by
TCSC, typical values of XC =XL = 10 and a 100 % im- max = cTmaxp
pedance compensation at the minimum ring angle min = ,cT max2 p (7)
are assumed here; the value of min is chosen based on
equations (4), so that Xe(min) = Xline ,5XC Equation (7) has been successfully used in [19] to rank con-
tingencies, and is adopted here to evaluate, from the voltage
B. Second Order Sensitivity Analysis collapse point of view, optimal locations of shunt and series
compensation. It is important to mention that the procedure
Alternatively to the methods described above for determin- proposed here to determine the most suitable bus/branch for
ing most suitable buses for the installation of SVCs and the the insertion of SVCs/TCSCs needs neither the denition of
most appropriate branches for placing TCSCs, one may use the collapse point nor the denition of the system load change
second order sensitivities as proposed here. pattern; hence, this technique can be directly applied to the
Since the ATC denition used in this paper is related to case where the system does not present a bifurcation. This is
the maximum power exchange between areas before voltage one of the main advantages of this technique, and has been
collapse occurs, it is reasonable to assess the quality of a can- conrmed in several studies by basically obtaining the same
didate bus/branch by means of voltage collapse related indices results when the sensitivities are computed at the initial load-
or sensitivities. Thus, using the ideas proposed in [9, 18], one ing conditions as when these are computed at the collapse
can readily determine the sensitivities of a voltage collapse in- point. The reason for this is that second order information
dex based on singular values with respect to various system regarding the system behavior is included in the analysis.
parameters, which in this case are the reactive power injections
(SVC) and the branch admittances (TCSC). This voltage col-
lapse index is specically dened as the minimum singular IV. Results
value of the Jacobian J = Dz F jo of equations (2), or of an All results presented in this paper were obtained for the
appropriate subset of equations like the load
ow equations; Italian power system depicted in Fig. 3. The network under
the corresponding sensitivities contain second order informa- examination corresponds to the ENEL transmission system in
tion, as these are determined based on the system Hessian, as its interconnected operation with the European System, and
described below. is modeled with about 700 buses, 1100 branches, 123 hydro-
As it is well known, the Singular Value Decomposition units and 109 thermal-units. The system data used here cor-
(SVD) of a matrix J is given by responds to the scenario before the blackout that stroke south-
n
X ern Italy in August 1994, characterized by a low load level and
J = U V T = i ui viT a large number of 380 kV lines both in maintenance and out
i=1 of service to avoid over-voltages. In particular, the intercon-
nection between the northern and the southern (Naples De-
where U and V are orthonormal matrices (u and v are the left partment) parts of the system was ensured by two of the four
and right singular vectors respectively), and is a diagonal 380 kV lines available (Valmontone-Presenzano and Villanova-
matrix whose elements i are the singular values of J , ordered Larino-Foggia) and by a single 220 kV line (Popoli-Capriati),
in ascending order. as illustrated in Fig. 4; the blackout took place when one of
Based on the concepts presented in [18], it is possible to the two 380 kV line tripped out (line Valmontone-Presenzano).
determine the in
uence of any control parameter p on the The total load on the system before the black out was 81700
minimum singular value min of J (or on the maximum sin- MW (including the UCPTE equivalent); the load on the Ital-
gular value max of J ,1 ). Thus, following a change z about ian system itself was 24000 MW/8200 Mvar.
a given equilibrium point zo , the new Jacobian J 0 may be The load for this system is modeled as follows:
approximated by PL = (Po + P )V a (8)
J 0 = J (zo + z ) J + H z QL = (Qo + Q )V b
4
where Po and Qo stand for the base system load; P and Q
represent the load variation as dened by the non-controllable
parameter (loading factor); and a and b dene the voltage
dependency of the load. Thus, a = b = 0 for constant PQ
loads, whereas, for voltage dependent loads, the values a = 1
and b = 2:5 are chosen, as these values have been successfully
used to represented the Italian system load in contingency
studies. The ATC cases studied in this case correspond to the
power transfer from the north and central parts of the Italian
system to the southern part of the network, which corresponds
to the main power corridor in this system. Thus, the following
realistic load and generation patterns are assumed:
All generators in the Milano, Torino, Venezia, Firenze
and Roma areas (north and central Italy) are assumed to
supply for the load changes; the European system does
not supply power for these changes.
