Sie sind auf Seite 1von 8

The Cold Front

Vol. 3 No. 1, 2003

INN THHIISS ISSSSUUEE CLOSED REFRIGERANT


• Closed Refrigerant Circuit 1-6
CIRCUIT FOR SCREW
for Screw Compressor Oil
Cooling
COMPRESSOR OIL COOLING
• Upcoming Ammonia Classes 2 Thermosiphon oil cooling (TSOC) is a popular choice for screw
compressor oil cooling. An alternative approach to traditional
• Noteworthy 2 thermosiphon design is to provide one or more dedicated
evaporative condensers in a closed-loop refrigerant circuit to
• PSM Auditing Course 7 meet the oil cooling heat rejection load. Tropicana Products’
new world-class machinery room in Bradenton, FL is one
• Benchmarking Study 8 example of a successful implementation of this concept.
Invitation
This article examines the closed refrigerant circuit oil cooling
approach in detail. We begin with a brief background on oil
cooling methods followed by a description of the approach. We
conclude the article with design and operational considerations.

BACKGROUND
IRC Staff With the current state of technology, oil cooling is an integral
and necessary part of industrial refrigeration screw compressor
operation. Screw compressors rely on oil to lubricate, seal,
Director quiet, clean, and cool the compressor’s rotors and bearings
Doug Reindl 608/265-3010 during operation. Because the oil is in direct contact with the
or 608/262-6381 refrigerant being compressed, it will increase in temperature as
it absorbs a portion of the refrigerant’s “heat of compression”.
Jim Elleson 608/262-6940 To prevent the oil from overheating, some means of cooling the
oil is required.
Todd Jekel 608/265-3008
Dan Dettmers 608/262-8221 The techniques available for screw compressor oil cooling can
be split into two categories: internal and external. Internal oil
Phone 608/262-8220 cooling involves cooling the oil within the compressor at some
stage during the compression process. The most common
Toll-free 1-866-635-4721 internal oil cooling approach is “liquid injection”, which involves
FAX 608/262-6209 expanding high-pressure liquid refrigerant directly into the body
Mail of the compressor to cool the oil. In liquid injection oil cooling,
949 East Washington Ave the oil supply temperature is controlled by metering the flow of
the high pressure liquid refrigerant to maintain a desired
Suite #2 discharge temperature (typically 130°F). Alternatively, oil can
Madison, WI 53703-2969 be cooled external to the compressor using a separate heat
exchanger. The medium that cools the oil can be water, glycol,
e-mail info@irc.wisc.edu or refrigerant. Water for oil cooling could originate from an
Website www.irc.wisc.edu evaporative condenser sump or if water use is not an issue,
once-through cooling. Glycol-cooled oil cooling systems are
configured as closed-loop systems with a dedicated fluid cooler

1
located outdoors (Figure 1). The most common Upcoming Ammonia Courses
approach for external oil cooling relies on the use of
a refrigerant in a thermosiphon arrangement. Ammonia Refrigeration System Safety
Although internal oil cooling offers low first-cost,
April 23-25, 2003 Madison, WI
ease of design, and installation, external
thermosiphon oil cooling (TSOC) is quickly Process Safety Management Audits Brochure
becoming the preferred choice for screw June 18-20, 2003 Madison, WI
compressor oil cooling. Compared to internal oil
cooling, external oil cooling has lower operating and Design of Ammonia Refrigeration Systems
maintenance costs as well as extended screw September 15-19, 2003 Madison, WI
compressor life. Several compressor
manufacturers are reporting that today, TSOC oil
cooling is specified in more than 50% of their new
Introduction to Ammonia Refrigeration
compressor sales. October 8-10, 2003 Madison, WI

Traditional TSOC designs position an elevated Ammonia Refrigeration Piping


thermosiphon pilot receiver in-line between the October 27-29, 2003 Madison, WI
condenser outlets and the high-pressure receiver
(Figure 2). Liquid from the pilot receiver falls by Intermediate Ammonia Refrigeration
gravity to feed individual oil coolers [IIAR Piping
Handbook, 2000] through the TSOC supply lines.
December 3-5, 2003 Madison, WI
The warmer oil gives up its heat to evaporate the
high-pressure liquid refrigerant supplied to the oil See http://www.irc.wisc.edu/training/ for more
coolers. The vapor generated by the evaporation information.

