Beruflich Dokumente
Kultur Dokumente
There are many good reasons for reducing (and sometimes maintaining) steam pressure. This
tutorial details common applications for direct operating, pilot operated, pneumatic, electric and
electropneumatic pressure control systems, including the advantages and disadvantages of each
different control method.
Use the quick links below to take you to the main sections of this tutorial:
There are many reasons for reducing steam pressure:
• Steam boilers are usually designed to work at high pressures in order to reduce their physical size.
Operating them at lower pressures can result in reduced output and 'carryover' of boiler water. It is,
therefore, usual to generate steam at higher pressure.
• Steam at high pressure has a relatively higher density, which means that a pipe of a given size can
carry a greater mass of steam at high pressure, than at low pressure. It is usually preferable to
distribute steam at high pressure as this allows smaller pipes to be used throughout most of the
distribution system.
• Lower condensing pressures at the point of use tend to save energy. Reduced pressure will lower
the temperature of the downstream pipework and reduce standing losses, and also reduce the
amount of flash steam generated when condensate from drain traps is discharging into vented
condensate collecting tanks.
It is worth noting that if condensate is continuously dumped to waste, perhaps because of the risk
of contamination, less energy will be lost if the condensing pressure is lower.
• Because steam pressure and temperature are related, control of pressure can be used to control
temperature in some processes. This fact is recognised in the control of sterilisers and autoclaves,
and is also used to control surface temperatures on contact dryers, such as those found in
papermaking and corrugator machines. Pressure control is also the basis of temperature control in
heat exchangers.
• For the same heating duty, a heat exchanger designed to operate on low-pressure steam will be
larger than one designed to be used on high-pressure steam. The low-pressure heat exchanger
might be less expensive because of a lower design specification.
• The construction of plant means that each item has a maximum allowable working pressure
(MAWP). If this is lower than the maximum possible steam supply pressure, the pressure must be
reduced so that the safe working pressure of the downstream system is not exceeded.
• Many plants use steam at different pressures. A 'stage' system where high-pressure condensate
from one process is flashed to steam for use in another part of the process is usually employed to
save energy. It may be necessary to maintain continuity of supply in the low pressure system at
times when not enough flash steam is being generated. A pressure reducing valve is ideally suited
for this purpose.
Advantages:
1. Inexpensive.
2. Small.
3. Easy to install.
4. Very robust, giving long life with minimum maintenance.
5. Tolerant of imperfect steam conditions.
6. Self-acting principle means that no external power is required.
Disadvantages:
Applications:
Non-critical, moderate load applications with constant running flowrates, for example:
Points to note:
Advantages:
1. Very robust.
2. Tolerant to wet and dirty steam.
3. Available in large sizes, so high flowrates are possible.
4. Easy to set and adjust.
5. Simple design means easy maintenance.
6. Self-acting principle means that no external power is required.
7. Able to handle pressure drops of 50:1 in small sizes, and 10:1 in large sizes.
Disadvantages:
1. Large proportional band means that close control of downstream pressure is improbable with large
changes in load.
2. Relatively high purchase cost, but lifetime cost is low.
3. Bulky.
Applications:
1. Distribution mains.
2. Boiler houses.
Points to note:
1. Because the diaphragm is subject to fairly low temperature limitations, a water seal is required on
steam applications. This adds to the cost slightly.
2. Because of the large proportional band, this type of valve is better suited to reducing steam
pressure to plant areas rather than individual plant items.
3. A bellows sealed stem ensures zero maintenance and zero emissions.
4. Although wide proportional band provides stability, care is needed if a safety valve needs to be set
close to the apparatus working pressure.
5. Suitable for liquid applications.
6. More expensive than a pilot operated valve, but less expensive than a pneumatic control system.
Fig. 8.1.2 General arrangement of a direct operating, self-acting pressure reducing station
The effect is a very narrow proportional band, typically less than 200 kPa.
This, together with low hysterisis, results in very tight and repeatable control of pressure, even with widely
varying flowrates.
Advantages:
1. Accurate and consistent pressure control, even at high and variable flowrates.
2. A variety of pilot valves may be used on one main valve. Pilot valve options include electrical
override, multi-pilot for a choice of control pressures, a surplussing option and remote control, as
well as different temperature/pressure control combinations.
3. Self-acting principle means that no external power is required.
4. Tolerant of varying upstream pressure.
Disadvantages:
Applications:
1. A system which requires accurate and consistent pressure control, and installations which have
variable and medium flowrates. For example: autoclaves, highly rated plant such as heat
exchangers and calorifiers.
2. A system where installation space is limited.
Points to note:
Advantages:
Disadvantages:
Applications:
A system which requires accurate and consistent pressure control, and installations which have variable and
high flowrates and/or variable or high upstream pressure. For example: autoclaves, highly rated plant such
as large heat exchangers and calorifiers.