The load is assumed to only increase in the Naples (70%)
and Palermo (30 %) areas for constant PQ loads. For
voltage dependent loads, only the loads in the Naples
Department are increased.
All Q and S limits on generators as well as limits on the
SVC and TCSC controllers were enforced for the ATC com-
putations in all cases. On the other hand, bus voltage and
current limits were only monitored and not strictly enforced,
as some of these limits overly constrained the transmission
system voltages and currents, yielding rather conservative re-
sults.
A. Constant PQ Loads
Fig. 3. The Italian system.
Figure 5 depicts the bifurcation diagram or PV curves for
the test system using constant PQ loads. Three bus voltages
are shown together with their corresponding voltage limits;
these buses belong to the Naples and Rome areas, which un-
dergo the largest voltage changes in the system. Observe that
the voltages exceed their limits; however, as indicated before,
these limits are not strictly enforced but only monitored. The
system presents a collapse point at the maximum value of ,
which corresponds to a maximum total loading condition of
82225 MW and an ATC of 528 MW; for this kind of load
model, the value of can be directly associated to the total
MW loading. It is interesting to notice that the maximum
power transfer to the Naples area, which does not correspond
to the ATC in this case, does not occur at the collapse or
maximum loading point, but on the lower (\unstable") side of
the bifurcation diagram.
The collapse in this case is actually due to one of the gen-
erators in the Naples area reaching an Smax limit [16]. How-
ever, the eigenvectors and singular vectors associated to the
smallest real eigenvalue and singular values can still be used
in this case to determine the optimal location of the FACTS
controllers, due to the proximity of this collapse point to a
saddle-node bifurcation (the smallest eigenvalue and singular
value is rather close to zero). Thus, Fig. 6 depicts the relative
sensitivities of the most signicant buses obtained from (a)
the bus voltage entries in the \zero" right eigenvector, and
(b) the singular value second order sensitivities to changes in
the reactive power bus injections computed using (7). From
these two graphs, one can rst observe that both techniques
point to similar system buses, all belonging to approximately
Fig. 4. Main transmission lines feeding the Naples Department. the same geographical area, as possible candidates to place
a SVC to have the most eect on the distance to collapse.
Based on these sensitivity values and the voltage levels of the
candidate buses, for both load models, the most adequate bus
is determined to be Popoli (220 kV); placing an SVC on any
5
700
450
400 650
350
600
ATC & PL max
Garigliano
MW
V [kV]
Naples Pmax
300 Larino
Capriati
550
500
200
450
150 0 50 100 150 200 250 300 350 400 450
8.17 8.18 8.19 8.2 8.21 8.22 8.23 Qsvc [Mvar]
Loading [MW]
(a)
4
x 10
Max. Load/Qsvc
ATC/Qsvc
1.02 0.5
1 PQ load
Relative V-entries
0.98 V load
Zero E-vector
0.48
0.96
0.94
0.92 0.46
MW/Mvar
0.9
0.88 0.44
0.86
0.84
POPOLI
PRESENZANO
GARIGLIANO
CAPRIATI
LATINA
0.42
0.4
0.38
50 100 150 200 250 300 350 400 450
Qsvc [Mvar]
Buses
(b)
(a) 450
1.2
PQ load V load
400
1
0.8
Sensitivities
350
0.6
ATC & PL max
Garigliano
V [kV]
LATINA
PRESENZANO
POPOLI
VILLANOVA
200
150
8.17 8.18 8.19 8.2 8.21 8.22 8.23 8.24
Buses Loading [MW] x 10
4
(b) (c)
Fig. 6. Normalized bus sensitivities for SVC placement: (a) \zero" Fig. 7. Results for constant PQ load and SVC at Popoli: (a)
right eigenvector analysis; (b) second order sensitivity analysis of maximum loadability and ATC versus SVC rating; (b) optimal
singular values at initial loading conditions. SVC rating computation; (c) voltage proles for optimal SVC
(QSV C = 320 Mvar).
