Datasheet UNIVERSAL COMPACT ORIFICE FLOW METER

DS-F-01

COMPAFLOW
Volumetric flow  Compressed Air

Mass flow  Gas

Net volumetric flow  Steam

 Liquid

Universal compact orifice flow meter


- combines a compact orifice flow sensor and
sotiphicated converter

One-piece flow sensor, pressure tested as an


assembly
- improved reliability with no leaks to trace
and rectify

Mass Flow version with optional, integral


temperature sensor and static pressure
sensor
- integral RTD and static pressure sensor for
direct reading of steam / gas mass and
corrected volume flow rates in a single unit

Integral impulse connections


- no impulse piping installation required
- provides repeatable DP connection across
installation locations

Reduced cost of installation


- only one piece to install
- eliminates need to supply and connect
separate manifold, transmitter and impulse
piping

Easy to specify
- single ordering code covers complete flow
meter Figure 1.
- only two orifice ratios for simple Compaflow shown with
specification process Yokogawa DP transmitter

1
Datasheet UNIVERSAL COMPACT ORIFICE FLOW METER
DS-F-01 COMPAFLOW

Compaflow Basic Principle of Operation


Compaflow is an orifice-based flow meter with a DP devices work on a principle based upon the Law of
difference - its advanced design greatly simplifies Conservation of Energy, where a restriction in the fluid
installation and commissioning. path causes an acceleration in the fluid velocity with a
corresponding increase in kinetic energy. The gain in
Compaflow is a stand-alone, orifice-based flow meter kinetic energy is at the expense of pressure energy,
that incorporates all the following features: resulting in a drop in fluid pressure across the narrowest
part of the restriction. The drop in pressure and the flow
 A wafer-bodied orifice carrier assembly with integral rate are linked by the following (albeit simplified)
square-edged, concentric plate and corner tapping relationship:
points Q=k√ DP
 Optional Integral 3-valve manifold
 DP transmitter, factory-mounted onto the sensor / where Q = fluid flow rate
manifold and pre-configured for the application k=aconstantforthatDPdevice
 Fully leak-tested and configured DP = the pressure difference across the restriction

Benefits The DP generated for a given class of device depends on


Compaflow avoids many of the difficulties involved in the bore of the restriction. Many calculation standards
the sizing, selection, procurement, installation and exist but in all cases the differential pressure produced
commissioning of conventional orifice plate installations. by the restriction is larger than would normally be
 With all the major components in one assembly, expected. This effect occurs because a stream is unable
Compaflow eliminates the problems of sourcing to follow the contours of a restriction perfectly, resulting
multiple components. Large savings in cost and time in a flow stream whose narrowest diameter (known as
due to the simplicity of design and installation. the Vena Contracta) is less than the diameter of the
 Integral transmitter and manifold with compact restriction.
tapping connections eliminates the need to run and
connect impulse piping and offers:
- guaranteed accuracy of positioning and
installation of the tapping points
- reduced possibility of impulse line blockage
 The assembly is pressure tested in the factory, giving
the user confidence that the connections between the
tapping points and the transmitter are completely free
of leaks
 Factory configuration of the meter saves the user
time during commissioning and ensures that the
flowmeter output span truly matches that of the
application flowrate Figure 2
 Choice of two discrete Beta ratio values, together
with the free sizing, selection and coding software,
simplifies the sizing and selection process The Vena Contracta increases the velocity (and
 Element centralizing system ensures every meter is therefore the kinetic energy) and this produces a larger
concentric with its pipe, thus avoiding significant drop in pressure than would normally be expected.
additional metering errors Some of the differential pressure generated is
recovered downstream of the unit but all DP devices
incur some loss, known as the 'irrecoverable pressure
loss', and this is usually expressed as a percentage of
the differential pressure. To correct for the Vena
Contracta effect, each device has a Discharge
Coefficient; a multiplying factor of less than 1 that is
part of the calculation. Typically, the smaller the Vena
Contracta compared with the bore of the device, the
larger the deviation from expectations and hence the
smaller the coefficient.

2
Datasheet UNIVERSAL COMPACT ORIFICE FLOW METER
DS-F-01 COMPAFLOW

Versions Compaflow V6200 - a compact flow meter for


Compaflow is available in three versions: general purpose measurement in volumetric units
(actual volume). It uses the sophiticated converter
Compaflow V684 -acompactflowmeterforgeneral V6200 and provides a flow rate and total display on 02
purpose measurement in volumetric units (actual LED lines. There is output 4 to 20 mA, Contacts,
volume). It uses the loop powered converter V684 and RS485...
provides a flow rate and total display on a single line
LCD. There is no output 4 to 20 mA.

