Beruflich Dokumente
Kultur Dokumente
1, 2011
Translated from Denki Gakkai Ronbunshi, Vol. 128-B, No. 10, October 2008, pp. 1235–1242
41
It should be noted that in Steps 2 to 5, the N switches
to be closed are restricted to switch combinations in which
N loops overlap to form a meshed configuration.
Below we consider the calculation of the switch
currents required for determination of the switches to be
opened in Step 3 so as to obtain a meshed configuration,
and the calculation of the line currents in a meshed configu-
ration required in order to find the power loss at Step 4.
42
Fig. 3. Variation of current with first switch closing.
(4)
(8)
(9)
Fig. 5. Variation of current with first switch opening.
43
Table 1. Section loads and impedances of example
system
44
Fig. 8. Branch exchange operations.
Fig. 9. Double-branch exchange operations. A loss minimization calculation was performed for
the 44-feeder distribution system described in Table 3. The
system has 1506 switches, including 218 open switches in
the initial state, and 1332 sections. The power loss in the
Table 2. Two-stage branch exchange operation initial state was 938.2371 kW.
Calculation results are given in Table 4, and Fig. 10
shows how power loss is reduced by successive iterations.
For comparison, the results obtained by the conventional
branch exchange method are also given. Here the CPU time
includes only the time required for branch exchange: data
read and other operations are not considered.
As is evident from Table 4 and Fig. 10, the double-
branch exchange method achieves better loss reduction than
the conventional branch exchange method. As regards com-
puting time, the conventional method requires about 0.8 s,
Table 3. Size of real-scale system while the double-branch exchange method requires about
4.4 s, or 5.5 times as long. However, this is a quite practical
time considering the system size.
5. Conclusions
45
In addition, methods should be developed to deal With the section length and impedance denoted by,
with constraints on the voltage and line capacity that are respectively, L and R, the current flowing at a distance x
ignored in this study (including the operation of voltage from the inflow end is Ix = Iin − (x / L)Il. The impedance of
regulators). a small section ∆x at a distance x from inflow end is ∆r =
The method proposed in this study can also be ap- (R/L)∆x. According to assumptions (3) and (4), the reactive
plied to distribution systems involving dispersed gener- part of the power flow can be ignored, and therefore the
ators, which have been gaining popularity. This, too, is a power loss in the small section ∆x can be expressed as
topic for future research. follows:
REFERENCES (A.1)
1. Ross DW, Patton J, Cohen AI, Carson M. New Therefore, the power loss in this section is
method for evaluating distribution automation and
control (DAC) systems benefits. IEEE Trans Power (A.2)
Apparatus Syst 1981;PAS-100:2978–2986.
2. Civanlar S, Grainger JJ, Yin H, Lee SSH. Distribution
2. Derivation of Power Loss Reduction Due to
feeder reconfiguration for loss reduction. IEEE Trans
Branch Exchange
Power Delivery 1988;3:1217–1223.
3. Baran ME, Wu FF. Network reconfiguration in dis-
tribution systems for loss reduction and load balanc- 2.1 Derivation of power loss increase due to
ing. IEEE Trans Power Delivery 1989;4:1401–1407. load addition
4. Merlin A, Back H. Search for a minimal-loss operat-
ing spanning tree configuration for an urban power Let us find the increase in the power loss when a load
distribution system. Proc 5th PSCC 1975;1:1–18. ∆I is added to the end of the transmission line as shown in
5. Shirmohammadi D, Hong HW. Reconfiguration of Fig. A.2.
electric distribution networks for resistive line losses With the load and impedance of section i denoted by,
reduction. IEEE Trans Power Delivery 1989;4:1492– respectively, Ii and Ri, the increase of the power loss in this
1498. section can be found by using Eq. (A.2) as follows:
6. Nara K, Satoh T, Kuwabara H, Aoki K, Kitagawa M,
Ishihara T. Distribution systems expansion planning
by multi-stage branch exchange. IEEE Trans Power
Syst 1992;7:208–214.
APPENDIX
(A.4)
Fig. A.1. Uniformly distributed load. Fig. A.2. Distribution line with added load.
46
Therefore, the increase of the power loss in the entire Now the following is obtained by substituting Eq. (A.9) into
distribution system is Eq. (A.7):
(A.5)
2.2 Derivation of Eq. (2)
(A.6)
Here ∆PF1, ∆PL, and ∆PF2 are the variations at, respectively,
sections l + 1 to n of feeder F1, sections 1 to l of feeder F1,
and feeder F2.
Using Eq. (A.5), ∆PF1 and ∆PF2 can be expressed as
follows:
(A.7)
(A.8) (A.11)
__
Here ∆Ei is the voltage drop of section i after the load Thus, from Eqs. (A.6), (A.8), (A.10), and (A.11),
transfer; it can be found from the voltage drop before the
load transfer as follows:
(A.12)
Here E1 and E1g are the voltage drops from feeders F1 and
F2 to the ends of the switch to be closed, respectively.
(A.9)
The part of the third term in curly brackets in Eq.
(A.12) can be transformed as follows:
(A.13)
(A.14)
Fig. A.3. Load transfer.
47
AUTHORS (from left to right)
Masahiko Murai (member) completed the M.E. program at Kyoto University in 1991 and joined Toshiba Corporation.
He is now affiliated with the Power and Industrial Systems R&D Center. His research interests are planning, operation and
control of power and energy systems. He is a member of ISCIE, SICE, ORSJ, and IEEE.
Yoko Kosaka (member) received a bachelor’s degree from Nihon University in 1990 and joined Toshiba Corporation. She
is now affiliated with the Power and Industrial Systems R&D Center. Her research interests are operation, supervision, control,
and analysis of power systems.
Takenori Kobayashi (senior member) completed the doctoral program at the University of Tokyo in 1995. He joined
Toshiba Corporation in 1994, and is now affiliated with the Power and Industrial Systems R&D Center. His research interests
are analysis, operation, and control of power and energy systems. He holds a D.Eng. degree, and is a member of IEEE.
Yumiko Kaneshiga (member) received a bachelor’s degree from Ochanomizu University in 1986 and joined Toshiba
Corporation. She is now affiliated with the Power Control Computer Systems Department, and is engaged in the development
of power systems control facilities.
48