INSTRUCTION MANUAL
I. INTRODUCTION
1.1 DESCRIPTION
FKGS Tan Delta (dissipation factor) Tester consists of variable frequency power, tan delta
bridge, testing transformer and standard capacitor. Variable frequency power can produce
five kinds of frequency: 45Hz, 50Hz, 55Hz, 60Hz and 65Hz under which test can be done.
Variable frequency technique adopted in this tester can ensure high accuracy in high
interference environment.
Wiring mode of internal main power:
CN---Standard capacitor
RN---Sampling resistance of reference signal
CVT---Voltage output terminal in CVT measurement by means of self-excitation.
(U<=50V, I<=30A)
1.2 SAFETY PRECAUTIONS
The tester can produce 12 kV high voltage which is outputted from HV output
terminal. Do make sure the GND earth terminal is well connected to earth.
All the operators and assistants must read this instruction manual carefully before
test and operate strictly as per this manual. Safety barrier must be set up around the
test field and must be with warning marks. Non-operators should not enter into this
safety barrier.
Operators are only allowed to press buttons in front panel. Touching or being close
to the HV output (within 20cm) is forbidden.
The test object must be disconnected with power. Never connect this tester to live
object.
Do not use the tester in flammable or explosive environment.
If the test equipment is operated properly and all grounds correctly made, test
personnel need not wear rubber gloves. As a routine safety procedure, however,
some users require that rubber gloves be worn, not only when making connections
to the HV terminals, but also when manipulating the controls. FANKE consider this
an excellent safety practice.
Follow the expert advice if the operators are with heart peacemaker which will be
affected by discharge, strong power and electromagnetism field.
WARNING
Operation disobeying the above safety precautions will result in accident and wrong
test result.
II. OPERATIONAL ENVIRONMENT
Double frequency test mode is suggested in high interference environment. For example, if
the frequency of interference source is 50Hz, we suggest using 45Hz/55Hz double
frequency to test and use 55Hz/65Hz to test if the frequency of interference source is 60Hz.
Test voltage must be higher than 5kV.
V. OPERATIONAL INSTRUCTION
Note:
Make sure GND terminal (earth terminal) is reliably connected with earth before
test.
The HV output terminal can output upto 12kV high voltage. Keep away from this
terminal.
The tester must be operated by high voltage professionals.
HV output wire must keep insulated to earth and the insulation level should be
higher that 12kV.
Make sure all the above instructions are followed or else damage to tester and human will
be introduced.
MEASUREMNET METHODS
Make sure GND earth terminal is well connected to earth in all test. HV lead must be
insulated to earth. Or the tester will be damaged.
FKGST provides nine kinds of connection mode. The test voltage can be higher than 12kV
in external HV, external standard capacitor, and ungrounded test specimen measurement. It
is forbidden that the test voltage is higher than 12kV in all the other eight connections. Or
else it will bring damage to the tester and even operator.
The capacitance of capacitor connecting to HV terminal must be much higher than that of
internal standard capacitor CN which is 50pF. And tan delta of this capacitor must be very
small or test accuracy will be affected.
Note: For the sake of personal safety, make sure that the earth terminal of the tester is
reliably connected to earth.
VI. OPERATIONAL INSTRUCTION AND DISPLAY
INPUT PARAMETER
SERIAL NUMBER: SN001
PHASE: RED
PART UNDER TEST: WINDING
TEST MODE: HV—LV GND
TEMP. AND HUMI.: 35℃ 70%
INPUT PARAMETER
Fig 13 parameter setting interface
SERIAL NUMBER: SN001 Ten digits can be input in each
Test parameter setting interface can set 5 parameters.
PHASE: RED
parameter setting. The input method is similar with that of cell phone.
PART UNDER TEST: WINDING
C button is clear is used
TEST toMODE:
clear. ↑↓button toHV—LV
move cursor.
GND When the time of pressing
button is short the cursor moves
TEMP. ANDhorizontally.
HUMI.: When 35℃ the70%time of pressing is long the cursor
moves vertically.
When it is need to test again after one test, parameter setting interface displays parameter
set for the previous test. Users can change these parameters here.
VIII. Warranty
All the products of Wuhan Fanke transformer manufacture Co., Ltd is guaranteed for one
year from the date of delivery. During this period overhaul and components replacement is
free. Incidental expenses, e.g. Transportation fee belong to users. We do not afford the cost
for repair caused by the following reasons:
Damages aroused by wiring error and incorrect operation
Damages brought by dismantlement and components replacement
without our permission
Damages caused by improper operation during transportation and
other portage of apparatus.