Points to note:
Advantages:
Disadvantages:
Applications:
A system which requires accurate and consistent pressure control, and installations which have variable and
high flowrates and/or variable or high upstream pressure, including autoclaves, highly rated plant such as
large heat exchangers and calorifiers, and main plant pressure reducing stations.
Points to note:
Advantages:
Disadvantages:
1. If a spring return actuator is required, the available shut-off pressure may be limited.
2. Relatively slow actuator speed, so only suitable for applications where the load changes slowly.
Applications:
1. Safety: If electrical power is lost the valve position cannot change unless a spring return actuator is
used.
2. Spring return actuators are expensive and bulky, with limited shut-off capability.
1. The valves are serving a critical application for which downtime is unacceptable
The equipment is operated on a 'one in operation, one on stand-by' basis to cover for breakdown
and maintenance situations.
2. The turndown ratio between the maximum and minimum flowrates is very high
The equipment is operated on a pressure sequence principle with one valve set at the ideal
downstream pressure, and the other at a slightly lower pressure.
When demand is at a maximum, both valves operate; when flow is reduced, the valve set at the lower
pressure shuts off first, leaving the second valve to control.
Point to note:
The valves selected for this type of application will require narrow proportional bands (such as pilot operated
pressure reducing valves or electro-pneumatic control systems) to avoid the downstream pressure dropping
too much at high flow rates.
Fig. 8.1.7 Parallel pressure reducing station
Consider the need to drop pressure from 25 bar g to 1 bar g. The primary reducing valve might reduce
pressure from 25 bar g to 5 bar g, which constitutes a pressure ratio of 5:1. The secondary reducing valve
would drop pressure from 5 bar g to 1 bar g, also 5:1. Both valves in series provide a pressure ratio of 25:1.
It is important to check the allowable pressure turndown ratio on the selected reducing valve, this may be
10:1 on a self-acting valve, but can be much higher on electrically or pneumatically operated valves. Be
aware that high pressure drops might have a tendency to create high noise levels. Refer to Tutorial 6.4 for
further details.
Fig. 8.1.8 Typical series pressure reducing station
The trapping point between the two reducing valves (Figure 8.1.8) is to stop a build up of condensate under
no-load conditions. If this were not fitted, radiation losses would cause condensate to fill the connecting pipe,
which would cause waterhammer the next time the load increased.
Desuperheaters
Desuperheating is the process by which superheated steam is either restored to its saturated state, or its
superheated temperature is reduced. Further coverage of de super heaters is given in Block 15.
The system in Figure 8.1.9 illustrates an arrangement of a pressure reducing station with a direct contact
type pipeline desuperheater.
In its basic form, good quality water (typically condensate) is directed into the superheated steam flow,
removing heat from the steam, causing a drop in the steam temperature.
Because of this, the temperature is always controlled at a value higher than the relevant saturation
temperature, usually at 5°C to 10°C above saturation.
For most applications, the basic system as shown in Figure 8.1.9 will work well. As the downstream
pressure is maintained at a constant value by the pressure control loop, the set value on the temperature
controller does not need to vary; it simply needs to be set at a temperature slightly above the corresponding
saturation temperature.
However, sometimes a more complex control system is required, and is shown in Figure 8.1.10. Should
there be a transient change in the superheated steam supply pressure, or a change in the water supply
temperature, the required water/steam flow ratio will also need to change.
A change in the water/steam flow ratio will also be required if the downstream pressure changes, as is
sometimes the case with certain industrial processes.
The 4-20 mA signal from the pressure transmitter is relayed to the pressure controller and the saturation
temperature computer, from which the computer continuously calculates the saturation temperature for the
downstream pressure, and transmits a 4-20 mA output signal to the temperature controller in relation to this
temperature.
The temperature controller is configured to accept the 4-20 mA signal from the computer to determine its set
point at 5°C to 10°C above saturation. In this way, if the downstream pressure varies due to any of the
reasons mentioned above, the temperature set point will also automatically vary. This will maintain the
correct water/steam ratio under all load or downstream pressure conditions.
Advantages:
1. The pressure sensor may be located in the steam space, or close to the control valve rather than in
the process medium itself. This is an advantage where it is difficult to measure the process
temperature.
2. This arrangement can be used to control a number of different elements from a single point.
Disadvantage:
1. Control is 'open loop', in that the sensor is not measuring the actual product temperature.
Applications:
Point to note:
Good air venting is essential (refer to Tutorial 11.12 for further details)
Fig. 8.1.15 Constant pressure steam supply to a control valve supplying a plate heat exchanger
Advantages:
This temperature gradient could, in turn, result in a distorted or poorly heated product.