Figure 1: Glycol fluid cooler (left) for screw compressor external glycol oil cooler (right).

Noteworthy
• In February, we welcomed Sargento Foods as the newest IRC Member Company.
Click here for the press release.
• Check out the coverage of the 2003 IRC Research & Technology Forum in
Process Cooling & Equipment. Click here for the article.
• Send items of note for next newsletter to Todd Jekel, tbjekel@wisc.edu.

2
Equalizer line

Compressor Discharge
Evaporative
Condenser(s)
Condenser
Liquid TS
Drain Vent
Line
Alternate Equalizer line

TSOC
Return Main
Pilot Liquid Drain
from other Thermosiphon
oil coolers Pilot Receiver

TSOC Supply Main


TSOC to other oil coolers
Return
Branches
TSOC
Supply
Branches
High-Pressure
Receiver
Oil cooler

Oil cooler

Liquid Feed
to Plant
Figure 2: Traditional TSOC piping (Not to scale).

process, along with any unboiled high-pressure liquid refrigerant that undergoes a change of phase rather
refrigerant entrained and carried over from the oil than a glycol that changes temperature
coolers, migrates back to the pilot receiver through
the TSOC return lines. In the pilot receiver, liquid When to consider
separates from the vapor for supply back to the oil When should a dedicated refrigerant circuit for
coolers. Vapor is relieved to the condenser inlet thermosiphon oil cooling be considered? There are
where the heat from the oil cooling process is several points of opportunity to evaluate the feasibility
rejected to the outside environment. Any high- of this approach for your systems and plants. A
pressure liquid draining from the condensers that system expansion is always a great opportunity to
exceeds the amount required to feed the oil coolers take a step back and consider what could be done, in
overflows to the system’s high-pressure receiver. the context of the expansion, to improve the system
safety, reliability, operability, safety, and productivity.
CLOSED REFRIGERANT CIRCUIT TSOC HEAT Some companies have formed energy SWAT teams.
REJECTION These teams can evaluate the dedicated TSOC
An alternative approach to the traditional design of refrigerant circuit as one approach to improve the
high-side piping and equipment for thermosiphon oil efficiency of refrigeration system through reduced
cooling involves dedicating a closed circuit refrigerant operational costs for heat rejection. There are other
loop with separate evaporative condenser(s) that advantages beyond the efficiency and operational
operate only to meet the oil cooling heat rejection issues that can justify the use of a dedicated
load as shown in Figure 3. Like the closed-loop evaporative condenser for thermosiphon oil cooling.
glycol fluid cooler system (Figure 1), the dedicated Let’s look at some advantages and disadvantages.
TSOC system is also a closed-loop. The dedicated
TSOC differs in that the working fluid is now a

3
Equalizer line

TSOC Refrigeration System


Compressor
Evaporative Evaporative
Discharge
Condenser Condenser(s)
Condenser
Liquid
Drain

TSOC
Return Main
from other
oil coolers Thermosiphon
Pilot Receiver TSOC
Supply Main
to other
TSOC oil coolers
Return
Branches
TSOC
Supply
Branches
High-Pressure
Receiver
Oil cooler

Oil cooler

Liquid Feed
to Plant
Figure 3: Closed refrigerant circuit TSOC piping (Not to scale).
Pros and Cons
The advantages of a closed-loop refrigerant circuit for thermosiphon oil cooling include:

• Improved refrigeration system efficiency and reduced operating costs for oil cooling loads
• Reduced maintenance by maintaining an oil-free refrigerant circuit for feeding oil cooler heat exchangers
• Simplification of high-pressure receiver equalizer piping and thermosiphon relief vent line piping
• Troubleshooting high-side operational issues is simplified

The disadvantages of segregating heat rejection for oil cooling are:

• Overcoming the “We’ve never done it that way before” attitude


• Provisions for redundant oil cooling

OPERATIONAL CONSIDERATIONS

Control
In our short courses, technical papers, and guidebooks, we have repeatedly talked about the benefits of lowering
or “floating” head pressure in industrial refrigeration systems. However, for a closed-circuit oil cooling system,
reducing the condensing pressure does not minimize energy use. Consider an oil cooling heat rejection system
designed to accommodate the full-load oil cooling requirements with a saturated refrigerant temperature of 95°F
(181 psig). How should that refrigerant circuit be controlled for efficient operation during off-design hours?

Since the oil cooling circuit is now segregated from the refrigeration system’s high-side, we can focus on how it
can be controlled for efficient operation. It is important to recognize that, unlike the rest of the refrigeration

4
system, a dedicated oil cooling refrigeration circuit pumps during ambient temperature conditions near
does not have compressors connected that would freezing (32°F) because the magnitude of
benefit from reduced “head pressure”. So if the oil evaporative condenser capacity change associated
cooling heat rejection system is designed for full-load with wet vs. dry operation (particularly with the high
oil cooling with a circuit pressure of 181 psig (95°F saturated condensing temperatures expected in the
saturation), then maintaining a set point pressure in sub-system) can create control loop stability
the oil cooling circuit at 181 psig (95°F) will problems.
accomplish the peak heat rejection without overuse
of condenser fan energy. The lower the refrigerant Condenser fan control for the thermosiphon circuit
set point pressure in the TSOC circuit, the greater the is an important aspect of this sub-system.
fan energy consumption. This simple operating set Condenser control can be enhanced by installing a
point strategy can be extended by re-setting the variable frequency drive(s) (VFD) on the condenser
circuit set point pressure upward as the oil cooling fan(s). This allows more precise control of the
load decreases; however, it is important to monitor thermosiphon circuit refrigerant pressure to its set
the oil supply temperatures to ensure each operating point while minimizing fan energy use. VFDs will
compressor has adequate oil cooling. also reduce the energy associated with oil cooling
heat rejection during off-design conditions. Off-
In Northern climates, design conditions are only one design conditions are a reduction in oil cooling load
aspect of operation, what about operation during due either to reduced refrigeration load or ambient
wintertime? The importance of wintertime operation wet-bulb. As implied earlier, the condenser fans on
is heightened when the oil-cooling load decreases the thermosiphon circuit need to be modulated to
during cold weather due to reduced compressor maintain the thermosiphon pilot receiver pressure
discharge pressures and reduced refrigeration load. at its control set point. Nominally, the circuit set
Typically, oil cooling loads are correlated with point will be 181 psig; however, the pilot receiver
ambient weather conditions in application such as pressure can be reset upward as the oil cooling
distribution centers, cold-storage warehouses, load decreases.
storage terminals, and other applications with
weather dependant loads. In cold climates, consider Reliability and Redundancy
locating the pilot receiver in the engine room to Redundancy or reliability is important to consider in
maintain the TSOC refrigerant circuit pressure above the design and operation of an oil cooling system.
103 psig (65°F saturation temperature) so oil within Will the refrigeration system need to be available
the coolers will remain warm enough to flow freely 24 hrs per day, 7 days per week and 365 days per
during compressor shutdowns. Avoid cycling water

Equalizer

Purge
Main

Thermosiphon Refrigeration System P-traps


Evaporative Globe Valve Evaporative
Condenser Closed Condensers
Purge
Solenoid

Figure 4: Purger considerations (Not all valves shown).

