User’s Guide
GU-1246
© 2007 MEGABRAS. All rights reserved.
Printed in Brazil.
3
~ Safety warnings
As the line is energized and the tower grounding state is, provisionally
unknown, the operator shall follow all the safety measures stated,
avoiding the existence of step and touch voltages which are possibly
dangerous. Refer to the company safety regulations for these matters.
Used symbols
V Caution, refer to User Guide
Z Battery
Y Printer
[ Backlight
Off / On
4
Index
1. Description......................................................................................................... 6
2. Control panel ..................................................................................................... 8
2.1. Connections and items................................................................................ 8
2.2. Keyboard .................................................................................................... 9
3. Power supply ................................................................................................... 10
3.1. Battery / battery charger............................................................................ 10
3.1.1. Battery description ............................................................................. 10
3.1.2. Battery status check........................................................................... 10
3.1.3. Recharge procedure........................................................................... 10
4. Printer.............................................................................................................. 11
4.1. Paper feed ................................................................................................ 11
4.2. Paper ........................................................................................................ 11
5. Real time clock and calendar ........................................................................... 12
6. Connecting the TM-25m................................................................................... 12
6.1. Meter location ........................................................................................... 12
6.2. Auxiliary rods set up.................................................................................. 12
7. Measuring........................................................................................................ 13
7.1. Selecting the type of measurement ........................................................... 13
7.1.1. Grounding resistance measurement................................................... 13
7.1.2. Grounding resistance measurement function with inductive component
compensation .............................................................................................. 13
7.2. Looking for the potential profile flat area.................................................... 15
7.3. Guard wire inductance .............................................................................. 15
8. Abnormalities indications on the display........................................................... 16
8.1. Excessively high earth resistance ............................................................. 16
8.2. Excessively high resistance in the auxiliary rods ....................................... 16
9. Auto power-off ................................................................................................. 17
10. Data collection in the computer ...................................................................... 17
10.1. RS232 output port ................................................................................... 17
10.2. Transfer data to a computer .................................................................... 17
11. Technical specifications ................................................................................. 20
11.1. Accessories ............................................................................................ 21
12. Warranty ........................................................................................................ 22
5
1. Description
Testing of the power transmission towers grounding (G) quality poses a
serious problem as they are all electrically interconnected by means of
Ground Wires which act as lightning rods, protecting the lines from
atmospheric discharges.
Thus, values that better represent the system capacity to ground lightning
currents than the ones obtained with low frequency conventional
equipments, even when disconnecting the ground wire, are obtained.
6
The test is performed by making the known-value current flow through the
earth diffusion resistance and an auxiliary electrode, called the current
electrode, and by measuring the voltage produced between grounding
and another auxiliary electrode, thrust into the ground in the area of the
potential created by flowing current (Potential Plateau).
7
2. Control panel
All of the TM-25m buttons, keys, outputs and connections are located on
the panel, and are easily accessible by the operator. The following
graphics show the function of each one of the equipment's items.
% "
& !
'
(
)
8
2.2. Keyboard
b
It prints the last test performed –
c
It sends stored memory data to a connected –
computer or data logger
a
It shows the battery charge status on the The battery charger is
display operating
e
Backlight - it activates the display light. After –
10 seconds the backlight will auto-turn off in
order to save the battery charge
f
It selects the grounding resistance It indicates selected
measurement function with inductive function
component compensation
g
It selects grounding resistance measurement It indicates selected
function (without compensation) function
h
The START key. Starts the test A measurement is
running
9
3. Power supply
The TM-25m has a built-in rechargeable battery. Furthermore, it can be
powered by mains supply or an external 12 V battery (car battery).
10
4. Printer
Pressing the b key will print the results and parameters of the last test.
ATTENTION: Do not pull the paper. Never try to put the paper back into
the printer. In any of these cases, the printer may be easily damaged.
4.2. Paper
This printer uses 37 mm - wide thermal paper, which comes in a 33 mm-
diameter reel. The figure shown below indicates how to put the paper.
White side
Yellow side
Press the ) key, (until the paper appears). To remove the old paper reel,
cut the paper next to it and press the ) key. The removal used-reel
operation must be carried out in this way due to the fact that the paper
movement is in one-way only, that is, the paper can be moved in one
direction only.
11
5. Real time clock and calendar
In order to provide an easier identification of each test, the TM-25m has a
built-in real-time clock/calendar. Date and time must be adjusted with a
PC software (available at www.megabras.com) that synchronizes the
equipment with the PC clock.
E S H
12
7. Measuring
13
Note: If the system tuning is not obtained (normally because the inductance of
the grounding systems is not significant), this will be shown in the display.
If the test is printed, the message “Undefined” for the values Rc and C, with L= 0
will be displayed.