6
7.5
1.2
PQ load Max. Load Diff./Comp.
1 ATC/Comp.
Relative DPij
V load
0.8 7
0.6
0.4
6.5
0.2
MW/%
0
VILLANOVA
VALMONTONE
MARTIGNONE
BARGI STAZ 2
BARGI STAZ 2
PRESENZANO
PRESENZANO
LARINO
VALMONTONE
FOGGIA
CALENZANO
GARIGLIANO
ROMA NORD
6
LARINO 5.5
Branches
5
20 30 40 50 60 70 80 90
(a)
1.2 450
1 PQ load
V load
Sensitivities
0.8 400
0.6
0.4 350
ATC & PL max
0.2 Garigliano
Larino
V [kV]
0 300 Capriati
ROMA NORD
VALMONTONE
PRESENZANO
POGGIO A C
VILLANOVA
PRESENZANO
LARINO
VILLANOVA
FOGGIA
VALMONTONE
MONTALTO
GARIGLIANO
MONTALTO
LARINO
250
200
Branches
150
8.17 8.18 8.19 8.2 8.21 8.22 8.23 8.24 8.25 8.26
(b)
Fig. 8. Normalized branch sensitivities for TCSC placement: (a)
relative power
ow changes; (b) second order sensitivity analysis of Fig. 9. Results for constant PQ load and TCSC at Valmontone-
singular values at initial loading conditions. Presenzano: (a) optimal TCSC compensation computation; (b)
voltage proles for optimal compensation (50%).
7
450
the plot of the fSV C cost function seems to suggest that a low
rating SVC (60 Mvar) would be more adequate; however,
400
such a small SVC would produce very little change on the
ATC (less than 30 MW), that it would not be justiable in
350 PL max practice. Figure 11(b) shows the system bifurcation diagram
for the optimal SVC; notice again the improvement on the
voltage proles and the slight increment on the value of at
ATC
300
250
(a) V. Conclusions
450
250
The paper also demonstrates that both rst and second order
200 sensitivity information obtained from collapse studies yield ba-
sically the same results, which can then be used to determine
150 optimal control parameters to improve system operation.
It is important to highlight the fact that all studies pre-
100 sented in this paper are based on steady state techniques, and
no consideration is given here to the dynamic response of the
50 system, which in some cases could also be a determinant factor
7.9 7.95 8 8.05 8.1
Loading [MW]
8.15 8.2 8.25
4
x 10 on the design process of FACTS controllers. Also, the volt-
(b) age dependent representation of loads in the Italian system
require more study, as the operational knowledge of the sys-
Fig. 10. Voltage proles for voltage dependent load model: (a) tem does not seem to match very well with some of the results
bifurcation diagram; (b) maximum loading. The system does not presented in this paper. Nevertheless, the system presented
present a voltage collapse due to bifurcation or control limits. a unique opportunity to develop and test new techniques for
the integral design of FACTS controllers.
B. Voltage Dependent Loads References
Similar studies are carried out for the Italian system us-
ing a voltage dependent load with a = 1 and b = 2:5 in (8), [1] R. P. Klump and T. J. Overbye, \A transmission-based voltage
as previously discussed. Thus, Fig. 10 depicts the (a) bifur- stability measure for available transfer capability (atc) calcu-
cation diagram and (b) PV curves obtained without FACTS lations," Proc. NAPS, MIT, November 1996, pp. 351{357.
controllers in the system. First, observe that the system does [2] C. A. Ayasum and R. Fischl, \On the region-wise analysis of
not present a bifurcation or generator limit (collapse) point, available transfer capability (atc)," Proc. NAPS, Wyoming,
and hence the voltage does not collapse by any of these mecha- October 1997, pp. 464{469.