Figure 4
Figure 3

Compaflow - a compact orifice flow meter with


Compaflow M128 - a compact mass-flow meter, other DP transmitter from Yokogawa, Foxboro, E&H,
giving measurement directly in mass units. It uses ABB...It can be volumetric & mass measurement.
the Mass converter M126 to measure DP, LCD Display is optional. 4-20mA Output is standard
temperature and pressure. It provides a flowrate with HART communication
display and transmits 4 to 20 mA proportional to the
mass or corrected volume flowrate.

Figure 6

F
i
g
Datasheet UNIVERSAL COMPACT ORIFICE FLOW METER
DS-F-01 COMPAFLOW

Specification - General Wetted materials


Orifice assembly, 304 stainless steel
Fluids stem and manifold Optional: 316/ 316L SS
- Compressed Air, Gas
- Saturated/Superheated Steam Converter sensor housing High impact plastic
- Liquid
Process isolating diaphragms 316/316L SS
LineSizes
25 mm, 40 mm, 50 mm, 80 mm, 100 mm, 150 mm, Seals (transmitter to manifold) PTFE
200mm(1in.,11/2in.,2in.,3in.,4in.,6in.,8in.)
Process Connections
Outputsignal Wafer body to fit between the following flange drillings:
Two-wire, 4 to 20 mA, Low flow cut-off facility, Optional
ASME B16.5 (ANSI) Class 150, 300 or 600
HARTcommunication
Optional RS485/Modbus communications (Compaflow DIN PN16, PN25, PN40 or Pn100
V6200&M126only)
Pipeline centralization assured by centralizing tool(s)
Outputcurrentlimits(toNAMURstandard) supplied with every unit as standard
Overloadcondition:
Lowerlimit3.8mA(configurable from3.7to4mA) Pressure limitations 100 bar (1450 psi) or as flange
Upperlimit20.5mA(configurable from20to22.5mA) rating, whichever is the lower

Alarmcurrent Temperature limitations


Minimum alarm current 3.8 mA (configurable from 3.7 to Process -20 to 121 °C (-4 to 250 °F)
4mA) -20 to 400 °C (-4 to 446 °F) for steam
Maximum alarm current 22 mA (configurable from 20 to
22.5mA)
Ambient -20 to 70 °C (-4 to 158 °F)
Standardsettingmaximumalarmcurrent

Powersupply Orifice plate bore at 20 °C (68 °F):


24VDCor230VAC/50Hz For Beta = 0.4
25 mm (1 in.) 10.66 mm (0.42 in.)
Indicators 40 mm (11/2 in.) 16.36 mm (0.644 in.)
Indicatorisstandardforallversions. 50 mm (2 in.) 20.99 mm (0.826 in.)
80 mm (3 in.) 31.17 mm (1.227 in.)
CompaflowV684: 100 mm (4 in.) 40.90 mm (1.610 in.)
Single line, 6-Digit LCD. Four keys for configuration and 150 mm (6 in.) 61.63 mm (2.426 in.)
management of device. Easy setup for quick 200 mm (8 in.) 81.10 mm (3.193 in.)
commissioning. Totalized and instantaneous flow
indication. Display also indicates diagnostic messages
For Beta = 0.65
andprovidesconfigurationfacilities.
25 mm (1 in.) 17.32 mm (0.682 in.)
CompaflowV6200: 40 mm (11/2 in.) 26.58 mm (1.047 in.)
Double line, 6-Digit LED. Four keys for configuration and 50 mm (2 in.) 34.11 mm (1.343 in.)
management of device. Easy setup for quick 80 mm (3 in.) 50.65 mm (1.994 in.)
commissioning. Totalized and instantaneous flow 100 mm (4 in.) 66.47 mm (2.617 in.)
indication. Display also indicates diagnostic messages 150 mm (6 in.) 100.15 mm (3.942 in.)
andprovidesconfigurationfacilities. 200 mm (8 in.) 131.78mm (5.188 in.)

