UL Recognized Component Marks:

What code authorities need to know


As a basis for approval, code authorities nents, which will not be compatible with all
look for UL Listing Marks to verify that end-product equipment applications. UL’s
products have been investigated for Listing evaluation of an end product includes
installation in the field in accordance with an investigation of the construction and
model codes. performance of all installed components.
During inspections of electrical installations, In addition to certifying products for field
code authorities may see a variety of installation in accordance with model codes,
certification marks, including the UL Listing UL investigates components that are used
Mark and UL Recognized Component Mark. by manufacturers to build UL Listed end
To properly approve the installation, it is products. In this way, UL can determine in
important for code authorities to understand advance safety features and ratings for
the meaning of each of these marks as well components. End-product manufacturers
as the important differences between them. can opt to use components that have
The UL Listing Mark is the most common already been subjected to limited testing to
certification mark seen and accepted by avoid repeat testing for the end-product
code authorities. Products bearing the UL certification. Plastic materials, definite
Listing Mark are usually either complete purpose contactors, board mounted relays
appliances, or equipment and materials that and motors are all examples of components
are intended for installation in accordance investigated by UL and bearing the UL
with model codes such as the National Recognized Component Mark. triggers additional evaluation of a
Electrical Code ® (NEC ®). These products Because components are only intended for component’s safety.
have been investigated using applicable installation in end products whose safety is An example of a UL Recognized Compo-
construction and performance require- evaluated by UL separately, they may be nent that a code authority may see in the
ments, and when installed in accordance incomplete in construction or restricted in field is a definite purpose contactor. It is not
with the manufacturer’s installation instruc- performance capabilities. This factor until a Recognized Component is installed
tions, should provide a safe, code-compliant precludes their safe installation by electri- within an end product that UL can verify
installation. The UL Guide Information for cians or contractors in the field. UL compliance with the conditions of accept-
each product category typically identifies Recognized Components have been ability. Examples of conditions of
the applicable installation code. evaluated by UL for factory installation within acceptability for a contactor may include:
Comparing UL Listing and Component equipment where the component’s limita-
• Component is not intended to be
Recognition is like comparing a car and an tions of use are known and investigated by
cycled by the operation of an automatic
engine. A car is a finished product, and an UL. Finally, UL Recognized Components
reset overload
engine is a necessary component. However, have conditions of acceptability that
describe how components can be used • Terminals are to be factory wired only
not every engine is compatible with every car.
The same is true for UL Recognized Compo- within end products. Using a component
outside the conditions of acceptability continued »

01
UL Recognized Component Marks (continued)

• Suitability of the connections, including What should code authorities do when they
spacing between factory connectors, encounter a UL Recognized Component
must be determined once installed within installed in the field? First, understand that
an end product the component has not been investigated
• Short circuit capability may need to be for field installation, but rather only for
evaluated in the end-use application installation in the factory in a complete
product investigated by UL. Second,
• Spacing from exposed live metal parts to remember that Recognized Components
the enclosure must be evaluated in an may be used in Listed equipment and
end product products, and to look for the complete UL
If a Recognized Component is installed in Listing Mark to determine if a product has
the field, the only way for UL to verify been investigated for an intended applica-
compliance with a component’s conditions tion. Finally, a product bearing only a UL
of acceptability is to conduct a UL Field Recognized Component Mark should be
Evaluation on the end product where the treated the same as an unlisted product.
component is installed.
A common use of UL Recognized Compo- Fig 1 Fig 2
nents is within industrial control panels.
Article 409 of the NEC covers industrial
control panels intended for general use at
less than 600 volts and defines them as an
assembly of two or more components,
consisting of power circuit components,
control circuit components or a combina-
tion of both. UL Lists industrial control
panels to UL 508A, the Standard for
Safety of Industrial Control Panels. UL
Guide Information can be located in the
UL White Book under the product category
Industrial Control Panels (NITW) or online
at www.ul.com/database.
The industrial control panel shown in Fig. 1
was field assembled using UL Recognized
Components. These components are not UL Listing Marks are composed of
intended for field installation, and have not four elements:
been evaluated by UL as part of a Listing 1. UL in a circle
investigation of the panel. As such, this
2. Word “LISTED”
panel would not be considered a UL Listed
3. Product identifier
industrial control panel.
4. Control or issue number
In contrast, the industrial control panel shown
in Fig. 2 has been evaluated as a complete
1 3
product. It is UL Listed and may also contain Enclosed
UL Recognized Components installed in Industrial
accordance with the UL Listing requirements.
Control
For electrical equipment, always look for the Panel
2
UL Listing Mark, which is your assurance
that samples of the end product, including 4 NO. XX 000000
all factory-installed components, have been
evaluated by UL and found to comply with
UL’s Listing requirements.

02 Copyright © material from the 2010 January Issue of The Code Authority: Electrical Connections newsletter.
This material may not reflect changes that have occurred since its original publication.