nisms in this case [11]. Second, the ATC (927 MW), dened as [3] G. Gross, editor, Proc. Workshop on ATC, University of Illi-
the maximum power transferred into the Naples Department, nois, Urbana-Champaign, IL, June 1997.
and the maximum loading (82111 MW) points do not coincide [4] A. R. Bergen, Power Systems Analysis. Prentice-Hall, New
in this case, and hence one can expect signicantly dierent Jersey, 1986.
results when using each of these criteria to select the optimal
controllers, as illustrated below for the SVC controller. [5] C. A. Ca~nizares, \Calculating optimal system parameters to
Based on rst and second order sensitivity analysis results maximize the distance to saddle-node bifurcations," IEEE
depicted in Fig. 6, and the cost function fSV C of equation Trans. Circuits and Systems{I, vol. 45, no. 3, 1998, pp. 225{
(5) depicted in Fig. 11(a), the optimal SVC, from the ATC 237.
point of view, is determined to be a 400 Mvar controller [6] N. G. Hingorani, \Flexible ac transmission systems," IEEE
located at the Popoli bus. In this case, the new ATC is 1080 Spectrum, April 1993, pp. 40{45.
MW, and the maximum loading is 82233 MW. Observe that [7] D. Maratukulam,editor, Proc. FACTS Conference I|The Fu-
a completely dierent SVC rating would be obtained if the ture in High-voltage Transmission, TR-100504, EPRI, March
maximum system loading is used to select the controller. Also, 1992.
8
[8] C. A. Ca~nizares and Z. T. Faur, \Analysis of SVC and TCSC
controllers in voltage collapse," IEEE/PES PE-200-PWRS-0-
0.44
2-1998, accepted for publication in IEEE Trans. Power Sys-
0.42
Max. Load Diff./Qsvc
ATC/Qsvc
tems, March 1998.
[9] A. Berizzi, P. Finazzi, D. Dosi, P. Marannino, and S. Corsi,
0.4 \First and second order methods for voltage collapse assess-
ment and security enhancement," IEEE Trans. Power Sys-
0.38
tems, vol. 13, no. 2, May 1998, pp. 543{551.
0.36 [10] L. Gyugyi, \Power electronics in electric utilities: Static var
compensators," Proceedings of the IEEE, vol. 76, no. 4, April
MW/Mvar
(a) http://www.power.uwaterloo.ca.
450 [14] C. A. Ca~nizares and F. L. Alvarado, \Point of collapse and
continuation methods for large ac/dc systems," IEEE Trans.
Power Systems, vol. 8, no. 1, February 1993, pp. 1{8.
400
[15] I. Dobson, \The irrelevance of load dynamics for the loading
margin to voltage collapse and its sensitivities," pp. 509{518
in [20].
[16] I. Dobson and L. Lu, \Voltage collapse precipitated by the
350
PL max
Larino
I, vol. 39, no. 9, September 1992, pp. 762{766.
300
Capriati
400
Claudio A. Ca~nizares (S'87, M'92) received the Electrical Engi-
neer diploma (1984) from the Escuela Politecnica Nacional (EPN),
350
PL max Quito-Ecuador, where he held dierent positions from 1983 to 1993.
His MS (1988) and PhD (1991) degrees in Electrical Engineering
are from the University of Wisconsin-Madison. Dr. Ca~nizares is
ATC
300
currently an Associate Professor at the University of Waterloo and
his research activities are mostly concentrated in the study of com-
V [kV]
200 Alberto Berizzi (M'93) received his M.Sc. degree (1990) and
his Ph.D. degree (1994) both in Electrical Engineering from the
150 Politecnico di Milano. Since 1992 he is Assistant Professor at the
Garigliano Electrical EngineeringDepartmentof the Politecnico di Milano. His
Larino
areas of research include power system analysis and voltage stability
Capriati
and control.
100