TM25M OO0000O
Test No. 15
12/08/2006 12:00
R= 9.04 Ohm
Rc= Undefined
C= Undefined
L= 0
14
7.2. Looking for the potential profile flat area
After getting the first Grounding Resistance Value, it is necessary to
obtain the greatest amount of points to trace the potential profile curve. In
order to do that, the potential rod (probe) should be always set up
perpendicular to the traced line, in several intermediate points between
the unknown electrode and the current rod, so as to obtain the kind of
curve showed below.
RV
D1 D2 D3 D
The Grounding Resistance Value will be the one obtained in the potential
profile flat zone. Rv in the above mentioned picture. If 3 measurements
with the same value or with an acceptable mistake made by the operator
could not be obtained, (5% is an usual acceptable value), current
electrode distance must be increased in, for example, 50 meters, and
several measurements should be taken again with the probe until finding
the potential profile flat zone. Check always the current.
15
8. Abnormalities indications on the display
If the TM-25m identifies any abnormality causing the measurements to be
excessively inaccurate, or not possible at all, a warning message will be
shown on the display, allowing the operator to identify and correct the
problem.
“R > 300 Ω”
16
9. Auto power-off
The TM-25m auto-turns off after 15 minutes of inactivity.
Meu computador
Windows Explorer
Lixeira
Programas
Documentos softwares
Configurações
Pesquisar
Ajuda
Executar
Desligar
Iniciar 12:00
17
To set up a new connection, enter a name and Descrição da conexão ? X
OK Cancelar
Choose the correct port in the next window. In País/região: Brasil (55)
OK Cancelar
Nenhum
Nenhum
OK Cancelar Aplicar
18
The computer is now correctly configured to receive data from the
equipment. Press the c key and the TM-25m will send all stored data to
the computer, while the display shows the following message “SENDING
DATA. WAIT...”.
Memory data are available for visualization and storage in the computer.
Most Laptops currently in the market do not have RS232 Port. In this
case, a USB è RS232 converter must be acquired, installing the
corresponding driver in the Laptop simulating a COM Port.
19
11. Technical specifications
Measurement ranges : 0 - 300 Ω
Operation frequency : 25000 Hz
Test currents : 20 mA automatic
Inductive component : Through bank of capacitors integrated to the
compensation equipment
Maximum capacity: 4.2 µF
Resolution: 10 nF
Measurement accuracy : ± 2.5 % of reading ± 1 digit
Display : Alphanumeric display (LCD)
Max. earth resistance of : 2000 Ω (current rod)
auxiliary rods 2000 Ω (voltage rod)
Built-in memory : It allows for the storage of 2000 tests readings in
its internal NVRAM memory.
Serial data output : RS232 @ 4800 bps.
Energy supply : Internal or external rechargeable battery, 12 V.
Internal battery autonomy: at least 2 hours
Battery charger : For 100 - 240 V~ 50/60 Hz
Operating temperature : -5°C to 50°C
Storage temperature : -15 °C to 65 °C
Humidity : Up to 95% RH (non condensing)
Dimensions : 340 x 295 x 152 mm
Equipment weight : Approx. 4.5 kg
20
11.1. Accessories
A set of accessories is provided with each earth meter. This set consists of the
following:
21
12. Warranty
MEGABRAS INDÚSTRIA ELETRÔNICA LTDA. (“MEGABRAS”) warrants to the
original purchaser that each equipment it manufactures will be free from defects in
material and workmanship under normal use and service. The warranty period is
valid for 24 months, except the built-in rechargeable battery that has 6 months, and
begins on the date of shipment. The manufacturer's warranty does not apply to any
product or accessories which, in the manufacturer's opinion, has been misused,
altered, neglected, or damaged by accident or abnormal conditions of operation
and handling.
To obtain warranty service, send the equipment, with a description of the difficult,
shipping and insurance prepaid, to MEGABRAS. The manufacturer assumes no
risk for damage in transit. MEGABRAS will, at its option, repair or replace the
defective equipment free of charge or refund your purchase price. However, if
MEGABRAS determines that the failure was caused by misuse, alteration, accident
or abnormal condition or handling, you will be charged for the repair and the
repaired equipment will be returned to you transportation prepaid.
This warranty is exclusive and is instead of all other warranties, express or implied,
including but not limited to any implied warranty or merchantability or fitness for a
particular purpose or use. MEGABRAS will not be responsible for any special,
indirect, incidental, or consequential damages or loss of data, whether in contract,
or otherwise.
Liability limitation
The liability for malfunctioning of the equipment is limited to the application of the
warranty pursuant to the aforementioned provisions. The manufacturer does not
take any responsibility for any eventual damage due to the use of the equipment
such as the loss of memory data, accidents in the field, loss of profit, etc.
22