Sie sind auf Seite 1von 43

VESDA ®

When Performance Counts

PA VISION SDN BHD Fire Safety


VESDA®
• Very Early Smoke Detection Apparatus

• Market Leaders In Early Warning Smoke Detection

• Founders of Aspirating Technology as we know it


today. Building Air Sampling Systems for 30 years

• Recognised worldwide as the global benchmark


technology

• Focus on Customer Support & Loss Prevention


Engineering

PA VISION SDN BHD 2 Fire Safety


What is Aspiration Smoke Detection?

PA VISION SDN BHD 3 Fire Safety


What is Aspiration Smoke Detection?

A system which draws air from an area, via a


pipe network, to a central detector which
monitors for small amounts of smoke

PA VISION SDN BHD 4 Fire Safety


VESDA is early warning…..

PA VISION SDN BHD 5 Fire Safety


Features of VESDA

• Absolute smoke detection


– once only calibration
– alarm thresholds set to defined smoke
obscuration levels

• The widest sensitivity range


– 0.005 to 20% Obs/m (0.0015 to 6% Obs/ft)
– alarm threshold setting to suit different
environments (inc AutoLearn)

PA VISION SDN BHD 6 Fire Safety


Features of VESDA

• Dual stage filter technology


– 1st to remove dust from air sample
– 2nd to provide clean air barriers to protect optical
components inside the detector

• Comprehensive Display (LCD & Bar graph)

• High efficiency aspirator

• Intelligent communications (VESDAnet)

PA VISION SDN BHD 7 Fire Safety


VESDAnet

PA VISION SDN BHD 8 Fire Safety


Why use aspiration smoke detection

• Earliest detection - avoid down time


• Avoid unnecessary suppression release
• Extra time is required for safe evacuation
• Smoke is difficult to detect
• Environmentally challenging areas
• Concealed detection is important
• Maintenance access is limited

PA VISION SDN BHD 9 Fire Safety


Earliest detection avoid down time

Critical processes cannot incur disruption or


down time

Telecommunications
Computer rooms
Banking operations
Production facilities

PA VISION SDN BHD 10 Fire Safety


Avoid unnecessary suppression release

Early warning gives time to investigate and


avoid unnecessary suppression release

Telecommunication
Data Centres
Equipment rooms
Electrical sub-stations

PA VISION SDN BHD 11 Fire Safety


Extra time required for evacuation

Environments where rapid exit is impeded

Underground Stations
Theatres
Public buildings
Churches

PA VISION SDN BHD 12 Fire Safety


Smoke is difficult to detect

Environments with high ceilings, high air


flows or vast open areas provide unique
characteristics

Clean rooms
Warehouses
Aircraft hangers
Computer rooms
Atria

PA VISION SDN BHD 13 Fire Safety


Environmentally challenging areas

Aggressive environments with high levels of


pollution or extreme temperature conditions

Cold Stores
Production areas
Paper mills
Underground tunnels
Mines
Industrial Plants

PA VISION SDN BHD 14 Fire Safety


Concealed detection is important

Interiors can not be spoilt by unsightly


conventional detectors

Casinos
Cathedrals
Stately Homes
Museums
Art Galleries
Modern Office Buildings

PA VISION SDN BHD 15 Fire Safety


Maintenance access is limited

Where access to the detection area is difficult

Warehouses
Ceiling voids
Production machinery
EMC Controlled areas

PA VISION SDN BHD 16 Fire Safety


Reference Sites

Telecommunication
Automotive
Wafer Fab
Power Generation
Oil & Gas
Banking
Museum
Library
Hospital
Entertainment

PA VISION SDN BHD 17 Fire Safety


Reference Sites Telecommunication Industry

Telstra Australia
British Telecom
AT&T Worldwide
Bell Corporation
MCI Corporation
Cable and Wireless
New Zealand Telecom
Nippon Telecom
Telekom Malaysia
Singapore Telecom
China Telecom
China Mobile
China Unicom

PA VISION SDN BHD 18 Fire Safety


Reference Sites Automotive Industry

General Motors Corp Various sites


General Motors Holden Adelaide
Toyota Melbourne
Ford Melbourne
Mitsubishi Adelaide
Chrysler Illinois
AC Delco Various sites
Honda Various sites
Saab Sweden
Daihatsu Various sites
Volvo Sweden
Peugeot France
MAN Trucks Germany

PA VISION SDN BHD 19 Fire Safety


Reference Sites Wafer Fab Industry

Singapore SSMC, Charter FAB 3, Charter FAB 7, ST Micro, UMC


Malaysia 1st Silicon, Silterra
Philippines Seagate, Intel, Maxtor and others
UK Hyundai, Intel, Motorola, Phillips, ShinEtsu, NEC
US Wafer Fab RFMD
Taiwan PSMC, TECO, TSMC, UMC, USC, Windbond,
WSMC, Phoenixtec Eng, E-Tron

PA VISION SDN BHD 20 Fire Safety


Reference Sites Power Generation

UK Berkeley Nuclear Power Station


Europe CERN Atomic Particle Accelerator
UK Sellafield Nuclear Power Station
Australia Loy Yang “A” Power Station Coal Fired
Australia Tumut Hydro Power Station
Australia Murray Hydro Power Station
Australia Jeeralang Power Station Gas Fired
Australia Newport Power Station Gas Fired