5
year? How will the oil cooling arrangement support Sub-system Charging
system operation in the event that the one or more of Charging of the oil cooling refrigerant circuit can be an
the oil cooling condensers require service? There iterative process. Because there will not be any oil
are several ways of achieving redundancy for cooling load during the initial start-up, liquid refrigerant
enhanced oil cooling reliability including: 1. provide will tend to fill the liquid supply piping, oil coolers and
alternate oil cooling source, such as liquid injection, individual oil cooler return piping branches to the level
on one or more compressors; 2. provide condenser in the pilot. Once operational, the return branch piping
flexibility by specifying more than one condenser to to the pilot will only be partially filled with liquid on the
meet oil cooling loads at design conditions; 3. a active oil coolers. It is important to closely monitor the
combination of #1 and #2; or 4. provide the ability to liquid level in the pilot receiver after initial startup to
cross-connect the oil cooling circuit with the avoid overfilling the pilot. A high liquid level will result
condensers used in the main refrigeration system for in turbulent conditions in the vapor space of the pilot
heat rejection. The cross-connection option for during operation.
redundancy requires that the pilot receiver be
connected to the refrigeration system condensers Reserve liquid in the pilot is less important in a
and high-pressure receiver as shown in Figure 2. dedicated thermosiphon system because the oil cooler
circuit is a fixed charge and the oil coolers are not
Purging “sharing” liquid with the entire refrigeration system.
Automatic purgers are used in industrial refrigeration However, a nominal liquid level in the pilot receiver is
systems using ammonia for removing non- needed to ensure that liquid can be fed to each oil
condensable gases to maintain efficient system cooler supply branch lines without starving any
operation. Typically, foul gas, drawn from individual branches.
purge points located at the top of each condenser
heat exchanger outlet, is piped to a foul gas main If the cross-connect option (discussed previously for
connected to one or more purgers (Figure 4). In a redundancy) is chosen, the thermosiphon system can
dedicated thermosiphon oil cooling circuit, two be charged directly from main refrigeration system
purging-related issues need to be addressed: 1. how using the cross-connect piping.
is it accomplished, and 2. when should it be done.
Oil Management
How? With a dedicated oil-cooling refrigerant circuit, In a traditional thermosiphon system, oil carry-over in
the set point pressure of the oil-cooling condenser the discharge line from screw compressors can
will generally be higher than the refrigeration system possibly accumulate in the refrigerant-side of oil
condensing (head) pressure. If the purge points for coolers. Draining oil from the refrigerant side of oil
the oil cooling condensers are on a common purge coolers is time consuming and presents considerable
main with the refrigeration system, the pressure safety risks. With a dedicated refrigerant circuit for oil
difference between the two systems presents a cooling, the refrigerant supply to oil coolers can be
problem. When the oil cooling circuit operates at a maintained oil free, thereby, eliminating the need to
pressure higher than the system condensing manage or drain oil from the oil coolers.
pressure, the purge solenoids for the system may be
forced open whenever a purge solenoid in the oil
CONCLUSION
cooling circuit opens. To avoid this problem, we
A thermosiphon refrigerant circuit and condenser
recommend one of two alternatives: 1. purge points
dedicated to oil cooling for screw compressors is an
from the two heat rejection systems be segregated
alternative to traditional thermosiphon configuration that
onto separate foul gas mains, or 2. isolate each of
offers reduced operational costs, simplified
the thermosiphon evaporative condenser purge
troubleshooting, and eliminates oil from the
points using the stop valve at the purge point (Figure
refrigeration side of the oil cooler. In addition to
4). These recommendations allow for operation of
presenting the concept, considerations for operation,
the oil cooling condenser at a higher pressure than
maintenance, and redundancy were briefly covered.
the system condensers without back-flowing foul gas
from the thermosiphon to the purge connections on
If you have questions or comments on this article,
the refrigeration system condensers.
please contact Todd Jekel at (608) 265-3008 or
When? Since a dedicated TSOC circuit will not tbjekel@wisc.edu.
accumulate non-condensables during operation, it is
advisable to take those purge points out of the purge
“rotation” except immediately after startup and
servicing that requires line breaking.

