Tomy Master
(0)
Hello experts.
If you go for ET200S (8 DI, 8 DQ, 4AI) then you will have around
Joined 7/2/2008 80 modules which means min. 2 interface modules.
Last visit: 4/4/2011 Number of IM depends on,
Posts: 528 1- I/Os centralized or distributed.
Rating: 2- Installation technique (many installation techniques can't afford
64 modules per IM).
(98)
For ET200M (32DI,32DQ & 8AI) then you will have 21 modules
which also means min. of 2 HF interface modules. You will need
deep S7-300 rail and active bus units for all modules.
ET200S has the advantage that it's mounted on 35mm DIN rail
which means it doesn't need deep S7-300 rack and active bus
modules.
Maybe the ET200S solution will be cheaper.
I don't know about price differences between the 2 solutions but I
think you should calculate it.
Hot swapping depends on both the CPU and the interface module.
For Profibus, Only S7-400 CPUs have OB83 in their operating
system which is essential for this kind of interrupts.
8/18/2009, 2:08 PM
(0)
Import of a Technical Reply of an User
J_Bell wrote:
Dear Tomy,
If you have a S7-400 you may use... I think at least these ET200 systems:
+ ET200S
+ ET200M (with active bus module)
+ ET200iSP
+ ET200pro
Best regards
J_Bell