3. Different operating temperatures can be achieved.
Disadvantage:
A complex system is required if efficiency is to be maintained. This might involve flash vessels and/or
thermo-compressors, as well as downstream applications which use the lower pressure pass-out steam.
Application:
Blow-through drying rolls in a paper mill.
Point to note:
A special controller or differential pressure transmitter is required to accept two inputs; one from the primary
steam supply and the other from the flash vessel. In this way, the pressure differential between the flash
vessel and the primary steam supply is maintained under all load conditions.
Surplussing control
Description
The objective is to maintain the pressure upstream of the control valve. Surplussing valves are discussed in
further detail in Tutorial 7.3, 'Self-acting pressure controls and applications'.
Applications:
1. Boilers on plants where the load can change by a large proportion over a very short period. The
sudden reduction in boiler pressure may result in increased turbulence and rapid flashing of the
boiler water, and large quantities of water being carried over into the pipework system.
2. Accumulators where surplus boiler output is used to heat a mass of water under pressure. This
stored energy is then released when the boiler has insufficient capacity.
Points to note:
1. Minimum pressure drop is usually required over the fully open control valve; this may mean a 'line
size' valve is needed.
2. Not all self-acting controls are suitable for this application and it is important to consult the
manufacturer before use.
The slave controller is configured to accept two input signals, and its set point will change (within defined
limits) depending on the electrical output signal from the master controller.
This form of control is very important where the pressure to the apparatus must be limited, despite the heat
demand.
Application:
The steam heated plate heat exchanger shown in Figure 8.1.19 is heating water circulating in a secondary
system. The heat exchanger has a maximum working pressure, consequently this is limited to that value in
the slave controller.
In order to control the secondary water temperature, a master controller and temperature transmitter
monitors the heat exchanger outflow temperature and sends a 4-20 mA signal to the slave controller, which
is used to vary the slave set point, between pre-determined limits.
Points to note:
1. An adequate pressure margin must exist between the set pressure of the safety valve and the
pressure limitation imposed by the controller.
2. The safety valve must not be used as a device to limit pressure in the heat exchanger; it must only
be used as a safety device.
Fig. 8.1.19 Cascaded controllers on the steam supply to a heat exchanger
Application:
The upstream pipework is a high-pressure distribution pipe possibly from a distribution manifold or steam
boiler supplying plant of a non-essential nature (Figure 8.1.20). Should the demand be higher than the
supply capacity, the valve closes and throttles the steam flow, maintaining the pressure in the upstream
pipework.
The master controller is set at the normal expected supply pressure. If the master detects a drop in
upstream pressure below its set value (due to an increase in demand) it reduces the set point in the slave
controller, in proportion to pre-determined limits.
The slave closes the valve until the steam demand falls to allow the upstream pressure to re-establish to the
required value. When this is achieved, the set point of the slave controller is set at its original value.
Fig. 8.1.20 General schematic arrangement of a reducing/surplussing valve
Typical settings
The output from the master controller is direct acting, that is, when the upstream pressure is at or above its
proportional band, the master's output signal is maximum at 20 mA; when at the bottom of, or below the
proportional band, the control signal is minimum at 4 mA.
When the control signal is 20 mA, the slave set point is the required downstream pressure; when the signal
is 4 mA, the slave set point is at a pre-determined minimum.
Consider the 'normal' upstream pressure to be 10 bar g, and the maximum allowable downstream pressure
to be 5 bar g. The minimum allowable upstream pressure is 8.5 bar g, which means that if this pressure is
reached the valve is fully shut. The minimum reduced pressure is set at 4.6 bar g.
Table 8.1.1
Application:
A typical application is a dairy cream pasteuriser requiring a pasteurisation temperature of 50°C. Because of
the low control temperature, if steam were applied directly to the pasteurisation heat exchanger, it is
possible that the relatively large amount of heat in the steam would make control difficult, causing the
system temperatures to oscillate, overheating and spoiling the cream.
To overcome this problem, the system in Figure 8.1.21 shows two heat exchangers. The pasteuriser is
heated by hot water supplied from the primary steam heated heat exchanger.
However, even with this arrangement, if only the master controller operated the valve, a time lag would be
introduced into the system, and poor control might again be the result.
Two controllers are therefore used, working in cascade, each receiving a 4-20 mA signal from their
respective temperature transmitters.
The slave controller is used to control the final temperature of the product within clearly defined limits
(perhaps between 49°C and 51°C). These values are altered by the master controller relative to the product
temperature such that, if the product temperature increases, the slave set point reduces in proportion.
Fig. 8.1.21 Schematic diagram showing a pasteuriser control using the cascade principle