PA VISION SDN BHD 21 Fire Safety


Reference Sites Oil & Gas Industry

Petronas
British Gas-Transco
Zeneca
ICI Headquarters
British Petroleum HQ
Shell Petroleum (worldwide)
ExxonMobil (worldwide)
BHP

PA VISION SDN BHD 22 Fire Safety


Reference Sites Banking Industry

Hong Kong Shanghai Banking Corporation


Australia and New Zealand Bank (ANZ)
National Australia Bank
Standard Chartered Bank
Treasury Finance Department
Saudi Cairo Bank
Saudi Holland Bank
London Stock Exchange
Commonwealth Bank
Reserve Bank Australia
US Treasury Dept

PA VISION SDN BHD 23 Fire Safety


Reference Sites Library

UK Bristol Library
Spain Colegio Notaris Library Barcelona
Australia Victorian State Library Melbourne
Australia National Library Canberra
Australia Parliament House (old) Archive Library
USA Wilson Library Minnesota
USA Secure Data Services (SDS)Media Lib.

PA VISION SDN BHD 24 Fire Safety


Reference Sites Museums

Shelburne Museum
S.S. Ticonderoga, a National Registered Historic Site
The Isabella Stewart Gardner Museum
The National Gallery Victoria Australia
The National War Museum Canberra Australia
American Museum Planetarium
Aylsebury Museum
Bonneville City Museum
Museum of Scotland

PA VISION SDN BHD 25 Fire Safety


Reference Sites Hospitals & Pharmaceutical

Royal Darwin Hospital


Queen Elizabeth Hospital Adelaide
Royal Melbourne Hospital
All MRI Facilities in Australia
ABC Hospital - Computer Room - Mexico
Beaumon Hospital - Computer Room - MI - USA
Burnside War Memorial Hospital - Australia
Commonwealth Serum Laboratories (CSL) Australia
University Medical Center AZ Tucson USA
Westmead Hospital Australia
Royal Childrens Hospital MRI Australia
Eventide Nursing Home Ward protection Australia
Albury Diagnostic Centre MRI NSW Australia

PA VISION SDN BHD 26 Fire Safety


Reference Sites Entertainment

Adelaide Entertainment Centre Australia


ADS Channel 10, South Australia
Crown Center & Development, Kansas City Kansas USA
Joint European Torus (JET) UK
Jupiters Casino Gold Coast, Queensland Australia

PA VISION SDN BHD 27 Fire Safety


VESDA LaserFOCUS (VLF-250 & 500)

Single sampling pipe


Pipe length 25m
250m2 area coverage
LED display
Bar graph display

Single sampling pipe


Pipe length 50 m
500m2 area coverage
LED display
Bar graph display

PA VISION SDN BHD 28 Fire Safety


VESDA LaserCOMPACT

Single sampling pipe


Pipe length 50m
500m2 area coverage
LED display
VESDAnet option

PA VISION SDN BHD 29 Fire Safety


VESDA LaserPLUS

4 sampling pipes
Pipe length 200m
2000m2 area cov.
Bar graph display
LED display
Programmer option
VESDAnet

PA VISION SDN BHD 30 Fire Safety


VESDA LaserSCANNER

4 sampling pipes
Pipe length 200m
Scanning option
Zone identification
2000m2 area cov.
Bar graph display
LED display
Programmer option
VESDAnet

PA VISION SDN BHD 31 Fire Safety


Pipe fittings and accessories

PA VISION SDN BHD 32 Fire Safety


Pipe fittings and accessories

PA VISION SDN BHD 33 Fire Safety


Mounting clip options

Saddle Clip Pipe Clip Offset Clip

PA VISION SDN BHD 34 Fire Safety


Sampling point location

PA VISION SDN BHD 35 Fire Safety


Approvals

Country Agency Standard Status


Australia SSL AS 1603.8 -1998 Passed
USA UL UL 268 : 1996 Passed
USA FM FM 3830 : 1997 Passed
Canada ULC UL 268 : 1996 Passed
UK LPCB TE 89423 Passed
Germany VdS CEA GEI 1-048 Passed
France AFNOR NFS 61-950 Passed
China NTC GB-4717-93 Passed

PA VISION SDN BHD 36 Fire Safety


EMC Compliances

All components of the VESDA system have been designed


to meet or exceed the following EMC standards

Country EMC standard Type

Australia AS/NZS 3548 Emissions

SMA tick AS 2362.7 Immunity

USA & Canada FCC Class B Emissions


(CISPR 22-B)

UK & Europe EN 50081-1 Emissions


EN 50130-4 Immunity

CE Mark EN 54-7 Immunity

PA VISION SDN BHD 37 Fire Safety


Siemens VESDA

PA VISION SDN BHD 38 Fire Safety


Authorised distributor

Why choose Siemens…..

Since October 2004 Vision System has appointed Siemens


(Building Technologies) as the global distributor for VESDA.

Siemens will provide marketing and technical support to


customers which includes engineering, design, installation,
commissioning and after sales service.

PA VISION SDN BHD 39 Fire Safety


Application examples (cabinet protection)

PA VISION SDN BHD 40 Fire Safety


Application examples (cabinet protection)

PA VISION SDN BHD 41 Fire Safety


Application examples (refrigeration)

PA VISION SDN BHD 42 Fire Safety


Application examples (in-rack sampling)

PA VISION SDN BHD 43 Fire Safety