6
Process Safety Management Audits
June 18-20, 2003 Madison, WI

Demand Forces Overflow Offering


Due to the demand for EPD’s Auditing PSM Systems course initially offered in January 2003, we have scheduled a
repeat “overflow” course for June. Don’t miss this opportunity to “raise the bar” on your plant’s process safety
management programs.

What Have Past Attendees Said About This Course?


“This is one of the most thorough, energetic, well-paced, and valuable content seminars I’ve ever attended!”
Phil Froncek, Agrilink Foods

“Very nicely laid out and thorough. The program was timely and will help us assure a safer workplace.”
Jeff Vorpahl, Packerland Packing

“Good tools to proceed with for conducting our audits and program improvements.”
Paul Brunette, Kraft Canada

Learn Sound Principles and Practices


Attend this course and learn sound principles and practices for conducting effective PSM compliance audits.
Compliance audits of PSM systems are one of the most effective means of continuously improving your plant’s PSM
program. Perform quality audits and reap the benefits of enhanced safety and more reliable “cold”.

Boost Your Understanding


The workshop format of this course will help you conduct high-performance, effective process safety management
systems audits. Our goals in offering this course are to help you
• understand a range of approaches for conducting PSM compliance audits
• assess and allocate required resources to conduct effective audits
• continuously improve PSM programs, and
• continuously improve the reliability and deliverability of “cold” as a result of conducting a compliance audit

Upon completion of the course, you will understand


• a wide range of audit types
• techniques for conducting effective PSM audits
• strategies for staffing and executing audits
• approaches for turning your audit results into PSM program improvements

Attend and Benefit


This course has been designed for
• PSM coordinators
• managers responsible for safety
• refrigeration personnel (operators, mechanics and supervisory staff)
• audit team members
• managers concerned with the reliability and dependability of “cold”
• others who want to learn more about enhanced refrigeration system safety and reliability

Take Home Valuable Compliance Audit Tools


As an attendee, you will receive a complete set of course notes. In addition, you will receive a CD-ROM with
valuable tools for conducting compliance audits at your facility.

Download a complete brochure including a course outline and registration materials by clicking here.

7
Benchmarking Refrigeration System Performance
Is your refrigeration plant energy efficient? How do you know?
Improving the energy efficiency of refrigeration systems can provide significant economic
and operational benefits. Unfortunately, very little information is currently available to
identify systems with above- or below-average energy use. The Industrial Refrigeration
Consortium (IRC) has initiated a research effort to develop benchmark data to help
refrigeration plant personnel assess their facilities' energy costs relative to other plants.

The IRC is currently seeking plants to take part in this research project. In exchange for
furnishing monthly energy use and load data, participating organizations will gain preferred
access to the benchmarking results, including:

• Prepublication copies of the final report (published reports will not be released for
18 months following completion of the work)
• Written status reports and telephone conference calls on work in progress
• Special assistance from investigators to resolve energy analysis questions
• Optional custom analysis of your plants' energy use

For more information, or to learn how to participate, download the project description from
our website at www.irc.wisc.edu.

ITT’SS NO
OTT TO
OOO LA
ATTEE!
Join the IRC in 2003
The IRC’s mission is to improve the safety, reliability, efficiency, and productivity of
industrial refrigeration systems. Our vision is to make continuous progress toward
improving the safety, productivity, and efficiency of the systems and technologies that form
the foundation of the industrial refrigeration industry.

Does your company have needs in the areas of education, technical assistance or strategic
planning for refrigeration? If so, please contact us to see how joining the IRC can benefit
you and your company.

N
NEEW
WSSLLEETTTTEERR IID SW
DEEAAS WEELLCCO
OM D!!
MEED
If it is of interest to you, it is undoubtedly of interest to
others.

Send Idea

Das könnte Ihnen auch gefallen