CompaflowM126: Performance
Double line, LCD Display, optional back lit.Three keys for
configuration and management of device. Easy setup for
Accuracy
quick commissioning. Totalized and instantaneous flow
indication. Display also indicates in/out transfer function, 1%
static pressure, sensor temperature and diagnostic
messagesandprovidesconfigurationfacilities. Repeatability
0.1%

4
Datasheet UNIVERSAL COMPACT ORIFICE FLOW METER
DS-F-01 COMPAFLOW

DP Span for DPT490 Transmitter

Sensor Code Min Span (KPa) Max Span (KPa)

0A 0.35 35

02 0.70 70

03 1.00 100

07 2.00 200

* Other DP Span can be specified when ordering

Upstream Pipes Requirements to ISO 5167:2003

Fitting Beta = 0.4 Beta = 0.65

Conical Reducer (2D-D) 5D 12D

Conical Expander (0.5D-D) 12D 28D

Single 90o Bend 16D 44D

2 off 90o bends in same plane 10D 44D

2 off 90o bends in different plane 50D 60D

Where D = Pipe diameter


Downstream = 5D

5
Datasheet UNIVERSAL COMPACT ORIFICE FLOW METER
DS-F-01 COMPAFLOW

Dimension Drawings
220

159 73

80

Figure 7.
Compaflow shown
with DPT490 J

Dimension Table - mm (inch)

Size H J E (J/2) D (H-E)

25 (1”) 190.8 (7.51) 50.8 ±1 (2 ±0.04) 25.4 ±0.5 (1 ±0.02) 165.4 ±5 (6.51 ±0.2)

40 (1 1/2”) 213.2 (8.39) 73.2 ±1 (2.88 ±0.04) 36.6 ±0.5 (1.44 ±0.02) 176.6 ±5 (6.95 ±0.2)

50 (2”) 232.1 (9.13) 92.1 ±1 (3.63 ±0.04) 46.05 ±0.5 (1.81 ±0.02) 186.05 ±5 (7.32 ±0.2)

80 (3”) 267 (10.51) 127 ±1 (4.99 ±0.04) 63.5 ±0.5 (2.50 ±0.02) 203.5 ±5 (8.01 ±0.2)

100 (4”) 317.2 (12.49) 157.2 ±1 (6.19 ±0.04) 78.6 ±0.5 (3.09 ±0.02) 238.6 ±5 (9.39 ±0.2)

150 (6”) 375.9 (14.80) 215.9 ±1 (8.50 ±0.04) 107.95 ±0.5 (4.25 ±0.02) 267.95 ±5 (10.55 ±0.2)

200 (8”) 429.9 (16.92) 269.9 ±1 (10.63 134.95 ±0.5 (5.31 ±0.02) 294.95 ±5 (11.61 ±0.2)

6
Datasheet UNIVERSAL COMPACT ORIFICE FLOW METER
DS-F-01 COMPAFLOW

Ordering Code

Example model code V 80 L 50 07 V6200

Model
Volume Flow V
Mass Flow (Integral Pt100) M
Size
25 25
40 40
50 50
80 80
90 90
100 100
150 150
200 200
Fluid
Liquid L
Gas G
Steam S
Beta ratio
0.4 40
0.65 65
Special (1) X1
DP Span Limit
0.35 .. 35 Kpa 0A
0.70 .. 70 Kpa 02
1.00 .. 100 Kpa 03
2.00 .. 200 Kpa 07
Other DP transmitter (2) X2
Indicating Totalizer
Loop powered indicator V684, panel mount V684
Sophiticated indicator V6200, panel mount V6200
Mass flow computer M126, panel mount M126
None (3) N1
Other (4) X3

(1): Beta ratio calculated from Sizing program


(2): This compaflow can be used with other DP Transmitters: Yokogawa, Foxboro,
Rosemount, ABB, E&H...
(3): May be specified when X2 was chosen in case the totalizer function is not
required or other DP transmitter has got totalizing function.
(4): Can be using with other totalizer

7
UNIVERSAL COMPACT ORIFICE FLOW METER
COMPAFLOW

Compaflow is a registered trademark of Dai Viet Controls & Instrumentation Company Ltd.
Modbus is a registered trademark of the Modbus-IDA organization
Daviteq is a registered trademark of Dai Viet Controls & Instrumentation Company Ltd.

Daviteq Company Limited


245 Hau Giang St., Ward5, Dist. 6
Ho Chi Minh City, SR Vietnam
Te l : + 8 4 - 8 - 6 2 9 3 . 2 6 6 2
Fax: +84-8-6293.2663
Email: info@daviteq.com
Printed in Vietnam (06.08) © Daviteq 2008 Http://www.daviteq.com